HomeMy WebLinkAbout2015 REPORTUnderground Storage Tank Program
DW Inspection Report , a
Permission to Inspect:
V F d
BAKERSFIELD FIRE DEPARTMENT
Prevention Services Division
2101 H Street
Bakersfield, CA 93301
Phone: 661-326-3979
Fax: 661-852-2171
Business Name: BAKERSFIELD POLICE DEPARTMENT-15-021-001050 Date:1/20/2015
Address Name: 1601 Truxtun Ave-CAD981973746 Inspector Name: Shane Gardner #8248557
Inspection Type: Routine 71 Report Final
NVO = No Violation Observed OUT = Out of Compliance NA = Not Applicable UD = Undetermined
COS = Corrected On Site RPT = Repeat Violation
Violation Program Requirement
4-
0 0ozo
SOC Comments
No 0> in 0
11 -1 kv0 '3
z 0 z
File Review
Facility Tank Information
2030021 Facility has a valid Permit Tank 1-15000-REG-DW
to Operate from the F-1 El F-1 NoneNone
Tank 2-
CUPA - 23 CCR 16 2712(1); Tank 3-
HSC 6.7 25284 Tank 4-
2010010 UST Operating Permit Z-4 S-r-
Application for Facility ev/4s 4w, r
information and Tank r-l' F-1 Noneinformation
submitted/maintained - 23
CCR 16 2711; HSC 6.7
25286(a)
2010001 Current BOE number
submitted to the CUPA F-1 None
and/or CERS - HSC 6.7
25286(c)
2030011 UST compliance
statement and/or
Designated Operator U F-1 None
current certification
submitted - 23 CCR 16 Ile
2715(a), 2715(b)
2030046 A complete and accurate
response plan has been
submitted, approved and None
maintained - 23 CCR 16
2632, 2634(e), 2641(h),
2712(i)
2030041 A complete and accurate
plot plan has been
submitted, approved and F-1 F-1 EJ None
maintained - 23 CCR 16
2632(d)(1 C), 2711(a)
2010006 Owner/Operator has not
made false statements or
representation on any r- F-1 None
required document - HSC
6.725299
2010003 Owner/Operator has a
DO and/or informed the
CUPA of any change (s) None
within 30 days - 23 CCR
16 2715(a)
Violation Program Requirement
4-
0 04) SOC Comments
No 0 M a
0
0 CL
120
wa
z 0 z M 0 W o>
Testing
2030002 Owner/Operator has
tested and certified leak None
detection equipment
annually - 23 CCR 16 2638
2030048 Secondary containment
testing conducted every
36 months in accordance None
with requirements - 23
CCR 16 2637
2030055 Spill buckets have been
tested annually as F] n None
required - HSC 6.7 25284.2
2010009 Secondary containment
test results submitted to
the CUPA within 30 days El None
after the test - 23 CCR 16
2--
2637(e)
2030064 CUPA was poperly
notified within the
prescribed number of r-J., None
hours prior to testing - 23 Al
CCR 16 26370, 2638(e),
2643(g), 2644.1(a)(4)
Install/Repair
2060009 Permits obtained to
install, replace, repair, or 2-- None
modify part of the UST
system - 23 CCR 16 2712
UST System Observation
General Monitoring
2030003 Leak detection system
maintains continuous RD
monitoring that activates None 1
an audible and visual Yes
alarm - 23 CCR 16 2632,
2634, 2636, 2666
2030016 The annular space of the
tank, piping and sumps RD
are continuously
monitored and activates None
the alarm - 23 CCR 16 Yes
2631(8), 2632(c)(2)(A)&(8),
2633(c), 2636(o
2030017 Product piping outside the
UDC is fail-safe and shuts
down the pump or None
restricts flow - 23 CCR 16
2636(0 (5)
2030018 Turbine sump monitor RD
activates an audible and
visual alarm or stops the In
None
flow of at the dispenser - Yes
23 CCR 16 2636(0 (1)
Underground Storage Tank Program - DW Inspection Report v 2.0
Violation Program Requirement o SOC Comments
No O F- CO ar ozozMyWo>
2030019 Monitoring system in the
UDCs activates an
audible and visual alarm None
or stops the flow at the
UDC -23 CCR 16
2636(0(1)___
2030043 Leak detection equipment RD
