HomeMy WebLinkAboutINSPECTION REPORT 2015Underground Storage Tan rogram DW Inspection Rep 'A Permission to Inspect: BAKERSFIELD FIRE DEPARTMENT Prevention Services Division 2101 H Street Bakersfield, CA 93301 Phone: 661 -326 -3979 Fax: 661 -852 -2171 �r f� Business Name: KERN HIGH SCHOOL DIST TRANS DEPT -15- 021 - 003244 Date: 12/7/2015 Address Name: 3701 E Belle Ter- CAL000129669 Inspector Name: Shane Gardner #8248557 Inspection Type: Routine Report: Final NVO = No Violation Observed OUT = Out of Compliance NA = Not Applicable UD = Undetermined COS = Corrected On Site RPT = Repeat Violation Violation Program Requirement ° o SOC Comments No m cc o z O z M v m W a> File Review Facility Tank Information 2030021 Facility has a valid Permit Tank 1- 12000- DW -REG to Operate from the Tank 2- 12000- DW -DSL CUPA - 23 CCR 16 2712(i); ® ❑ ❑ ❑ ❑ ❑ None Tank 3- 1000 -DW -Used Oil HSC 6.7 25284 Tank 4- 2010010 UST Operating Permit Application for Facility information and Tank information ® ❑ ❑ ❑ ❑ ❑ None submitted /maintained - 23 CCR 16 2711; HSC 6.7 25286 a 2010001 Current BOE number submitted to the CUPA ® ❑ ❑ ❑ ❑ None and /or CERS - HSC 6.7 25286(c 2030011 UST compliance statement and /or Designated Operator ® ❑ ❑ ❑ ❑ None current certification submitted - 23 CCR 16 2715(a), 2715(b 2030046 A complete and accurate response plan has been submitted, approved and ❑ ® ❑ 1:1 ❑ ❑ None maintained - 23 CCR 16 2632, 2634(e), 2641(h), 2712(1) 2030041 A complete and accurate plot plan has been submitted, approved and ❑ ® ❑ ❑ ❑ ❑ Minor maintained - 23 CCR 16 2632 (1)(C), 2711(a)(8) 2010006 Owner /Operator has not made false statements or representation on any ® ❑ ❑ ❑ ❑ ❑ None required document - HSC 6.7 25299 2010003 Owner /Operator has a DO and /or informed the CUPA of any change (s) ® ❑ ❑ ❑ ❑ F-1 None within 30 days - 23 CCR 16 2715(a) Violation Program Requirement 0. 0 C S -0 C Comments No a 0 (L 4) %_ Q) 0 z 0 z C) W Testing 2030002 Owner/Operator has 25 days late tested and certified leak None detection equipment annually - 23 CCR 16 2638 2030048 Secondary containment testing conducted every 36 months in accordance ❑ ❑ ❑ ❑ None with requirements - 23 CCR 16 2637 2030055 Spill buckets have been 25 days late tested annually as None requir d - HSC 6.7 25284.2 2010009 Secondary containment test results submitted to the CUPA within 30 days None after the test - 23 CCR 16 2637(e) 2030064 CUPA was poperly notified within the prescribed number of None hours prior to testing - 23 CCR 16 2637(0, 2638(e), 2643(8), 2644.1(a)(4) Install/Repair 2060009 Permits obtained to install, replace, repair, or E ❑ ❑ ❑ ❑ ❑ None modify part of the UST system - 23 CCR 16 2712 UST System Observation General Monitoring 2030003 Leak detection system maintains continuous RD monitoring that activates None ❑ an audible and visual Yes alarm - 23 CCR 16 2632, 2634, 2636, 2666 2030016 The annular space of the tank, piping and sumps are continuously RD monitored and activates 2 ❑ ❑ ❑ ❑ ❑ None ❑ the alarm - 23 CCR 16 Yes 2631(8), 2632(c)(2)(A)&(8), 2633(c), 2636(o 2030017 Product piping outside the UDC is fail-safe and shuts down the pump or 0 ❑ ❑ ❑ ❑ ❑ None restricts flow - 23 CCR 16 2636(1) (5) 2030018 Turbine sump monitor activates an audible and RD visual alarm or stops the None ❑ flow of at the dispenser - Yes 23 CCR 16 2636(t) (1) Underground Storage Tank Program - DW Inspection Report v 2.0 Violation Program Requirement ,o SOC Comments No d "0 .