HomeMy WebLinkAbout2016 FMC CUPA INSP. REPORTBakersfield, Fire-Department Prevention
2101 H St
Bakersfield CA. 93301
661-326-3911
Underground Storage Tank Program
SW Inspection Report
NOTICE TO COMPLY/NOTICE OF VIOLATION
Business Name: Wholesale Fuels, Inc. 1001
Date:02/11/2016
Address Name: 2200 East Brundage Lane, Bakersfield, CA93307
Inspector Name: Kristopher Karns (8292402)
Inspection Type: Routine
[ Report :Final
NVO = No Violation Observed OUT = Out of Compliance NA = Not Applicable UD = Undetermined
COS = Corrected On Site RPT = Repeat Violation
Violation
Program Requirement
4-
0 00
SOC
Comments
No
0
CO)
0
Is-%
00
z
0
z
M
0
4) -
>
File Review
Facility Tank Information
2030021
Facility has a valid Permit
Tank 1 - 10000-CLR DIES -SW
to Operate from the
Tank 2 - 10000-DYED DIES -SW
CUPA - 23 CCR 16 2712(i);
Tank 3 - 20000-CLR DIES -SW
HSC 6.7 25284
None
Tank 4 - 20000-REG UNL -SW
Tank 5 - 20000 - DYED DIES -SW
Tank 6 - 20000 - DYED DIES -SW
2010010
UST Operating Permit
Application for Facility
information and Tank
information
None
submitted/maintained - 23
CCR 16 2711; HSC 6.7
25286(a)
2010001
Current BOE number
submitted to the CUPA
None
and/or CERS - HSC 6.7
25286(c)
2030011
UST compliance
statement and/or
Designated Operator
None
current certification
submitted - 23 CCR 16
2715(a), 2715(b)
2030046
A complete and accurate
response plan has been
submitted, approved and
'&':: ENI
❑
❑ I
None
maintained - 23 CCR 16
2632, 2634(e), 2641(h),
2712(i)
2030041
A complete and accurate
UST Plot plan not accepted in CERS on
plot plan has been -
12/28/2015 must include sensor
submitted, approved and
❑
None
location.
maintained - 23 CCR 16
2632(4 )(1)(C), 2711(a)
2010006
Owner/Operator has not
UST Monitoring Plan indicates T-1 and
made false statements or
T-2 as using ball floats for overfill when
representation on any
there are no ball floats for T-1 or T-2.
required document - HSC
None
T-1 and T-2 states that pr6cision
product line testing is conducted, when
6.725299
it is unable to be conducted as both
lines do not have ball valves installed
and are currently not testable.
Bakersfield Fire Department Prevention
2101 H St
Bakersfield CA. 93301
661-326-3911
Underground Storage Tank Program
SW Inspection Report
NOTICE TO COMPLY/NOTICE OF VIOLATION
Violation
Program Requirement
48 0
0
SOC
Comments
No
O>
0 V)
a
o
Z
0
Z
M
0
W
4)
0 >
2010003
Owner/Operator has a
DO and/or informed the
CUPA of any change (s)
None
within 30 days - 23 CCR
16 2715(a)
Testing
2030002
Owner/Operator has
2015 and 2016 FMC's conducted past
tested and certified leak
El
E
El
El
R
❑
None
annual due date. From this point
detection equipment
forward all FMC's will be conducted on
annually - 23 CCR 16 2638
annual due date.
