HomeMy WebLinkAboutDel Taco Bakersfield Well Prox ELD Test Results UST System Well Proximity Test Report
ELD Test Date:
Customer:
Location:
Tested By: CGRS, Inc.
5444 Dry Creek Road
Sacramento, CA 95838
Project No:6‐13116‐16006‐9058
Stuart's Petroleum
Del Taco
11 E. 4th St.
Bakersfield, CA 93307
3624 California Ave.
Bakersfield, CA 93309
June 16, 2016
Location:CGRS Project No :
Test Date:
CGRS Techs:
CA Tank Tech Signature:
Sergio L. Nunez CA Tank Tester #06‐1727 Date
Reviewed by:
Chris Murphy Director of CA Operations Date
3624 California Ave.
Well Proximity ELD Test Results
6/17/2016
6/22/2016
DieselPrimary Containment SystemPASS
87 OctanePrimary Containment SystemPASS
91 OctanePrimary Containment SystemPASS
Test Certification
Well Proximity Enhanced Leak Detection (ELD)
Del TacoJune 16, 2016
6‐13116‐16006‐9058
Bakersfield, CA 93309
Sergio L. Nunez
This document certifies that the UST systems listed below at the above referenced location has
been tested and passed the Enhanced Tracer Tight, tightness test. CGRS further certifies that this
test meets the testing requirements for underground storage tank systems as per the California
Code Regulations, Title 23, Chapter 16 Section 2644.1 (a) (1& 2).
Test Date:Technicians:
Site Information Contractor Information
Facility:Contractor Name :
Address:Address:
City, State, Zip:City, State, Zip:
County:Contact:
CUPA Contact:Telephone/Email:
CUPA Phone/Email:
Tank No.Capacity (gal.)ProductTypeManufacturerDepth to GWTank Bottom (in.)Product Level (in.)BrineTest Result
Tank 112,00087 OctaneDouble WallTrusco>‐96 in.15661NoPASS
Tank 28,00091 OctaneDouble WallTrusco>‐96 in.15629NoPASS
Tank 34,000DieselDouble WallTrusco>‐96 in.15679NoPASS
Tank Top SumpsManufacturerDiameter (in.)Depth (in.)Volume (gal.)DescriptionTest Result
S1Unknown4252311.8787 TSPASS
S2Unknown4252311.8791 TSPASS
S3Unknown4252311.87DSL TSPASS
UDCs ManufacturerLength (in.)Width (in.)Depth (in.)Volume (gal.)DescriptionTest Result
UDC1Bravo421836117.821PASS
UDC2Bravo421836117.822PASS
UDC3Bravo421836117.823PASS
UDC4Bravo421836117.824PASS
UDC5Bravo421836117.825PASS
Transition SumpManufacturerLength (in.)Width (in.)Depth (in.)Volume (gal.)DescriptionTest Result
N/AN/AN/AN/AN/AN/AN/AN/A
Spill BucketsTankDiameter (cm.)Depth (cm.)Initial TimeInitial Reading (in.)Final TimeFinal Reading (in.)Test Result
87 Fill87 Tank273014:001015:0010PASS
87 Vapor87 Tank273014:001415:0014PASS
91 Fill91 Tank273014:001615:0016PASS
91 Vapor91 Tank273014:001015:0010PASS
DSL FillDiesel Tank273014:001015:0010PASS
Product PipingManufacturerTypeSize (in.)Length (ft.)Test Result
87 PL1APTDW Flex1.555PASS
87 PL2APTDW Flex1.550PASS
91 PL1APTDW Flex1.550PASS
91 PL2APT15 ft EnviroflexDW Flex1.545PASS
DSL PLTotal ContainmentOmniflexDW Flex235PASS
Vent PipingManufacturerTypeSize (in.)Length (ft.)Test Result
87/91 VentA.O. SmithSW Fiberglass365PASS
Diesel VentA.O. SmithSW Fiberglass225PASS
Vapor PipingManufacturerTypeSize (in.)Length (ft.)Test Result
VRA.O. SmithSW Fiberglass3110PASS
ItemTestTestedSample IDConcentrationDateTimeDescription (How & volume collected, Notes)
Reviewed ByDateCA Tank Tester Signature Date
Bakersfield, CA 93309
Well Proximity Project Worksheet
Del Taco
3624 California Ave.
6/16/16
Rich Environmental
Sergio L. Nunez
5643 Brooks Ct.
Bakersfield, CA 93308
6/17/2016
Leak Logs/Repairs
James Rich
PIPING
COMPONENTS IN CONTAINMENT
TANKS
661‐392‐8687/jamie1.res@gmail.com
Kern
Vicki Furnish; Bakersfield Fire Dept.
661‐862‐8743/hazmatprogram@co.kern.ca.us; 661‐326‐
3979/ctperkins@bakersfieldfire.us
CA License No.
6/22/2016 06‐1727
Customer:CGRS Project #:Site Location:
6‐13116‐16006‐9058
Bakersfield, CA 93307Bakersfield, CA 93309
Site Plan/Drawing
Stuart's PetroleumDel Taco
3624 California Ave.11 E. 4th St.