Loading...
HomeMy WebLinkAboutFMC 2015MONITORING SYSTEM CERTIFICATION For Use By All Jurisdictions Within the State of CaliforniaAuthority Cited: Chapter 6.7, Health and Safety Code; Chapter 16, Division 3, Title 23, California Code of Regulations This form must be used to document testing and servicing of monitoring equipment. A separate certification or report must be prepared for each monitoring system control panel by the technician who performs the work. A copy of this form must be provided to the tank system owner/operator. The owner/operator must submit a copy of this form to the local agency regulating UST systems within 30 days of test date. A.General Information Facility Name:Bldg. No.: Site Address:City:Zip: Facility Contact Person: Contact Phone No.: Make/Model of Monitoring System:Date of Testing/Servicing: B.Inventory of Equipment Tested/Certified Check the appropriate boxes to indicate specific equipment inspected/serviced: Tank ID:Tank ID: In-Tank Gauging Probe.Model:In-Tank Gauging Probe.Model: Annular Space or Vault Sensor.Model:Annular Space or Vault Sensor.Model: Piping Sump / Trench Sensor(s).Model:Piping Sump / Trench Sensor(s).Model: Fill Sump Sensor(s).Model:Fill Sump Sensor(s).Model: Mechanical Line Leak Detector.Model:Mechanical Line Leak Detector.Model: Electronic Line Leak Detector.Model:Electronic LineLeak Detector.Model: Tank Overfill / High-Level Sensor.Model:Tank Overfill / High-Level Sensor.Model: Other (specify equipment type and model in Section E on Page 2).Other (specify equipment type and model in Section E on Page 2). Tank ID:Tank ID: In-Tank Gauging Probe.Model:In-Tank Gauging Probe.Model: Annular Space or Vault Sensor.Model:Annular Space or Vault Sensor.Model: Piping Sump / TrenchSensor(s).Model:Piping Sump / Trench Sensor(s).Model: Fill Sump Sensor(s).Model:Fill Sump Sensor(s).Model: Mechanical Line Leak Detector.Model:Mechanical Line Leak Detector.Model: Electronic Line Leak Detector.Model:Electronic Line Leak Detector.Model: Tank Overfill / High-Level Sensor.Model:Tank Overfill / High-Level Sensor.Model: Other (specify equipment type and model in Section E on Page 2).Other (specify equipment type and model in Section E on Page 2). Dispenser ID:Dispenser ID: Dispenser Containment Sensor(s).Model:Dispenser Containment Sensor(s).Model: Shear Valve(s).Shear Valve(s). Dispenser Containment Float(s) and Chain(s).Dispenser Containment Float(s) and Chain(s). Dispenser ID:Dispenser ID: Dispenser Containment Sensor(s).Model:Dispenser Containment Sensor(s).Model: Shear Valve(s).Shear Valve(s). Dispenser Containment Float(s) and Chain(s).Dispenser Containment Float(s) and Chain(s). Dispenser ID:Dispenser ID: Dispenser Containment Sensor(s).Model:Dispenser Containment Sensor(s).Model: Shear Valve(s).Shear Valve(s). Dispenser Containment Float(s) and Chain(s).Dispenser Containment Float(s) and Chain(s). *If the facility contains more tanks or dispensers, copy this form. Include information for every tank and dispenser at the facility. C.Certification -I certify that the equipment identified in this document was inspected/serviced in accordance with the manufacturers’ guidelines. Attached to this Certification is information (e.g. manufacturers' checklists)necessary to verify that this information is correct and a Plot Plan showing the layout of monitoring equipment. For any equipment capable of generating such reports, I have also attached a copy of the report;(check all that apply):System set-up Alarm history report Technician Name (print):Signature: Certification No.:License. No.:804904 Testing Company Name:Confidence UST Services, Inc.Phone No.:(800)339-9930 Site Address:Date of Testing/Servicing: Page 1 of 3 RamcoExpress 2222FStreetBakersfield93301 Rami (661)324-1758 Veeder-RootTLS-350 12/16/2015 10,000gal.Regular 847390-107 794390-409 794390-409 794380-208 794380-208 PLLD OPW61-SO 10,000gal.Plus 847390-107 PLLD OPW61-SO 10,000gal.Super 847390-107 794390-409 794380-208 OPW61-SO PLLD 1-2 3-4 AustinSterling B45438 2222FStreet Bakersfield,CA9330112/16/2015 Monitoring System Certification D.Results of Testing/Servicing Software Version Installed: Complete the following checklist: Yes No*Isthe audible alarm operational? Yes No*Is the visual alarm operational? Yes No*Were all sensors visually inspected, functionally tested, and confirmed operational? Yes No*Were all sensors installed at lowest point of secondary containment and positioned so that other equipment will not interfere with their proper operation? Yes No* N/A If alarms are relayed to a remote monitoring station, is all communications equipment (e.g., modem) operational? Yes No* N/A For pressurized piping systems, does the turbine automatically shut down if the piping secondary containment monitoring system detects a leak, fails to operate, or is electrically disconnected? If yes: which sensors initiate positive shut-down? (Check all that apply) Sump/Trench Sensors; Dispenser Containment Sensors. Did you confirm positive shut-down due to leaks and sensor failure/disconnection? Yes; No. Yes No* N/A For tank systems that utilize the monitoring system as the primary tank overfill warning device (i.e., no mechanical overfill prevention valve is installed), is the overfill warning alarm visible and audible at the tank fill point(s) and operating properly? If so, at what percent oftank capacity does the alarm trigger? % Yes*NoWas any monitoring equipment replaced? If yes, identify specific sensors, probes, or other equipment