2030048
Secondary containment
testing conducted every
36 months in accordance
0
❑
❑
❑
❑
❑
None
with requirements - 23
CCR 16 2637
2030055
Spill buckets have been
tested annually as
None
required - HSC 6.7 25284.2
2010009
Secondary containment
test results submitted to
the CUPA within 30 days
None
after the test - 23 CCR 16
2637(e)
2030042
0.1 gph annual line test
performed and passed for
RD
pressurized piping without
❑
❑
❑
❑
r-1
None
❑
fail safe or shut down - 23
Yes
CCR 16 26360(4)
2030050
0.1 gallon per hour piping
integrity test conducted
RD
every three years (pre-
❑
❑
0
❑
❑
❑
None
[:1
January 1984) - 23 CCR
Yes
16 2643(d)
2030051
Piping integrity test or
overfill integrity test
conducted every two
❑
❑
0
❑
1:1
❑
None
years (pre-January 1,
1984) - 23 CCR 16 2643(e)
2030029
Lined or repaired steel
tank was inspected within
RP
10 years of lining and
0
❑
❑
1:1
❑
❑
None
❑
every 5 years after - 23
Yes
CCR 16 2663
2030028
Tank lining certification
submitted to the CUPA
within 30 days, proper
1:1
❑
❑
None
tests and inspector used -
23 CCR 16 2663
2030067
ELD testing conducted
every 36 months on USTs
located within 1,000 feet
❑
❑
Z
None
of a public drinking well -
23 CCR 16 2644.1 (a) (3)
Bakersfield Fire Department Prevention
2101 H St
Bakersfield CA. 93301
661-326-3911
Underground Storage Tank Program
SW Inspection Report
NOTICE TO COMPLY/NOTICE OF VIOLATION
Violation
Program Requirement
'8 r-
0
SOC
Comments
No
a
0
0-
C 0
0)'5
Z
0
z
M
0
W
2010005
ELD testing results sent
to the board and the
CUPA within 60 days of
❑
❑
ED
❑
None
completion of the test - 23
CCR 16 2644.1 (q) (5)
2030056
SIR Report submitted
annually to the CUPA - 23
❑
❑
0
❑
❑
❑
None
CCR 16 2646. 16)
2030064
CUPA was properly
notified within the
prescribed number of
❑
❑
❑
❑
None
hours prior to testing - 23
CCR 16 26370, 2638(e),
2643(8), 2644.1(a)(4)
Install/Repair
2060009
Permits obtained to
install, replace, repair, or
Z
None
modify part of the UST
system - 23 CCR 16 2712
UST System Observation
General Monitoring
2030003
Leak detection system
maintains continuous
RD
monitoring that activates
None
❑
an audible and visual
Yes
alarm - 23 CCR 16 2632,
2634, 2636, 2666
2030017
Product piping outside the
UDC is fail-safe and shuts
down the pump or
S
❑
❑
❑
❑
❑
None
restricts flow - 23 CCR 16
2636(0(5)
2030018
Turbine sump monitor
activates an audible and
RD
visual alarm or stops the
❑
❑
N
None
❑
flow of at the dispenser -
Yes
23 CCR 16 2636 0(1
2030019
Monitoring system in the
UDCs activates an
audible and visual alarm
Z
None
or stops the flow at the
UDC - 23 CCR 16
2636 (0(1)
2030043
Leak detection equipment
A total of 3 liquid sensors are daisy
properly programmed or
RD
chained. New wire will need to be
properly operated - 23
None
[D
pulled to individually terminate sensor
CCR 16 2632, 2634, 2636,
Yes
wiring in Monitor. Also Line Leak
2666
detection system not properly operated.
2060005
System constructed with
UDC's only
a monitoring system
capable of detecting entry
❑
❑
11
1:1
❑
None
into secondary
containment - HSC 6.7
25291(b)
Bakersfield Fire Department Prevention
2101 H St
Bakersfield CA. 93301
661-326-3911
Underground Storage Tank Program
SW Inspection Report
NOTICE TO COMPLY/NOTICE OF VIOLATION
Violation
Program Requirement
43 C
0 0
SOC
Comments
No
:R.
d
a
0
=
Z
z
0
z
M
0
W
Gj
2060014
Correct leak detection
NOTE: The correct leak detection
equipment installed for
RD
equipment is installed, however leak
the type of system
0
El
❑
❑
F-1
❑
None
❑
detection equipment was not installed
present - 23 CCR 16 2638,
Yes
properly.
