HomeMy WebLinkAbout2016 FMC RESULTS (2)MONITORING SYSTEM CERTIFICATION
For Use By All Jurisdictions Within the State of CaliforniaAuthority Cited: Chapter 6.7, Health and Safety Code; Chapter 16, Division 3, Title 23, California Code of Regulations
This form must be used to document testing and servicing of monitoring equipment. A separate certification or report must be prepared for each
monitoring system control panel by the technician who performs the work. A copy of this form must be provided to the tank system owner/operator.
The owner/operator must submit a copy of this form to the local agency regulating UST systems within 30 days of test date.
A.General Information
Facility Name:Bldg. No.:
Site Address:City:Zip:
Facility Contact Person: Contact Phone No.:
Make/Model of Monitoring System:Date of Testing/Servicing:
B.Inventory of Equipment Tested/Certified
Check the appropriate boxes to indicate specific equipment inspected/serviced:
Tank ID:Tank ID:
In-Tank Gauging Probe.Model:In-Tank Gauging Probe.Model:
Annular Space or Vault Sensor.Model:Annular Space or Vault Sensor.Model:
Piping Sump / Trench Sensor(s).Model:Piping Sump / Trench Sensor(s).Model:
Fill Sump Sensor(s).Model:Fill Sump Sensor(s).Model:
Mechanical Line Leak Detector.Model:Mechanical Line Leak Detector.Model:
Electronic Line Leak Detector.Model:Electronic LineLeak Detector.Model:
Tank Overfill / High-Level Sensor.Model:Tank Overfill / High-Level Sensor.Model:
Other (specify equipment type and model in Section E on Page 2).Other (specify equipment type and model in Section E on Page 2).
Tank ID:Tank ID:
In-Tank Gauging Probe.Model:In-Tank Gauging Probe.Model:
Annular Space or Vault Sensor.Model:Annular Space or Vault Sensor.Model:
Piping Sump / TrenchSensor(s).Model:Piping Sump / Trench Sensor(s).Model:
Fill Sump Sensor(s).Model:Fill Sump Sensor(s).Model:
Mechanical Line Leak Detector.Model:Mechanical Line Leak Detector.Model:
Electronic Line Leak Detector.Model:Electronic Line Leak Detector.Model:
Tank Overfill / High-Level Sensor.Model:Tank Overfill / High-Level Sensor.Model:
Other (specify equipment type and model in Section E on Page 2).Other (specify equipment type and model in Section E on Page 2).
Dispenser ID:Dispenser ID:
Dispenser Containment Sensor(s).Model:Dispenser Containment Sensor(s).Model:
Shear Valve(s).Shear Valve(s).
Dispenser Containment Float(s) and Chain(s).Dispenser Containment Float(s) and Chain(s).
Dispenser ID:Dispenser ID:
Dispenser Containment Sensor(s).Model:Dispenser Containment Sensor(s).Model:
Shear Valve(s).Shear Valve(s).
Dispenser Containment Float(s) and Chain(s).Dispenser Containment Float(s) and Chain(s).
Dispenser ID:Dispenser ID:
Dispenser Containment Sensor(s).Model:Dispenser Containment Sensor(s).Model:
Shear Valve(s).Shear Valve(s).
Dispenser Containment Float(s) and Chain(s).Dispenser Containment Float(s) and Chain(s).
*If the facility contains more tanks or dispensers, copy this form. Include information for every tank and dispenser at the facility.
C.Certification -I certify that the equipment identified in this document was inspected/serviced in accordance with the manufacturers’
guidelines. Attached to this Certification is information (e.g. manufacturers' checklists)necessary to verify that this information is
correct and a Plot Plan showing the layout of monitoring equipment. For any equipment capable of generating such reports, I have also
attached a copy of the report;(check all that apply):System set-up Alarm history report
Technician Name (print):Signature:
Certification No.:License. No.:804904
Testing Company Name:Confidence UST Services, Inc.Phone No.:(800)339-9930
Site Address:Date of Testing/Servicing:
Page 1 of 3
#1001/WholesaleFuels,Inc.
2200EastBrundageLaneBakersfield93307
OmeroGarcia (661)393-7000
Veeder-RootTLS-35002/11/2016
10,000gal.T-1L-SClearDiesel
847390-107
WPLLD
847390-107
10,000gal.T-2L-SDyedDiesel
847390-107
WPLLD
847390-107
20,000galT-3ClearDiesel
847390-107
WPLLD
847390-107
20,000gal.T-4Unleaded
847390-107
WPLLD
847390-107
T-1L-SClearDiesel
794380-208
T-2L-SDyedDiesel
794380-208
T-3ClearDiesel
794380-208 794380-208
T-4Unleaded
T-5DyedDiesel
794380-208
T-6DyedDiesel
794380-208
DustinReese
B43426
2200EastBrundageLane Bakersfield,CA93307 02/11/2016
794380-208
794380-208
794380-208 794380-208
MONITORING SYSTEM CERTIFICATION
For Use By All Jurisdictions Within the State of CaliforniaAuthority Cited: Chapter 6.7, Health and Safety Code; Chapter 16, Division 3, Title 23, California Code of Regulations
This form must be used to document testing and servicing of monitoring equipment. A separate certification or report must be prepared for each
monitoring system control panel by the technician who performs the work. A copy of this form must be provided to the tank system owner/operator.
The owner/operator must submit a copy of this form to the local agency regulating UST systems within 30 days of test date.
A.General Information
Facility Name:Bldg. No.:
Site Address:City:Zip:
Facility Contact Person: Contact Phone No.:
Make/Model of Monitoring System:Date of Testing/Servicing:
B.Inventory of Equipment Tested/Certified
Check the appropriate boxes to indicate specific equipment inspected/serviced:
Tank ID:Tank ID:
In-Tank Gauging Probe.Model:In-Tank Gauging Probe.Model:
Annular Space or Vault Sensor.Model:Annular Space or Vault Sensor.Model:
Piping Sump / Trench Sensor(s).Model:Piping Sump / Trench Sensor(s).Model:
Fill Sump Sensor(s).Model:Fill Sump Sensor(s).Model:
Mechanical Line Leak Detector.Model:Mechanical Line Leak Detector.Model:
Electronic Line Leak Detector.Model:Electronic LineLeak Detector.Model:
Tank Overfill / High-Level Sensor.Model:Tank Overfill / High-Level Sensor.Model:
Other (specify equipment type and model in Section E on Page 2).Other (specify equipment type and model in Section E on Page 2).
Tank ID:Tank ID:
In-Tank Gauging Probe.Model:In-Tank Gauging Probe.Model:
Annular Space or Vault Sensor.Model:Annular Space or Vault Sensor.Model:
Piping Sump / TrenchSensor(s).Model:Piping Sump / Trench Sensor(s).Model:
Fill Sump Sensor(s).Model:Fill Sump Sensor(s).Model:
Mechanical Line Leak Detector.Model:Mechanical Line Leak Detector.Model:
Electronic Line Leak Detector.Model:Electronic Line Leak Detector.Model:
Tank Overfill / High-Level Sensor.Model:Tank Overfill / High-Level Sensor.Model:
Other (specify equipment type and model in Section E on Page 2).Other (specify equipment type and model in Section E on Page 2).
Dispenser ID:Dispenser ID:
Dispenser Containment Sensor(s).Model:Dispenser Containment Sensor(s).Model:
Shear Valve(s).Shear Valve(s).
Dispenser Containment Float(s) and Chain(s).Dispenser Containment Float(s) and Chain(s).
Dispenser ID:Dispenser ID:
Dispenser Containment Sensor(s).Model:Dispenser Containment Sensor(s).Model:
Shear Valve(s).Shear Valve(s).
Dispenser Containment Float(s) and Chain(s).Dispenser Containment Float(s) and Chain(s).
Dispenser ID:Dispenser ID:
Dispenser Containment Sensor(s).Model:Dispenser Containment Sensor(s).Model:
Shear Valve(s).Shear Valve(s).
Dispenser Containment Float(s) and Chain(s).Dispenser Containment Float(s) and Chain(s).
*If the facility contains more tanks or dispensers, copy this form. Include information for every tank and dispenser at the facility.
C.Certification -I certify that the equipment identified in this document was inspected/serviced in accordance with the manufacturers’
guidelines. Attached to this Certification is information (e.g. manufacturers' checklists)necessary to verify that this information is
correct and a Plot Plan showing the layout of monitoring equipment. For any equipment capable of generating such reports, I have also
attached a copy of the report;(check all that apply):System set-up Alarm history report
Technician Name (print):Signature:
Certification No.:License. No.:804904
Testing Company Name:Confidence UST Services, Inc.Phone No.:(800)339-9930
Site Address:Date of Testing/Servicing:
Page 1 of 3
Veeder-Root TLS-350
20,000gal.T-5L-SDyedDiesel
■847390-107
■WPLLD
■847390-107
20,000gal.T-6L-SDyedDiesel
■847390-107
■WPLLD
■847390-107
20,000gal.(AST)T-7L-SDyedDiesel
■847390-107 ■
■
■847390-107
12,000gal.(AST)T-8ClearDiesel
847390-107
WPLLD ■WPLLD
■847390-107
#1001/Wholesale Fuels, Inc.
2200 East Brundage Lane Bakersfield 39907
Omero Garcia (661) 393-7000
02/11/2016
X X
Dustin Reese
B43426
2200 East Brundage Lane, Bakersfield, CA 93307 02/11/2016
Monitoring System Certification
D.Results of Testing/Servicing
Software Version Installed:
Complete the following checklist:
Yes No*Isthe audible alarm operational?
Yes No*Is the visual alarm operational?
Yes No*Were all sensors visually inspected, functionally tested, and confirmed operational?
Yes No*Were all sensors installed at lowest point of secondary containment and positioned so that other equipment will
not interfere with their proper operation?
Yes No*
N/A
If alarms are relayed to a remote monitoring station, is all communications equipment (e.g., modem)
operational?
Yes No*
N/A
For pressurized piping systems, does the turbine automatically shut down if the piping secondary containment
monitoring system detects a leak, fails to operate, or is electrically disconnected? If yes: which sensors initiate
positive shut-down? (Check all that apply) Sump/Trench Sensors; Dispenser Containment Sensors.
Did you confirm positive shut-down due to leaks and sensor failure/disconnection? Yes; No.
Yes No*
N/A
For tank systems that utilize the monitoring system as the primary tank overfill warning device (i.e., no
mechanical overfill prevention valve is installed), is the overfill warning alarm visible and audible at the tank
fill point(s) and operating properly? If so, at what percent oftank capacity does the alarm trigger? %
Yes*NoWas any monitoring equipment replaced? If yes, identify specific sensors, probes, or other equipment replaced
and list the manufacturer name and model for all replacement parts in Section E, below.
Yes*NoWas liquid found inside any secondary containment systems designed as dry systems? (Check all that apply)
Product; Water. If yes, describe causes in Section E, below.
Yes No*Was monitoring system set-up reviewed to ensure proper settings? Attach set up reports, if applicable
Yes No*Is all monitoring equipment operational per manufacturer’s specifications?
*In Section E below, describe how and when these deficiencies were or will be corrected.
E.Comments:
Page 2 of 3
123.02
90
I changed out the capacitor for the overfill, and the mag probe float kit for tank #1 and still need to change out the float kit for tank #5 .
The reason I was not able to perform audible and visual alarm with all sensors was due to the fact that the sensors are daisychain together so proper
Location for each sensors audible and visual alarm could not be confirmed. The sensor wire will need to be fixed before I can conduct this test again.
Monitoring System Certification
F.In-Tank Gauging / SIR Equipment: Check this box if tank gauging is used only for inventory control.
Check this box if no tank gauging or SIR equipment is installed.
This section must be completed if in-tank gauging equipment is used to perform leak detection monitoring.
Complete the following checklist:
Yes No*Has all input wiring been inspected for proper entry and termination, including testing for ground faults?
Yes No*Were all tank gauging probes visually inspected for damage and residue buildup?
Yes No*Was accuracy of system product level readings tested?
Yes No*Was accuracy of system water level readings tested?
Yes No*Were all probes reinstalled properly?
Yes No*Were all items on the equipment manufacturer’s maintenance checklist completed?
* In the Section H, below, describe how and when these deficiencies were or will be corrected.
G.Line Leak Detectors (LLD):Check this box if LLDs are not installed.
Complete the following checklist:
Yes No*
N/A
For equipment start-up or annual equipment certification, was a leak simulated to verify LLD performance?
(Check all that apply)Simulated leak rate: 3 g.p.h.; 0.1 g.p.h ; 0.2 g.p.h.
Yes No*Were all LLDs confirmed operational and accurate within regulatory requirements?
Yes No*Was the testing apparatus properly calibrated?
Yes No*
N/A
For mechanical LLDs, does the LLD restrict product flow if it detects a leak?
Yes No*
N/A
For electronic LLDs, does the turbine automatically shut off if the LLD detects a leak?
Yes No*
N/A
For electronic LLDs, does the turbine automatically shut off if any portion of the monitoring system is disabled
or disconnected?
Yes No*
N/A
For electronic LLDs, does the turbine automatically shut off if any portion of the monitoring system malfunctions
or fails a test?
Yes No*
N/A
For electronic LLDs, have all accessible wiring connections been visually inspected?
Yes No*Were all items on the equipment manufacturer’s maintenance checklist completed?
* In the Section H, below, describe how and when these deficiencies were or will be corrected.
H.Comments:
Page 3 of 3
The probe for tank #5 was missing the water float, and could not be properly tested until the float kid is replaced.
