Loading...
HomeMy WebLinkAbout2016 tank testRICH ENVIRONMENTAL 5643 BROOKS CT.- BAKERSFIELD, CA 93308 OFF. (661)392 -8687 FAX(661)588 -7808 ALERT 1000 UNDERFILL & 1050X ULLAGE SYSTEM & ACURITE TM. PRECISION UNDERGROUND STORAGE TANK SYSTEM LEAK TEST TEST RESULTS DATE: 01/22/2016 BILLING: ROSS SESSIONS SITE: FREEWAY LIQUOR/TMP 13216 CHEYENNE MTN DR 2140 BRUNDAGE LANE BAKERSFIELD, CA 93314 BAKERSFIELD, CA 93307 PRODUCT VOLUME %FULL WETTED NON - WETTED PRODUCT LEAK WATER IN �(GAL) PORT ON PO TION LINE-- DETECTOR TANK (11- 17 -15) PREMIUM 10,000 EMPTY% N/A FAIL N/A N/A 0" (11- 30 -15) UNLEADED 10,000 EMPTY% N/A PASS N/A N/A 0" (12- 03 -15) PREMIUM 10,000 EMPTY% N/A PASS N/A N/A 0" COMMENTS MEASUREMENTS SHOWED THAT WATER IN THE BACKFILL AREA AT THE TIME OF TESTING WAS BELOW TANK BOTTTOM:, AND THEREFORE NOT A FACTER IN TEST DETERMINATION. A MONITORING WELL OR A WELL POINT WAS DRIVEN IN THE BACKFILL AREA TO DETERMINE THAT THERE IS NO WATER IN THE BACKFILL AT TANK BOTTOM. A PRECISION TEST WAS PERFORMED ON TANKS AT THE ABOVE LOCATION USING THE ALERT 1000 UNDERFILL SYSTEM AND THE ALERT 1050 ULLAGE SYSTEM. I HAVE REVIEWED THE DATA PRODUCED IN CONJUNCTION WITH THIS TEST PURPOSE OF VERIFYING THE RESULTS AND CERTIFYING THE TANK SYSTEMS. THE TESTING WAS PERFORMED IN ACCORDANCE WITH ALERT PROTOCOL, AND THEREFORE SATISFIES ALL REQUIREMENTS FOR SUCH TESTING AS SET FORTH BY NFPA - 329 -92 AND USEPA 40 CFR PARTS 280. THE RESULTS OF TESTING ARE SHOWN ON THE FOLLOWING PAGE, AND INDICATE WHETHER THE WETTED J A I` D ITO?NT- AA.IETTE'D - PORTION PASSED OR FAILED. INCLUDED WITH THE REPORT ARE REPRODUCTION OF DATA COMPLIED DURING THE TEST WHICH FORMED THE BASIS FOR THESE CONCLUSIONS. THIS INFORMATION IS STORED IN A PERMANENT FILE IF FUTURE VERIFICATION OF TEST RESULTS IS NEEDED, I DECLARE UNDER PENALTY OF PERJURY THAT I AM A LICENSED TANK TESTER IN THE STATE OF CALIFONIA AND THAT THE INFORMATION CONTAINED IN THIS REPORT IS TRUE AND CORRECT TO THE BEST OF MY KNOWLEDGE. TEST CE IFIED BY: JAMS J C CER 90 -1072 RECEIVED MAR 07 2016