HomeMy WebLinkAboutTank Integrity Testing 4-15-16Water Sensor Indication: I declare under penalty of perjury that testing was done by a licensed
Water Intrusion No Water XXX N/A tank tester in the State of California and the information in this report
__ __ __ __ __ __ __ __ __ __ __ __ __ __ __ true and correct to the best of my knowledge. XXX PASS INCONCLUSIVE Technician: ZANE NIMMO
FAIL Ullage (Dry) Signature: OTTL# 04-1676 ICC 5263322-UT ICC 5263322-U3 Oregon UST Service # 26755 Oregon UST Tank Tightness # 26756 Nevada UT-2206
Comments:
PRECISION TANK TEST 416 2nd Street Phone: (209) 744-0112 Galt, CA 95632 Fax: (209) 744-0116 afforda@softcom.net
Site Name:
Site Address: City/ State:
MESA MARIN CHEVRON 11101 HIGHWAY 178 BAKERSFEILD, CA 93306
Equipment: Triangle TEI System 5000W TEI Ullage System
Test Date: 4/15/2016
Tank 1 Tank Product: 87 Ullage: 3,160 Volume: 6,825 Tank Size: 9,985
PRESSURE SENSOR CALCULATION WATER SENSOR CALIBRATION
Prod. “
61.3
X Prod. Wt.
.026
=
PSI (1) 1.59
Cal #1 Cal #2 Cal #3
“ Water In Tank
0
X .036 =
PSI (2) 0
: AVERAGE
(1) + (2) = Positive Head Pressure In Tank
=
PSI (3) 1.59
Water Intrusion Test Period: Began
Ended
“Water Outside Tank
0
X .036 =
PSI (4) 0
Test Period Calculation:
(3)
Head Pressure
- (4)
Outside Water Pressure
=
PSI (5)
1.59 +/-
Avg
/ 3780 =
“A” Factor
/ .05 =
Test Time
(5) 1.59
+
.5 PSI
+ PSI (6)
.50
Groundwater Depth Determination:
TEST PRESSURE PSI (7)
2.09 +/-
By: TESTER
If (6) is less than .5 PSI, (7) shall be .5 PSI 2.09
Where or How: NO KNOWN WATER
TIME PRESSURE Blower Started 1100
0.00
Height 47”
T Test Pressure Reached 1148
2.09
Bottom To Grade 142”
Blower Turned Off 1155
2.14
Product Ground in Tank Water
61.3” N / A”
Test Began 1155
2.14
Water in Tank 0”
Dia. 95”
Test Ended 1158
2.14
Water Sensor Indication: I declare under penalty of perjury that testing was done by a licensed
Water Intrusion No Water XXX N/A tank tester in the State of California and the information in this report
__ __ __ __ __ __ __ __ __ __ __ __ __ __ __ true and correct to the best of my knowledge. XXX PASS INCONCLUSIVE Technician: ZANE NIMMO
FAIL Ullage (Dry) Signature: OTTL# 04-1676 ICC 5263322-UT ICC 5263322-U3 Oregon UST Service # 26755 Oregon UST Tank Tightness # 26756 Nevada UT-2206
Comments:
PRECISION TANK TEST 416 2nd Street Phone: (209) 744-0112 Galt, CA 95632 Fax: (209) 744-0116 afforda@softcom.net
Site Name:
Site Address: City/ State:
MESA MARIN CHEVRON 11101 HIGHWAY 178 BAKERSFIELD, CA 93306
Equipment: Triangle TEI System 5000W TEI Ullage System
Test Date: 4/15/2016
Tank 2 Tank Product: DIE Ullage: 7,565 Volume: 2,420 Tank Size: 9,985
PRESSURE SENSOR CALCULATION WATER SENSOR CALIBRATION
Prod. “
27.7
X Prod. Wt.