replaced and list the manufacturer name and model for all replacement parts in Section E, below. Yes*NoWas liquid found inside any secondary containment systems designed as dry systems? (Check all that apply) Product; Water. If yes, describe causes in Section E, below. Yes No*Was monitoring system set-up reviewed to ensure proper settings? Attach set up reports, if applicable Yes No*Is all monitoring equipment operational per manufacturer’s specifications? * In Section E below, describe how and when these deficiencies were or will be corrected. E.Comments: Page 2 of 3 333.03 Monitoring System Certification F.In-Tank Gauging / SIR Equipment: Check this box if tank gauging is used only for inventory control. Check this box if no tank gauging or SIR equipment is installed. This section must be completed if in-tank gauging equipment is used to perform leak detection monitoring. Complete the following checklist: Yes No*Has all input wiring been inspected for proper entry and termination, including testing for ground faults? Yes No*Were all tank gauging probes visually inspected for damage and residue buildup? Yes No*Was accuracy of system product level readings tested? Yes No*Was accuracy of system water level readings tested? Yes No*Were all probes reinstalled properly? Yes No*Were all items on the equipment manufacturer’s maintenance checklist completed? * In the Section H, below, describe how and when these deficiencies were or will be corrected. G.Line Leak Detectors (LLD):Check this box if LLDs are not installed. Complete the following checklist: Yes No* N/A For equipment start-up or annual equipment certification, was a leak simulated to verify LLD performance? (Check all that apply)Simulated leak rate: 3 g.p.h.; 0.1 g.p.h ; 0.2 g.p.h. Yes No*Were all LLDs confirmed operational and accurate within regulatory requirements? Yes No*Was the testing apparatus properly calibrated? Yes No* N/A For mechanical LLDs, does the LLD restrict product flow if it detects a leak? Yes No* N/A For electronic LLDs, does the turbine automatically shut off if the LLD detects a leak? Yes No* N/A For electronic LLDs, does the turbine automatically shut off if any portion of the monitoring system is disabled or disconnected? Yes No* N/A For electronic LLDs, does the turbine automatically shut off if any portion of the monitoring system malfunctions or fails a test? Yes No* N/A For electronic LLDs, have all accessible wiring connections been visually inspected? Yes No*Were all items on the equipment manufacturer’s maintenance checklist completed? * In the Section H, below, describe how and when these deficiencies were or will be corrected. H.Comments: Page 3 of 3 Leak Detector Test Results Sheet Customer Address: Work Order: Site Address: Test Date: Site Contact: Phone: Technician: Phone: 800-339-9930 ICC No.: Product Type LLD Type Model Serial No. Check Valve Holding Pressure Bleed Off ML. Leak Rate Tested: Pass/Fail 3 gph @ 10 psi 3 gph @ 10 psi 3 gph @ 10 psi 3 gph @ 10 psi 3 gph @ 10 psi 3 gph @ 10 psi 3 gph @ 10 psi 3 gph @ 10 psi Technician Name: Technician No.: Signature: Date: RamcoExpress 2222FStreet Bakersfield,CA93301 35527 12/16/2015 8339953-UT Regular Electronic PLLD AustinSterling (661)324-1758Rami Bakersfield,CA93301 2222FStreet RamcoExpress 15 psi65 ml Pass PLLDElectronicPlus 13 psi65 ml Pass PLLDElectronicPremium 12 psi70 ml Pass AustinSterling 8339953-UT 12/16/2015 Monterey AMPM Responses Received: 200 ARCO 5526 900 MONTEREY ST BAKERSFIELD,CA93305 805-861-1972 NOV 23, 2015 8:26 AM TANK PRODUCT GALLONS INCHES WATER DEG F ULLAGE 1 UNLEADED SYPHON 3367 30.97 0.0 70.2 8260 2 UNLEADED MAIN 3558 32.19 0.0 72.4 8069 3 PREMIUM 3151 29.56 0.0 76.7 8476 I90500 NOV 23, 2015 8:26 AM SOFTWARE REVISION LEVEL VERSION 334.00 SOFTWARE# 346334-100-A CREATED - 15.05.29.10.36 S-MODULE# 330160-004-a SYSTEM FEATURES: PERIODIC IN-TANK TESTS ANNUAL IN-TANK TESTS ISD/APM I50500 NOV 23, 2015 8:26 AM SYSTEM TYPE AND LANGUAGE FLAG SYSTEM UNITS U.S. SYSTEM LANGUAGE ENGLISH SYSTEM DATE/TIME FORMAT MON DD YYYY HH:MM:SS xM I50201 NOV 23, 2015 8:26 AM SHIFT TIME 1 : 6:00 AM I50202 NOV 23, 2015 8:26 AM SHIFT TIME 2 : DISABLED I50203 NOV 23, 2015 8:26 AM SHIFT TIME 3 : DISABLED I50204 NOV 23, 2015 8:26 AM SHIFT TIME 4 : DISABLED I54600 NOV 23, 2015 8:26 AM TANK PER TST NEEDED WRN: DISABLED I54900 NOV 23, 2015 8:26 AM TANK ANN TST NEEDED WRN: DISABLED I55300 NOV 23, 2015 8:26 AM LINE RE-ENABLE METHOD PASS LINE TEST I55600 NOV 23, 2015 8:26 AM LINE PER TST NEEDED WRN: DISABLED I55900 NOV 23, 2015 8:26 AM LINE ANN TST NEEDED WRN: DISABLED I50D00 NOV 23, 2015 8:26 AM PRINT TC VOLUMES ENABLED I50E00 NOV 23, 2015 8:26 AM TEMP COMPENSATION VALUE (DEG F ): 60.0 I60B00 NOV 23, 2015 8:26 AM STICK HEIGHT OFFSET ENABLE STATUS DISABLED I51400 NOV 23, 2015 8:26 AM H-PROTOCOL DATA FORMAT HEIGHT I51A01 NOV 23, 2015 8:26 AM DAYLIGHT SAVING TIME DISABLED I51B00 NOV 23, 2015 8:26 AM I51600 NOV 23, 2015 8:26 AM RE-DIRECT LOCAL PRINTOUT DISABLED I50400 NOV 23, 2015 8:26 AM 232 SECURITY CODE PORT SECURITY CODE STATUS 1 000000 DISABLED 2 000000 DISABLED 3 000000 DISABLED 4 000000 DISABLED 5 000000 DISABLED 6 000000 DISABLED I21900 NOV 23, 2015 8:26 AM TANK CHART SECURITY DISABLED I5BD00 NOV 23, 2015 8:26 AM CUSTOM ALARM LABELS DISABLED I56000 NOV 23, 2015 8:26 AM MASS/DENSITY DISABLED I88101 NOV 23, 2015 8:26 AM PORT SETTINGS: COMM BOARD : 1 (EDIM ) RS-232 SECURITY CODE : DISABLED I88102 NOV 23, 2015 8:26 AM PORT SETTINGS: COMM BOARD : 2 (S-SAT ) BAUD RATE : 9600 PARITY : NONE STOP BIT : 1 STOP DATA LENGTH: 8 DATA RS-232 SECURITY CODE : DISABLED DTR NORMAL STATE: HIGH I88103 NOV 23, 2015 8:26 AM I88104 NOV 23, 2015 8:26 AM I88105 NOV 23, 2015 8:26 AM PORT SETTINGS: COMM BOARD : 5 (RS-485) BAUD RATE : 2400 PARITY : EVEN STOP BIT : 1 STOP DATA LENGTH: 7 DATA RS-232 SECURITY CODE : DISABLED I88106 NOV 23, 2015 8:26 AM PORT SETTINGS: COMM BOARD : 6 (RS-232) BAUD RATE : 9600 PARITY : NONE STOP BIT : 2 STOP DATA LENGTH: 8 DATA RS-232 SECURITY CODE : DISABLED I52000 NOV 23, 2015 8:26 AM RECEIVER AUTO DIAL TYPE & START TIME RCVR LOCATION LABEL DIAL TYPE START TIME 1 ON DATE ??? 