HSC 6.7 25290.1, 25290.2,
25291
2060015
Sensor located in the
RD
proper position/location -
None
❑
23 CCR 16 2630(d), 2641(a)
Yes
2030062
Facility is in compliance
with not tampering with or
RD
disabling leak detection
[D
❑
❑
❑
❑
❑
None
r1
devices or alarms - HSC
Yes
6.7 25299(a)(9)
2030034
Tag/sticker on affixed
Unable to tag or affix sticker to
monitoring equipment
monitoring equipment and monitoring
being certified, repaired,
❑
0
1:1
1:1
❑
F-1
None
system, as equipment could not be
or replaced - 23 CCR 16
certified as it was not installed or
26380
operated in accordance with
manufactures specifications.
Cathodic Protection
2030009
Impressed-current system
Missing 3 year Cathodic protection
is turned on and
RP
testing results in lazerfiche, not
functioning properly and
F-1
None
0
uploaded in CERS, check UST Binder
inspected as required - 23
Yes
for results. Last results for testing were
CCR 16 2635(a)(2)
from 2008.
Single Walled
Tank Monitoring
2030004
Automatic tank gauge
tests the tank at least
RD
once per month at 0.1
❑
None
F-1
gallons per hour - 23 CCR
Yes
16 2643(b)(2)
2030005
The 0.2 gallons per hour
continuous in tank leak
RD
detection test is being
None
❑
conducted - 23 CCR 16
Yes
2643(N(5)
2030006
Monthly 0.2 gallons per
hour automatic tank
RD
gauging test on a single
❑
❑
None
❑
wall tank is being
Yes
conducted - 23 CCR 16
2643(b)(1)
2060002
Automatic tank
gauging/continuous in
RD
tank leak detection
S
❑
❑
❑
1:1
❑
None
❑
system installed/properly
Yes
functioning - 23 CCR 16
2643, HSC 6.7 25292(a)
2030030
Weekly manual tank
gauging performed in
RD
accordance to the
❑
❑
N
❑
❑
❑
None
❑
required specifications -
Yes
23 CCR 16 2645
Bakersfield Fire Department Prevention
2101 H St
Bakersfield CA. 93301
661-326-3911
Underground Storage Tank Program
SW Inspection Report
NOTICE TO COMPLY/NOTICE OF VIOLATION
Violation
Program Requirement
SOC
Comments
No
0::01
13
0
0.
0
Z
0
Z
n
0
2030022
Groundwater and/or
vadose zone monitoring
❑
F-1
0
❑
❑
F-1
None
conducted as required -
23 CCR 16 2647, 2648
Single Walled
Piping Monitoring
2030052
Piping monitored hourly
Line Leak Detector system is not
and a 0.2 gph monthly or
RD
certified for .1 or .2gph testing.
0.1 gph annual line
None
Precision line testing is being
conducted annually on T3,4,5,and 6.
integrity test is performed
Yes
However it is not being conducted on T-
- 23 CCR 16 2641 (a),
1 or T-2 and is required.
2643(c)
Line Leak
Detector
2060012
Line leak detector
installed on pressurized
RD
piping system - HSC 6.7
❑
❑
❑
❑
None
❑
25290. 1 (h), 25290.2(8),
Yes
25291(1), 25292(e),
2636(f) (2)
2030026
Line leak detectors detect
This box was left blank. Line leak
a 3 gph leak and/or
RD
detectors were not tested as tests
audible and visual alarm
El
D
EJ
❑
None
would be inconclusive due to the
improper installation and operation of
function properly - 23
Yes
line leak equipment. Once repaired all
CCR 16 2636(0(6),
line leaks will be re-tested.