Installation set up for the electronic LLD is not properly installed per manufacturers specs and a 3 g.p.h. @ 10 psi test could not be conducted to
To ensure proper operation. They will need to make the necessary repairs to fix the installation set up and retest all failing Monitoring Certification
Test.
System Setup
Whole Sale Fuels: Responses Received:
200 WHOLE SALE FUELS 2200 E BRUNDAGE BAKERSFIELD CA 93304 FEB 11, 2016 9:24 AM TANK PRODUCT GALLONS INCHES WATER DEG F ULLAGE 1 L-S CLEAR 733 12.00 1.4 68.2 9267 2 L-S DYED 777 12.50 1.8 68.4 9223 3 CLEAR DIESEL 1012 11.55 1.0 66.6 19551 4 UNLEADED 415 6.32 0.0 65.0 20148 5 L-S DYED 10225 59.74 27.1 65.0 10338 6 L-S DYED 1270 13.49 5.4 71.9 19293 7 L-S DYED 3239 25.76 0.0 60.8 17324 8 CLEAR DIESEL 440 7.57 0.0 53.1 11560 I90500 FEB 11, 2016 9:24 AM SOFTWARE REVISION LEVEL VERSION 123.02 SOFTWARE# 346123-100-C CREATED - 02.11.25.15.17 S-MODULE# 330160-062-A SYSTEM FEATURES: PERIODIC IN-TANK TESTS ANNUAL IN-TANK TESTS CSLD PLLD 0.10 AUTO 0.20 REPETITIV WPLLD 0.10 AUTO 0.20 REPETITIV I50500 FEB 11, 2016 9:24 AM SYSTEM TYPE AND LANGUAGE FLAG SYSTEM UNITS U.S. SYSTEM LANGUAGE ENGLISH SYSTEM DATE/TIME FORMAT MON DD YYYY HH:MM:SS xM I50201 FEB 11, 2016 9:24 AM
SHIFT TIME 1 : 11:00 PM I50202 FEB 11, 2016 9:24 AM SHIFT TIME 2 : 12:00 AM I50203 FEB 11, 2016 9:24 AM SHIFT TIME 3 : 1:00 AM I50204 FEB 11, 2016 9:24 AM SHIFT TIME 4 : 2:00 AM I54600 FEB 11, 2016 9:24 AM TANK PER TST NEEDED WRN: DISABLED I54900 FEB 11, 2016 9:24 AM TANK ANN TST NEEDED WRN: DISABLED I55300 FEB 11, 2016 9:24 AM LINE RE-ENABLE METHOD PASS LINE TEST
I55600 FEB 11, 2016 9:24 AM LINE PER TST NEEDED WRN: DISABLED I55900 FEB 11, 2016 9:24 AM LINE ANN TST NEEDED WRN: DISABLED I50D00
FEB 11, 2016 9:24 AM PRINT TC VOLUMES ENABLED I50E00 FEB 11, 2016 9:24 AM TEMP COMPENSATION VALUE (DEG F ): 60.0 I60B00 FEB 11, 2016 9:25 AM STICK HEIGHT OFFSET ENABLE STATUS DISABLED I51400 FEB 11, 2016 9:25 AM H-PROTOCOL DATA FORMAT HEIGHT I51A01 FEB 11, 2016 9:25 AM DAYLIGHT SAVING TIME DISABLED I51B00 FEB 11, 2016 9:25 AM I51600
FEB 11, 2016 9:25 AM RE-DIRECT LOCAL PRINTOUT DISABLED I50400 FEB 11, 2016 9:25 AM 232 SECURITY CODE PORT SECURITY CODE STATUS 1 000000 DISABLED 2 000000 DISABLED 3 000000 DISABLED 4 000000 DISABLED
5 000000 DISABLED 6 000000 DISABLED 9999FF1B I5BD00 FEB 11, 2016 9:25 AM CUSTOM ALARM LABELS DISABLED 9999FF1B I88101 FEB 11, 2016 9:25 AM PORT SETTINGS: COMM BOARD : 1 (RS-232) BAUD RATE : 9600 PARITY : NONE STOP BIT : 1 STOP DATA LENGTH: 8 DATA RS-232 SECURITY CODE : DISABLED I88102 FEB 11, 2016 9:25 AM I88103 FEB 11, 2016 9:25 AM I88104 FEB 11, 2016 9:25 AM
I88105 FEB 11, 2016 9:25 AM I88106 FEB 11, 2016 9:25 AM I52000 FEB 11, 2016 9:25 AM I60100
FEB 11, 2016 9:25 AM TANK CONFIGURATION DEVICE LABEL CONFIGURED 1 L-S CLEAR ON 2 L-S DYED ON 3 CLEAR DIESEL ON 4 UNLEADED ON 5 L-S DYED ON 6 L-S DYED ON 7 L-S DYED ON 8 CLEAR DIESEL ON I60200 FEB 11, 2016 9:25 AM TANK PRODUCT LABEL TANK PRODUCT LABEL 1 L-S CLEAR 2 L-S DYED 3 CLEAR DIESEL 4 UNLEADED 5 L-S DYED 6 L-S DYED 7 L-S DYED 8 CLEAR DIESEL I60300 FEB 11, 2016 9:25 AM TANK PRODUCT CODE TANK PRODUCT LABEL 1 L-S CLEAR 1 2 L-S DYED 2 3 CLEAR DIESEL 3 4 UNLEADED 4 5 L-S DYED 5 6 L-S DYED 6 7 L-S DYED 7
8 CLEAR DIESEL 8 I60900 FEB 11, 2016 9:25 AM TANK THERMAL COEFFICIENT TANK PRODUCT LABEL 1 L-S CLEAR 0.000450 2 L-S DYED 0.000450 3 CLEAR DIESEL 0.000450 4 UNLEADED 0.000700 5 L-S DYED 0.000450 6 L-S DYED 0.000450 7 L-S DYED 0.000450 8 CLEAR DIESEL 0.000450
I60700 FEB 11, 2016 9:25 AM TANK DIAMETER TANK PRODUCT LABEL INCHES 1 L-S CLEAR 95.00 2 L-S DYED 95.00 3 CLEAR DIESEL 120.00 4 UNLEADED 120.00 5 L-S DYED 120.00 6 L-S DYED 120.00 7 L-S DYED 120.00 8 CLEAR DIESEL 96.00 I60A00 FEB 11, 2016 9:25 AM TANK FULL VOLUME TANK PRODUCT LABEL TANK PROFILE GALLONS 1 L-S CLEAR 1 PT 10000 2 L-S DYED 1 PT 10000 3 CLEAR DIESEL 1 PT 20563 4 UNLEADED 1 PT 20563 5 L-S DYED 1 PT 20563 6 L-S DYED 1 PT 20563 7 L-S DYED 1 PT 20563 8 CLEAR DIESEL 1 PT 12000 I60400 FEB 11, 2016 9:25 AM TANK FULL VOLUME TANK PRODUCT LABEL GALLONS 1 L-S CLEAR 10000 2 L-S DYED 10000 3 CLEAR DIESEL 20563 4 UNLEADED 20563 5 L-S DYED 20563 6 L-S DYED 20563 7 L-S DYED 20563 8 CLEAR DIESEL 12000
I60500 FEB 11, 2016 9:25 AM TANK 4 POINT VOLUMES TANK PRODUCT LABEL GALLONS 1 L-S CLEAR 10000 0 0 0 2 L-S DYED 10000 0 0 0 3 CLEAR DIESEL 20563 0 0 0 4 UNLEADED 20563 0 0 0 5 L-S DYED 20563 0 0 0 6 L-S DYED 20563 0 0 0 7 L-S DYED 20563 0 0 0 8 CLEAR DIESEL 12000 0 0 0
I60600 FEB 11, 2016 9:25 AM TANK 20 POINT VOLUMES TANK PRODUCT LABEL GALLONS 1 L-S CLEAR 10000 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 2 L-S DYED 10000 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 3 CLEAR DIESEL 20563 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 4 UNLEADED 20563 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 5 L-S DYED 20563 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 6 L-S DYED 20563 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 7 L-S DYED 20563 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 8 CLEAR DIESEL 12000 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0
0 0 0 0 I61500 FEB 11, 2016 9:25 AM TANK PRODUCT LABEL METER DATA 1 L-S CLEAR NO 2 L-S DYED NO 3 CLEAR DIESEL NO 4 UNLEADED NO 5 L-S DYED NO 6 L-S DYED NO 7 L-S DYED NO 8 CLEAR DIESEL NO
I62F00 FEB 11, 2016 9:25 AM MAG PROBE FLOAT SIZE TANK PRODUCT LABEL FLOAT SIZE: 1 L-S CLEAR 4.0 INCHES 2 L-S DYED 4.0 INCHES 3 CLEAR DIESEL 4.0 INCHES 4 UNLEADED 4.0 INCHES 5 L-S DYED 4.0 INCHES 6 L-S DYED 2.0 INCHES 7 L-S DYED 3.0 INCHES 8 CLEAR DIESEL 4.0 INCHES I62700 FEB 11, 2016 9:25 AM TANK HIGH WATER WARNING LIMIT TANK PRODUCT LABEL INCHES 1 L-S CLEAR 4.0 2 L-S DYED 4.0 3 CLEAR DIESEL 4.0 4 UNLEADED 4.0 5 L-S DYED 4.0 6 L-S DYED 4.0 7 L-S DYED 4.0 8 CLEAR DIESEL 4.0 9999FF1B I62400 FEB 11, 2016 9:25 AM TANK HIGH WATER LEVEL LIMIT TANK PRODUCT LABEL INCHES 1 L-S CLEAR 5.0 2 L-S DYED 5.0 3 CLEAR DIESEL 5.0 4 UNLEADED 5.0
5 L-S DYED 5.0 6 L-S DYED 5.0 7 L-S DYED 5.0 8 CLEAR DIESEL 5.0 I62800 FEB 11, 2016 9:25 AM TANK MAXIMUM VOLUME LIMIT TANK PRODUCT LABEL GALLONS 1 L-S CLEAR 10000 2 L-S DYED 10000 3 CLEAR DIESEL 20563 4 UNLEADED 20563 5 L-S DYED 20563 6 L-S DYED 20563
7 L-S DYED 20563 8 CLEAR DIESEL 12000 I62300 FEB 11, 2016 9:25 AM TANK OVERFILL LEVEL LIMIT TANK PRODUCT LABEL GALLONS 1 L-S CLEAR 9000 2 L-S DYED 9000 3 CLEAR DIESEL 18506 4 UNLEADED 18506 5 L-S DYED 18506 6 L-S DYED 18506 7 L-S DYED 18506 8 CLEAR DIESEL 10800 I62200 FEB 11, 2016 9:25 AM TANK HIGH PRODUCT LIMIT TANK PRODUCT LABEL GALLONS 1 L-S CLEAR 9500 2 L-S DYED 9500 3 CLEAR DIESEL 19535 4 UNLEADED 19535 5 L-S DYED 19535 6 L-S DYED 19535 7 L-S DYED 19535 8 CLEAR DIESEL 11400 I62900 FEB 11, 2016 9:25 AM TANK DELIVERY REQUIRED LIMIT TANK PRODUCT LABEL GALLONS 1 L-S CLEAR 100 2 L-S DYED 100 3 CLEAR DIESEL 205
4 UNLEADED 205 5 L-S DYED 205 6 L-S DYED 205 7 L-S DYED 205 8 CLEAR DIESEL 205 I62100 FEB 11, 2016 9:25 AM TANK LOW PRODUCT LIMIT TANK PRODUCT LABEL GALLONS 1 L-S CLEAR 500 2 L-S DYED 500 3 CLEAR DIESEL 500 4 UNLEADED 500 5 L-S DYED 500
6 L-S DYED 500 7 L-S DYED 0 8 CLEAR DIESEL 0 I62600 FEB 11, 2016 9:25 AM TANK LEAK ALARM LIMIT TANK PRODUCT LABEL GALLONS 1 L-S CLEAR 75 2 L-S DYED 75 3 CLEAR DIESEL 75 4 UNLEADED 75 5 L-S DYED 75 6 L-S DYED 75 7 L-S DYED 75 8 CLEAR DIESEL 75 I62500 FEB 11, 2016 9:25 AM TANK SUDDEN LOSS LIMIT TANK PRODUCT LABEL GALLONS 1 L-S CLEAR 99 2 L-S DYED 99 3 CLEAR DIESEL 200 4 UNLEADED 99 5 L-S DYED 99 6 L-S DYED 99 7 L-S DYED 99 8 CLEAR DIESEL 99 I60800 FEB 11, 2016 9:25 AM TANK TILT TANK PRODUCT LABEL INCHES 1 L-S CLEAR 2.40 2 L-S DYED 2.95
3 CLEAR DIESEL 0.50 4 UNLEADED 3.00 5 L-S DYED 0.00 6 L-S DYED 3.00 7 L-S DYED 0.00 8 CLEAR DIESEL -5.00 I60B00 FEB 11, 2016 9:25 AM STICK HEIGHT OFFSET ENABLE STATUS DISABLED I60C00 FEB 11, 2016 9:25 AM
