HomeMy WebLinkAboutINSPECTION REPORT 2015BAKERSFIELD FIRE DEPARTMENT
Prevention Services Division
Underground Storage Tank Program 2101 H St . reet
DW Inspection Report Bakersfield, CA 93301
Permission to Inspect: 2 1'``Phone: 661-326-3979
Fax: 661-852-2171
Business Name: Arco #82454 (15-021-68589) Date:7/28/15
Address Name: 2800 Panama Lane Inspector Name: Kris Karns (8292402)
Inspection Type: Routine Report: Final
NVO = No Violation Observed OUT = Out of Compliance NA = Not Applicable UD = Undetermined
COS = Corrected On Site RPT = Repeat Violation
Violation Program Requirement 00 SOC Comments
No 0> M a 0
2 0 z M 0 W
File Review
Facility Tank Information
2030021 Facility has a valid Permit Tank 1-10000-REG Master-DW
to Operate from the Tank 2-10000-REG Siphon-DW
CUPA - 23 CCR 16 2712(1); Z None Tank 3-10000-REG Siphon-DW
HSC 6.7 25284 Tank 4 10000-SUP-DW
2010010 UST Operating Permit
Application for Facility
information and Tank
information Z None
submitted/maintained - 23
CCR 16 2711; HSC 6.7
25286(a)
2010001 Current BOE number
submitted to the CUPA Z None
and/or CERS - HSC 6.7
2030011
25286(c) _
UST compliance Designated Operator Certifications
statement and/or
in CERS are expired.
Designated Operator Z F-1 n None
current certification
submitted - 23 CCR 16
2715(a), 2715(b)
2030046 A complete and accurate Update info in CERS, last update
response plan has been in 2012.
submitted, approved and Z 1 F-1 None
maintained - 23 CCR 16
2632, 2634(e), 2641(h),
2712(i)
2030041 A complete and accurate Update plot plan in CERS, and
plot plan has been include all underground
submitted, approved and None piping.
maintained - 23 CCR 16
2632(d)(1)(C), 2711(a)(8)
2010006 Owner/Operator has not
made false statements or
representation on any Z F-1 r-1 n None
required document - HSC
6.725299
Violation Program Requirement o SOC Comments
No o Q o a a,c
z O z D 0 05
2010003 Owner /Operator has a
DO and /or informed the
CUPA of any change (s) None
within 30 days - 23 CCR
16 2715(a)
Testing
2030002 Owner /Operator has
tested and certified leak FJ R None
detection equipment
annual) - 23 CCR 16 2638
2030048 Secondary containment
testing conducted every
36 months in accordance None
with requirements - 23
CCR 16 2637
2030055 Spill buckets have been
tested annually as None
required - HSC 6.7 25284.2
2010009 Secondary containment
test results submitted to
the CUPA within 30 days None
after the test - 23 CCR 16
2637(e)
2030064 CUPA was poperly
notified within the
prescribed number of None
hours prior to testing - 23
CCR 16 26370, 2638(e),
2643(g), 2644.1(a)(4)
Install /Repair
2060009 Permits obtained to
install, replace, repair, or None
modify part of the UST
system - 23 CCR 16 2712
UST System Observation
General Monitoring
2030003 Leak detection system
maintains continuous RD
monitoring that activates None
an audible and visual Yes
alarm - 23 CCR 16 2632,
2634, 2636, 2666
2030016 The annular space of the 91 Annular Sensor would not
tank, piping and sumps activate when tested. Technician
are continuously
RD replaced with a new sensor like for
monitored and activates None like. New sensor was re- tested
and confirmed oprational.
the alarm - 23 CCR 16 Yes Violation was corrected on site.