properly programmed or
properly operated - 23 None
CCR 16 2632, 2634, 2636, Yes
2666
2060005 System constructed with
a monitoring system
capable of detecting entry None
into secondary
containment - HSC 6.7
25291(p)
2060014 Correct leak detection
equipment installed for RD
the type of system None
present - 23 CCR 16 2638, Yes
HSC 6.7 25290.1, 25290.2,
25291
2060015 Sensor located in the RD
proper position /location - None
23 CCR 16 2630(d), 2641(a) Yes
2030062 Facility is in compliance RDwithnottamperingwithor
disabling leak detection None
devices or alarms - HSC Yes
6.7 25299 a 9
2060022 System constructed with
a monitoring system
capable of detecting entry None
into secondary
containment - HSC 6.7
25290.2(d)
2030034 Tag /sticker on affixed
monitoring equipment
being certified, repaired, E] None
or replaced - 23 CCR 16
2638(
VPH Monitoring VPH
2030065 Interstitial monitoring of RDtheannularspacesofthe
UST is properly None
maintained - HSC 6.7 Yes
25290.1(e
2060023 System constructed with
a monitoring system
capable of detecting entry
into secondary None
containment - HSC 6.7
25290.1(d)
Underground Storage Tank Program - DW Inspection Report v 2.0
Violation Program Requirement
4-
0
0 0 SOC Comments
No O> M 0 0 0-
42 =
00
Z 0 Z 3 U 4)
Line Leak Detector
2060012 Line leak detector
installed on pressurized RD
piping system - HSC 6.7 None
25290.1(h), 25290.2(8), Yes
25291(0, 25292(e),
2636(0 (2)
2030026 Line leak detectors detect
a 3 gph leak and/or RD
audible and visual alarm F-1 None
function properly - 23 Yes
CCR 16 2636(0(6),
2666(c)
2030027 Turbine shuts down when RDaleakisdetectedor
when line leak detector is 1:1 None
disconnected - 23 CCR 16 Yes
2666(c)
2030025 Pressurized piping able to
detect a 3.0 gph leak PE RD
within an hour, and None F]
restricts the flow or Yes
alarms - 23 CCR 16
2636(0 (2)
Secondary Containment
2060010 UST storing a hazardous RD
substance has secondary None
containment - HSC 6.7 Yes
25292
Underground Storage Tank Program - DW Inspection Report v 2.0
Violation Program Requirement
4-
0 00 = SOC Comments
No
a 0 CL
42 (a
Z 0 Z
2030008 UDC, sumps, and/or
other secondary
containment in good None
condition and/or are free
of debris/liquid - HSC 6.7
25290.1, 25290.2, 25291
2030040 Secondarily contained RD
piping maintained to allow D' None
liquid to drain into sump -.,, Yes
23 CCR 16 2630(d), 2641 (a)
2060006 Secondary containment
piping slopes back to the None
collection sump - 23 CCR
16 263(c)
2030047 Secondary containment
maintained tight and has
been confirmed by testing F] None
23 CCR 16 2662; HSC 6.7
25290.1(c)(2), 25290.2(c)(2),
25291(a), 25292(e)
2030060 Entry fittings in secondary
containment for UST
system maintained El None
tight/sealed - 23 CCR 16 Len
2630, 2635(d), 2636(c),
2666
2060020 Spill bucket is installed RPandhasafunctionaldrain
valve or other means to ej None
remove liquid - 23 CCR 16 Yes
2635(b), 2665
2030054 Spill bucket maintained in RP
good condition and free of El 1:1 None
debris and/or liquid - 23 Yes
CCR 16 2635(b), 2715(c)(2)
2060019 Spill bucket to has a
minimum capacity of five El E-1 None
gallons - 23 CCR 16
2635(b), 2665
Overfill
2030035 UST system is operated RPtopreventunauthorized
release, including spills None F-1
and overfills - HSC 6.7 Yes
25292.1 (a)
2030036 Overfill prevention system RPhasnotbeenoverridden
and meets overfill grEE:1 None
requirements - 23 CCR 16 Yes
2635(b)(2), 2665 — I
Underground Storage Tank Program - DW Inspection Report v 2.0
Violation Program Requirement o SOC Comments
No 0>
a 0 a.