2666(c)
2030027
Turbine shuts down when
Not confirmed as line leak detectors
a leak is detected or
RD
were not tested.
when line leak detector is
❑
❑
❑
❑
❑
❑
None
r-1
disconnected - 23 CCR 16
Yes
2666(c)
2030025
Pressurized piping able to
Not confirmed as line leak detectors
detect a 3.0 gph leak
RD
were not tested.
within an hour, and
❑
F-1
❑
❑
El
F-1
None
❑
restricts the flow or
Yes
alarms - 23 CCR 16
2636 (0(2)
Suction Piping
2030053
Suction piping sloped to
drain back into storage
RD
tank, one check valve and
❑
❑
Z
❑
❑
❑
None
F-1
inspections conducted -
Yes
23 CCR 16 2636(a)(3),
2641(b)
Secondary Containment
2030008
UDC, sumps, and/or
UDCs only
other secondary
containment in good
F-1
1:1
❑
❑
❑
None
condition and/or are free
of debris/liquid - HSC 6.7
25290.1, 25290.2, 25291
2030047
Secondary containment
UDC's Only
maintained tight and has
been confirmed by testing
E
EJ
❑
❑
❑
❑
None
- 23 CCR 16 2662, HSC 6.7
25290.1(c)(2), 25290.2(c)(2),
25291(a), 25292(e)
Bakersfield Fire Department Prevention
2101 H St
Bakersfield CA. 93301
661-326-3911
Underground Storage Tank Program
SW Inspection Report
NOTICE TO COMPLY/NOTICE OF VIOLATION
Violation
Program Requirement
'a C
4) 0
SOC
Comments
No
C)
0
M
=
42 W
p-5
2
0
Z
M
0
W
05
2030060
Entry fittings in secondary
No entry fittings in UDC's. UDCs do
containment for UST
not have piping ran through it, only
system maintained
❑
❑ 1:1
0
❑
1:1
❑ Ej
None
being used as a catch pan under
tight/sealed - 23 CCR 16
Loading rack meter.
2630, 2635(d), 2636(c),
2666
2060020
Spill bucket is installed
and has a functional drain
RP
valve or other means to
None
❑
remove liquid - 23 CCR 16
Yes
2635(b), 2665
2030054
Spill bucket maintained in
RP
Tank #1 initial Spill Bucket test failed. A
good condition and free of
None
E
new Fill Adaptor was installed. Spill
debris and/or liquid - 23
Bucket was re-tested and passed.
CCR 16 2635(b), 2715(c)(2)
Yes
Violation corrected on site.
2060019
Spill bucket to has a
Tank #2,3,4,5 and 6 Spill Buckets do
minimum capacity of five
None
not have the minimum capacity of 5
gallons - 23 CCR 16
gallons.
2635(b), 2665
Overfill
2030035
UST system is operated
to prevent unauthorized
RP
release, including spills
0
F-1
1:1
❑
None
❑
and overfills - HSC 6.7
Yes
25292.1 (a)
2030036
Overfill prevention system
External Overfill alarm would not
has not been overridden
RP
activate a visual alarm. A new light
and meets overfill
❑
0
1:1
1:1
❑
❑
None
0
bulb and capacitor were installed.
requirements - 23 CCR 16
Yes
Overfill was then re-tested and
2635(b)(2), 2665
confirmed operational. Violation was
corrected on site.
On Site Records
Certifications
2030023
Required designated
operators or contractors
maintain a proper and
❑
❑
❑
❑
❑
None
current ICC certification -
23 CCR 16 2715
2030024
Service technician,
installer, and/ or
employee maintain a
None
proper license - 23 CCR
162715
2030031
Employee or contractor
obtained and maintained
proper manufacturer
None
certification - 23 CCR 16
2715
2010007
Submit/maintain current
Certificate of Financial
Responsibility /mechanism
of financial assurance -
❑
❑
❑
F-I
None
23 CCR 16 2711; 23 CCR
18 2808.1, 2809-2809.2,
HSC 6.7 25292.2; HSC
6.75 25299.30-25299.34
Bakersfield Fire Department Prevention
2101 H St
Bakersfield CA. 93301
661-326-3911
Underground Storage Tank Program
SW Inspection Report
NOTICE TO COMPLY/NOTICE OF VIOLATION
Violation
Program Requirement
�8 00
SOC
Comments
No
R.