TANK STICK HEIGHT OFFSET TANK PRODUCT LABEL INCHES 1 L-S CLEAR 0.00 2 L-S DYED 0.00 3 CLEAR DIESEL 0.00 4 UNLEADED 0.00 5 L-S DYED 0.00 6 L-S DYED 0.00 7 L-S DYED 0.00 8 CLEAR DIESEL 0.00 I61200 FEB 11, 2016 9:25 AM TANK MANIFOLDED PARTNERS TANK PRODUCT LABEL SIPHON MANIFOLDED TANKS LINE MANIFOLDED TANKS 1 L-S CLEAR NONE NONE 2 L-S DYED NONE NONE 3 CLEAR DIESEL NONE NONE 4 UNLEADED NONE NONE 5 L-S DYED NONE NONE 6 L-S DYED NONE NONE 7 L-S DYED NONE NONE 8 CLEAR DIESEL NONE NONE I63600 FEB 11, 2016 9:25 AM PERIODIC LEAK TEST MIN VOLUME TANK PRODUCT LABEL GALLONS 1 L-S CLEAR 1000 2 L-S DYED 1000 3 CLEAR DIESEL 2056 4 UNLEADED 2056 5 L-S DYED 2056 6 L-S DYED 2056 7 L-S DYED 2056 8 CLEAR DIESEL 2056
I62A00 FEB 11, 2016 9:25 AM ANNUAL LEAK TEST MIN VOLUME TANK PRODUCT LABEL GALLONS 1 L-S CLEAR 1000 2 L-S DYED 1000 3 CLEAR DIESEL 2056 4 UNLEADED 2056 5 L-S DYED 2056 6 L-S DYED 2056 7 L-S DYED 2056 8 CLEAR DIESEL 2056 I62C00 FEB 11, 2016 9:25 AM
TANK PERIODIC TEST TYPE TANK PRODUCT LABEL PERIODIC TEST TYPE 1 L-S CLEAR STANDARD 2 L-S DYED STANDARD 3 CLEAR DIESEL STANDARD 4 UNLEADED STANDARD 5 L-S DYED STANDARD 6 L-S DYED STANDARD 7 L-S DYED STANDARD 8 CLEAR DIESEL STANDARD I62D00 FEB 11, 2016 9:25 AM TANK LEAK TEST FAIL ALARMS TANK PRODUCT LABEL 1 L-S CLEAR GROSS TEST FAIL ALARM DISABLED PERIODIC TEST FAIL ALARM DISABLED ANNUAL TEST FAIL ALARM DISABLED 2 L-S DYED GROSS TEST FAIL ALARM DISABLED PERIODIC TEST FAIL ALARM DISABLED ANNUAL TEST FAIL ALARM DISABLED 3 CLEAR DIESEL GROSS TEST FAIL ALARM DISABLED PERIODIC TEST FAIL ALARM DISABLED ANNUAL TEST FAIL ALARM DISABLED 4 UNLEADED GROSS TEST FAIL ALARM DISABLED PERIODIC TEST FAIL ALARM DISABLED ANNUAL TEST FAIL ALARM DISABLED 5 L-S DYED GROSS TEST FAIL ALARM DISABLED PERIODIC TEST FAIL ALARM DISABLED ANNUAL TEST FAIL ALARM DISABLED 6 L-S DYED GROSS TEST FAIL ALARM DISABLED PERIODIC TEST FAIL ALARM DISABLED ANNUAL TEST FAIL ALARM DISABLED
7 L-S DYED GROSS TEST FAIL ALARM DISABLED PERIODIC TEST FAIL ALARM DISABLED ANNUAL TEST FAIL ALARM DISABLED 8 CLEAR DIESEL GROSS TEST FAIL ALARM DISABLED PERIODIC TEST FAIL ALARM DISABLED ANNUAL TEST FAIL ALARM DISABLED I63100 FEB 11, 2016 9:25 AM TANK LEAK TEST AVERAGING TANK PRODUCT LABEL ANNUAL PERIODIC 1 L-S CLEAR OFF OFF
2 L-S DYED OFF OFF 3 CLEAR DIESEL OFF OFF 4 UNLEADED OFF OFF 5 L-S DYED OFF OFF 6 L-S DYED OFF OFF 7 L-S DYED OFF OFF 8 CLEAR DIESEL OFF OFF I63000 FEB 11, 2016 9:25 AM IN-TANK LEAK TEST NOTIFY TANK PRODUCT LABEL TANK TEST NOTIFY: 1 L-S CLEAR OFF 2 L-S DYED OFF 3 CLEAR DIESEL OFF 4 UNLEADED OFF 5 L-S DYED OFF 6 L-S DYED OFF 7 L-S DYED OFF 8 CLEAR DIESEL OFF I63200 FEB 11, 2016 9:25 AM TANK TEST SIPHON BREAK TANK PRODUCT LABEL SIPHON BREAK 1 L-S CLEAR OFF 2 L-S DYED OFF 3 CLEAR DIESEL OFF 4 UNLEADED OFF 5 L-S DYED OFF 6 L-S DYED OFF 7 L-S DYED OFF 8 CLEAR DIESEL OFF I61000
FEB 11, 2016 9:25 AM TANK DELIVERY DELAY TANK PRODUCT LABEL 1 L-S CLEAR 1 2 L-S DYED 1 3 CLEAR DIESEL 1 4 UNLEADED 1 5 L-S DYED 1 6 L-S DYED 1 7 L-S DYED 1 8 CLEAR DIESEL 1 I63A00 FEB 11, 2016 9:25 AM
LOW LEVEL PUMP THRESHOLD FOR SEQUENTIAL LINE MANIFOLD TANK PRODUCT LABEL PUMP THRESHOLD 1 L-S CLEAR 10.00% 2 L-S DYED 10.00% 3 CLEAR DIESEL 10.00% 4 UNLEADED 10.00% 5 L-S DYED 10.00% 6 L-S DYED 10.00% 7 L-S DYED 10.00% 8 CLEAR DIESEL 10.00% I61100 FEB 11, 2016 9:25 AM LEAK TEST METHOD - - - - - - - - - - - - TEST CSLD : TANK 1 Pd = 95% CLIMATE FACTOR:EXTREME EVAP COMP: NO GROSS TEST AUTO-CONFIRM: DISABLED REPORT ONLY: DISABLED TST EARLY STOP:DISABLED TEST CSLD : TANK 2 Pd = 95% CLIMATE FACTOR:EXTREME EVAP COMP: NO GROSS TEST AUTO-CONFIRM: DISABLED REPORT ONLY: DISABLED TST EARLY STOP:DISABLED
TEST CSLD : TANK 3 Pd = 95% CLIMATE FACTOR:EXTREME EVAP COMP: NO GROSS TEST AUTO-CONFIRM: DISABLED REPORT ONLY: DISABLED TST EARLY STOP:DISABLED TEST CSLD : TANK 4 Pd = 95% CLIMATE FACTOR:EXTREME EVAP COMP: NO
GROSS TEST AUTO-CONFIRM: DISABLED REPORT ONLY: DISABLED TST EARLY STOP:DISABLED TEST CSLD : TANK 5 Pd = 95% CLIMATE FACTOR:EXTREME EVAP COMP: NO GROSS TEST AUTO-CONFIRM: DISABLED REPORT ONLY: DISABLED TST EARLY STOP:DISABLED TEST CSLD : TANK 6 Pd = 95% CLIMATE FACTOR:EXTREME EVAP COMP: NO GROSS TEST AUTO-CONFIRM: DISABLED REPORT ONLY: DISABLED TST EARLY STOP:DISABLED TEST ON DATE : TANK 7 JAN 10, 2015 START TIME : 3:52 AM TEST RATE :0.20 GAL/HR DURATION : 2 HOURS TST EARLY STOP:DISABLED TEST ON DATE : TANK 8 JAN 10, 2015 START TIME : 3:52 AM
TEST RATE :0.20 GAL/HR DURATION : 2 HOURS TST EARLY STOP:DISABLED I61300 FEB 11, 2016 9:25 AM CSLD PROBABLITY OF DETECTION T 1:L-S CLEAR : Pd = 95% T 2:L-S DYED : Pd = 95% T 3:CLEAR DIESEL : Pd = 95% T 4:UNLEADED : Pd = 95% T 5:L-S DYED : Pd = 95% T 6:L-S DYED : Pd = 95%
I61400 FEB 11, 2016 9:25 AM CSLD CLIMATE FACTOR T 1:L-S CLEAR : EXTREME T 2:L-S DYED : EXTREME T 3:CLEAR DIESEL : EXTREME T 4:UNLEADED : EXTREME T 5:L-S DYED : EXTREME T 6:L-S DYED : EXTREME I61600 FEB 11, 2016 9:25 AM TANK PRODUCT LABEL CAL UPDATE 1 L-S CLEAR IMMEDIATE 2 L-S DYED IMMEDIATE 3 CLEAR DIESEL IMMEDIATE 4 UNLEADED IMMEDIATE 5 L-S DYED IMMEDIATE 6 L-S DYED IMMEDIATE 7 L-S DYED IMMEDIATE 8 CLEAR DIESEL IMMEDIATE I61A00 FEB 11, 2016 9:25 AM IN-TANK LEAK TEST EARLY STOP TANK PRODUCT LABEL TST EARLY STOP: 1 L-S CLEAR DISABLED 2 L-S DYED DISABLED 3 CLEAR DIESEL DISABLED 4 UNLEADED DISABLED 5 L-S DYED DISABLED 6 L-S DYED DISABLED 7 L-S DYED DISABLED 8 CLEAR DIESEL DISABLED
I61B00 FEB 11, 2016 9:25 AM IN-TANK LEAK GROSS TEST AUTO-CONFIRM TANK PRODUCT LABEL AUTO-CONFIRM 1 L-S CLEAR DISABLED 2 L-S DYED DISABLED 3 CLEAR DIESEL DISABLED 4 UNLEADED DISABLED 5 L-S DYED DISABLED 6 L-S DYED DISABLED I61C00 FEB 11, 2016 9:25 AM
CSLD REPORT ONLY TANK PRODUCT LABEL CSLD REPORT ONLY 1 L-S CLEAR DISABLED 2 L-S DYED DISABLED 3 CLEAR DIESEL DISABLED 4 UNLEADED DISABLED 5 L-S DYED DISABLED 6 L-S DYED DISABLED I62B00 FEB 11, 2016 9:25 AM TANK LAST ANNUAL TEST TANK PRODUCT LABEL DATE 1 L-S CLEAR ??? 0, 0 2 L-S DYED ??? 0, 0 3 CLEAR DIESEL ??? 0, 0 4 UNLEADED ??? 0, 0 5 L-S DYED ??? 0, 0 6 L-S DYED ??? 0, 0 7 L-S DYED ??? 0, 0 8 CLEAR DIESEL ??? 0, 0 I63300 FEB 11, 2016 9:25 AM LEAK TEST REPORT FORMAT: NORMAL I63400 FEB 11, 2016 9:25 AM RECONCILIATION WARNING LIMIT TANK PRODUCT LABEL GALLONS 1 L-S CLEAR 0 2 L-S DYED 0 3 CLEAR DIESEL 0 4 UNLEADED 0
5 L-S DYED 0 6 L-S DYED 0 7 L-S DYED 0 8 CLEAR DIESEL 0 I63500 FEB 11, 2016 9:25 AM RECONCILIATION ALARM LIMIT TANK PRODUCT LABEL GALLONS 1 L-S CLEAR 1 2 L-S DYED 1 3 CLEAR DIESEL 1 4 UNLEADED 1 5 L-S DYED 1 6 L-S DYED 1
7 L-S DYED 1 8 CLEAR DIESEL 1 I63900 FEB 11, 2016 9:25 AM ACCU CHART END SHAPE FACTOR TANK PRODUCT LABEL 1 L-S CLEAR END FACTOR: NONE 2 L-S DYED END FACTOR: NONE 3 CLEAR DIESEL END FACTOR: NONE 4 UNLEADED END FACTOR: NONE 5 L-S DYED END FACTOR: NONE 6 L-S DYED END FACTOR: NONE 7 L-S DYED END FACTOR: NONE 8 CLEAR DIESEL END FACTOR: NONE
I78000 FEB 11, 2016 9:25 AM PRESSURE LINE LEAK SETUP Q 1:L-S CLEAR TYP:2.0/3.0IN FIBERGLASS 2.0IN DIA LEN:100 FEET 3.0IN DIA LEN:200 FEET 0.20 GPH TEST: REPETITIV 0.10 GPH TEST: AUTO SHUTDOWN RATE: 3.0 GPH LOW PRESSURE SHUTOFF:NO LOW PRESSURE : 0 PSI T 1:L-S CLEAR DISPENSE MODE:
STANDARD SENSOR: NON-VENTED PRESSURE OFFSET: 5.0PSI Q 2:L-S DYED TYP:2.0/3.0IN FIBERGLASS 2.0IN DIA LEN:150 FEET 3.0IN DIA LEN:150 FEET 0.20 GPH TEST: REPETITIV 0.10 GPH TEST: AUTO SHUTDOWN RATE: 3.0 GPH LOW PRESSURE SHUTOFF:NO LOW PRESSURE : 0 PSI T 2:L-S DYED DISPENSE MODE: STANDARD SENSOR: NON-VENTED PRESSURE OFFSET: 5.0PSI Q 3:CLEAR DIESEL TYP:2.0/3.0IN FIBERGLASS 2.0IN DIA LEN:400 FEET 3.0IN DIA LEN:200 FEET 0.20 GPH TEST: DISABLED 0.10 GPH TEST: DISABLED SHUTDOWN RATE: 3.0 GPH LOW PRESSURE SHUTOFF:NO LOW PRESSURE : 0 PSI T 3:CLEAR DIESEL DISPENSE MODE: STANDARD SENSOR: NON-VENTED PRESSURE OFFSET: 5.0PSI Q 4:UNLEADED TYP:2.0/3.0IN FIBERGLASS 2.0IN DIA LEN:300 FEET