.031
=
PSI (1) 0.85
Cal #1 Cal #2 Cal #3
“ Water In Tank
0
X .036 =
PSI (2) 0
: AVERAGE
(1) + (2) = Positive Head Pressure In Tank
=
PSI (3) 0.85
Water Intrusion Test Period: Began
Ended
“Water Outside Tank
0
X .036 =
PSI (4) 0
Test Period Calculation:
(3)
Head Pressure
- (4)
Outside Water Pressure
=
PSI (5)
0.85 +/-
Avg
/ 3780 =
“A” Factor
/ .05 =
Test Time
(5) 0.85
+
.5 PSI
+ PSI (6)
0.50
Groundwater Depth Determination:
TEST PRESSURE PSI (7)
1.35 +/-
By: TESTER
If (6) is less than .5 PSI, (7) shall be .5 PSI 1.35
Where or How: NO KNOWN WATER
TIME PRESSURE Blower Started 1100
0.00
Height 50”
T Test Pressure Reached 1130
1.35
Bottom To Grade 145”
Blower Turned Off 1133
1.48
Product Ground in Tank Water
27.7” N / A”
Test Began 1135
1.48
Water in Tank 0”
Dia. 95”
Test Ended 1138
1.48
Water Sensor Indication: I declare under penalty of perjury that testing was done by a licensed
Water Intrusion No Water XXX N/A tank tester in the State of California and the information in this report
__ __ __ __ __ __ __ __ __ __ __ __ __ __ __ true and correct to the best of my knowledge. XXX PASS INCONCLUSIVE Technician: ZANE NIMMO
FAIL Ullage (Dry) Signature: OTTL# 04-1676 ICC 5263322-UT ICC 5263322-U3 Oregon UST Service # 26755 Oregon UST Tank Tightness # 26756 Nevada UT-2206
Comments:
PRECISION TANK TEST 416 2nd Street Phone: (209) 744-0112 Galt, CA 95632 Fax: (209) 744-0116 afforda@softcom.net
Site Name:
Site Address: City/ State:
MESA MARIN CHEVRON 11101 HIGHWAY 178 BAKERSFIELD, CA 93306
Equipment: Triangle TEI System 5000W TEI Ullage System
Test Date: 4/15/2016
Tank 3 Tank Product: 91 Ullage: 5,694 Volume: 4,291 Tank Size: 9,985
PRESSURE SENSOR CALCULATION WATER SENSOR CALIBRATION
Prod. “
42.2
X Prod. Wt.
.026
=
PSI (1) 1.09
Cal #1 Cal #2 Cal #3
“ Water In Tank
0
X .036 =
PSI (2) 0
: AVERAGE
(1) + (2) = Positive Head Pressure In Tank
=
PSI (3) 1.09
Water Intrusion Test Period: Began
Ended
“Water Outside Tank
0
X .036 =
PSI (4) 0
Test Period Calculation:
(3)
Head Pressure
- (4)
Outside Water Pressure
=
PSI (5)
1.09 +/-
Avg
/ 3780 =
“A” Factor
/ .05 =
Test Time
(5) 1.09
+
.5 PSI
+ PSI (6)
.50
Groundwater Depth Determination:
TEST PRESSURE PSI (7)
1.59 +/-
By: TESTER
If (6) is less than .5 PSI, (7) shall be .5 PSI 1.59
Where or How: NO KNOWN WATER
TIME PRESSURE Blower Started 1100
0.00
Height 56”
T Test Pressure Reached 1144
1.59
Bottom To Grade 151”
Blower Turned Off 1155
2.14
Product Ground in Tank Water
42.2” N / A”
Test Began 1158
2.14
Water in Tank 0”
Dia. 95”
Test Ended 1201
2.13
Water Sensor Indication: I declare under penalty of perjury that testing was done by a licensed
Water Intrusion No Water XXX N/A tank tester in the State of California and the information in this report
__ __ __ __ __ __ __ __ __ __ __ __ __ __ __ true and correct to the best of my knowledge. XXX PASS INCONCLUSIVE Technician: ZANE NIMMO
FAIL Ullage (Dry) Signature: OTTL# 04-1676 ICC 5263322-UT ICC 5263322-U3 Oregon UST Service # 26755 Oregon UST Tank Tightness # 26756 Nevada UT-2206
Comments:
PRECISION TANK TEST 416 2nd Street Phone: (209) 744-0112 Galt, CA 95632 Fax: (209) 744-0116 afforda@softcom.net
Site Name:
Site Address: City/ State:
MESA MARIN CHEVRON 11101 HIGHWAY 178 BAKERSFIELD, CA 93306
Equipment: Triangle TEI System 5000W TEI Ullage System
Test Date: 4/15/2016
Tank 4 Tank Product: 89 Ullage: 6,969 Volume: 3,016 Tank Size: 9,985
PRESSURE SENSOR CALCULATION WATER SENSOR CALIBRATION
Prod. “
32.4
X Prod. Wt.
.026
=
PSI (1) 0.84
Cal #1 Cal #2 Cal #3
“ Water In Tank
0
X .036 =
PSI (2) 0
: AVERAGE
(1) + (2) = Positive Head Pressure In Tank
=
PSI (3) 0.84
Water Intrusion Test Period: Began
Ended
“Water Outside Tank
0
X .036 =
PSI (4) 0
Test Period Calculation:
(3)
Head Pressure
- (4)
Outside Water Pressure
=
PSI (5)
0.84 +/-
Avg
/ 3780 =
“A” Factor
/ .05 =
Test Time
(5) 0.84
+
.5 PSI
+ PSI (6)
0.50
Groundwater Depth Determination:
TEST PRESSURE PSI (7)
1.34 +/-
By: TESTER
If (6) is less than .5 PSI, (7) shall be .5 PSI 1.34
Where or How: NO KNOWN WATER
TIME PRESSURE Blower Started 1100
0.00
Height 56”
T Test Pressure Reached 1137
1.34
Bottom To Grade 151”
Blower Turned Off 1155
2.14
Product Ground in Tank Water
32.4” 0”
Test Began 1201
2.13
Water in Tank 0”
Dia. 95”
Test Ended 1204
2.13