23, 2015 DISABLED 2 ON DATE ??? 23, 2015 DISABLED 3 ON DATE ??? 23, 2015 DISABLED 4 ON DATE ??? 23, 2015 DISABLED 5 ON DATE ??? 23, 2015 DISABLED 6 ON DATE ??? 23, 2015 DISABLED 7 ON DATE ??? 23, 2015 DISABLED 8 ON DATE ??? 23, 2015 DISABLED I60100 NOV 23, 2015 8:27 AM TANK CONFIGURATION DEVICE LABEL CONFIGURED 1 UNLEADED SYPHON ON 2 UNLEADED MAIN ON 3 PREMIUM ON 4 OFF I60200 NOV 23, 2015 8:27 AM TANK PRODUCT LABEL TANK PRODUCT LABEL 1 UNLEADED SYPHON 2 UNLEADED MAIN 3 PREMIUM 4 I60300 NOV 23, 2015 8:27 AM TANK PRODUCT CODE TANK PRODUCT LABEL 1 UNLEADED SYPHON 1 2 UNLEADED MAIN 2 3 PREMIUM 3 4 4 I60900 NOV 23, 2015 8:27 AM TANK THERMAL COEFFICIENT TANK PRODUCT LABEL 1 UNLEADED SYPHON 0.000700 2 UNLEADED MAIN 0.000700 3 PREMIUM 0.000700 4 0.000000 I60700 NOV 23, 2015 8:27 AM TANK DIAMETER TANK PRODUCT LABEL INCHES 1 UNLEADED SYPHON 92.00 2 UNLEADED MAIN 92.00 3 PREMIUM 92.00 4 0.00 I60A00 NOV 23, 2015 8:27 AM TANK FULL VOLUME TANK PRODUCT LABEL TANK PROFILE GALLONS 1 UNLEADED SYPHON 4 PTS 11627 2 UNLEADED MAIN 4 PTS 11627 3 PREMIUM 4 PTS 11627 4 1 PT 0 I60400 NOV 23, 2015 8:27 AM TANK FULL VOLUME TANK PRODUCT LABEL GALLONS 1 UNLEADED SYPHON 11627 2 UNLEADED MAIN 11627 3 PREMIUM 11627 4 0 I60500 NOV 23, 2015 8:27 AM TANK 4 POINT VOLUMES TANK PRODUCT LABEL GALLONS 1 UNLEADED SYPHON 11627 9438 5814 2190 2 UNLEADED MAIN 11627 9438 5814 2190 3 PREMIUM 11627 9438 5814 2190 4 0 0 0 0 I60600 NOV 23, 2015 8:27 AM TANK 20 POINT VOLUMES TANK PRODUCT LABEL GALLONS 1 UNLEADED SYPHON 11627 0 0 0 0 9438 0 0 0 0 5814 0 0 0 0 2190 0 0 0 0 2 UNLEADED MAIN 11627 0 0 0 0 9438 0 0 0 0 5814 0 0 0 0 2190 0 0 0 0 3 PREMIUM 11627 0 0 0 0 9438 0 0 0 0 5814 0 0 0 0 2190 0 0 0 0 4 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 I61500 NOV 23, 2015 8:27 AM TANK PRODUCT LABEL METER DATA 1 UNLEADED SYPHON NO 2 UNLEADED MAIN NO 3 PREMIUM NO 4 NO I62F00 NOV 23, 2015 8:27 AM MAG PROBE FLOAT SIZE TANK PRODUCT LABEL FLOAT SIZE: 1 UNLEADED SYPHON 4.0 IN. 2 UNLEADED MAIN 4.0 IN. 3 PREMIUM 4.0 IN. I62700 NOV 23, 2015 8:27 AM TANK HIGH WATER WARNING LIMIT TANK PRODUCT LABEL INCHES 1 UNLEADED SYPHON 1.5 2 UNLEADED MAIN 1.5 3 PREMIUM 1.5 I64200 NOV 23, 2015 8:27 AM WATER ALARM FILTER TANK PRODUCT LABEL 1 UNLEADED SYPHON LOW 2 UNLEADED MAIN LOW 3 PREMIUM LOW I62400 NOV 23, 2015 8:27 AM TANK HIGH WATER LEVEL LIMIT TANK PRODUCT LABEL INCHES 1 UNLEADED SYPHON 2.0 2 UNLEADED MAIN 2.0 3 PREMIUM 2.0 I62800 NOV 23, 2015 8:27 AM TANK MAXIMUM VOLUME LIMIT TANK PRODUCT LABEL GALLONS 1 UNLEADED SYPHON 11627 2 UNLEADED MAIN 11627 3 PREMIUM 11627 4 0 I62300 NOV 23, 2015 8:27 AM TANK OVERFILL LEVEL LIMIT TANK PRODUCT LABEL GALLONS 1 UNLEADED SYPHON 10464 2 UNLEADED MAIN 10464 3 PREMIUM 10464 4 0 I62200 NOV 23, 2015 8:27 AM TANK HIGH PRODUCT LIMIT TANK PRODUCT LABEL GALLONS 1 UNLEADED SYPHON 11046 2 UNLEADED MAIN 11046 3 PREMIUM 11046 4 0 I62900 NOV 23, 2015 8:27 AM TANK DELIVERY REQUIRED LIMIT TANK PRODUCT LABEL GALLONS 1 UNLEADED SYPHON 930 2 UNLEADED MAIN 1163 3 PREMIUM 1163 4 0 I62100 NOV 23, 2015 8:27 AM TANK LOW PRODUCT LIMIT TANK PRODUCT LABEL GALLONS 1 UNLEADED SYPHON 1250 2 UNLEADED MAIN 1250 3 PREMIUM 1500 4 0 I62600 NOV 23, 2015 8:27 AM TANK LEAK ALARM LIMIT TANK PRODUCT LABEL GALLONS 1 UNLEADED SYPHON 99 2 UNLEADED MAIN 99 3 PREMIUM 99 4 99 I62500 NOV 23, 2015 8:27 AM TANK SUDDEN LOSS LIMIT TANK PRODUCT LABEL GALLONS 1 UNLEADED SYPHON 99 2 UNLEADED MAIN 99 3 PREMIUM 99 4 99 I60800 NOV 23, 2015 8:27 AM TANK TILT TANK PRODUCT LABEL INCHES 1 UNLEADED SYPHON 2.00 2 UNLEADED MAIN 2.00 3 PREMIUM 3.00 4 0.00 I60B00 NOV 23, 2015 8:27 AM STICK HEIGHT OFFSET ENABLE STATUS DISABLED I60C00 NOV 23, 2015 8:27 AM TANK STICK HEIGHT OFFSET TANK PRODUCT LABEL INCHES 1 UNLEADED SYPHON 0.00 2 UNLEADED MAIN 0.00 3 PREMIUM 0.00 4 0.00 I61200 NOV 23, 2015 8:27 AM TANK MANIFOLDED PARTNERS TANK PRODUCT LABEL SIPHON MANIFOLDED TANKS LINE MANIFOLDED TANKS 1 UNLEADED SYPHON 2 NONE 2 UNLEADED MAIN 1 NONE 3 PREMIUM NONE NONE 4 NONE NONE I63600 NOV 23, 2015 8:27 AM PERIODIC LEAK TEST MIN VOLUME TANK PRODUCT LABEL GALLONS 1 UNLEADED SYPHON 3488 2 UNLEADED MAIN 3488 3 PREMIUM 3488 4 0 I62A00 NOV 23, 2015 8:27 AM ANNUAL LEAK TEST MIN VOLUME TANK PRODUCT LABEL GALLONS 1 UNLEADED SYPHON 3488 2 UNLEADED MAIN 3488 3 PREMIUM 3488 4 0 I62C00 NOV 23, 2015 8:27 AM TANK PERIODIC TEST TYPE TANK PRODUCT LABEL PERIODIC TEST TYPE 1 UNLEADED SYPHON STANDARD 2 UNLEADED MAIN STANDARD 3 PREMIUM STANDARD 4 STANDARD I62D00 NOV 23, 2015 8:27 AM TANK LEAK TEST FAIL ALARMS TANK PRODUCT LABEL 1 UNLEADED SYPHON GROSS TEST FAIL ALARM DISABLED PERIODIC TEST FAIL ALARM DISABLED ANNUAL TEST FAIL ALARM DISABLED 2 UNLEADED MAIN GROSS TEST FAIL ALARM DISABLED PERIODIC TEST FAIL ALARM DISABLED ANNUAL TEST FAIL ALARM DISABLED 3 PREMIUM GROSS TEST FAIL ALARM DISABLED PERIODIC TEST FAIL ALARM DISABLED ANNUAL TEST FAIL ALARM DISABLED 4 GROSS TEST FAIL ALARM DISABLED PERIODIC TEST FAIL ALARM DISABLED ANNUAL