3.0IN DIA LEN:150 FEET 0.20 GPH TEST: DISABLED 0.10 GPH TEST: DISABLED SHUTDOWN RATE: 3.0 GPH LOW PRESSURE SHUTOFF:NO LOW PRESSURE : 0 PSI T 4:UNLEADED DISPENSE MODE: STANDARD SENSOR: NON-VENTED PRESSURE OFFSET: 5.0PSI Q 5:L-S DYED TYP:2.0/3.0IN FIBERGLASS 2.0IN DIA LEN:500 FEET
3.0IN DIA LEN:200 FEET 0.20 GPH TEST: DISABLED 0.10 GPH TEST: DISABLED SHUTDOWN RATE: 3.0 GPH LOW PRESSURE SHUTOFF:NO LOW PRESSURE : 0 PSI T 5:L-S DYED DISPENSE MODE: STANDARD SENSOR: NON-VENTED PRESSURE OFFSET: 5.0PSI Q 6:L-S DYED TYP:2.0/3.0IN FIBERGLASS 2.0IN DIA LEN:135 FEET 3.0IN DIA LEN: 25 FEET 0.20 GPH TEST: DISABLED 0.10 GPH TEST: DISABLED SHUTDOWN RATE: 3.0 GPH LOW PRESSURE SHUTOFF:NO LOW PRESSURE : 0 PSI T 6:L-S DYED DISPENSE MODE: STANDARD SENSOR: NON-VENTED PRESSURE OFFSET: 5.0PSI I77700 FEB 11, 2016 9:25 AM I77800 FEB 11, 2016 9:26 AM I78C00
FEB 11, 2016 9:26 AM PRESSURE LINE LEAK 0.20 TEST SCHEDULE LINE 0.20 GPH TEST Q 1:L-S CLEAR REPETITIV Q 2:L-S DYED REPETITIV Q 3:CLEAR DIESEL DISABLED Q 4:UNLEADED DISABLED Q 5:L-S DYED DISABLED Q 6:L-S DYED DISABLED I78300 FEB 11, 2016 9:26 AM PRESSURE LINE LEAK 0.10 TEST SCHEDULE
LINE 0.10 GPH TEST Q 1:L-S CLEAR AUTO Q 2:L-S DYED AUTO Q 3:CLEAR DIESEL DISABLED Q 4:UNLEADED DISABLED Q 5:L-S DYED DISABLED Q 6:L-S DYED DISABLED I78F00 FEB 11, 2016 9:26 AM PRESSURE LINE LEAK DISPENSE THRESHOLD LINE LOW PRESSURE Q 1:L-S CLEAR 0 PSI Q 2:L-S DYED 0 PSI Q 3:CLEAR DIESEL 0 PSI Q 4:UNLEADED 0 PSI Q 5:L-S DYED 0 PSI Q 6:L-S DYED 0 PSI I78700 FEB 11, 2016 9:26 AM PRESSURE LLD SETUP REPORT Q 1:L-S CLEAR - NO ALARM ASSIGNMENTS - Q 2:L-S DYED - NO ALARM ASSIGNMENTS - Q 3:CLEAR DIESEL - NO ALARM ASSIGNMENTS - Q 4:UNLEADED - NO ALARM ASSIGNMENTS - Q 5:L-S DYED - NO ALARM ASSIGNMENTS -
Q 6:L-S DYED - NO ALARM ASSIGNMENTS - I70200 FEB 11, 2016 9:26 AM LIQUID LABEL DEVICE LABEL 1 PANS 2 PANS 3 PANS 4 5
6 7 8 I70300 FEB 11, 2016 9:26 AM LIQUID TYPE SENSOR LOCATION TYPE 1 PANS NORMALLY CLOSED 2 PANS NORMALLY CLOSED 3 PANS NORMALLY CLOSED 4 TRI-STATE (SINGLE FLOAT) 5 TRI-STATE (SINGLE FLOAT) 6 TRI-STATE (SINGLE FLOAT) 7 TRI-STATE (SINGLE FLOAT) 8 TRI-STATE (SINGLE FLOAT) I70400 FEB 11, 2016 9:26 AM LIQUID CATEGORY SENSOR LOCATION CATEGORY 1 PANS DISPENSER PAN 2 PANS DISPENSER PAN 3 PANS DISPENSER PAN 4 OTHER SENSORS 5 OTHER SENSORS 6 OTHER SENSORS 7 OTHER SENSORS 8 OTHER SENSORS I74200 FEB 11, 2016 9:26 AM
I74300 FEB 11, 2016 9:26 AM I74400 FEB 11, 2016 9:26 AM I74700 FEB 11, 2016 9:26 AM I74800 FEB 11, 2016 9:26 AM
I74900 FEB 11, 2016 9:26 AM I7BC00 FEB 11, 2016 9:26 AM I80200 FEB 11, 2016 9:26 AM I80300 FEB 11, 2016 9:26 AM I80400 FEB 11, 2016 9:26 AM I80700 FEB 11, 2016 9:26 AM RELAY LABEL DEVICE LABEL 1 SHUTDOWN EPA 2 OVERFILL ALARM 3 PANS 1,2,3 4 PANS 4,5,6 I80900 FEB 11, 2016 9:26 AM RELAY ORIENTATION
RELAY DESIGNATION ORIENTATION 1 SHUTDOWN EPA NORMALLY OPEN 2 OVERFILL ALARM NORMALLY OPEN 3 PANS 1,2,3 NORMALLY CLOSED 4 PANS 4,5,6 NORMALLY CLOSED I80B00 FEB 11, 2016 9:26 AM RELAY TANK ASSIGNMENT RELAY DESIGNATION TANK 1 SHUTDOWN EPA NONE 2 OVERFILL ALARM NONE 3 PANS 1,2,3 NONE 4 PANS 4,5,6 NONE
I80A00 FEB 11, 2016 9:26 AM RELAY TYPE RELAY DESIGNATION TYPE 1 SHUTDOWN EPA STANDARD 2 OVERFILL ALARM STANDARD 3 PANS 1,2,3 STANDARD 4 PANS 4,5,6 STANDARD 9999FF1B I80800 FEB 11, 2016 9:26 AM RELAY SETUP REPORT R 1:SHUTDOWN EPA TYPE: STANDARD NORMALLY OPEN IN-TANK ALARMS ALL:LEAK ALARM T 7:OVERFILL ALARM LIQUID SENSOR ALMS ALL:FUEL ALARM ALL:SENSOR OUT ALARM R 2:OVERFILL ALARM TYPE: STANDARD NORMALLY OPEN IN-TANK ALARMS ALL:OVERFILL ALARM
ALL:HIGH PRODUCT ALARM ALL:MAX PRODUCT ALARM LIQUID SENSOR ALMS ALL:FUEL ALARM ALL:SENSOR OUT ALARM ALL:SHORT ALARM R 3:PANS 1,2,3 TYPE: STANDARD NORMALLY CLOSED LIQUID SENSOR ALMS ALL:FUEL ALARM ALL:SENSOR OUT ALARM
ALL:SHORT ALARM R 4:PANS 4,5,6 TYPE: STANDARD NORMALLY CLOSED LIQUID SENSOR ALMS ALL:FUEL ALARM ALL:SENSOR OUT ALARM ALL:SHORT ALARM I79000 FEB 11, 2016 9:26 AM I79100 FEB 11, 2016 9:26 AM 9999FF1B 9999FF1B 9999FF1B 9999FF1B 9999FF1B 9999FF1B 9999FF1B 9999FF1B 9999FF1B 9999FF1B 9999FF1B
PLLD N CSLD Hist: I38200 FEB 11, 2016 2:14 PM WHOLE SALE FUELS 2200 E BRUNDAGE BAKERSFIELD CA 93304 PRESSURE LINE LEAK ALARM HISTORY REPORT Q 1:L-S CLEAR FEB 8, 2016 4:44 PM PLLD SHUTDOWN ALARM FEB 8, 2016 4:44 PM GROSS LINE FAIL JAN 28, 2016 2:38 PM PLLD SHUTDOWN ALARM JAN 28, 2016 2:38 PM GROSS LINE FAIL JAN 25, 2016 2:44 PM PLLD SHUTDOWN ALARM JAN 25, 2016 2:44 PM GROSS LINE FAIL JAN 22, 2016 8:22 AM PLLD SHUTDOWN ALARM JAN 22, 2016 8:22 AM GROSS LINE FAIL JAN 20, 2016 2:53 PM PLLD SHUTDOWN ALARM JAN 20, 2016 2:53 PM GROSS LINE FAIL Q 2:L-S DYED FEB 8, 2016 5:06 PM PLLD SHUTDOWN ALARM FEB 8, 2016 5:06 PM GROSS LINE FAIL FEB 2, 2016 4:24 PM PLLD SHUTDOWN ALARM FEB 2, 2016 4:24 PM GROSS LINE FAIL FEB 2, 2016 11:39 AM PLLD SHUTDOWN ALARM FEB 2, 2016 11:39 AM GROSS LINE FAIL OCT 8, 2015 1:25 PM PLLD SHUTDOWN ALARM OCT 8, 2015 1:25 PM GROSS LINE FAIL OCT 8, 2015 11:50 AM PLLD SHUTDOWN ALARM OCT 8, 2015 11:50 AM GROSS LINE FAIL
Q 3:CLEAR DIESEL FEB 8, 2016 4:21 PM PLLD SHUTDOWN ALARM FEB 8, 2016 4:21 PM GROSS LINE FAIL MAR 2, 2015 11:19 AM PLLD SHUTDOWN ALARM MAR 2, 2015 11:19 AM GROSS LINE FAIL FEB 3, 2015 3:22 PM PLLD SHUTDOWN ALARM FEB 3, 2015 3:22 PM GROSS LINE FAIL Q 4:UNLEADED FEB 9, 2016 7:57 AM PLLD SHUTDOWN ALARM FEB 9, 2016 7:57 AM GROSS LINE FAIL FEB 8, 2016 3:41 PM PLLD SHUTDOWN ALARM FEB 8, 2016 3:41 PM GROSS LINE FAIL JAN 26, 2016 3:10 PM PLLD SHUTDOWN ALARM JAN 26, 2016 3:10 PM GROSS LINE FAIL JAN 26, 2016 2:59 PM PLLD SHUTDOWN ALARM JAN 26, 2016 2:59 PM GROSS LINE FAIL JAN 26, 2016 2:18 PM PLLD SHUTDOWN ALARM JAN 26, 2016 2:18 PM GROSS LINE FAIL Q 5:L-S DYED FEB 11, 2016 6:19 AM PLLD SHUTDOWN ALARM FEB 11, 2016 6:19 AM GROSS LINE FAIL FEB 8, 2016 3:10 PM PLLD SHUTDOWN ALARM FEB 8, 2016 3:10 PM GROSS LINE FAIL
DEC 18, 2015 3:33 AM PLLD SHUTDOWN ALARM DEC 18, 2015 3:33 AM GROSS LINE FAIL MAY 14, 2015 4:21 PM PLLD SHUTDOWN ALARM MAY 14, 2015 4:21 PM GROSS LINE FAIL
MAY 13, 2015 1:42 AM PLLD SHUTDOWN ALARM MAY 13, 2015 1:42 AM GROSS LINE FAIL Q 6:L-S DYED FEB 11, 2016 10:55 AM PLLD SHUTDOWN ALARM FEB 11, 2016 10:55 AM GROSS LINE FAIL FEB 8, 2016 2:39 PM PLLD SHUTDOWN ALARM FEB 8, 2016 2:39 PM GROSS LINE FAIL FEB 8, 2016 2:24 PM FUEL OUT DEC 19, 2015 5:43 PM FUEL OUT MAR 2, 2015 12:19 PM PLLD SHUTDOWN ALARM MAR 2, 2015 12:19 PM GROSS LINE FAIL
Test Hist: I37400
FEB 11, 2016 2:25 PM WHOLE SALE FUELS 2200 E BRUNDAGE BAKERSFIELD CA 93304 PRESSURE LINE LEAK TEST HISTORY Q 1:L-S CLEAR LAST 3.0 PASS: FEB 11, 2016 11:35 AM FIRST 0.10 PASS EACH MONTH: SEP 3, 2015 11:56 AM MAR 2, 2015 3:12 PM APR 5, 2011 12:24 PM FIRST 0.20 PASS EACH MONTH: FEB 9, 2016 4:59 PM DEC 9, 2015 12:26 PM NOV 4, 2015 9:50 AM OCT 5, 2015 2:09 PM SEP 3, 2015 11:37 AM AUG 4, 2015 2:52 PM JUL 2, 2015 3:55 PM JUN 1, 2015 10:55 AM MAY 6, 2015 8:18 AM APR 8, 2015 12:25 PM MAR 2, 2015 2:53 PM Q 2:L-S DYED LAST 3.0 PASS: FEB 11, 2016 11:35 AM FIRST 0.10 PASS EACH MONTH: SEP 1, 2015 12:49 PM MAR 2, 2015 3:07 PM FIRST 0.20 PASS EACH MONTH: FEB 1, 2016 2:59 PM JAN 5, 2016 1:56 PM DEC 4, 2015 8:21 AM NOV 2, 2015 12:20 PM OCT 2, 2015 8:30 AM SEP 1, 2015 12:30 PM AUG 4, 2015 9:31 AM
JUL 2, 2015 4:17 PM JUN 1, 2015 9:38 AM MAY 4, 2015 1:49 PM APR 6, 2015 9:13 AM MAR 2, 2015 2:48 PM Q 3:CLEAR DIESEL LAST 3.0 PASS: FEB 11, 2016 10:16 AM FIRST 0.10 PASS EACH MONTH: SEP 28, 2011 10:23 AM FIRST 0.20 PASS EACH MONTH: Q 4:UNLEADED LAST 3.0 PASS: FEB 11, 2016 10:15 AM FIRST 0.10 PASS EACH MONTH: APR 27, 2011 7:08 AM FIRST 0.20 PASS EACH MONTH: Q 5:L-S DYED LAST 3.0 PASS: FEB 11, 2016 10:56 AM FIRST 0.10 PASS EACH MONTH: JUL 12, 2011 2:36 PM FIRST 0.20 PASS EACH MONTH: Q 6:L-S DYED LAST 3.0 PASS: FEB 11, 2016 12:22 PM FIRST 0.10 PASS EACH MONTH: FIRST 0.20 PASS EACH MONTH:
Alarm Hist Before