2631(8), 2632(c)(2)(A) &(B),
2633(c), 2636
2030017 Product piping outside the
UDC is fail -safe and shuts
down the pump or El E] None
restricts flow - 23 CCR 16
2636(0 (5)
Underground Storage Tank Program - DW Inspection Report v 2.0
Violation Program Requirement 0.0 SOC Comments
No
Q in O a Do
z O z U j
2030018 Turbine sump monitor RD
activates an audible and
visual alarm or stops the None
flow of at the dispenser - Yes
23 CCR 16 2636( (1)
2030019 Monitoring system in the
UDCs activates an
audible and visual alarm None
or stops the flow at the
UDC -23 CCR 16
2636 (0(1)
2030043 Leak detection equipment RD
properly programmed or
properly operated - 23 None F]
CCR 16 2632, 2634, 2636, Yes
2666
2060005 System constructed with
a monitoring system
capable of detecting entry None
into secondary
containment - HSC 6.7
25291(b)
2060014 Correct leak detection
equipment installed for RD
the type of system None
present - 23 CCR 16 2638, Yes
HSC 6.7 25290.1, 25290.2,
25291
2060015 Sensor located in the RD
proper position /location - None
23 CCR 16 2630(d), 2641(a) Yes
2030062 Facility is in compliance RD
with not tampering with or
disabling leak detection None
devices or alarms - HSC Yes
6.7 25299(a)(9)
2060022 System constructed with
a monitoring system
capable of detecting entry None
into secondary
containment - HSC 6.7
25290.2(d)
2030034 Tag /sticker on affixed
monitoring equipment
being certified, repaired, None
or replaced - 23 CCR 16
2638(1)
VPH Monitoring VPH
2030065 Interstitial monitoring of RDtheannularspacesofthe
UST is properly None
maintained - HSC 6.7 Yes
25290.1(e
Underground Storage Tank Program - DW Inspection Report v 2.0
Violation Program Requirement 0
0.0 SOC Comments
No 0 a 0 M c
Z 0 Z M 0 4)>
2060023 System constructed with
a monitoring system
capable of detecting entry
into secondary None
containment - HSC 6.7
25290.1(d)
Line Leak Detector
2060012 Line leak detector
installed on pressurized RD
piping system - HSC 6.7 None
25290.1(h), 25290.2(g), Yes
252910, 25292(e),
2636(0(2)
2030026 Line leak detectors detect
a 3 gph leak and/or RD
audible and visual alarm None 1
function properly - 23 Yes
CCR 16 26360(6),
2666(c)
2030027 Turbine shuts down when RDaleakisdetectedor
when line leak detector is 0 None
disconnected - 23 CCR 16 Yes
2666
2030025 Pressurized piping able to
detect a 3.0 gph leak RD
within an hour, and None
restricts the flow or Yes
alarms - 23 CCR 16
2636(0(2)
Secondary Containment
2060010 UST storing a hazardous RD
substance has secondary Z None
containment - HSC 6.7 Yes
25292
Underground Storage Tank Program - DW Inspection Report v 2.0
Violation Program Requirement 0
4) SOC Comments
No 0> 0 fL
42 (u
Z 0 Z D V
2030008 UDC, sumps, and/or
other secondary
containment in good Z F-1 None
condition and/or are free
of debris/liquid - HSC 6.7
25290.1, 25290.2, 25291
2030040 Secondarily contained RD
piping maintained to allow Ej F-1 None
liquid to drain into sump - Yes
23 CCR 16 2630(d), 2641 (a)
2060006 Secondary containment
piping slopes back to the Z None
collection sump - 23 CCR
16 263(c)
2030047 Secondary containment
maintained tight and has
been confirmed by testing F-1 F-I None
23 CCR 16 2662, HSC 6.7
25290.1(c)(2), 25290.2(c)(2),
25291 (a), 25292(e)
2030060 Entry fittings in secondary
containment for UST
system maintained F-1 None
tight/sealed - 23 CCR 16
2630, 2635(d), 2636(c),
2666
2060020 Spill bucket is installed RPandhasafunctionaldrain
valve or other means to 0 None
remove liquid - 23 CCR 16 Yes
2635(b), 2665
2030054 Spill bucket maintained in RP
good condition and free of 0 None F
debris and/or liquid - 23 Yes
CCR 16 2635(b), 2715(c)(2)
2060019 Spill bucket to has a
minimum capacity of five 0 r'-j None
gallons - 23 CCR 16
2635(b), 2665
Overfill
2030035 UST system is operated RPtopreventunauthorized
release, including spills None
and overfills - HSC 6.7 Yes
25292.1 (a)
2030036 Overfill prevention system RPhasnotbeenoverridden
and meets overfill 0 F-1 None F-1
requirements - 23 CCR 16 Yes
2635(b)(2), 2665 1 1
Underground Storage Tank Program - DW Inspection Report v 2.0
Violation Program Requirement d o SOC Comments
No Oj Q 0 O a as c
O ozOzD
On Site Records
Certifications
2030023 Required designated
operators or contractors
maintain a proper and None
current ICC certification -
23 CCR 16 2715
2030024 Service technician,
installer, and/ or
employee maintain a None
proper license - 23 CCR
162715
2030031 Employee or contractor
obtained and maintained
proper manufacturer None
certification - 23 CCR 16
2715
2010007 Submit/maintain current Update current Certificate of
Certificate of Financial Financial Responsibility in CERS.