4
in
CO)
0
t
42
0"a
z
0
z
M
0
W
>
2030007
Positive statement of
compatibility for UST
system components
❑
❑
❑
❑
❑
None
submitted and maintained
on site - 23 CCR 16 2631(j)
Designated Operator
2010004
Copies of DO inspections
for last 12 months and list
of trained employees
❑
❑
❑
❑
❑
None
maintained - 23 CCR 16
2715
2030013
Designated operator
properly conducted the
monthly inspection and
F-1
❑
❑
None
the reports are complete -
23 CCR 16 2715
2030010
DO notified operator of
any condition observed
during the monthly
E
❑
❑
❑
❑
❑
None
inspection that may
require action - 23 CCR 16
2715(d)
2030012
DO employee training
performed, current for at
least one employee on
None
site, and a log kept - 23
CCR 16 2715(c)(6 ), 2715(o
Logs
2030001
Leak detection alarm
Q-1 went into a Gross Line Fail Alarm
logs, maintenance and
on 1/20/2016, 1/22/2016, and
records of appropriate
❑
F]
None
1/28/2016. No documentation of follow
up action, and a gross line fail alarm will
follow-up actions
not clear itself.
maintained - 23 CCR 16
2632, 2634, 2712(b)
2030020
Unburied fuel piping
RD
visually inspected at least
❑
F-1
❑
r-1
None
❑
monthly and log kept -
Yes
HSC 6.7 25281.5(b)(3)
2030049
Suction pipe monitored
daily and results logged -
❑
❑
0
❑
r-1
❑
None
23 CCR 16 2643(d)
2030057
When SIR results indicate
failure: The facility met all
RD
corrective action
❑
❑
0.
❑
❑
❑
None
❑
requirements - 23 CCR 16
Yes
2646.1 (d)
2030058
All Statistical Inventory
Reconciliation (SIR)
requirements met - 23
CCR 16 2646.1
RD
❑
F-]
❑
None
r_1
Yes
Bakersfield Fire Department Prevention
2101 H St
Bakersfield CA. 93301
661 - 326 -3911
Underground Storage Tank Program
SW Inspection Report
NOTICE TO COMPLY/NOTICE OF VIOLATION
Violation
Program Requirement
o
SOC
Comments
No
as =
0)75 t.
z
O
z
v
w
o>
Maintenance /Tests
2010008
Monitoring, maintenance,
repairs, linings, and
RD
upgrade records
®
❑
❑
❑
❑
❑
None
❑
maintained for the proper
Yes
time period - 23 CCR 16
2712(b)
. . . . . . . . . .
Ba kersfield Fire Department Prevention
2101 H St
Bakersfield CA. 93301
661-326-3911
Underground Storage Tank Program
SW Inspection Report
NOTICE TO COMPLY/NOTICE OF VIOLATION
Violation
Program Requirement
00
a).-
SOC
Comments
No
M
4
In
0
IL
4L) vW
cc
0)0
Z
0
2
2010002
Records of cathodic
protection systems testing
Z
E]
Ej
❑
E:]
❑
None
maintained - 23 CCR 16
2635, 2712(b)
Documentation
2030033
Failure to maintain on site
UST monitoring plan not accurate with
an approved monitoring
F-1
Z
r-1
❑
F-1
❑
None
equipment actually present on site, and
plan - 23 CCR 16 2632,
leak detection methods being used.
