HomeMy WebLinkAbout2013 TANK INSPECTIONTo: Sessions Site: Jim's Mobil Address: 3200 i= Street SPECIAL INSPECTION REPORT Bakersfield, CA Date: January 22, 2013 The following results for the above location represent the conclusions of the Special Inspection, which are to be presented to the regulatory agency. Tank No. 1- South Capacity 10,000 gallons Dimensions 711" x 27' Product Fuel CCR rdle 23 -2663 (b) Tank has been cleaned so that no residue remains on the tank walls (c) (A) Determine that tank has been vacuum tested at a vacuum of 5.3 inches of Hg for not less than one minute. (B) Witness ultrasound test - average of 75% or greater of original thickness. Visually checked the internal lining for discontinuity, compression, tension cracking and corrosion_ Test for thickness and hardness of the lining in accordance with nationally recognized industry codes. Test the lining using an electrical resistance Holiday Detector in accordance with nationally recognized industry codes, Holidays located, repaired and re- tested (d) Tank is suitable for continued use for a minimum of five (5) years (e) Tank is suitable for continued use for a minimum of five (5) years D�IfLY if it is relined, or other improvements are made. (f) The tank lining is no longer suitable for continued use and shall be closed in accordance with Article 7. Coating Inspector Thomas M. Allen, III Professional Engineer Robert Paul P.E. Address 2243 Aspen Mirror Way Suite 204 Laughlin, ITV 89029 Signature: Registered Professional Engineer No. Corrosion 111 Expiration Date: 3/3112014 PASS FAIL X X X X X X X STAMP To: Sessions Site: Jim's Mobil Address: 32001" Street SPECIAL INSPECTION REPORT Bakersfield, CA Date: January 22, 2013 The following results for the above location represent the conclusions of the Special Inspection, which are to be presented to the regulatory agency. Tank No. 2- North Capacity 10,000 gallons Dimensions 7'11" x 27' Product Fuel CCR Title 23-2663 (b) Tank has been cleaned so that no residue remains on the tank walls (c) (A) Determine that tank has been vacuum tested at a vacuum of 5.3 inches of Hg for not less than one minute. (13) Witness ultrasound test -average of 75% or greater of original thickness. Visually checked the internal lining for discontinuity, compression, tension cracking and corrosion. Test for thickness and hardness of the lining in accordance with nationally recognized industry codes. Test the lining using an electrical resistance Holiday Detector in accordance with nationally recognized fq industry codes, Holidays located, repaired and re-tested (d) Tank is suitable for continued use for a minimum of five (5) years (e) Tank is suitable for continued use for a minimum of five (5) years O LY if it is relined, or other improvements are made. (f) The tank lining is no longer suitable for continued use and shall be closed in accordance with Article 7. Coating Inspector Thomas M. Allen, III Professional Engineer Robert Paul P.E. Address 2243 Aspen Mirror Way Suite 204 Laughlin, NV 89029 Signature: Registered Professional Engineer No. Corrosion 111 Expiration Date: 3/3112014 PASS FAIL X X X X X X *4 STAMP