HomeMy WebLinkAboutTANK INTEGRITY RESULTStow)-V %v
RICH ET MROWENTAL
5643 BROOKS CT.- BAKERSFIELD, CA 93308
OFF. (661)392 -8687 FAX(661)588 -7808
ALERTi 1000 UNpfflgFffL & 1050X ULLAGE S_YSjEM & A E `
PRECISION UNDERGROUND STORAGE TANK. SYSTEM LEAK TEST
I TE, ST RES_iJLTS
DATE: 10/28/15
BILLING: HUNGRY' S MARKET SITE: HUNGRY' S MARKET
3711 MT VERNON AVE 3711 MT VERNON AVE
BAKE SFIELD, CA 93306 BAKERSFIELD, CA 93308
PRODUCT VOLVME %FULL WETTED NON - WETTED PRODUCT LEAK WATER IN
- — — ..- .,........ter . A i.Tirr
UNL -87 10, F 00 00% N/A PASS N/A N/A 0"
PREM -91 10,000 00% N/A FAIL N/A N/A 0
DIESEL 10,000 00% N/A PASS N/A NIA 0"
I
COMNENTS: WAS UNABLE TO PULL A VACUUM GREATER THAN - .15PSI TO PERFORM
PRECISION TANK. TAST ON PREM -91 EMPTY TANK.
CONIMENTS
RECISION TEST WAS PERFORMED ON TANK(S) AT THE ABOVE LOCATION USING THE
AP
ALERT 1050X ULLAGE SYSTEM. I HAVE REVIEWED THE DATA PRODUCED IN
CONJUNCTION WITH THIS TEST PURPOSE
PERFORMED IN ACCORDANCE WITH ALERT
THE TANK SYSTEMS. THE TESTING W
PROTOCOL, AND THEREFORE SATISFIES ALL REQUIREMENTS FOR SUCH TESTING AS SET
FORTH BY NFPA- 329 -92 AND USEPA 40 CFR PARTS 280.
THE RESULTS OF TESTING ARE SHOWN ON THE FOLLOWING PAGE, AND INDICATE
WHETHER THE NETTED
AND NON - WETTED PORTION PASSED OR FAILED. INCLUDED WITH
THE REPORT ARE REPRODUCTION OF DATA COMPLIED DURING THE TEST WHICH FORMED
THE BASIS FOR THESE CONCLUSIONS. THIS INFORMATION IS STORED IN A PERMANENT
FILE IF FUTURE VERIFICATION OF TEST RESULTS IS NEEDED.
I DECLARE UNDER PENALTY OF PERJURE �O I��T QN LICENSED
CONTAINED IN THIS
IN
THE STATE OTC CALIFONIA AND THAT TH
REPORT IS TROE AND CORRECT TO THE BEST OF MY KNOWLEDGE.
TEST C RTIFIEI3 BY:
f
S J RICH
CERT# 90 -1072