2634, 2711, 2712(1 )
2030037
Written agreement
between the tank owner
and tank operator to
monitor the tank system
ED
❑
❑
❑
F-1
F-1
None
is maintained - 23 CCR 16
2620(b); HSC 6.7
25284(a)(3)
2030061
Suspected or actual
unauthorized release
RD
reported in appropriate
Z
None
❑
time frame - HSC 6.7
Yes
29294,29295
General Operating
Requirements
Permit Condition/Approval
2030039
Compliance with all
Failure to comply with many operating
operating permit
None
permit conditions.
conditions - 23 CCR 16
2712, HSC 6.7 25299
2030059
UST system maintained
in accordance with
exclusion/exemption
None
status - HSC 6.7 25281.6,
25283.5
2030014
Owner/Operator received
approval and has
implemented a training
Z
None
program at an unstaffed
facility - 23 CCR 16
2715( (2
2030015
Facility exhibited that the
Method used to monitor tanks is
method used to monitor
correct, but method being used to
the tank meets the
None
monitor lines is incorrect.
monitoring methods in
2643(f) - 23 CCR 16 2643
Red Tag
2030045
Red Tag information is
Red Tags were installed on all 6 UST
legible and has not been
F]
El
EJ
❑
❑
None
turbine pump circuit breakers, under the
tampered with - 23 CCR
California Fire Code.
16 2717.1(8
2030044
Facility did not allow for
Site will not be able to have fuel
deposit of petroleum into
deliveries other than a retain out of
a UST that has a red tag
Z
None
header bar in less than 5 gallon
affixed to the fill - 23 CCR
increments. No dispensing no fuel
162717.1(0
deliveries will be allowed until violations
have been corrected.
Install/Repair
Bakersfield Fire Department Prevention
2101 H St
Bakersfield CA. 93301
661- 326 -3911
F� t'
Underground Storage Tank Program
SW Inspection Report
NOTICE TO COM PLY/NOTICE OF VIOLATION
Violation
Program Requirement
o
SOC
Comments
No
:O
a
o
O
a
coo
z
O
z
M
U
W
0
2030066
Repaired and retested the
system due to a failed
ELD test when located
❑
❑
®
❑
❑
❑
None
within 1000' of public well
- HSC 6.7 25292.4(d),
25292.5(c)
2060018
Existing SW piping is
constructed of FRP,
RP
cathodically protected
®
❑
❑
❑
❑
❑
None
❑
steel, or steel clad with
Yes
FRP - 23 CCR 16 2666(b);
HSC 6.7 25292 e 2)
2060021
Striker plate installed and
positioned correctly - 23
❑
❑
❑
®
❑
❑
None
CCR 16 2631 c , 2662(d
2060004
Corrosion protection
installed for USTs and
RP
cathodic protection
®
❑
❑
❑
❑
❑
None'
❑
system meets the
Yes
consensus standards - 23
CCR 16 2635(a) (2) (A)
❑ There were no violations noted for this inspection.
®This report shall serve as a "NOTICE TO COMPLY" for Minor Violations, and a "NOTICE OF VIOLATION" for
Major violations. You are, hereby, ordered to correct the above noted violations within 30 days, or according to
correction summaries provided. Formal enforcement and /or penalty assessment may be initiated for any
violations noted, and for those not corrected in a timely manner. (NOTE: If this is a preliminary report, a final report
will follow.)
Inspectors Signature: c-L-ti Date: l0 lid 16
Inspector: Enter # of Violations: RD: 2 RP: _3
Check one box for facility Significant _ Operational Status (SOC) to be reported to SWRC13 and US EPA:
❑ SOC with both Release Detection and Release Detection (Facility has no Release Prevention and no Release
Prevention Violations)
® Not in SOC (Facility has both Release Prevention and Release Detection Violations)
❑SOC with Release Detection only (Facility has no Release Detection violations but one or more Release Prevention
violations)
❑ SOC with Release Prevention only (Facility has no Release Prevention violations but one or more Release Detection
violations)