Loading...
HomeMy WebLinkAboutSPECIAL INSPECTION REPORT 5-29-2013To: Sessions SPECIAL INSP CTION REPORT Site: Lucky 7 ?ate: May 29, 2013 Address: 725 S. Union Ave. Bakersfield, CA:. 93 07 The following results for the above location represent the conclusions of the Special inspection, which are to be presented to the regulatory agency. Tank No. 2 Capacity. 7,000 gallons Dimensions 8'x 20' Product Fuel CCR Title 23 -2863 PASS FAIL (b) Tank has beer' cleaned so that. no. residue remains on the tank walls X (c) (A) betermin e': that tank has been. vacuum tested at a . X vacuun .of 5..3 inches of g for not less than one minute. (8), Witness ultrasound test -average-of 75 or. X greater of original thickness. Visually checked the internal lining for-disdontinuity,. X compression, tension cracking and corrosion. Tesf for thickness and hardrm .ss of the lining in X accordarice.with babonaliy recognized industry cedes. Test-the lining using an electrical - resistance .Holiday . X Detecto in accordance with nationally recognized. industry codes, Holidays located; repaired'and ra- tested X (d) Tank is suitable for continued use a -minimuhl of five (5 }years (e) Tank is suitable for continued use fob ininimutn of five (5) y ears ONLY if it is relined, or other improvements are made. (f) The tank lining is no longer s.ij4ableI for continued use and shall be closed in. accordance with Ar icle. 7. Grating Inspector, Thomas M. Allet1, III .Professional Engineer Robert Paul• R.E ST ` Address 2243 Aspen Mirror W y.Suite 204 Laughlin, NV 89029 Signature: r� Registered Professional Engineer No.. CoirosiOn,'111 Expiration Qate: 313172014:: To: Sessions SPECIAL INSPECTION REPORT Site: Lucky 7 Address: 726 S. Union Ave. Bakersfield, CA 93307 Date: May 29, 2013 The following results for the above location represent the conclusions of the Special Inspection, which are to be presented to the regulatory agency. Tank No. I Capacity 10,000 gallons Dimensions 8' x 27' Product Fuel CCR Title 23-2663 PASS FAIL (b) Tank has been cleaned so that no residue remains on the tank walls X (c) (A) Determine that tank has been vacuum tested at a X vacuum of 5.3 inches of Hg for not less than one minute. (8) Witness ultrasound test -average of 75 or X greater of original thickness. Visually checked the internal lining for discontinuity, X compression, tension cracking and corrosion. Test for thickness and hardness of the lining in X accordance with nationally recognized industry codes. Test the lining using an electrical resistance Holiday X Detector in accordance with nationally recognized industry codes, Holidays located, repaired and re-tested X (d) Tank is suitable for continued use for a minimum of five (5) years (e) Tank is suitable for continued use for a minimum of five (5) years ONL Y if it is relined, or other improvements are made. (f) The tank lining is no longer suitable for continued use and shall be closed in accordance with Article 7. Coating Inspector Thomas M. Men, III Professional Engineer Robert Paul P.E STAMP Address 2243 Aspen Mirror Way Suite 204 Laughlin, NV 89029 Signature: Registered Professional Engineer No. Corrosion 111 Expiration Date: 313112014.