TEST FAIL ALARM DISABLED I63100 NOV 23, 2015 8:27 AM TANK LEAK TEST AVERAGING TANK PRODUCT LABEL ANNUAL PERIODIC 1 UNLEADED SYPHON OFF OFF 2 UNLEADED MAIN OFF OFF 3 PREMIUM OFF OFF 4 OFF OFF I63000 NOV 23, 2015 8:27 AM IN-TANK LEAK TEST NOTIFY TANK PRODUCT LABEL TANK TEST NOTIFY: 1 UNLEADED SYPHON OFF 2 UNLEADED MAIN OFF 3 PREMIUM OFF 4 OFF I63200 NOV 23, 2015 8:27 AM TANK TEST SIPHON BREAK TANK PRODUCT LABEL SIPHON BREAK 1 UNLEADED SYPHON OFF 2 UNLEADED MAIN OFF 3 PREMIUM OFF 4 OFF I61000 NOV 23, 2015 8:27 AM TANK DELIVERY DELAY TANK PRODUCT LABEL 1 UNLEADED SYPHON 5 2 UNLEADED MAIN 1 3 PREMIUM 5 4 1 I63A00 NOV 23, 2015 8:27 AM LOW LEVEL PUMP THRESHOLD FOR SEQUENTIAL LINE MANIFOLD TANK PRODUCT LABEL PUMP THRESHOLD 1 UNLEADED SYPHON 10.00% 2 UNLEADED MAIN 10.00% 3 PREMIUM 10.00% 4 10.00% I61100 NOV 23, 2015 8:27 AM LEAK TEST METHOD - - - - - - - - - - - - TEST ON DATE : ALL TANK MAR 22, 2011 START TIME : 7:55 PM TEST RATE :0.20 GAL/HR DURATION : 2 HOURS TST EARLY STOP:DISABLED I61300 NOV 23, 2015 8:27 AM CSLD PROBABLITY OF DETECTION I61400 NOV 23, 2015 8:27 AM CSLD CLIMATE FACTOR I61600 NOV 23, 2015 8:27 AM TANK PRODUCT LABEL CAL UPDATE 1 UNLEADED SYPHON IMMEDIATE 2 UNLEADED MAIN IMMEDIATE 3 PREMIUM IMMEDIATE 4 IMMEDIATE I61A00 NOV 23, 2015 8:27 AM IN-TANK LEAK TEST EARLY STOP TANK PRODUCT LABEL TST EARLY STOP: 1 UNLEADED SYPHON DISABLED 2 UNLEADED MAIN DISABLED 3 PREMIUM DISABLED 4 DISABLED I61B00 NOV 23, 2015 8:27 AM IN-TANK LEAK GROSS TEST AUTO-CONFIRM I61C00 NOV 23, 2015 8:27 AM CSLD REPORT ONLY I62B00 NOV 23, 2015 8:27 AM TANK LAST ANNUAL TEST TANK PRODUCT LABEL DATE 1 UNLEADED SYPHON ??? 0, 0 2 UNLEADED MAIN ??? 0, 0 3 PREMIUM ??? 0, 0 4 ??? 0, 0 I63300 NOV 23, 2015 8:27 AM LEAK TEST REPORT FORMAT: NORMAL I63400 NOV 23, 2015 8:27 AM RECONCILIATION WARNING LIMIT TANK PRODUCT LABEL GALLONS 1 UNLEADED SYPHON 0 2 UNLEADED MAIN 0 3 PREMIUM 0 4 0 I63500 NOV 23, 2015 8:27 AM RECONCILIATION ALARM LIMIT TANK PRODUCT LABEL GALLONS 1 UNLEADED SYPHON 1 2 UNLEADED MAIN 1 3 PREMIUM 1 4 1 I63900 NOV 23, 2015 8:27 AM ACCU CHART END SHAPE FACTOR TANK PRODUCT LABEL 1 UNLEADED SYPHON END FACTOR: NONE 2 UNLEADED MAIN END FACTOR: NONE 3 PREMIUM END FACTOR: NONE 4 END FACTOR: NONE I78000 NOV 23, 2015 8:27 AM I77700 NOV 23, 2015 8:27 AM I77800 NOV 23, 2015 8:27 AM I78C00 NOV 23, 2015 8:27 AM I78300 NOV 23, 2015 8:27 AM I78F00 NOV 23, 2015 8:27 AM I78700 NOV 23, 2015 8:27 AM I70200 NOV 23, 2015 8:27 AM LIQUID LABEL DEVICE LABEL 1 ANNULAR SYPHON 2 SYPHON FILL SUMP 3 SYPHON TURBINE SUMP 4 ANNULAR MAIN UNL 5 MAIN UNL FILL 6 MAIN UNL TURBINE 7 PREMIUM ANNULAR 8 PREMIUM FILL SUMP 9 PREMIUM TURBINE SUMP 10 1-2 UDC 11 3-4 UDC 12 5-6 UDC 13 7-8 UDC 14 9-10 UDC 15 11-12 UDC 16 I70300 NOV 23, 2015 8:27 AM LIQUID TYPE SENSOR LOCATION TYPE 1 ANNULAR SYPHON TRI-STATE (SINGLE FLOAT) 2 SYPHON FILL SUMP TRI-STATE (SINGLE FLOAT) 3 SYPHON TURBINE SUMP TRI-STATE (SINGLE FLOAT) 4 ANNULAR MAIN UNL TRI-STATE (SINGLE FLOAT) 5 MAIN UNL FILL TRI-STATE (SINGLE FLOAT) 6 MAIN UNL TURBINE TRI-STATE (SINGLE FLOAT) 7 PREMIUM ANNULAR TRI-STATE (SINGLE FLOAT) 8 PREMIUM FILL SUMP TRI-STATE (SINGLE FLOAT) 9 PREMIUM TURBINE SUMP TRI-STATE (SINGLE FLOAT) 10 1-2 UDC TRI-STATE (SINGLE FLOAT) 11 3-4 UDC TRI-STATE (SINGLE FLOAT) 12 5-6 UDC TRI-STATE (SINGLE FLOAT) 13 7-8 UDC TRI-STATE (SINGLE FLOAT) 14 9-10 UDC TRI-STATE (SINGLE FLOAT) 15 11-12 UDC TRI-STATE (SINGLE FLOAT) 16 TRI-STATE (SINGLE FLOAT) I70400 NOV 23, 2015 8:27 AM LIQUID CATEGORY SENSOR LOCATION CATEGORY 1 ANNULAR SYPHON ANNULAR SPACE 2 SYPHON FILL SUMP OTHER SENSORS 3 SYPHON TURBINE SUMP PIPING SUMP 4 ANNULAR MAIN UNL ANNULAR SPACE 5 MAIN UNL FILL OTHER SENSORS 6 MAIN UNL TURBINE STP SUMP 7 PREMIUM ANNULAR ANNULAR SPACE 8 PREMIUM FILL SUMP OTHER SENSORS 9 PREMIUM TURBINE SUMP STP SUMP 10 1-2 UDC DISPENSER PAN 11 3-4 UDC DISPENSER PAN 12 5-6 UDC DISPENSER PAN 13 7-8 UDC DISPENSER PAN 14 9-10 UDC DISPENSER PAN 15 11-12 UDC DISPENSER PAN 16 OTHER SENSORS I74200 NOV 23, 2015 8:27 AM I74300 NOV 23, 2015 8:27 AM I74400 NOV 23, 2015 8:27 AM I74700 NOV 23, 2015 8:27 AM I74800 NOV 23, 2015 8:27 AM I74900 NOV 23, 2015 8:27 AM I7BC00 NOV 23, 2015 8:27 AM I80200 NOV 23, 2015 8:27 AM I80300 NOV 23, 2015 8:27 AM I80400 NOV 23, 2015 8:27 AM I80700 NOV 23, 2015 8:27 AM RELAY LABEL DEVICE LABEL 1 UNLEADED SHUTDOWN 2 PREMIUM SHUTDOWN 3 OVERFILL ALARM 4 I80900 NOV 23, 2015 8:27 AM RELAY ORIENTATION RELAY DESIGNATION ORIENTATION 1 UNLEADED SHUTDOWN NORMALLY CLOSED 2 PREMIUM SHUTDOWN NORMALLY CLOSED 3 OVERFILL ALARM NORMALLY OPEN 4 NORMALLY OPEN I80B00 NOV 23, 2015 8:27 AM RELAY TANK ASSIGNMENT RELAY DESIGNATION TANK 1 UNLEADED SHUTDOWN 2 2 PREMIUM SHUTDOWN 3 3 OVERFILL ALARM NONE 4 NONE I80A00 NOV 23, 2015 8:27 AM RELAY TYPE RELAY DESIGNATION TYPE 1 UNLEADED SHUTDOWN STANDARD 2 PREMIUM SHUTDOWN STANDARD 3 OVERFILL ALARM STANDARD 4 STANDARD I80C00 NOV 23, 2015 8:27 AM I80800 NOV 23, 2015 8:27 AM RELAY SETUP REPORT R 1:UNLEADED SHUTDOWN TYPE: STANDARD NORMALLY CLOSED TANK #: 2 IN-TANK ALARMS ALL:LEAK ALARM LIQUID SENSOR ALMS L 1:FUEL ALARM L 2:FUEL ALARM L 3:FUEL ALARM L 5:FUEL ALARM L 6:FUEL ALARM L10:FUEL ALARM L11:FUEL ALARM L12:FUEL ALARM L13:FUEL ALARM L14:FUEL ALARM L15:FUEL ALARM L 1:SENSOR OUT ALARM L 2:SENSOR OUT ALARM L 3:SENSOR OUT ALARM L 5:SENSOR OUT ALARM L 6:SENSOR OUT ALARM L10:SENSOR OUT ALARM L11:SENSOR OUT ALARM L12:SENSOR OUT ALARM L13:SENSOR OUT ALARM L14:SENSOR OUT ALARM L15:SENSOR OUT ALARM L 1:SHORT ALARM L 2:SHORT ALARM L 3:SHORT ALARM L 5:SHORT ALARM L 6:SHORT ALARM L10:SHORT ALARM L11:SHORT