� °- z O z D 0 W o> 2030019 Monitoring system in the UDCs activates an audible and visual alarm ® ❑ ❑ ❑ ❑ ❑ None or stops the flow at the UDC -23 CCR 16 26360(1 2030043 Leak detection equipment properly programmed or RD properly operated - 23 ® ❑ ❑ ❑ ❑ ❑ None ❑ CCR 16 2632, 2634, 2636, Yes 2666 2060005 System constructed with a monitoring system capable of detecting entry ® ❑ ❑ ❑ ❑ ❑ None into secondary containment - HSC 6.7 25291 b 2060014 Correct leak detection equipment installed for RD the type of system ® ❑ ❑ ❑ ❑ ❑ None ❑ present - 23 CCR 16 2638; Yes HSC 6.7 25290.1, 25290.2, 25291 2060015 Sensor located in the RD proper position /location - ® ❑ ❑ ❑ ❑ ❑ None ❑ 23 CCR 16 2630(d), 2641(a) Yes 2030062 Facility is in compliance with not tampering with or RD disabling leak detection ® ❑ ❑ ❑ ❑ ❑ None ❑ devices or alarms - HSC Yes 6.7 25299(a)(9) 2060022 System constructed with a monitoring system capable of detecting entry ® ❑ ❑ ❑ ❑ ❑ None into secondary containment - HSC 6.7 25290.2(d) 2030034 Tag /sticker on affixed monitoring equipment being certified, repaired, ® ❑ ❑ ❑ ❑ ❑ None or replaced - 23 CCR 16 2638 (0 VPH Monitoring VPH 2030065 Interstitial monitoring of the annular spaces of the RD UST is properly ❑ ❑ ® ❑ ❑ ❑ None ❑ maintained - HSC 6.7 Yes 25290.1( 2060023 System constructed with a monitoring system capable of detecting entry into secondary ❑ ❑ ® ❑ ❑ ❑ None containment - HSC 6.7 25290.1(d) Underground Storage Tank Program - DW Inspection Report v 2.0 Violation Program Requirement 0 0.0 S O-C Comments No 0 0 . 16.0 cc 0) 0 Z 0 Z M M Q W Line Leak Detector 2060012 Line leak detector installed on pressurized RD piping system - HSC 6.7 M F-1 n [-1 one None ❑ 25290. 1 (h), 25290.2(g), 25291(o, 25292(e), Yes 2636 (2) 2030026 Line leak detectors detect a 3 gph leak and/or RD audible and visual alarm None F1 function properly - 23 CCR 16 2636(0(6), Yes 2666(c) 2030027 Turbine shuts down when a leak is detected or RD when line leak detector is F-1 ❑ N ❑ ❑ ❑ None r-1 disconnected - 23 CCR 16 Yes 2666(c) 2030025 Pressurized piping able to detect a 3.0 gph leak RD within an hour, and n n F] n ❑ None F] restricts the flow or Yes alarms - 23 CCR 16 2636(0(2) Secondary Containment 2060010 UST storing a hazardous RD substance o dary None n containment HSC 6.7 Yes 25292 Underground Storage Tank Program - DW Inspection Report v 2.0 Violation Program Requirement 4- 0 Q).o SOC Comments No ? :) < 13 0 0. O)o Z 0 Z 05 2030008 UDC, sumps, and/or other secondary containment in good Z None condition and/or are free of debris/liquid - HSC 6.7 25290.1, 25290.2, 25291 2030040 Secondarily contained RD piping maintained to allow Z None ❑ liquid to drain into sump - Yes 23 CCR 16 2630(d), 2641(a) 2060006 Secondary containment piping slopes back to the Z None collection sump - 23 CCR 16 263(c) 2030047 Secondary containment maintained tight and has been confirmed by testing Z ❑ ❑ E:] ❑ ❑ None - 23 CCR 16 2662; HSC 6.7 25290.1(c) (2), 25290.2(c) (2), 25291 a , 25292(e) 2030060 Entry fittings in secondary containment for UST system maintained Z None tight/sealed - 23 CCR 16 2630, 2635(d), 2636(c), 2666 2060020 Spill bucket is installed and has a functional drain RP valve or other means to None ❑ remove liquid - 23 CCR 16 Yes 2635(b), 2665 2030054 Spill bucket maintained in RP good condition and free of Z 1:1 ❑ ❑ E - In None ❑ debris and/or liquid - 23 Yes CCR 16 2635(b), 2715(c)(2) 2060019 Spill bucket to has a minimum capacity of five Z None gallons - 23 CCR 16 2635(b), 2665 Overfill * 2030035 UST system is operated to prevent unauthorized RP release, including spills Z ❑ ❑ ❑ ❑ ❑ None ❑ and overfills - HSC 6.7 Yes 25292.1 (a) 2030036 Overfill prevention system has not been overridden RP and meets overfill Z ❑ ❑ None ❑ requirements - 23 CCR 16 Yes 2635(b)(2), 2665 Underground Storage Tank Program - DW Inspection Report v 2.0 Violation Program Requirement m SOC Comments No I-- =) < C). co 0 I 0. -- 0)0 z 0 z D 0 w On Site Records Certifications 2030023 Required designated operators or contractors maintain a proper and 0 ❑ ❑ ❑ ❑ ❑ None current ICC certification - 23 CCR 16 2715 2030024 Service technician, installer, and/ or employee maintain a None proper license - 23 CCR 162715 2030031 Employee or contractor obtained and maintained proper manufacturer ❑ ❑ None certification - 23 CCR 16 2715 2010007 Submit/maintain current Certificate of Financial Responsibility /mechanism of financial assurance - 0 F1 n ❑ El None 23 CCR 16 