as
Mo
2 0 z D
On Site Records
Certifications
2030023 Required designated
operators or contractors
maintain a proper and 1:1 F-1 None
current ICC certification -
23 CCR 16 2715
2030024 Service technician,
installer, and/ or
employee maintain a None
proper license - 23 CCR
162715
2030031 Employee or contractor
obtained and maintained
proper manufacturer PT None
certification - 23 CCR 16
2715
2010007 Submit/maintain current
Certificate of Financial
Responsibility /mechanism
of financial assurance - None
23 CCR 16 2711; 23 CCR/
18 2808.1, 2809-2809.2;
HSC 6.7 25292.2; HSC
6.75 25299.30-25299.34
Designated Operator
2010004 Copies of DO inspections
for last 12 months and list
of trained employees F-1 None
maintained - 23 CCR 16
2715
2030013 Designated operator
properly conducted the
monthly inspection and F-1 r-1 None
the reports are complete -
23 CCR 16 2715
2030010 DO notified operator of
any condition observed
during the monthly
oA
None
inspection that may
require action - 23 CCR 16
2715(d)__
2030012 DO employee training
performed, current for at
least one employee on None
site, and a log kept - 23
CCR 16 2715(c)(6), 27150
Underground Storage Tank Program - DW Inspection Report v 2.0
Violation Program Requirement m 2 SOC Comments
No 0 a a 0 CL 0)o
Z 0 Z
Logs
2030001 Leak detection alarm
logs, maintenance and RD
records of appropriate A E] None
follow-up actions Yes
maintained - 23 CCR 16
2632, 2634, 2712(b)
Maintenance/Tests
2010008 Monitoring, maintenance,
repairs, linings, and RD
upgrade records None
maintained for the proper Yes
time period - 23 CCR 16
2712(b)
Documentation
2030033 Failure to maintain on site
an approved monitoring PT r_1 None
plan - 23 CCR 16 2632,
2634, 2711, 2712(1)
2030037 Written agreement
between the tank owner
and tank operator to
monitor the tank system None
is maintained - 23 CCR 16A
2620(b); HSC 6.7
25284(a)(3)
2030061 Suspected or actual RD
unauthorized release
reported in appropriate None
time frame - HSC 6.7 Yes
29294,29295
General Operating Requirements
Permit Condition/Approval
2030039 Compliance with all
operating permit E:] None
conditions - 23 CCR 16
2712; HSC 6.7 25299
2030059 UST system maintained
in accordance with
exclusion/exemption 0' None
status - HSC 6.7 25281.6,
25283.5
2030014 Owner/Operator received
approval and has
implemented a training None
program at an unstaffed
facility - 23 CCR 16
2715 (0(2)
2030015 Facility exhibited that the
method used to monitor
the tank meets the
monitoring methods in None
2643(f) - 23 CCR 16 2643
Underground Storage Tank Program - DW Inspection Report v 2.0
Violation Program Requirement
4-
0 0 SOC Comments
No
M a
W
0 L
z 0 z 0 0 W oy
Red Tag
2030045 Red Tag information is
legible and has not been El Zrol None
tampered with - 23 CCR
16 2717.1 (g)
2030044 Facility did not allow for
deposit of petroleum into
a UST that has a red tag None
affixed to the fill - 23 CCR
162717.1(0
Install/Repair
2060024 UST system is made of or
lined with materials that
are compatible with the None
substance stored - 23
CCR 16 2631.1
2060021 Striker plate installed and
positioned correctly - 23 None
CCR 16 2631(c), 2662(d
17VThere were no violations noted for this inspection.
fMis report shall serve as a "NOTICE TO COMPLY" for Minor Violations, and a "NOTICE OF VIOLATION" for
Major violations. You are, hereby, ordered to correct the above noted violations within 30 days, or according to
correction summaries provided. Formal enforcement and/or penalty assessment may be initiated for any
violations noted, and for those not corrected in a timely manner. (NOTE: If this is a preliminary report, a final report
will follow.)
Inspectors Signature: Date:
Inspector: Enter # of Violations: RP:
Check one box for facility Significant Operational Status (SOC) to be reported to SWRCB and US EPA:
0 'SOC with both Release Detection and Release Detection (Facility has no Release Prevention and no Release
Prevention Violations)
Not in SOC (Facility has both Release Prevention and Release Detection Violations)
SOC with Release Detection only (Facility has no Release Detection violations but one or more Release Prevention
violations)
SOC with Release Prevention only (Facility has no Release Prevention violations but one or more Release Detection
violations)
Underground Storage Tank Program - DW Inspection Report v 2.0