ALARM L12:SHORT ALARM L13:SHORT ALARM L14:SHORT ALARM L15:SHORT ALARM ISD SITE ALARMS ISD GROSS PRES FAIL ISD DEGRD PRES FAIL ISD VAPOR LEAK FAIL ISD VP PRES FAIL ISD VP STATUS FAIL ISD SETUP FAIL ISD SENSOR OUT FAIL ISD HOSE ALARMS ALL:GROSS COLLECT FAIL ALL:DEGRD COLLECT FAIL ALL:FLOW COLLECT FAIL R 2:PREMIUM SHUTDOWN TYPE: STANDARD NORMALLY CLOSED TANK #: 3 LIQUID SENSOR ALMS L 7:FUEL ALARM L 8:FUEL ALARM L 9:FUEL ALARM L10:FUEL ALARM L11:FUEL ALARM L12:FUEL ALARM L13:FUEL ALARM L14:FUEL ALARM L15:FUEL ALARM ALL:SENSOR OUT ALARM ALL:SHORT ALARM ISD SITE ALARMS ISD GROSS PRES FAIL ISD DEGRD PRES FAIL ISD VAPOR LEAK FAIL ISD VP PRES FAIL ISD VP STATUS FAIL ISD SETUP FAIL ISD SENSOR OUT FAIL ISD HOSE ALARMS ALL:GROSS COLLECT FAIL ALL:DEGRD COLLECT FAIL ALL:FLOW COLLECT FAIL R 3:OVERFILL ALARM TYPE: STANDARD NORMALLY OPEN TANK #: NONE IN-TANK ALARMS ALL:OVERFILL ALARM R 4: TYPE: STANDARD NORMALLY OPEN TANK #: NONE - NO ALARM ASSIGNMENTS - I79000 NOV 23, 2015 8:28 AM EDIM:1 VR:330273-002-C TD:97.11.13.15.52 I79100 NOV 23, 2015 8:28 AM I72300 NOV 23, 2015 8:28 AM ARCO 5526 900 MONTEREY ST BAKERSFIELD,CA93305 805-861-1972 SMARTSENSOR ASSIGNMENT DEVICE LABEL CATEGORY 01 1-2 AFM AIR FLOW METER 02 3-4 AFM AIR FLOW METER 03 5-6 AFM AIR FLOW METER 04 7-8 AIR FLOW METER 05 9-10 AFM AIR FLOW METER 06 11-12 AFM AIR FLOW METER 07 UNKNOWN 08 ATMP ATM P SENSOR 09 PRESSURE SENSOR VAPOR PRESSURE 10 UNKNOWN 11 UNKNOWN 12 UNKNOWN 13 UNKNOWN 14 UNKNOWN 15 UNKNOWN 16 CCVP VAPOR VALVE 17 UNKNOWN 18 UNKNOWN 19 UNKNOWN 20 UNKNOWN 21 UNKNOWN 22 UNKNOWN 23 UNKNOWN 24 UNKNOWN 25 UNKNOWN 26 UNKNOWN 27 UNKNOWN 28 UNKNOWN 29 UNKNOWN 30 UNKNOWN 31 UNKNOWN 32 UNKNOWN 33 UNKNOWN 34 UNKNOWN 35 UNKNOWN 36 UNKNOWN 37 UNKNOWN 38 UNKNOWN 39 UNKNOWN 40 UNKNOWN I72A00 NOV 23, 2015 8:28 AM VACUUM SENSOR VOLUME DEVICE LABEL VOLUME IV4E00 NOV 23, 2015 8:28 AM ARCO 5526 900 MONTEREY ST BAKERSFIELD,CA93305 805-861-1972 EVR/ISD SETUP TYPE: BALANCE IV4F00 NOV 23, 2015 8:28 AM ARCO 5526 900 MONTEREY ST BAKERSFIELD,CA93305 805-861-1972 NOZZLE A/L RANGE A/L RATIO: 0.95 - 1.15 IV4000 NOV 23, 2015 8:28 AM ARCO 5526 900 MONTEREY ST BAKERSFIELD,CA93305 805-861-1972 VAPOR PROCESSOR TYPE VEEDER-ROOT POLISHER IV4700 NOV 23, 2015 8:28 AM ARCO 5526 900 MONTEREY ST BAKERSFIELD,CA93305 805-861-1972 ASSESSMENT TIME START TIME: 11:59 PM TIME DELAY MINUTES: 1 IV5200 NOV 23, 2015 8:28 AM ARCO 5526 900 MONTEREY ST BAKERSFIELD,CA93305 805-861-1972 ACCEPT HIGH ORVR: NO IV4A00 NOV 23, 2015 8:28 AM ARCO 5526 900 MONTEREY ST BAKERSFIELD,CA93305 805-861-1972 ISD HOSE TABLE HOSE FP FP AFM REL HOSE ID ID LABEL ID ID LABEL 01 00 01 06 02 BLEND3 02 01 02 06 02 BLEND3 03 02 03 01 02 BLEND3 04 03 04 01 02 BLEND3 05 04 05 02 02 BLEND3 06 05 06 02 02 BLEND3 07 06 07 03 02 BLEND3 08 07 08 03 02 BLEND3 09 08 09 04 02 BLEND3 10 09 10 04 02 BLEND3 11 10 11 05 02 BLEND3 12 11 12 05 02 BLEND3 IV4B00 NOV 23, 2015 8:28 AM ARCO 5526 900 MONTEREY ST BAKERSFIELD,CA93305 805-861-1972 PRODUCT/HOSE MAP TABLE FP AFID M1/H1 M2/H2 M3/H3 M4/H4 00 06 00/01 09/01 01/01 xx/xx 01 06 00/02 09/02 01/02 xx/xx 02 01 00/03 09/03 01/03 xx/xx 03 01 00/04 09/04 01/04 xx/xx 04 02 00/05 09/05 01/05 xx/xx 05 02 00/06 09/06 01/06 xx/xx 06 03 01/07 09/07 00/07 xx/xx 07 03 00/08 09/08 01/08 xx/xx 08 04 00/09 09/09 01/09 xx/xx 09 04 00/10 09/10 01/10 xx/xx 10 05 00/11 01/11 09/11 xx/xx 11 05 00/12 09/12 01/12 xx/xx IV4900 NOV 23, 2015 8:28 AM ARCO 5526 900 MONTEREY ST BAKERSFIELD,CA93305 805-861-1972 LABEL TABLE ID LABEL 01 UNASSIGNED 02 BLEND3 03 REGULAR 04 MID GRADE 05 PREMIUM 06 GOLD 07 BRONZE 08 SILVER 09 BLEND2 10 BLEND4 IV1000 NOV 23, 2015 8:28 AM ISD VERSION: 01.05 Monterey AMPM Responses Received: I10200 NOV 23, 2015 8:24 AM ARCO 5526 900 MONTEREY ST BAKERSFIELD,CA93305 805-861-1972 SYSTEM CONFIGURATION SLOT BOARD TYPE POWER ON RESET CURRENT 1 UNUSED 9743308 9658802 2 7SMARTSENSOR BD 504417 504029 3 8SMARTSENSOR BD 39374 39344 4 INTERSTITIAL BD 200596 200358 5 INTERSTITIAL BD 201603 201238 6 4 PROBE / G.T. 162661 162499 7 UNUSED 9724517 9634158 8 UNUSED 9725264 9640291 9 UNUSED 9718572 9629136 10 RELAY BOARD 14889 14910 11 UNUSED 9718045 9635313 12 UNUSED 9715231 9621980 13 UNUSED 9723627 9636091 14 UNUSED 9713363 9623603 15 UNUSED 9722945 9633469 16 UNUSED 9709737 9632136 COMM 1 ELEC DISP INT. 100441 100409 COMM 2 SERIAL SAT BD 479891 479252 COMM 3 UNUSED 9724484 9627469 COMM 4 UNUSED 9713495 9631114 COMM 5 RS485 SERIAL BD 68398 68255 COMM 6 RS232 SERIAL BD 14999 14999 I90200 NOV 23, 2015 8:24 AM SOFTWARE REVISION LEVEL VERSION 334.00 SOFTWARE# 346334-100-A CREATED - 15.05.29.10.36 S-MODULE# 330160-004-a SYSTEM FEATURES: PERIODIC IN-TANK TESTS ANNUAL IN-TANK TESTS ISD/APM I11100 NOV 23, 2015 8:24 AM ARCO 5526 900 MONTEREY ST BAKERSFIELD,CA93305 805-861-1972 PRIORITY ALARM HISTORY ID CATEGORY DESCRIPTION ALARM TYPE STATE DATE TIME OTHER MISSING HOSE SETUP CLEAR 11-16-15 7:37AM OTHER MISSING RELAY SETUP CLEAR 11-16-15 1:01AM s 1 OTHER 1-2 AFM COMMUNICATION ALARM CLEAR 11-16-15 12:57AM OTHER MISS VAPOR PRES SEN CLEAR 11-16-15 12:47AM OTHER PMC SETUP FAIL CLEAR 11-16-15 12:47AM s 9 OTHER PRESSURE SENSOR COMMUNICATION ALARM CLEAR 11-16-15 12:45AM OTHER MISS VAPOR FLOW MTR CLEAR 11-16-15 12:44AM OTHER PMC SETUP FAIL ALARM 11-16-15 12:44AM OTHER MISSING TANK SETUP CLEAR 11-16-15 12:44AM OTHER MISSING RELAY SETUP ALARM 11-16-15 12:44AM s 6 OTHER 11-12 AFM COMMUNICATION ALARM CLEAR 11-16-15 12:44AM s 5 OTHER 9-10 AFM COMMUNICATION ALARM CLEAR 11-16-15 12:44AM s 4 OTHER 7-8 COMMUNICATION ALARM CLEAR 11-16-15 12:43AM s 9 