Whole Sale Fuels: Responses Received:
I10200 FEB 11, 2016 9:30 AM WHOLE SALE FUELS 2200 E BRUNDAGE BAKERSFIELD CA 93304 SYSTEM CONFIGURATION SLOT BOARD TYPE POWER ON RESET CURRENT 1 4 PROBE / G.T. 163153 161068 2 4 PROBE / G.T. 162246 160667 3 INTERSTITIAL BD 199063 200973 4 PLLD SENSOR BD 3821 3881 5 UNUSED 4940725 4971691 6 UNUSED 4938412 4972442 7 UNUSED 4937107 4981241 8 UNUSED 4936355 4978077 9 UNUSED 4933739 4974690 10 RELAY BOARD 14967 14987 11 PLLD POWER BD 100985 101007 12 PLLD POWER BD 100676 100821 13 UNUSED 4941391 4984339 14 UNUSED 4941351 4983765 15 UNUSED 4939770 4983014 16 UNUSED 4940383 4985248 COMM 1 RS232 SERIAL BD 15027 15027 COMM 2 UNUSED 4933977 4965951 COMM 3 UNUSED 4933640 4960929 COMM 4 UNUSED 4938484 4955966 COMM 5 UNUSED 4936112 4955334 COMM 6 UNUSED 4936072 4964211 I90200 FEB 11, 2016 9:30 AM SOFTWARE REVISION LEVEL VERSION 123.02 SOFTWARE# 346123-100-C CREATED - 02.11.25.15.17 S-MODULE# 330160-062-A SYSTEM FEATURES: PERIODIC IN-TANK TESTS ANNUAL IN-TANK TESTS CSLD PLLD 0.10 AUTO 0.20 REPETITIV WPLLD 0.10 AUTO 0.20 REPETITIV I11100
FEB 11, 2016 9:30 AM WHOLE SALE FUELS 2200 E BRUNDAGE BAKERSFIELD CA 93304 PRIORITY ALARM HISTORY ID CATEGORY DESCRIPTION ALARM TYPE STATE DATE TIME T 3 TANK CLEAR DIESEL LOW PRODUCT ALARM CLEAR 2-11-16 9:16AM T 5 TANK L-S DYED SUDDEN LOSS ALARM CLEAR 2-11-16 9:15AM T 5 TANK L-S DYED PROBE OUT CLEAR 2-11-16 9:14AM T 6 TANK L-S DYED HIGH WATER ALARM ALARM 2-11-16 9:13AM T 6 TANK L-S DYED SUDDEN LOSS ALARM CLEAR 2-11-16 9:09AM T 6 TANK L-S DYED PROBE OUT CLEAR 2-11-16 9:09AM T 6 TANK L-S DYED PROBE OUT ALARM 2-11-16 9:07AM T 6 TANK L-S DYED SUDDEN LOSS ALARM ALARM 2-11-16 9:07AM T 1 TANK L-S CLEAR SUDDEN LOSS ALARM CLEAR 2-11-16 9:07AM T 1 TANK L-S CLEAR PROBE OUT CLEAR 2-11-16 9:06AM T 5 TANK L-S DYED PROBE OUT ALARM 2-11-16 9:05AM T 2 TANK L-S DYED SUDDEN LOSS ALARM CLEAR 2-11-16 9:05AM T 1 TANK L-S CLEAR PROBE OUT ALARM 2-11-16 9:05AM T 5 TANK L-S DYED SUDDEN LOSS ALARM ALARM 2-11-16 9:04AM T 1 TANK L-S CLEAR SUDDEN LOSS ALARM ALARM 2-11-16 9:04AM T 2 TANK L-S DYED PROBE OUT CLEAR 2-11-16 9:04AM T 2 TANK L-S DYED PROBE OUT ALARM 2-11-16 9:03AM T 2 TANK L-S DYED SUDDEN LOSS ALARM ALARM 2-11-16 9:03AM T 4 TANK UNLEADED SUDDEN LOSS ALARM CLEAR 2-11-16 9:01AM T 4 TANK UNLEADED LOW PRODUCT ALARM ALARM 2-11-16 9:00AM T 4 TANK UNLEADED PROBE OUT CLEAR 2-11-16 9:00AM T 4 TANK UNLEADED PROBE OUT ALARM 2-11-16 8:59AM T 4 TANK UNLEADED SUDDEN LOSS ALARM ALARM 2-11-16 8:58AM T 3 TANK CLEAR DIESEL LOW PRODUCT ALARM ALARM 2-11-16 8:58AM Q 5 OTHER L-S DYED PLLD SHUTDOWN ALARM CLEAR 2-11-16 7:30AM Q 5 OTHER L-S DYED GROSS LINE FAIL CLEAR 2-11-16 7:30AM Q 5 OTHER L-S DYED PLLD SHUTDOWN ALARM ALARM 2-11-16 6:19AM Q 5 OTHER L-S DYED GROSS LINE FAIL ALARM 2-11-16 6:19AM Q 1 OTHER L-S CLEAR PERIODIC LINE FAIL CLEAR 2-09-16 4:59PM T 5 TANK L-S DYED HIGH WATER ALARM ALARM 2-09-16 3:56PM T 5 TANK L-S DYED HIGH WATER ALARM CLEAR 2-09-16 3:49PM T 5 TANK L-S DYED SUDDEN LOSS ALARM CLEAR 2-09-16 3:49PM T 5 TANK L-S DYED SUDDEN LOSS ALARM ALARM 2-09-16 3:48PM Q 4 OTHER UNLEADED PLLD SHUTDOWN ALARM CLEAR 2-09-16 8:10AM Q 4 OTHER UNLEADED GROSS LINE FAIL CLEAR 2-09-16 8:10AM Q 4 OTHER UNLEADED PLLD SHUTDOWN ALARM ALARM 2-09-16 7:57AM
Q 4 OTHER UNLEADED GROSS LINE FAIL ALARM 2-09-16 7:57AM T 5 TANK L-S DYED HIGH WATER ALARM ALARM 2-08-16 5:31PM T 5 TANK L-S DYED SUDDEN LOSS ALARM CLEAR 2-08-16 5:20PM T 5 TANK L-S DYED PROBE OUT CLEAR 2-08-16 5:19PM T 5 TANK L-S DYED PROBE OUT ALARM 2-08-16 5:18PM T 5 TANK L-S DYED PROBE OUT CLEAR 2-08-16 5:18PM Q 2 OTHER L-S DYED PLLD SHUTDOWN ALARM CLEAR 2-08-16 5:07PM Q 2 OTHER L-S DYED GROSS LINE FAIL CLEAR 2-08-16 5:07PM T 5 TANK L-S DYED PROBE OUT ALARM 2-08-16 5:06PM Q 2 OTHER L-S DYED PLLD SHUTDOWN ALARM ALARM 2-08-16 5:06PM Q 2 OTHER L-S DYED GROSS LINE FAIL ALARM 2-08-16 5:06PM T 5 TANK L-S DYED HIGH WATER ALARM CLEAR 2-08-16 4:55PM T 5 TANK L-S DYED SUDDEN LOSS ALARM ALARM 2-08-16 4:54PM Q 1 OTHER L-S CLEAR PLLD SHUTDOWN ALARM CLEAR 2-08-16 4:53PM I11200
FEB 11, 2016 9:30 AM WHOLE SALE FUELS 2200 E BRUNDAGE BAKERSFIELD CA 93304 NON-PRIORITY ALARM HISTORY ID CATEGORY DESCRIPTION ALARM TYPE STATE DATE TIME T 2 TANK L-S DYED INVALID FUEL LEVEL ALARM 2-11-16 9:23AM T 3 TANK CLEAR DIESEL DELIVERY NEEDED CLEAR 2-11-16 9:16AM T 3 TANK CLEAR DIESEL INVALID FUEL LEVEL CLEAR 2-11-16 9:16AM T 6 TANK L-S DYED HIGH WATER WARNING ALARM 2-11-16 9:13AM T 4 TANK UNLEADED INVALID FUEL LEVEL ALARM 2-11-16 9:00AM T 3 TANK CLEAR DIESEL DELIVERY NEEDED ALARM 2-11-16 8:58AM T 3 TANK CLEAR DIESEL INVALID FUEL LEVEL ALARM 2-11-16 8:58AM T 5 TANK L-S DYED HIGH WATER WARNING ALARM 2-09-16 3:56PM T 5 TANK L-S DYED HIGH WATER WARNING CLEAR 2-09-16 3:49PM T 5 TANK L-S DYED HIGH WATER WARNING ALARM 2-08-16 5:31PM T 5 TANK L-S DYED HIGH WATER WARNING CLEAR 2-08-16 4:56PM T 1 TANK L-S CLEAR INVALID FUEL LEVEL CLEAR 2-08-16 11:34AM T 1 TANK L-S CLEAR INVALID FUEL LEVEL ALARM 2-08-16 11:31AM T 2 TANK L-S DYED HIGH PRODUCT ALARM CLEAR 2-08-16 11:29AM T 2 TANK L-S DYED HIGH PRODUCT ALARM ALARM 2-08-16 11:27AM T 5 TANK L-S DYED HIGH WATER WARNING ALARM 2-08-16 11:24AM T 2 TANK L-S DYED HIGH PRODUCT ALARM CLEAR 2-08-16 11:23AM T 2 TANK L-S DYED HIGH PRODUCT ALARM ALARM 2-08-16 11:20AM T 1 TANK L-S CLEAR HIGH PRODUCT ALARM CLEAR 2-08-16 11:19AM T 1 TANK L-S CLEAR HIGH PRODUCT ALARM ALARM 2-08-16 11:18AM T 5 TANK L-S DYED LOW TEMP WARNING CLEAR 2-08-16 11:12AM T 5 TANK L-S DYED LOW TEMP WARNING ALARM 2-08-16 11:10AM T 5 TANK L-S DYED HIGH PRODUCT ALARM CLEAR 2-08-16 11:01AM T 5 TANK L-S DYED HIGH PRODUCT ALARM ALARM 2-08-16 11:00AM T 4 TANK UNLEADED HIGH PRODUCT ALARM CLEAR 2-08-16 10:58AM T 4 TANK UNLEADED HIGH PRODUCT ALARM ALARM 2-08-16 10:57AM T 5 TANK L-S DYED INVALID FUEL LEVEL CLEAR 2-08-16 10:35AM T 5 TANK L-S DYED INVALID FUEL LEVEL ALARM 2-08-16 10:29AM SYSTEM PRINTER ERROR CLEAR 2-08-16 10:00AM SYSTEM PAPER OUT CLEAR 2-08-16 10:00AM SYSTEM PRINTER ERROR ALARM 2-08-16 9:59AM SYSTEM PAPER OUT ALARM 2-08-16 9:59AM SYSTEM PAPER OUT CLEAR 2-08-16 9:59AM SYSTEM PRINTER ERROR CLEAR 2-08-16 9:59AM SYSTEM PAPER OUT ALARM 2-08-16 9:59AM SYSTEM PAPER OUT CLEAR 2-08-16 9:59AM
SYSTEM PAPER OUT ALARM 2-08-16 9:59AM SYSTEM PAPER OUT CLEAR 2-08-16 9:59AM SYSTEM PAPER OUT ALARM 2-08-16 9:59AM SYSTEM PAPER OUT CLEAR 2-08-16 9:59AM SYSTEM PAPER OUT ALARM 2-08-16 9:59AM SYSTEM PRINTER ERROR ALARM 2-08-16 9:59AM SYSTEM PRINTER ERROR CLEAR 2-05-16 12:56PM SYSTEM PRINTER ERROR ALARM 2-05-16 12:56PM SYSTEM PRINTER ERROR CLEAR 2-02-16 4:38PM SYSTEM PRINTER ERROR ALARM 2-02-16 4:38PM SYSTEM PRINTER ERROR CLEAR 2-02-16 4:38PM SYSTEM PRINTER ERROR ALARM 2-02-16 4:38PM SYSTEM PRINTER ERROR CLEAR 1-29-16 10:14AM SYSTEM PAPER OUT CLEAR 1-29-16 10:14AM I20600
FEB 11, 2016 9:30 AM WHOLE SALE FUELS 2200 E BRUNDAGE BAKERSFIELD CA 93304 TANK ALARM HISTORY TANK 1 L-S CLEAR OVERFILL ALARM FEB 8, 2016 11:18 AM DEC 1, 2015 5:22 PM NOV 30, 2015 2:44 PM SUDDEN LOSS ALARM FEB 11, 2016 9:04 AM FEB 8, 2016 10:27 AM FEB 8, 2016 10:10 AM HIGH PRODUCT ALARM FEB 8, 2016 11:18 AM AUG 4, 2015 5:32 PM MAR 2, 2015 1:23 PM INVALID FUEL LEVEL FEB 8, 2016 11:31 AM PROBE OUT FEB 11, 2016 9:05 AM FEB 8, 2016 11:29 AM FEB 8, 2016 10:10 AM NO CSLD IDLE TIME MAR 7, 2015 3:55 PM TANK 2 L-S DYED OVERFILL ALARM FEB 8, 2016 11:27 AM FEB 8, 2016 11:20 AM DEC 1, 2015 5:53 AM SUDDEN LOSS ALARM FEB 11, 2016 9:03 AM APR 27, 2015 1:11 PM HIGH PRODUCT ALARM FEB 8, 2016 11:27 AM FEB 8, 2016 11:20 AM AUG 3, 2015 12:52 PM
INVALID FUEL LEVEL FEB 11, 2016 9:23 AM SEP 17, 2015 1:41 PM AUG 18, 2015 8:16 AM PROBE OUT FEB 11, 2016 9:03 AM FEB 8, 2016 11:28 AM APR 27, 2015 1:38 PM MAX PRODUCT ALARM AUG 3, 2015 12:52 PM TANK 3 CLEAR DIESEL HIGH WATER ALARM AUG 3, 2015 6:58 AM AUG 3, 2015 6:20 AM AUG 2, 2015 8:06 PM OVERFILL ALARM FEB 8, 2016 10:51 AM DEC 7, 2015 7:53 AM