2711; 23 CCR 18 2808.1, 2809-2809.2, HSC 6.7 25292.2; HSC 6.75 25299.30-25299.34 Designated Operator 2010004 Copies of DO inspections for last 12 months and list of trained employees 0 ❑ ❑ ❑ ❑ ❑ None maintained - 23 CCR 16 2715 2030013 Designated operator properly conducted the monthly inspection and None the reports are complete - 23 CCR 16 2715 2030010 DO notified operator of any condition observed during the monthly 1:1 ❑ ❑ ❑ None inspection that may require action - 23 CCR 16 2715(d) 2030012 DO employee training performed, current for at least one employee on 2 ❑ ❑ ❑ ❑ ❑ None site, and a log kept - 23 CCR 16 2715(c)(6), 2715(1) Underground Storage Tank Program - DW Inspection Report v 2.0 Violation Program Requirement 4- 0 0 SOC Comments No a 0 0. 0a Z 0 Z Logs 2030001 Leak detection alarm logs, maintenance and RD records ' of appropriate ❑ ❑ ❑ None ❑ follow-up actions maintained - 23 CCR 16 Yes 2632, 2634, 2712(b) Maintenance/Tests 2010008 Monitoring, maintenance, repairs, linings, and RD upgrade records ❑ ❑ None ❑ maintained for the proper Yes time period - 23 CCR 16 2712(b) Documentation 2030033 Failure to maintain on site an approved monitoring ❑ ❑ ❑ [:j None plan - 23 CCR 16 2632, 2634, 2711, 2712(1) 2030037 Written agreement between the tank owner and tank operator to monitor the tank system Z ❑ ❑ ❑ ❑ ❑ None is maintained - 23 CCR 16 2620(b); HSC 6.7 25284(a)(3) 2030061 Suspected or actual unauthorized release RD reported in appropriate ❑ ❑ Z ❑ 1:1 ❑ None ❑ time frame - HSC 6.7 Yes 29294,29295 General Operating Requirements Permit Condition/Approval 2030039 Compliance with all operating permit Z 1:1 D ❑ ❑ ❑ None conditions - 23 CCR 16 2712, HSC 6.7 25299 2030059 UST system maintained in accordance with exclusion/exemption 1:1 ❑ ❑ ❑ ❑ None status - HSC 6.7 25281.6, 25283.5 2030014 Owner/Operator received approval and has implemented a training ❑ 1:1 Z ❑ ❑ ❑ None program at an unstaffed facility - 23 CCR 16 2715 (2) 2030015 Facility exhibited that the method used to monitor the tank meets the monitoring methods in None 2643(f) - 23 CCR 16 2643 Underground Storage Tank Program - DW Inspection Report v 2.0 Violation Program Requirement ° o SOC Comments No OO D <t o O a �o z O z M V W of Red Tag 2030045 Red Tag information is legible and has not been ❑ ❑ ® ❑ ❑ ❑ None tampered with - 23 CCR 16 2717.1( 2030044 Facility did not allow for deposit of petroleum into a UST that has a red tag ❑ ❑ ® ❑ ❑ ❑ None affixed to the fill - 23 CCR 162717.1(0 Install /Repair 2060024 UST system is made of or lined with materials that are compatible with the ® ❑ ❑ ❑ ❑ ❑ None substance stored - 23 CCR 16 2631.1 2060021 Striker plate installed and positioned correctly - 23 ® ❑ ❑ ❑ ❑ ❑ None CCR 16 2631(c), 2662(d ❑ There were no violations noted for this inspection. ®This report shall serve as a "NOTICE TO COMPLY" for Minor Violations, and a "NOTICE OF VIOLATION" for Major violations. You are, hereby, ordered to correct the above noted violations within 30 days, or according to correction summaries provided. Formal enforcement and /or penalty assessment may be initiated for any violations noted, and for those not corrected in a timely manner. (NOTE: If this is a preliminary report, a final report will follow.) Inspectors Signature:Ci;� Date: 1 z'-'7 `'- /S"— Inspector: Enter # of Violations: RD: � RP. Check one box for facility Significant Operational Status (SOC) to be reported to SWRCB and US EPA: tT-SOC with both Release Detection and Release Detection (Facility has no Release Prevention and no Release Prevention Violations) ❑ Not in SOC (Facility has both Release Prevention and Release Detection Violations) ❑SOC with Release Detection only (Facility has no Release Detection violations but one or more Release Prevention violations) ❑ SOC with Release Prevention only (Facility has no Release Prevention violations but one or more Release Detection violations) Underground Storage Tank Program - DW Inspection Report v 2.0