OTHER PRESSURE SENSOR COMMUNICATION ALARM ALARM 11-16-15 12:42AM s 1 OTHER 1-2 AFM COMMUNICATION ALARM ALARM 11-16-15 12:42AM s 6 OTHER 11-12 AFM COMMUNICATION ALARM ALARM 11-16-15 12:41AM s 5 OTHER 9-10 AFM COMMUNICATION ALARM ALARM 11-16-15 12:41AM s 4 OTHER 7-8 COMMUNICATION ALARM ALARM 11-16-15 12:41AM SYSTEM BATTERY IS OFF CLEAR 5-29-15 8:00AM OTHER MISS VAPOR PRES SEN ALARM 5-29-15 8:00AM OTHER MISS VAPOR FLOW MTR ALARM 5-29-15 8:00AM OTHER MISSING HOSE SETUP ALARM 5-29-15 8:00AM OTHER MISSING TANK SETUP ALARM 5-29-15 8:00AM SYSTEM BATTERY IS OFF ALARM 5-29-15 8:00AM I11200 NOV 23, 2015 8:24 AM ARCO 5526 900 MONTEREY ST BAKERSFIELD,CA93305 805-861-1972 NON-PRIORITY ALARM HISTORY ID CATEGORY DESCRIPTION ALARM TYPE STATE DATE TIME I20600 NOV 23, 2015 8:24 AM ARCO 5526 900 MONTEREY ST BAKERSFIELD,CA93305 805-861-1972 TANK ALARM HISTORY TANK 1 UNLEADED SYPHON TANK 2 UNLEADED MAIN TANK 3 PREMIUM TANK 5 TANK 6 TANK 7 TANK 8 TANK 9 TANK 10 TANK 11 TANK 12 TANK 13 TANK 14 TANK 15 TANK 16 I38200 NOV 23, 2015 8:24 AM I30200 NOV 23, 2015 8:24 AM ARCO 5526 900 MONTEREY ST BAKERSFIELD,CA93305 805-861-1972 LIQUID ALARM HISTORY REPORT SENSOR LOCATION 1 ANNULAR SYPHON 2 SYPHON FILL SUMP 3 SYPHON TURBINE SUMP 4 ANNULAR MAIN UNL 5 MAIN UNL FILL 6 MAIN UNL TURBINE 7 PREMIUM ANNULAR 8 PREMIUM FILL SUMP 9 PREMIUM TURBINE SUMP 10 1-2 UDC 11 3-4 UDC 12 5-6 UDC 13 7-8 UDC 14 9-10 UDC 15 11-12 UDC I31600 NOV 23, 2015 8:24 AM ARCO 5526 900 MONTEREY ST BAKERSFIELD,CA93305 805-861-1972 SMART SENSOR ALARM HISTORY REPORT SENSOR LOCATION 1 1-2 AFM NOV 16, 2015 12:42 AM COMMUNICATION ALARM 2 3-4 AFM 3 5-6 AFM 4 7-8 NOV 16, 2015 12:41 AM COMMUNICATION ALARM 5 9-10 AFM NOV 16, 2015 12:41 AM COMMUNICATION ALARM 6 11-12 AFM NOV 16, 2015 12:41 AM COMMUNICATION ALARM 8 ATMP 9 PRESSURE SENSOR NOV 16, 2015 12:42 AM COMMUNICATION ALARM 16 CCVP I40200 NOV 23, 2015 8:24 AM I40300 NOV 23, 2015 8:24 AM I34200 NOV 23, 2015 8:24 AM I34700 NOV 23, 2015 8:24 AM IV0100 NOV 23, 2015 8:24 AM ARCO 5526 900 MONTEREY ST BAKERSFIELD,CA93305 805-861-1972 ISD ALARM STATUS REPORT EVR TYPE: BALANCE ISD TYPE: 01.05 VAPOR PROCESSOR TYPE: VEEDER-ROOT POLISHER OVERALL STATUS :PASS EVR VAPOR COLLECTION :PASS EVR VAPOR CONTAINMENT :PASS ISD MONITOR UP-TIME :100% EVR/ISD PASS TIME :100% VAPOR PROCESSOR :PASS WARNING ALARMS DATE TIME DESCRIPTION READING VALUE 15-10-27 10:00:28 SENSOR OUT SELFTEST E 1 15-10-26 10:00:09 SENSOR OUT SELFTEST E 1 15-10-26 10:00:09 VAPOR CONTAINMENT LEAKAGE GROSS FAIL 15-10-25 10:00:09 SENSOR OUT SELFTEST E 1 15-10-25 10:00:09 VAPOR CONTAINMENT LEAKAGE GROSS FAIL 15-10-24 10:00:09 SENSOR OUT SELFTEST E 1 15-10-24 10:00:09 VAPOR CONTAINMENT LEAKAGE GROSS FAIL 15-10-23 10:00:09 SENSOR OUT SELFTEST E 1 15-10-22 10:00:09 SENSOR OUT SELFTEST E 1 15-10-21 10:00:09 SENSOR OUT SELFTEST E 1 FAILURE ALARMS DATE TIME DESCRIPTION READING VALUE 15-10-30 10:00:18 SENSOR OUT SELFTEST E 1 15-10-29 10:00:09 SENSOR OUT SELFTEST E 1 15-10-28 10:00:16 SENSOR OUT SELFTEST E 1 14-06-22 10:00:58 VAPOR CONTAINMENT LEAKAGE CFH@2 INCHES WC 15.05 14-04-14 10:01:08 FLOW PERFORMANCE HOSE BLOCKAGE FP10 BLEND3 13-11-04 10:00:09 FLOW PERFORMANCE HOSE BLOCKAGE FP 3 BLEND3 13-11-03 10:00:09 FLOW PERFORMANCE HOSE BLOCKAGE FP 3 BLEND3 13-07-15 10:00:09 FLOW PERFORMANCE HOSE BLOCKAGE FP 3 BLEND3 13-07-14 10:00:09 FLOW PERFORMANCE HOSE BLOCKAGE FP 3 BLEND3 13-07-13 10:00:09 FLOW PERFORMANCE HOSE BLOCKAGE FP 3 BLEND3 SHUTDOWN & MISCELLANEOUS EVENTS DATE TIME DESCRIPTION ACTION/NAME 15-11-22 00:00:09 READINESS ISD:PP EVR:PPP ISD & EVR READY 15-11-21 00:00:47 READINESS ISD:PP EVR:PNP EVR READINESS PENDING 15-11-20 00:00:09 READINESS ISD:PP EVR:PNP EVR READINESS PENDING 15-11-19 00:00:09 READINESS ISD:PP EVR:PNP EVR READINESS PENDING 15-11-18 16:32:20 PROCESSOR MODE AUTOMATIC 15-11-18 15:46:11 PROCESSOR MODE MANUAL 15-11-18 15:46:01 PROCESSOR MODE AUTOMATIC 15-11-18 15:13:49 READINESS ISD:PP EVR:NNN EVR READINESS PENDING 15-11-18 15:13:49 ISD STARTUP 15-11-18 15:12:59 ISD SHUTDOWN Monterey AMPM Responses Received: I10200 NOV 23, 2015 1:48 PM ARCO 5526 900 MONTEREY ST BAKERSFIELD,CA93305 805-861-1972 SYSTEM CONFIGURATION SLOT BOARD TYPE POWER ON RESET CURRENT 1 UNUSED 9743308 9615697 2 7SMARTSENSOR BD 504417 504561 3 8SMARTSENSOR BD 39374 39304 4 INTERSTITIAL BD 200596 200502 5 INTERSTITIAL BD 201603 201293 6 4 PROBE / G.T. 162661 162519 7 UNUSED 9724517 9600686 8 UNUSED 9725264 9593571 9 UNUSED 9718572 9599254 10 RELAY BOARD 14889 14865 11 UNUSED 9718045 9605031 12 UNUSED 9715231 9594570 13 UNUSED 9723627 9595329 14 UNUSED 9713363 9597626 15 UNUSED 9722945 9584979 16 UNUSED 9709737 9597737 COMM 1 ELEC DISP INT. 100441 100438 COMM 2 SERIAL SAT BD 479891 479870 COMM 3 UNUSED 9724484 9589240 COMM 4 UNUSED 9713495 9596020 COMM 5 RS485 SERIAL BD 68398 68342 COMM 6 RS232 SERIAL BD 14999 14999 I90200 NOV 23, 2015 1:48 PM SOFTWARE REVISION LEVEL VERSION 334.00 SOFTWARE# 346334-100-A CREATED - 15.05.29.10.36 S-MODULE# 330160-004-a SYSTEM FEATURES: PERIODIC IN-TANK TESTS ANNUAL IN-TANK TESTS ISD/APM I11100 NOV 23, 2015 1:48 PM ARCO 5526 900 MONTEREY ST BAKERSFIELD,CA93305 805-861-1972 PRIORITY ALARM HISTORY ID CATEGORY DESCRIPTION ALARM TYPE STATE DATE TIME L 7 ANNULAR PREMIUM ANNULAR FUEL ALARM CLEAR 11-23-15 12:43PM L 7 ANNULAR PREMIUM ANNULAR FUEL ALARM ALARM 11-23-15 12:39PM L 7 ANNULAR PREMIUM ANNULAR FUEL ALARM CLEAR 11-23-15 12:39PM L 7 ANNULAR PREMIUM ANNULAR FUEL ALARM ALARM 11-23-15 12:38PM L 7 ANNULAR PREMIUM ANNULAR FUEL ALARM CLEAR 11-23-15 12:37PM L 7 ANNULAR PREMIUM ANNULAR