SEP 29, 2015 5:27 PM LOW PRODUCT ALARM FEB 11, 2016 8:58 AM AUG 3, 2015 1:20 PM AUG 3, 2015 12:53 PM SUDDEN LOSS ALARM FEB 8, 2016 10:03 AM AUG 3, 2015 1:41 PM AUG 3, 2015 12:31 PM HIGH PRODUCT ALARM DEC 7, 2015 7:56 AM SEP 29, 2015 5:27 PM AUG 3, 2015 12:48 PM INVALID FUEL LEVEL FEB 11, 2016 8:58 AM AUG 3, 2015 12:54 PM AUG 3, 2015 12:33 PM PROBE OUT FEB 8, 2016 10:04 AM AUG 3, 2015 1:47 PM AUG 3, 2015 12:32 PM HIGH WATER WARNING AUG 3, 2015 6:58 AM AUG 3, 2015 6:20 AM AUG 2, 2015 8:06 PM DELIVERY NEEDED FEB 11, 2016 8:58 AM JUL 7, 2015 6:54 AM JUL 7, 2015 12:04 AM MAX PRODUCT ALARM AUG 3, 2015 6:10 AM JUL 30, 2015 2:48 PM JUL 30, 2015 1:05 PM LOW TEMP WARNING JUL 7, 2015 5:57 AM JUL 7, 2015 12:04 AM JUL 6, 2015 9:34 PM TANK 4 UNLEADED OVERFILL ALARM FEB 8, 2016 10:54 AM LOW PRODUCT ALARM FEB 11, 2016 9:00 AM SUDDEN LOSS ALARM FEB 11, 2016 8:58 AM
FEB 8, 2016 10:27 AM FEB 8, 2016 10:06 AM HIGH PRODUCT ALARM FEB 8, 2016 10:57 AM MAR 2, 2015 1:30 PM INVALID FUEL LEVEL FEB 11, 2016 9:00 AM PROBE OUT FEB 11, 2016 8:59 AM FEB 8, 2016 11:01 AM FEB 8, 2016 10:06 AM TANK 5 L-S DYED HIGH WATER ALARM FEB 9, 2016 3:56 PM FEB 8, 2016 5:31 PM FEB 8, 2016 11:24 AM
OVERFILL ALARM FEB 8, 2016 11:00 AM AUG 7, 2015 1:51 PM AUG 4, 2015 4:15 PM LOW PRODUCT ALARM FEB 8, 2016 10:29 AM SUDDEN LOSS ALARM FEB 11, 2016 9:04 AM FEB 9, 2016 3:48 PM FEB 8, 2016 4:54 PM HIGH PRODUCT ALARM FEB 8, 2016 11:00 AM MAY 12, 2015 6:02 AM APR 27, 2015 2:02 PM INVALID FUEL LEVEL FEB 8, 2016 10:29 AM PROBE OUT FEB 11, 2016 9:05 AM FEB 8, 2016 5:18 PM FEB 8, 2016 5:06 PM HIGH WATER WARNING FEB 9, 2016 3:56 PM FEB 8, 2016 5:31 PM FEB 8, 2016 11:24 AM LOW TEMP WARNING FEB 8, 2016 11:10 AM APR 27, 2015 2:02 PM TANK 6 L-S DYED HIGH WATER ALARM FEB 11, 2016 9:13 AM OVERFILL ALARM FEB 8, 2016 2:36 PM FEB 8, 2016 11:14 AM SUDDEN LOSS ALARM FEB 11, 2016 9:07 AM FEB 8, 2016 10:28 AM APR 27, 2015 12:47 PM HIGH PRODUCT ALARM MAR 2, 2015 1:35 PM INVALID FUEL LEVEL FEB 3, 2015 2:07 PM PROBE OUT FEB 11, 2016 9:07 AM FEB 8, 2016 2:33 PM FEB 8, 2016 11:15 AM
HIGH WATER WARNING FEB 11, 2016 9:13 AM NO CSLD IDLE TIME APR 27, 2015 1:58 PM APR 27, 2015 12:40 PM APR 27, 2015 12:37 PM TANK 7 L-S DYED HIGH WATER ALARM FEB 23, 2015 12:11 PM FEB 21, 2015 1:32 PM FEB 19, 2015 9:59 AM OVERFILL ALARM JAN 31, 2016 4:46 PM INVALID FUEL LEVEL FEB 23, 2015 3:48 PM FEB 22, 2015 2:44 PM FEB 3, 2015 6:25 PM
PROBE OUT FEB 23, 2015 3:40 PM FEB 23, 2015 2:21 PM FEB 23, 2015 1:45 PM HIGH WATER WARNING FEB 23, 2015 12:11 PM FEB 21, 2015 1:32 PM FEB 19, 2015 9:59 AM PERIODIC TEST FAIL FEB 10, 2015 8:00 AM LOW TEMP WARNING FEB 23, 2015 12:01 PM FEB 21, 2015 5:57 PM FEB 21, 2015 1:26 PM TANK 8 CLEAR DIESEL PERIODIC TEST FAIL FEB 8, 2015 7:31 AM I38200 FEB 11, 2016 9:30 AM WHOLE SALE FUELS 2200 E BRUNDAGE BAKERSFIELD CA 93304 PRESSURE LINE LEAK ALARM HISTORY REPORT Q 1:L-S CLEAR FEB 8, 2016 4:44 PM PLLD SHUTDOWN ALARM FEB 8, 2016 4:44 PM GROSS LINE FAIL JAN 28, 2016 2:38 PM PLLD SHUTDOWN ALARM JAN 28, 2016 2:38 PM GROSS LINE FAIL JAN 25, 2016 2:44 PM PLLD SHUTDOWN ALARM JAN 25, 2016 2:44 PM GROSS LINE FAIL JAN 22, 2016 8:22 AM PLLD SHUTDOWN ALARM JAN 22, 2016 8:22 AM GROSS LINE FAIL JAN 20, 2016 2:53 PM PLLD SHUTDOWN ALARM JAN 20, 2016 2:53 PM GROSS LINE FAIL Q 2:L-S DYED
FEB 8, 2016 5:06 PM PLLD SHUTDOWN ALARM FEB 8, 2016 5:06 PM GROSS LINE FAIL FEB 2, 2016 4:24 PM PLLD SHUTDOWN ALARM FEB 2, 2016 4:24 PM GROSS LINE FAIL FEB 2, 2016 11:39 AM PLLD SHUTDOWN ALARM FEB 2, 2016 11:39 AM GROSS LINE FAIL OCT 8, 2015 1:25 PM PLLD SHUTDOWN ALARM OCT 8, 2015 1:25 PM GROSS LINE FAIL OCT 8, 2015 11:50 AM PLLD SHUTDOWN ALARM OCT 8, 2015 11:50 AM GROSS LINE FAIL Q 3:CLEAR DIESEL FEB 8, 2016 4:21 PM PLLD SHUTDOWN ALARM FEB 8, 2016 4:21 PM GROSS LINE FAIL MAR 2, 2015 11:19 AM PLLD SHUTDOWN ALARM MAR 2, 2015 11:19 AM GROSS LINE FAIL FEB 3, 2015 3:22 PM PLLD SHUTDOWN ALARM FEB 3, 2015 3:22 PM GROSS LINE FAIL
Q 4:UNLEADED FEB 9, 2016 7:57 AM PLLD SHUTDOWN ALARM FEB 9, 2016 7:57 AM GROSS LINE FAIL FEB 8, 2016 3:41 PM PLLD SHUTDOWN ALARM FEB 8, 2016 3:41 PM GROSS LINE FAIL JAN 26, 2016 3:10 PM PLLD SHUTDOWN ALARM JAN 26, 2016 3:10 PM GROSS LINE FAIL JAN 26, 2016 2:59 PM PLLD SHUTDOWN ALARM JAN 26, 2016 2:59 PM GROSS LINE FAIL JAN 26, 2016 2:18 PM PLLD SHUTDOWN ALARM JAN 26, 2016 2:18 PM GROSS LINE FAIL Q 5:L-S DYED FEB 11, 2016 6:19 AM PLLD SHUTDOWN ALARM FEB 11, 2016 6:19 AM GROSS LINE FAIL FEB 8, 2016 3:10 PM PLLD SHUTDOWN ALARM FEB 8, 2016 3:10 PM GROSS LINE FAIL DEC 18, 2015 3:33 AM PLLD SHUTDOWN ALARM DEC 18, 2015 3:33 AM GROSS LINE FAIL MAY 14, 2015 4:21 PM PLLD SHUTDOWN ALARM MAY 14, 2015 4:21 PM GROSS LINE FAIL MAY 13, 2015 1:42 AM PLLD SHUTDOWN ALARM MAY 13, 2015 1:42 AM GROSS LINE FAIL Q 6:L-S DYED FEB 8, 2016 2:39 PM PLLD SHUTDOWN ALARM FEB 8, 2016 2:39 PM GROSS LINE FAIL FEB 8, 2016 2:24 PM FUEL OUT DEC 19, 2015 5:43 PM FUEL OUT MAR 2, 2015 12:19 PM PLLD SHUTDOWN ALARM MAR 2, 2015 12:19 PM GROSS LINE FAIL I30200 FEB 11, 2016 9:30 AM WHOLE SALE FUELS 2200 E BRUNDAGE BAKERSFIELD CA 93304 LIQUID ALARM HISTORY REPORT
SENSOR LOCATION 1 PANS FEB 8, 2016 1:04 PM FUEL ALARM FEB 8, 2016 12:52 PM FUEL ALARM FEB 8, 2016 12:15 PM FUEL ALARM 2 PANS FEB 8, 2016 2:44 PM FUEL ALARM FEB 8, 2016 1:03 PM FUEL ALARM FEB 8, 2016 12:58 PM FUEL ALARM 3 PANS FEB 8, 2016 1:37 PM FUEL ALARM FEB 8, 2016 1:34 PM FUEL ALARM FEB 8, 2016 1:24 PM FUEL ALARM 9999FF1B
I40200 FEB 11, 2016 9:30 AM I40300 FEB 11, 2016 9:30 AM I34200 FEB 11, 2016 9:30 AM I34700 FEB 11, 2016 9:30 AM
9999FF1B
Alarm Hist After
Whole Sale Fuels: Responses Received:
I10200 FEB 11, 2016 1:57 PM WHOLE SALE FUELS 2200 E BRUNDAGE BAKERSFIELD CA 93304 SYSTEM CONFIGURATION SLOT BOARD TYPE POWER ON RESET CURRENT 1 4 PROBE / G.T. 163153 162249 2 4 PROBE / G.T. 162246 160693 3 INTERSTITIAL BD 199063 200185 4 PLLD SENSOR BD 3821 3815 5 UNUSED 4940725 4909825 6 UNUSED 4938412 4907953 7 UNUSED 4937107 4909569 8 UNUSED 4936355 4907401 9 UNUSED 4933739 4908187 10 RELAY BOARD 14967 14987 11 PLLD POWER BD 100985 100568 12 PLLD POWER BD 100676 100732 13 UNUSED 4941391 4911931 14 UNUSED 4941351 4912187 15 UNUSED 4939770 4912719 16 UNUSED 4940383 4909941 COMM 1 RS232 SERIAL BD 15027 15027 COMM 2 UNUSED 4933977 4901290 COMM 3 UNUSED 4933640 4902236 COMM 4 UNUSED 4938484 4899142 COMM 5 UNUSED 4936112 4899930 COMM 6 UNUSED 4936072 4898728 I90200 FEB 11, 2016 1:57 PM SOFTWARE REVISION LEVEL VERSION 123.02 SOFTWARE# 346123-100-C CREATED - 02.11.25.15.17 S-MODULE# 330160-062-A SYSTEM FEATURES: PERIODIC IN-TANK TESTS ANNUAL IN-TANK TESTS CSLD PLLD 0.10 AUTO 0.20 REPETITIV WPLLD 0.10 AUTO 0.20 REPETITIV I11100
FEB 11, 2016 1:57 PM WHOLE SALE FUELS 2200 E BRUNDAGE BAKERSFIELD CA 93304 PRIORITY ALARM HISTORY ID CATEGORY DESCRIPTION ALARM TYPE STATE DATE TIME L 3 DISP PAN PANS FUEL ALARM CLEAR 2-11-16 12:32PM L 2 DISP PAN PANS FUEL ALARM CLEAR 2-11-16 12:31PM L 1 DISP PAN PANS FUEL ALARM CLEAR 2-11-16 12:31PM L 2 DISP PAN PANS FUEL ALARM ALARM 2-11-16 12:31PM L 1 DISP PAN PANS FUEL ALARM ALARM 2-11-16 12:30PM L 3 DISP PAN PANS FUEL ALARM ALARM 2-11-16 12:30PM L 3 DISP PAN PANS FUEL ALARM CLEAR 2-11-16 12:27PM L 3 DISP PAN PANS FUEL ALARM ALARM 2-11-16 12:27PM L 3 DISP PAN PANS FUEL ALARM CLEAR 2-11-16 12:27PM L 3 DISP PAN PANS FUEL ALARM ALARM 2-11-16 12:26PM L 1 DISP PAN PANS FUEL ALARM CLEAR 2-11-16 12:26PM L 1 DISP PAN PANS FUEL ALARM ALARM 2-11-16 12:25PM L 2 DISP PAN PANS FUEL ALARM CLEAR 2-11-16 12:25PM L 2 DISP PAN PANS FUEL ALARM ALARM 2-11-16 12:24PM L 2 DISP PAN PANS FUEL ALARM CLEAR 2-11-16 12:24PM L 2 DISP PAN PANS FUEL ALARM ALARM 2-11-16 12:24PM L 2 DISP PAN PANS FUEL ALARM CLEAR 2-11-16 12:23PM L 2 DISP PAN PANS FUEL ALARM ALARM 2-11-16 12:23PM Q 6 OTHER L-S DYED PLLD SHUTDOWN ALARM CLEAR 2-11-16 12:22PM Q 6 OTHER L-S DYED GROSS LINE FAIL CLEAR 2-11-16 12:22PM T 5 TANK L-S DYED HIGH WATER ALARM ALARM 2-11-16 11:48AM T 5 TANK L-S DYED PROBE OUT CLEAR 2-11-16 11:37AM T 5 TANK L-S DYED PROBE OUT ALARM 2-11-16 11:35AM T 5 TANK L-S DYED OVERFILL ALARM CLEAR 2-11-16 11:33AM T 5 TANK L-S DYED OVERFILL ALARM ALARM 2-11-16 11:31AM T 5 TANK L-S DYED OVERFILL ALARM CLEAR 2-11-16 11:28AM T 5 TANK L-S DYED OVERFILL ALARM ALARM 2-11-16 11:27AM T 5 TANK L-S DYED MAX PRODUCT ALARM CLEAR 2-11-16 11:27AM T 5 TANK L-S DYED MAX PRODUCT ALARM ALARM 2-11-16 11:26AM T 5 TANK L-S DYED HIGH WATER ALARM CLEAR 2-11-16 11:23AM T 5 TANK L-S DYED PROBE OUT CLEAR 2-11-16 11:22AM T 5 TANK L-S DYED PROBE OUT ALARM 2-11-16 11:19AM T 5 TANK L-S DYED SUDDEN LOSS ALARM CLEAR 2-11-16 11:17AM T 5 TANK L-S DYED SUDDEN LOSS ALARM ALARM 2-11-16 11:15AM Q 6 OTHER L-S DYED PLLD SHUTDOWN ALARM ALARM 2-11-16 10:55AM Q 6 OTHER L-S DYED GROSS LINE FAIL ALARM 2-11-16 10:55AM