Responsibility /mechanism
of financial assurance - None
23 CCR 16 2711; 23 CCR
18 2808.1, 2809 - 2809.2;
HSC 6.7 25292.2; HSC
6.75 25299.30- 25299.34
Designated Operator
2010004 Copies of DO inspections
for last 12 months and list
of trained employees None
maintained - 23 CCR 16
2715
2030013 Designated operator
properly conducted the
monthly inspection and None
the reports are complete -
23 CCR 16 2715
2030010 DO notified operator of
any condition observed
during the monthly None
inspection that may
require action - 23 CCR 16
2715(d)
2030012 DO employee training
performed, current for at
least one employee on None
site, and a log kept - 23
CCR 16 2715(c)(6), 2715(
Underground Storage Tank Program - DW Inspection Report v 2.0
Violation Program Requirement
4-
0 04) SOC Comments
No
a
W
0 0.
42 (0
0)75
Z 0 Z M 4)
Logs
2030001 Leak detection alarm
logs, maintenance and RD
records of appropriate None
follow-up actions Yes
maintained - 23 CCR 16
2632, 2634, 2712(b)
Maintenance/Tests
2010008 Monitoring, maintenance,
repairs, linings, and RD
upgrade records N None
maintained for the proper Yes
time period - 23 CCR 16
2712(b)
Documentation
2030033 Failure to maintain on site Update Monitoring Plan in CERS
an approved monitoring None
and in binder.
plan - 23 CCR 16 2632,
2634, 2711, 2712(1)
2030037 Written agreement Update Owner and Operator
between the tank owner agreement in CERS.
and tank operator to
monitor the tank system None
is maintained - 23 CCR 16
2620(b); HSC 6.7
25284(a)(3)
2030061 Suspected or actual
unauthorized release RD
reported in appropriate None
time frame - HSC 6.7 Yes
29294,29295
General Operating Requirements
Permit Condition/Approval
2030039 Compliance with all All info in CERS needs to be
operating permit None maintained and updated annually.
conditions - 23 CCR 16
2712, HSC 6.7 25299
2030059 UST system maintained
in accordance with
exclusion/exemption Z None
status - HSC 6.7 25281.6,
25283.5
2030014 Owner/Operator received
approval and has
implemented a training None
program at an unstaffed
facility - 23 CCR 16
2715 2)
2030015 Facility exhibited that the
method used to monitor
the tank meets the
monitoring methods in None
2643(f) - 23 CCR 16 2643
Underground Storage Tank Program - DW Inspection Report v 2.0
Violation Program Requirement o SOC Comments
No C0 12
z O z M y W o>
Red Tag
2030045 Red Tag information is
legible and has not been None
tampered with - 23 CCR
16 2717.1(g)
2030044 Facility did not allow for
deposit of petroleum into
a UST that has a red tag None
affixed to the fill - 23 CCR
16 2717.1(
Install /Repair
2060024 UST system is made of or
lined with materials that
are compatible with the None
substance stored - 23
CCR 16 2631.1
2060021 Striker plate installed and
positioned correctly - 23 E None
CCR 16 2631(c), 2662(d)
There were no violations noted for this inspection.
This report shall serve as a "NOTICE TO COMPLY" for Minor Violations, and a "NOTICE OF VIOLATION" for
Major violations. You are, hereby, ordered to correct the above noted violations within 30 days, or according to
correction summaries provided. Formal enforcement and /or penalty assessment may be initiated for any
violations noted, and for those not corrected in a timely manner. (NOTE: If this is a preliminary report, a final report
will follow.)
Inspectors Signature: IL A-A . - -_ Date: /as li s
Inspector: Enter # of Violations: RD: I RP: 0
Check one box for facility Significant Operational Status (SOC) to be reported to SWRCB and US EPA:
SOC with both Release Detection and Release Detection (Facility has no Release Prevention and no Release
Prevention Violations)
Not in SOC (Facility has both Release Prevention and Release Detection Violations)
SOC with Release Detection only (Facility has no Release Detection violations but one or more Release Prevention
violations)
SOC with Release Prevention only (Facility has no Release Prevention violations but one or more Release Detection
violations)
Underground Storage Tank Program - DW Inspection Report v 2.0