FUEL ALARM ALARM 11-23-15 12:37PM L 7 ANNULAR PREMIUM ANNULAR FUEL ALARM CLEAR 11-23-15 12:34PM L 7 ANNULAR PREMIUM ANNULAR FUEL ALARM ALARM 11-23-15 12:34PM L 7 ANNULAR PREMIUM ANNULAR FUEL ALARM CLEAR 11-23-15 12:00PM L 7 ANNULAR PREMIUM ANNULAR SENSOR OUT ALARM CLEAR 11-23-15 11:51AM L 7 ANNULAR PREMIUM ANNULAR FUEL ALARM ALARM 11-23-15 11:51AM L 4 ANNULAR ANNULAR MAIN UNL SENSOR OUT ALARM CLEAR 11-23-15 11:46AM L 3 PIPE SYPHON TURBINE SUMP SENSOR OUT ALARM CLEAR 11-23-15 11:46AM L 1 ANNULAR ANNULAR SYPHON SENSOR OUT ALARM CLEAR 11-23-15 11:46AM L 2 OTHER SYPHON FILL SUMP SENSOR OUT ALARM CLEAR 11-23-15 11:46AM L 8 OTHER PREMIUM FILL SUMP SENSOR OUT ALARM CLEAR 11-23-15 11:46AM L 6 STP SUMP MAIN UNL TURBINE SENSOR OUT ALARM CLEAR 11-23-15 11:46AM L15 DISP PAN 11-12 UDC SENSOR OUT ALARM CLEAR 11-23-15 11:46AM L 5 OTHER MAIN UNL FILL SENSOR OUT ALARM CLEAR 11-23-15 11:46AM L11 DISP PAN 3-4 UDC SENSOR OUT ALARM CLEAR 11-23-15 11:45AM L14 DISP PAN 9-10 UDC SENSOR OUT ALARM CLEAR 11-23-15 11:45AM L10 DISP PAN 1-2 UDC SENSOR OUT ALARM CLEAR 11-23-15 11:45AM L13 DISP PAN 7-8 UDC SENSOR OUT ALARM CLEAR 11-23-15 11:45AM L12 DISP PAN 5-6 UDC SENSOR OUT ALARM CLEAR 11-23-15 11:45AM L 9 STP SUMP PREMIUM TURBINE SUMP SENSOR OUT ALARM CLEAR 11-23-15 11:45AM L 8 OTHER PREMIUM FILL SUMP SENSOR OUT ALARM ALARM 11-23-15 11:45AM L 4 ANNULAR ANNULAR MAIN UNL SENSOR OUT ALARM ALARM 11-23-15 11:45AM L 1 ANNULAR ANNULAR SYPHON SENSOR OUT ALARM ALARM 11-23-15 11:45AM L 3 PIPE SYPHON TURBINE SUMP SENSOR OUT ALARM ALARM 11-23-15 11:45AM L 6 STP SUMP MAIN UNL TURBINE SENSOR OUT ALARM ALARM 11-23-15 11:45AM L 2 OTHER SYPHON FILL SUMP SENSOR OUT ALARM ALARM 11-23-15 11:45AM L15 DISP PAN 11-12 UDC SENSOR OUT ALARM ALARM 11-23-15 11:45AM L10 DISP PAN 1-2 UDC SENSOR OUT ALARM ALARM 11-23-15 11:45AM L 9 STP SUMP PREMIUM TURBINE SUMP SENSOR OUT ALARM ALARM 11-23-15 11:45AM L14 DISP PAN 9-10 UDC SENSOR OUT ALARM ALARM 11-23-15 11:45AM L12 DISP PAN 5-6 UDC SENSOR OUT ALARM ALARM 11-23-15 11:45AM L 5 OTHER MAIN UNL FILL SENSOR OUT ALARM ALARM 11-23-15 11:45AM L13 DISP PAN 7-8 UDC SENSOR OUT ALARM ALARM 11-23-15 11:45AM L11 DISP PAN 3-4 UDC SENSOR OUT ALARM ALARM 11-23-15 11:44AM T 1 TANK UNLEADED SYPHON PROBE OUT CLEAR 11-23-15 11:36AM T 1 TANK UNLEADED SYPHON OVERFILL ALARM CLEAR 11-23-15 11:36AM T 1 TANK UNLEADED SYPHON PROBE OUT ALARM 11-23-15 11:36AM T 1 TANK UNLEADED SYPHON OVERFILL ALARM ALARM 11-23-15 11:35AM T 1 TANK UNLEADED SYPHON MAX PRODUCT ALARM CLEAR 11-23-15 11:28AM T 1 TANK UNLEADED SYPHON MAX PRODUCT ALARM ALARM 11-23-15 11:27AM T 1 TANK UNLEADED SYPHON PROBE OUT CLEAR 11-23-15 11:26AM T 1 TANK UNLEADED SYPHON PROBE OUT ALARM 11-23-15 11:25AM T 2 TANK UNLEADED MAIN PROBE OUT CLEAR 11-23-15 11:24AM T 2 TANK UNLEADED MAIN OVERFILL ALARM CLEAR 11-23-15 11:23AM T 2 TANK UNLEADED MAIN PROBE OUT ALARM 11-23-15 11:23AM I11200 NOV 23, 2015 1:48 PM ARCO 5526 900 MONTEREY ST BAKERSFIELD,CA93305 805-861-1972 NON-PRIORITY ALARM HISTORY ID CATEGORY DESCRIPTION ALARM TYPE STATE DATE TIME T 1 TANK UNLEADED SYPHON HIGH PRODUCT ALARM CLEAR 11-23-15 11:35AM T 1 TANK UNLEADED SYPHON HIGH PRODUCT ALARM ALARM 11-23-15 11:27AM T 2 TANK UNLEADED MAIN HIGH PRODUCT ALARM CLEAR 11-23-15 11:23AM T 2 TANK UNLEADED MAIN HIGH PRODUCT ALARM ALARM 11-23-15 11:23AM T 2 TANK UNLEADED MAIN HIGH PRODUCT ALARM CLEAR 11-23-15 11:21AM T 2 TANK UNLEADED MAIN HIGH PRODUCT ALARM ALARM 11-23-15 11:21AM T 3 TANK PREMIUM HIGH PRODUCT ALARM CLEAR 11-23-15 11:18AM T 3 TANK PREMIUM HIGH PRODUCT ALARM ALARM 11-23-15 11:17AM T 3 TANK PREMIUM INVALID FUEL LEVEL CLEAR 11-23-15 11:17AM T 3 TANK PREMIUM DELIVERY NEEDED CLEAR 11-23-15 11:17AM T 3 TANK PREMIUM INVALID FUEL LEVEL ALARM 11-23-15 11:14AM T 3 TANK PREMIUM DELIVERY NEEDED ALARM 11-23-15 11:14AM L 7 ANNULAR PREMIUM ANNULAR SETUP DATA WARNING CLEAR 11-23-15 9:56AM L 7 ANNULAR PREMIUM ANNULAR SETUP DATA WARNING ALARM 11-23-15 9:55AM I20600 NOV 23, 2015 1:48 PM ARCO 5526 900 MONTEREY ST BAKERSFIELD,CA93305 805-861-1972 TANK ALARM HISTORY TANK 1 UNLEADED SYPHON OVERFILL ALARM NOV 23, 2015 11:35 AM HIGH PRODUCT ALARM NOV 23, 2015 11:27 AM PROBE OUT NOV 23, 2015 11:36 AM NOV 23, 2015 11:25 AM MAX PRODUCT ALARM NOV 23, 2015 11:27 AM TANK 2 UNLEADED MAIN OVERFILL ALARM NOV 23, 2015 11:23 AM HIGH PRODUCT ALARM NOV 23, 2015 11:23 AM NOV 23, 2015 11:21 AM PROBE OUT NOV 23, 2015 11:23 AM NOV 23, 2015 11:20 AM TANK 3 PREMIUM OVERFILL ALARM NOV 23, 2015 11:17 AM LOW PRODUCT ALARM NOV 23, 2015 11:14 AM HIGH PRODUCT ALARM NOV 23, 2015 11:17 AM INVALID FUEL LEVEL NOV 23, 2015 11:14 AM PROBE OUT NOV 23, 2015 11:18 AM NOV 23, 2015 11:14 AM DELIVERY NEEDED NOV 23, 2015 11:14 AM TANK 5 TANK 6 TANK 7 TANK 8 TANK 9 TANK 10 TANK 11 TANK 12 TANK 13 TANK 14 TANK 15 TANK 16 I38200 NOV 23, 2015 1:48 PM I30200 NOV 23, 2015 1:48 PM ARCO 5526 900 MONTEREY ST BAKERSFIELD,CA93305 805-861-1972 LIQUID ALARM HISTORY REPORT SENSOR LOCATION 1 ANNULAR SYPHON NOV 23, 2015 11:45 AM SENSOR OUT ALARM NOV 23, 2015 9:26 AM FUEL ALARM 2 SYPHON FILL SUMP NOV 23, 2015 11:45 AM SENSOR OUT ALARM 3 SYPHON TURBINE SUMP NOV 23, 2015 11:45 AM SENSOR OUT ALARM NOV 23, 2015 9:16 AM FUEL ALARM 4 ANNULAR MAIN UNL NOV 23, 2015 11:45 AM SENSOR OUT ALARM NOV 23, 2015 9:35 AM FUEL ALARM 5 MAIN UNL FILL NOV 23, 2015 11:45 AM SENSOR OUT ALARM 6 MAIN UNL TURBINE NOV 23, 2015 11:45 AM SENSOR OUT ALARM NOV 23, 2015 9:22 AM FUEL ALARM 7 PREMIUM ANNULAR NOV 23, 2015 12:39 PM FUEL ALARM NOV 23, 2015 12:38 PM FUEL ALARM NOV 23, 2015 12:37 PM FUEL ALARM 8 PREMIUM FILL SUMP NOV 23, 2015 