T 1 TANK L-S CLEAR PROBE OUT CLEAR 2-11-16 10:20AM T 1 TANK L-S CLEAR PROBE OUT ALARM 2-11-16 10:18AM T 1 TANK L-S CLEAR PROBE OUT CLEAR 2-11-16 10:14AM T 1 TANK L-S CLEAR OVERFILL ALARM CLEAR 2-11-16 10:12AM T 1 TANK L-S CLEAR PROBE OUT ALARM 2-11-16 10:12AM T 1 TANK L-S CLEAR OVERFILL ALARM ALARM 2-11-16 10:11AM T 1 TANK L-S CLEAR PROBE OUT CLEAR 2-11-16 10:07AM T 1 TANK L-S CLEAR OVERFILL ALARM CLEAR 2-11-16 10:02AM T 1 TANK L-S CLEAR PROBE OUT ALARM 2-11-16 10:02AM T 1 TANK L-S CLEAR OVERFILL ALARM ALARM 2-11-16 10:02AM T 1 TANK L-S CLEAR OVERFILL ALARM CLEAR 2-11-16 9:58AM T 1 TANK L-S CLEAR OVERFILL ALARM ALARM 2-11-16 9:56AM T 2 TANK L-S DYED PROBE OUT CLEAR 2-11-16 9:53AM T 2 TANK L-S DYED OVERFILL ALARM CLEAR 2-11-16 9:52AM I11200
FEB 11, 2016 1:57 PM WHOLE SALE FUELS 2200 E BRUNDAGE BAKERSFIELD CA 93304 NON-PRIORITY ALARM HISTORY ID CATEGORY DESCRIPTION ALARM TYPE STATE DATE TIME SYSTEM PRINTER ERROR CLEAR 2-11-16 1:11PM SYSTEM PRINTER ERROR ALARM 2-11-16 1:11PM SYSTEM PAPER OUT CLEAR 2-11-16 1:11PM SYSTEM PAPER OUT ALARM 2-11-16 1:08PM SYSTEM PAPER OUT CLEAR 2-11-16 1:08PM SYSTEM PAPER OUT ALARM 2-11-16 1:08PM SYSTEM PAPER OUT CLEAR 2-11-16 1:08PM SYSTEM PAPER OUT ALARM 2-11-16 1:08PM SYSTEM PAPER OUT CLEAR 2-11-16 1:08PM SYSTEM PAPER OUT ALARM 2-11-16 1:08PM SYSTEM PAPER OUT CLEAR 2-11-16 1:08PM SYSTEM PAPER OUT ALARM 2-11-16 1:08PM SYSTEM PAPER OUT CLEAR 2-11-16 1:08PM SYSTEM PAPER OUT ALARM 2-11-16 1:08PM SYSTEM PAPER OUT CLEAR 2-11-16 1:07PM SYSTEM PAPER OUT ALARM 2-11-16 1:07PM SYSTEM PAPER OUT CLEAR 2-11-16 1:07PM SYSTEM PRINTER ERROR CLEAR 2-11-16 1:07PM SYSTEM PAPER OUT ALARM 2-11-16 1:07PM SYSTEM PAPER OUT CLEAR 2-11-16 1:07PM SYSTEM PAPER OUT ALARM 2-11-16 1:07PM SYSTEM PAPER OUT CLEAR 2-11-16 1:07PM SYSTEM PAPER OUT ALARM 2-11-16 1:07PM SYSTEM PAPER OUT CLEAR 2-11-16 1:07PM SYSTEM PAPER OUT ALARM 2-11-16 1:07PM SYSTEM PAPER OUT CLEAR 2-11-16 1:07PM SYSTEM PAPER OUT ALARM 2-11-16 1:07PM SYSTEM PAPER OUT CLEAR 2-11-16 1:07PM SYSTEM PAPER OUT ALARM 2-11-16 1:07PM SYSTEM PAPER OUT CLEAR 2-11-16 1:07PM SYSTEM PAPER OUT ALARM 2-11-16 1:07PM SYSTEM PAPER OUT CLEAR 2-11-16 1:07PM SYSTEM PAPER OUT ALARM 2-11-16 1:07PM SYSTEM PAPER OUT CLEAR 2-11-16 1:07PM SYSTEM PAPER OUT ALARM 2-11-16 1:07PM SYSTEM PAPER OUT CLEAR 2-11-16 1:07PM
SYSTEM PAPER OUT ALARM 2-11-16 1:07PM SYSTEM PAPER OUT CLEAR 2-11-16 1:07PM SYSTEM PAPER OUT ALARM 2-11-16 1:07PM SYSTEM PAPER OUT CLEAR 2-11-16 1:07PM SYSTEM PAPER OUT ALARM 2-11-16 1:07PM SYSTEM PAPER OUT CLEAR 2-11-16 1:07PM SYSTEM PAPER OUT ALARM 2-11-16 1:07PM SYSTEM PRINTER ERROR ALARM 2-11-16 1:07PM SYSTEM PAPER OUT CLEAR 2-11-16 1:07PM SYSTEM PRINTER ERROR CLEAR 2-11-16 12:55PM SYSTEM PAPER OUT ALARM 2-11-16 12:55PM SYSTEM PAPER OUT CLEAR 2-11-16 12:55PM SYSTEM PAPER OUT ALARM 2-11-16 12:55PM SYSTEM PAPER OUT CLEAR 2-11-16 12:55PM I20600
FEB 11, 2016 1:57 PM WHOLE SALE FUELS 2200 E BRUNDAGE BAKERSFIELD CA 93304 TANK ALARM HISTORY TANK 1 L-S CLEAR OVERFILL ALARM FEB 11, 2016 10:11 AM FEB 11, 2016 10:02 AM FEB 11, 2016 9:56 AM SUDDEN LOSS ALARM FEB 11, 2016 9:04 AM FEB 8, 2016 10:27 AM FEB 8, 2016 10:10 AM HIGH PRODUCT ALARM FEB 11, 2016 10:11 AM FEB 8, 2016 11:18 AM AUG 4, 2015 5:32 PM INVALID FUEL LEVEL FEB 8, 2016 11:31 AM PROBE OUT FEB 11, 2016 10:18 AM FEB 11, 2016 10:12 AM FEB 11, 2016 10:02 AM NO CSLD IDLE TIME MAR 7, 2015 3:55 PM TANK 2 L-S DYED OVERFILL ALARM FEB 11, 2016 9:50 AM FEB 8, 2016 11:27 AM FEB 8, 2016 11:20 AM SUDDEN LOSS ALARM FEB 11, 2016 9:03 AM APR 27, 2015 1:11 PM HIGH PRODUCT ALARM FEB 8, 2016 11:27 AM FEB 8, 2016 11:20 AM AUG 3, 2015 12:52 PM
INVALID FUEL LEVEL FEB 11, 2016 9:23 AM SEP 17, 2015 1:41 PM AUG 18, 2015 8:16 AM PROBE OUT FEB 11, 2016 9:52 AM FEB 11, 2016 9:03 AM FEB 8, 2016 11:28 AM MAX PRODUCT ALARM AUG 3, 2015 12:52 PM TANK 3 CLEAR DIESEL HIGH WATER ALARM AUG 3, 2015 6:58 AM AUG 3, 2015 6:20 AM AUG 2, 2015 8:06 PM OVERFILL ALARM FEB 11, 2016 9:49 AM FEB 8, 2016 10:51 AM
DEC 7, 2015 7:53 AM LOW PRODUCT ALARM FEB 11, 2016 8:58 AM AUG 3, 2015 1:20 PM AUG 3, 2015 12:53 PM SUDDEN LOSS ALARM FEB 8, 2016 10:03 AM AUG 3, 2015 1:41 PM AUG 3, 2015 12:31 PM HIGH PRODUCT ALARM DEC 7, 2015 7:56 AM SEP 29, 2015 5:27 PM AUG 3, 2015 12:48 PM INVALID FUEL LEVEL FEB 11, 2016 8:58 AM AUG 3, 2015 12:54 PM AUG 3, 2015 12:33 PM PROBE OUT FEB 11, 2016 9:49 AM FEB 8, 2016 10:04 AM AUG 3, 2015 1:47 PM HIGH WATER WARNING AUG 3, 2015 6:58 AM AUG 3, 2015 6:20 AM AUG 2, 2015 8:06 PM DELIVERY NEEDED FEB 11, 2016 8:58 AM JUL 7, 2015 6:54 AM JUL 7, 2015 12:04 AM MAX PRODUCT ALARM AUG 3, 2015 6:10 AM JUL 30, 2015 2:48 PM JUL 30, 2015 1:05 PM LOW TEMP WARNING JUL 7, 2015 5:57 AM JUL 7, 2015 12:04 AM JUL 6, 2015 9:34 PM TANK 4 UNLEADED OVERFILL ALARM FEB 11, 2016 9:46 AM FEB 8, 2016 10:54 AM LOW PRODUCT ALARM FEB 11, 2016 9:00 AM
SUDDEN LOSS ALARM FEB 11, 2016 8:58 AM FEB 8, 2016 10:27 AM FEB 8, 2016 10:06 AM HIGH PRODUCT ALARM FEB 8, 2016 10:57 AM MAR 2, 2015 1:30 PM INVALID FUEL LEVEL FEB 11, 2016 9:00 AM PROBE OUT FEB 11, 2016 9:47 AM FEB 11, 2016 8:59 AM FEB 8, 2016 11:01 AM TANK 5 L-S DYED HIGH WATER ALARM FEB 11, 2016 11:48 AM FEB 9, 2016 3:56 PM FEB 8, 2016 5:31 PM
OVERFILL ALARM FEB 11, 2016 11:31 AM FEB 11, 2016 11:27 AM FEB 8, 2016 11:00 AM LOW PRODUCT ALARM FEB 8, 2016 10:29 AM SUDDEN LOSS ALARM FEB 11, 2016 11:15 AM FEB 11, 2016 9:04 AM FEB 9, 2016 3:48 PM HIGH PRODUCT ALARM FEB 8, 2016 11:00 AM MAY 12, 2015 6:02 AM APR 27, 2015 2:02 PM INVALID FUEL LEVEL FEB 11, 2016 11:37 AM FEB 8, 2016 10:29 AM PROBE OUT FEB 11, 2016 11:35 AM FEB 11, 2016 11:19 AM FEB 11, 2016 9:05 AM HIGH WATER WARNING FEB 11, 2016 11:48 AM FEB 9, 2016 3:56 PM FEB 8, 2016 5:31 PM MAX PRODUCT ALARM FEB 11, 2016 11:26 AM LOW TEMP WARNING FEB 8, 2016 11:10 AM APR 27, 2015 2:02 PM TANK 6 L-S DYED HIGH WATER ALARM FEB 11, 2016 9:13 AM OVERFILL ALARM FEB 11, 2016 9:43 AM FEB 11, 2016 9:37 AM FEB 8, 2016 2:36 PM SUDDEN LOSS ALARM FEB 11, 2016 9:07 AM FEB 8, 2016 10:28 AM APR 27, 2015 12:47 PM HIGH PRODUCT ALARM MAR 2, 2015 1:35 PM
INVALID FUEL LEVEL FEB 3, 2015 2:07 PM PROBE OUT FEB 11, 2016 9:44 AM FEB 11, 2016 9:07 AM FEB 8, 2016 2:33 PM HIGH WATER WARNING FEB 11, 2016 9:13 AM NO CSLD IDLE TIME APR 27, 2015 1:58 PM APR 27, 2015 12:40 PM APR 27, 2015 12:37 PM TANK 7 L-S DYED HIGH WATER ALARM FEB 23, 2015 12:11 PM FEB 21, 2015 1:32 PM FEB 19, 2015 9:59 AM
OVERFILL ALARM JAN 31, 2016 4:46 PM INVALID FUEL LEVEL FEB 23, 2015 3:48 PM FEB 22, 2015 2:44 PM FEB 3, 2015 6:25 PM PROBE OUT FEB 23, 2015 3:40 PM FEB 23, 2015 2:21 PM FEB 23, 2015 1:45 PM HIGH WATER WARNING FEB 23, 2015 12:11 PM FEB 21, 2015 1:32 PM FEB 19, 2015 9:59 AM PERIODIC TEST FAIL FEB 10, 2015 8:00 AM LOW TEMP WARNING FEB 23, 2015 12:01 PM FEB 21, 2015 5:57 PM FEB 21, 2015 1:26 PM TANK 8 CLEAR DIESEL PERIODIC TEST FAIL FEB 8, 2015 7:31 AM I38200 FEB 11, 2016 1:57 PM WHOLE SALE FUELS 2200 E BRUNDAGE BAKERSFIELD CA 93304 PRESSURE LINE LEAK ALARM HISTORY REPORT Q 1:L-S CLEAR FEB 8, 2016 4:44 PM PLLD SHUTDOWN ALARM FEB 8, 2016 4:44 PM GROSS LINE FAIL JAN 28, 2016 2:38 PM PLLD SHUTDOWN ALARM JAN 28, 2016 2:38 PM GROSS LINE FAIL JAN 25, 2016 2:44 PM PLLD SHUTDOWN ALARM JAN 25, 2016 2:44 PM GROSS LINE FAIL JAN 22, 2016 8:22 AM PLLD SHUTDOWN ALARM
