HomeMy WebLinkAbout2013 TANK INSPECTIONTo: Sessions
Site: Jim's Mobil
Address: 3200 i= Street
SPECIAL INSPECTION REPORT
Bakersfield, CA
Date: January 22, 2013
The following results for the
above location represent the conclusions of the Special Inspection, which are
to be presented to the regulatory agency.
Tank No.
1- South
Capacity
10,000 gallons
Dimensions
711" x 27'
Product
Fuel
CCR rdle 23 -2663
(b) Tank has been cleaned so that no residue remains on the tank walls
(c) (A) Determine that tank has been vacuum tested at a
vacuum of 5.3 inches of Hg for not less than one minute.
(B) Witness ultrasound test - average of 75% or
greater of original thickness.
Visually checked the internal lining for discontinuity,
compression, tension cracking and corrosion_
Test for thickness and hardness of the lining in
accordance with nationally recognized industry codes.
Test the lining using an electrical resistance Holiday
Detector in accordance with nationally recognized
industry codes, Holidays located, repaired and re- tested
(d) Tank is suitable for continued use for a minimum of five (5) years
(e) Tank is suitable for continued use for a minimum of five (5) years
D�IfLY if it is relined, or other improvements are made.
(f) The tank lining is no longer suitable for continued use and shall be
closed in accordance with Article 7.
Coating Inspector Thomas M. Allen, III
Professional Engineer Robert Paul P.E.
Address 2243 Aspen Mirror Way Suite 204 Laughlin, ITV 89029
Signature:
Registered Professional Engineer No. Corrosion 111
Expiration Date: 3/3112014
PASS FAIL
X
X
X
X
X
X
X
STAMP
To: Sessions
Site: Jim's Mobil
Address: 32001" Street
SPECIAL INSPECTION REPORT
Bakersfield, CA
Date: January 22, 2013
The following results for the above location represent the conclusions of the Special Inspection, which are
to be presented to the regulatory agency.
Tank No. 2- North
Capacity 10,000 gallons
Dimensions 7'11" x 27'
Product Fuel
CCR Title 23-2663
(b) Tank has been cleaned so that no residue remains on the tank walls
(c) (A) Determine that tank has been vacuum tested at a
vacuum of 5.3 inches of Hg for not less than one minute.
(13) Witness ultrasound test -average of 75% or
greater of original thickness.
Visually checked the internal lining for discontinuity,
compression, tension cracking and corrosion.
Test for thickness and hardness of the lining in
accordance with nationally recognized industry codes.
Test the lining using an electrical resistance Holiday
Detector in accordance with nationally recognized fq
industry codes, Holidays located, repaired and re-tested
(d) Tank is suitable for continued use for a minimum of five (5) years
(e) Tank is suitable for continued use for a minimum of five (5) years
O LY if it is relined, or other improvements are made.
(f) The tank lining is no longer suitable for continued use and shall be
closed in accordance with Article 7.
Coating Inspector Thomas M. Allen, III
Professional Engineer Robert Paul P.E.
Address 2243 Aspen Mirror Way Suite 204 Laughlin, NV 89029
Signature:
Registered Professional Engineer No. Corrosion 111
Expiration Date: 3/3112014
PASS FAIL
X
X
X
X
X
X
*4
STAMP