11:45 AM SENSOR OUT ALARM 9 PREMIUM TURBINE SUMP NOV 23, 2015 11:45 AM SENSOR OUT ALARM NOV 23, 2015 9:20 AM FUEL ALARM 10 1-2 UDC NOV 23, 2015 11:45 AM SENSOR OUT ALARM NOV 23, 2015 10:11 AM FUEL ALARM 11 3-4 UDC NOV 23, 2015 11:44 AM SENSOR OUT ALARM NOV 23, 2015 10:22 AM FUEL ALARM 12 5-6 UDC NOV 23, 2015 11:45 AM SENSOR OUT ALARM NOV 23, 2015 10:30 AM FUEL ALARM 13 7-8 UDC NOV 23, 2015 11:45 AM SENSOR OUT ALARM NOV 23, 2015 10:26 AM FUEL ALARM 14 9-10 UDC NOV 23, 2015 11:45 AM SENSOR OUT ALARM NOV 23, 2015 10:33 AM FUEL ALARM 15 11-12 UDC NOV 23, 2015 11:45 AM SENSOR OUT ALARM NOV 23, 2015 10:39 AM FUEL ALARM I31600 NOV 23, 2015 1:48 PM ARCO 5526 900 MONTEREY ST BAKERSFIELD,CA93305 805-861-1972 SMART SENSOR ALARM HISTORY REPORT SENSOR LOCATION 1 1-2 AFM NOV 16, 2015 12:42 AM COMMUNICATION ALARM 2 3-4 AFM 3 5-6 AFM 4 7-8 NOV 16, 2015 12:41 AM COMMUNICATION ALARM 5 9-10 AFM NOV 16, 2015 12:41 AM COMMUNICATION ALARM 6 11-12 AFM NOV 16, 2015 12:41 AM COMMUNICATION ALARM 8 ATMP 9 PRESSURE SENSOR NOV 16, 2015 12:42 AM COMMUNICATION ALARM 16 CCVP I40200 NOV 23, 2015 1:48 PM I40300 NOV 23, 2015 1:48 PM I34200 NOV 23, 2015 1:48 PM I34700 NOV 23, 2015 1:48 PM IV0100 NOV 23, 2015 1:48 PM ARCO 5526 900 MONTEREY ST BAKERSFIELD,CA93305 805-861-1972 ISD ALARM STATUS REPORT EVR TYPE: BALANCE ISD TYPE: 01.05 VAPOR PROCESSOR TYPE: VEEDER-ROOT POLISHER OVERALL STATUS :PASS EVR VAPOR COLLECTION :PASS EVR VAPOR CONTAINMENT :PASS ISD MONITOR UP-TIME :100% EVR/ISD PASS TIME :100% VAPOR PROCESSOR :PASS WARNING ALARMS DATE TIME DESCRIPTION READING VALUE 15-10-27 10:00:28 SENSOR OUT SELFTEST E 1 15-10-26 10:00:09 SENSOR OUT SELFTEST E 1 15-10-26 10:00:09 VAPOR CONTAINMENT LEAKAGE GROSS FAIL 15-10-25 10:00:09 SENSOR OUT SELFTEST E 1 15-10-25 10:00:09 VAPOR CONTAINMENT LEAKAGE GROSS FAIL 15-10-24 10:00:09 SENSOR OUT SELFTEST E 1 15-10-24 10:00:09 VAPOR CONTAINMENT LEAKAGE GROSS FAIL 15-10-23 10:00:09 SENSOR OUT SELFTEST E 1 15-10-22 10:00:09 SENSOR OUT SELFTEST E 1 15-10-21 10:00:09 SENSOR OUT SELFTEST E 1 FAILURE ALARMS DATE TIME DESCRIPTION READING VALUE 15-10-30 10:00:18 SENSOR OUT SELFTEST E 1 15-10-29 10:00:09 SENSOR OUT SELFTEST E 1 15-10-28 10:00:16 SENSOR OUT SELFTEST E 1 14-06-22 10:00:58 VAPOR CONTAINMENT LEAKAGE CFH@2 INCHES WC 15.05 14-04-14 10:01:08 FLOW PERFORMANCE HOSE BLOCKAGE FP10 BLEND3 13-11-04 10:00:09 FLOW PERFORMANCE HOSE BLOCKAGE FP 3 BLEND3 13-11-03 10:00:09 FLOW PERFORMANCE HOSE BLOCKAGE FP 3 BLEND3 13-07-15 10:00:09 FLOW PERFORMANCE HOSE BLOCKAGE FP 3 BLEND3 13-07-14 10:00:09 FLOW PERFORMANCE HOSE BLOCKAGE FP 3 BLEND3 13-07-13 10:00:09 FLOW PERFORMANCE HOSE BLOCKAGE FP 3 BLEND3 SHUTDOWN & MISCELLANEOUS EVENTS DATE TIME DESCRIPTION ACTION/NAME 15-11-23 11:48:27 READINESS ISD:PP EVR:NNN EVR READINESS PENDING 15-11-23 11:48:27 ISD STARTUP 15-11-23 11:47:36 ISD SHUTDOWN 15-11-22 00:00:09 READINESS ISD:PP EVR:PPP ISD & EVR READY 15-11-21 00:00:47 READINESS ISD:PP EVR:PNP EVR READINESS PENDING 15-11-20 00:00:09 READINESS ISD:PP EVR:PNP EVR READINESS PENDING 15-11-19 00:00:09 READINESS ISD:PP EVR:PNP EVR READINESS PENDING 15-11-18 16:32:20 PROCESSOR MODE AUTOMATIC 15-11-18 15:46:11 PROCESSOR MODE MANUAL 15-11-18 15:46:01 PROCESSOR MODE AUTOMATIC SWRCB, January 2006 Spill Bucket Testing Report Form This form is intended for use by contractors performing annual testing of UST spill containment structures. The completed form and printouts from tests (if applicable), should be provided to the facility owner/operator forsubmittal to the local regulatory agency. 1.FACILITY INFORMATION Facility Name:Date of Testing: Facility Address: Facility Contact:Phone: Date Local Agency Was Notified of Testing : Name of Local Agency Inspector (if present during testing): 2.TESTING CONTRACTOR INFORMATION Company Name:Confidence UST Services, Inc. Technician Conducting Test: Credentials1:CSLB Contractor ICC Service Tech. SWRCB Tank Tester Other (Specify) License Number(s):CSLB#804904 ICC# 3.SPILL BUCKET TESTING INFORMATION Test Method Used:Hydrostatic Vacuum Other Test Equipment Used:Lake TestEquipment Resolution:0.0625” Identify Spill Bucket (By Tank Number, Stored Product, etc.) 1234 Bucket Installation Type: Direct Bury Contained in Sump Direct Bury Contained in Sump Direct Bury Contained in Sump Direct Bury Contained in Sump Bucket Diameter: Bucket Depth: Wait time between applying vacuum/water and start of test: Test Start Time (TI): Initial Reading (RI): Test End Time (TF): Final Reading (RF): Test Duration (TF – TI): Change in Reading (RF -RI): Pass/Fail Threshold or Criteria: Test Result: Pass Fail Pass Fail Pass Fail Pass Fail Comments –(include information on repairs made prior to testing, and recommended follow-up for failed tests) CERTIFICATION OF TECHNICIAN RESPONSIBLE FOR CONDUCTING THIS TESTING I hereby certify that all the information contained in this report is true, accurate, and in full compliance with legal requirements. Technician’s Signature:________________________________________________ Date:_________ 1 State laws and regulations do not currently require testing to be performed by a qualified contractor. However, local requirements may be more stringent. RamcoExpress 12/16/2015 2222FStreet Bakersfield,CA93301 Rami(661)324-1758 11/12/2015 Shane Gardner AustinSterling 8339953-UT Regular 12.00" 11.25" 5min. 9:15 am 8.75" 10:15 am 8.75" 1hour 0.00" 0.0625" Plus 12.00" 11.25" 5min. 9:15 am 7.75" 10:15 am 7.75" 1hour 0.00" 0.0625"0.0625" Super 12.00" 11.25" 5min. 9:15 am 7.00" 10:15 am 7.00" 1hour 0.00" 12/16/2015