JAN 22, 2016 8:22 AM GROSS LINE FAIL JAN 20, 2016 2:53 PM PLLD SHUTDOWN ALARM JAN 20, 2016 2:53 PM GROSS LINE FAIL Q 2:L-S DYED FEB 8, 2016 5:06 PM PLLD SHUTDOWN ALARM FEB 8, 2016 5:06 PM GROSS LINE FAIL FEB 2, 2016 4:24 PM PLLD SHUTDOWN ALARM FEB 2, 2016 4:24 PM GROSS LINE FAIL FEB 2, 2016 11:39 AM PLLD SHUTDOWN ALARM FEB 2, 2016 11:39 AM GROSS LINE FAIL OCT 8, 2015 1:25 PM PLLD SHUTDOWN ALARM OCT 8, 2015 1:25 PM GROSS LINE FAIL OCT 8, 2015 11:50 AM PLLD SHUTDOWN ALARM OCT 8, 2015 11:50 AM GROSS LINE FAIL Q 3:CLEAR DIESEL FEB 8, 2016 4:21 PM PLLD SHUTDOWN ALARM
FEB 8, 2016 4:21 PM GROSS LINE FAIL MAR 2, 2015 11:19 AM PLLD SHUTDOWN ALARM MAR 2, 2015 11:19 AM GROSS LINE FAIL FEB 3, 2015 3:22 PM PLLD SHUTDOWN ALARM FEB 3, 2015 3:22 PM GROSS LINE FAIL Q 4:UNLEADED FEB 9, 2016 7:57 AM PLLD SHUTDOWN ALARM FEB 9, 2016 7:57 AM GROSS LINE FAIL FEB 8, 2016 3:41 PM PLLD SHUTDOWN ALARM FEB 8, 2016 3:41 PM GROSS LINE FAIL JAN 26, 2016 3:10 PM PLLD SHUTDOWN ALARM JAN 26, 2016 3:10 PM GROSS LINE FAIL JAN 26, 2016 2:59 PM PLLD SHUTDOWN ALARM JAN 26, 2016 2:59 PM GROSS LINE FAIL JAN 26, 2016 2:18 PM PLLD SHUTDOWN ALARM JAN 26, 2016 2:18 PM GROSS LINE FAIL Q 5:L-S DYED FEB 11, 2016 6:19 AM PLLD SHUTDOWN ALARM FEB 11, 2016 6:19 AM GROSS LINE FAIL FEB 8, 2016 3:10 PM PLLD SHUTDOWN ALARM FEB 8, 2016 3:10 PM GROSS LINE FAIL DEC 18, 2015 3:33 AM PLLD SHUTDOWN ALARM DEC 18, 2015 3:33 AM GROSS LINE FAIL MAY 14, 2015 4:21 PM PLLD SHUTDOWN ALARM MAY 14, 2015 4:21 PM GROSS LINE FAIL MAY 13, 2015 1:42 AM PLLD SHUTDOWN ALARM MAY 13, 2015 1:42 AM GROSS LINE FAIL Q 6:L-S DYED FEB 11, 2016 10:55 AM PLLD SHUTDOWN ALARM FEB 11, 2016 10:55 AM GROSS LINE FAIL FEB 8, 2016 2:39 PM PLLD SHUTDOWN ALARM FEB 8, 2016 2:39 PM GROSS LINE FAIL FEB 8, 2016 2:24 PM FUEL OUT DEC 19, 2015 5:43 PM FUEL OUT MAR 2, 2015 12:19 PM PLLD SHUTDOWN ALARM MAR 2, 2015 12:19 PM GROSS LINE FAIL I30200 FEB 11, 2016 1:57 PM
WHOLE SALE FUELS 2200 E BRUNDAGE BAKERSFIELD CA 93304 LIQUID ALARM HISTORY REPORT SENSOR LOCATION 1 PANS FEB 11, 2016 12:30 PM FUEL ALARM FEB 11, 2016 12:25 PM FUEL ALARM FEB 8, 2016 1:04 PM FUEL ALARM 2 PANS FEB 11, 2016 12:31 PM FUEL ALARM FEB 11, 2016 12:24 PM FUEL ALARM FEB 11, 2016 12:24 PM FUEL ALARM 3 PANS
FEB 11, 2016 12:30 PM FUEL ALARM FEB 11, 2016 12:27 PM FUEL ALARM FEB 11, 2016 12:26 PM FUEL ALARM 9999FF1B I40200 FEB 11, 2016 1:57 PM I40300 FEB 11, 2016 1:57 PM I34200 FEB 11, 2016 1:57 PM I34700 FEB 11, 2016 1:57 PM 9999FF1B
SWRCB, January 2006
Spill Bucket Testing Report Form
This form is intended for use by contractors performing annual testing of UST spill containment structures. The completed form and
printouts from tests (if applicable), should be provided to the facility owner/operator forsubmittal to the local regulatory agency.
1.FACILITY INFORMATION
Facility Name:Date of Testing:
Facility Address:
Facility Contact:Phone:
Date Local Agency Was Notified of Testing :
Name of Local Agency Inspector (if present during testing):
2.TESTING CONTRACTOR INFORMATION
Company Name:Confidence UST Services, Inc.
Technician Conducting Test:
Credentials1:CSLB Contractor ICC Service Tech. SWRCB Tank Tester Other (Specify)
License Number(s):CSLB#804904 ICC#
3.SPILL BUCKET TESTING INFORMATION
Test Method Used:Hydrostatic Vacuum Other
Test Equipment Used:Lake TestEquipment Resolution:0.0625”
Identify Spill Bucket (By Tank
Number, Stored Product, etc.)
1234
Bucket Installation Type: Direct Bury
Contained in Sump
Direct Bury
Contained in Sump
Direct Bury
Contained in Sump
Direct Bury
Contained in Sump
Bucket Diameter:
Bucket Depth:
Wait time between applying
vacuum/water and start of test:
Test Start Time (TI):
Initial Reading (RI):
Test End Time (TF):
Final Reading (RF):
Test Duration (TF – TI):
Change in Reading (RF -RI):
Pass/Fail Threshold or
Criteria:
Test Result: Pass Fail Pass Fail Pass Fail Pass Fail
Comments –(include information on repairs made prior to testing, and recommended follow-up for failed tests)
CERTIFICATION OF TECHNICIAN RESPONSIBLE FOR CONDUCTING THIS TESTING
I hereby certify that all the information contained in this report is true, accurate, and in full compliance with legal requirements.
Technician’s Signature:________________________________________________ Date:_________
1 State laws and regulations do not currently require testing to be performed by a qualified contractor. However, local requirements
may be more stringent.
#1001/WholesaleFuels,Inc.02/11/2016
2200EastBrundageLane Bakersfield,CA93307
OmeroGarcia(661)393-7000
01/12/2016
Kris Karns
DustinReese
8216722-UT
T-1L-SClearDiesel
12.00"
14.25"
5min.
9:40 am
14.00"
10:40 am
14.00"
1hour
0.00"
0.0625"
T-2L-SDyedDiesel
12.00"
13.75"
5min.
9:40 am
13.50"
10:40 am
13.50"
1hour
0.00"
0.0625"0.0625"
T-3ClearDiesel
12.00"
13.75"
5min.
9:40 am
13.75"
10:40 am
13.75"
1hour
0.00"
T-4Unleaded
12.00"
14.00"
5min.
9:40 am
13.75"
10:40 am
13.75"
1hour
0.00"
0.0625"
All fill spill buckets except for tank #1 could not hold the required 5 gallons, tanks # 2,3,4,5, and 6 fill spill buckets will need to be fixed so that they can
Hold there temporary 5 gallons as required. After all repairs are made we will need to come back and test all failing spill buckets to make sure that they
are properly in order per local regulation.
02/11/2016
SWRCB, January 2006
Spill Bucket Testing Report Form
This form is intended for use by contractors performing annual testing of UST spill containment structures. The completed form and
printouts from tests (if applicable), should be provided to the facility owner/operator forsubmittal to the local regulatory agency.
1.FACILITY INFORMATION
Facility Name:Date of Testing:
Facility Address:
Facility Contact:Phone:
Date Local Agency Was Notified of Testing :
Name of Local Agency Inspector (if present during testing):
2.TESTING CONTRACTOR INFORMATION
Company Name:Confidence UST Services, Inc.
Technician Conducting Test:
Credentials1:CSLB Contractor ICC Service Tech. SWRCB Tank Tester Other (Specify)
License Number(s):CSLB#804904 ICC#
3.SPILL BUCKET TESTING INFORMATION
Test Method Used:Hydrostatic Vacuum Other
Test Equipment Used:Lake TestEquipment Resolution:0.0625”
Identify Spill Bucket (By Tank
Number, Stored Product, etc.)
1234
Bucket Installation Type: Direct Bury
Contained in Sump
Direct Bury
Contained in Sump
Direct Bury
Contained in Sump
Direct Bury
Contained in Sump
Bucket Diameter:
Bucket Depth:
Wait time between applying
vacuum/water and start of test:
Test Start Time (TI):
Initial Reading (RI):
Test End Time (TF):
Final Reading (RF):
Test Duration (TF – TI):
Change in Reading (RF -RI):
Pass/Fail Threshold or
Criteria:
Test Result: Pass Fail Pass Fail Pass Fail Pass Fail
Comments –(include information on repairs made prior to testing, and recommended follow-up for failed tests)
CERTIFICATION OF TECHNICIAN RESPONSIBLE FOR CONDUCTING THIS TESTING
I hereby certify that all the information contained in this report is true, accurate, and in full compliance with legal requirements.
Technician’s Signature:________________________________________________ Date:_________
1 State laws and regulations do not currently require testing to be performed by a qualified contractor. However, local requirements
may be more stringent.
#1001/WholesaleFuels,Inc.
2200EastBrundageLane
OmeroGarcia
T-5L-SDyedDiesel
12.00"
14.00"
5min.
9:40 am
14.00"
10:40 am
14.00"
1hour
0.00"
0.0625"
T-6L-SDyedDiesel
12.00"
14.25"
5min.
9:40 am
14.00"
10:40 am
14.00"
1hour
0.00"
0.0625"