HomeMy WebLinkAboutCUPA Report 2014UNIFIED PROGRAM INSPECTION CHECKLIST
Underground Storage Tank Program
BAKERSFIELD FIRE DEPARTMENT
Prevention Services Division
2101 H Street
Bakersfield, CA 93301
Phone: 661 -326 -3979
Fax: 661 -852 -2171
Facility Name:
Gosford Shell
Date of Inspection:
5- /y
Time In: 00 Time Out:
Address:
4050 Gosford a ersiel , CA 93309
Inspected by: Ernie Medina
ICC# 8012428 -UT
Contact:
Heng Chao
Type of Inspection:
DKAnnual Compliance Re- inspection CI Complaint
Phone:
6 1) 304-4083
Permission for Inspection Granted by:
Tank ID 41 2 3 4
Size 12,000 10,000 107000 10, 000
Contents REG REG PREM DSL
Construction DWF DWF DWF DWF
Tank Monitoring:
DW: Continuous Interstitial Monitoring
X Dry Brine/Hydrostatic Vacuum /Pressure. X
SW: SIR and Line Test every 2 years.
SW: ATG 0.1 annual.
SW: ATG 0.2 monthly. El
SW: Continuous In -Tank Leak Detection (CITLD).
SW: Tank Gauging.
SW: Vadose /GW Monitoring. El
Other Description: El
Piping Monitoring:
DW Suction: Continuous Interstitial at UDC and Tank Sump.
DW Pressurized: Interstitial at UDC and Turbine Sump and 3.0 gph LLD,
Annual Line Test or Auto - shutdown and Failsafe. D
DW VPH Monitoring: Includes lines, sumps, fill pipe, vapor lines, etc.
SW Conventional Suction: Triennial 0.1 gph line test., and daily
monitoring.
E] 0
SW Pressurized: Line 0.1 gph annual or 0.2 gph monthly line test and
LLD with Auto - Shutdown. El
SW or DW Safe Suction.
SW: Vadose Zone or GW Monitoring.
DW or SW: Gravity Flow Pipe.
Other Description:
References to the Health and Safetv Code, the California Code of Regulations and the Code of Federal Regulations throughout this Appendix are
intended to be useful but are not necessarily exhaustive ofall legal references that might apply or be relevant to a specific compliance determination.
Laws and regulations are subject to change, so the references contained herein may not be up to date. It is the responsibility of the owner and operator
to know and comply with all applicable legal requirements.
UNDERGROUND STORAGE TANK COMPLIANCE INSPECTION REPORT
Facility Name: Date:
Bakersfield Fire Department — Prevention Services Division, 2101 H Street, Bakersfield, CA 93301 (661) 326-3979
C_
If in compliance, check the box. Check NA if not applicable.
If a violation, determine if Minor, Class 11, or Class 1, or To ViolationsBeDetermined (TBD) if uncertain and will be determined
later.
R55 M
s; a
g
mkgW 4
A fii
2, f.,.# ""Nk `WW
File Review
X1 LIST Permit to Operate is current. HSC 25284(a), 25299(a)(1) 25299 (b)(1)
02 Transfer of permit and/or change of information provided within
30 days of ownership/information changes. HSC 25284(b) (c); T23
CCR 2712(d)
1543 LIST form information current/correct for facility, including BOE
number. HSC 25286(x)
194 Fees are paid up-to-date. HSC 25285(c), 25287
D4 5 Monitoring Plan approved for current owner with appropriate
content and level of detail. T23 CCR 2632(d), 2634 (d), 2641(h)
6 Current Emergency Response Plan submitted with appropriate 171
Al6ecl 411 Ceaflc---c
content and level of detail. T23 CCR 2632(d), 2634 (d), 2641(h) 7h c- (_ acz I C uv,0 A-
N 7 Plot Plan/Site Map submitted with appropriate content and 4"44 324 -3 a)
level of detail. T23 CCR 2632(d), 2634(d), 2641(h), 2711(a)(8)
08 Owner/Operator agreement submitted, if required. HSC 25284(a)(3)
9 Certification of Compliance and Designated Operator
Certification submitted by current tank owner. T23 CCR 2715
3610 Certificate of Financial Responsibility submitted and is current
for the permit period. HSC 25292.2,25299.30-25299.34; T23 CCR 2711; 2808.1;
2809-2809.2
11 Monitoring system certification (most recent) conducted within
allowable timeframe (sensors and console). Results submitted
and show all required components with passing results. HSC
25284.1(a) (4) (c ; T23 CCR 2638
5(12 Spill-bucket test results (most recent) conducted within
allowable time frame. Results submitted and indicate a passing 1test. HSC 25284.2
X13 Leak Detector testing conducted within allowable time frame.
The most recent annual certification submitted and shows RD RD RD RD
passing results. 40 CFR 280.40(a)(2), 280.43(g)(1)&(2), 280.44(a); HSC 25292(e);
T23 CCR 2638, 26416)
f,14 Secondary containment testing conducted within allowable
time frame. Most recent testing results submitted and indicate
a passing test. HSC 25284. 1(a)(4)(B); T23 CCR 2637(a)
15 Pipe and/or tank integrity testing conducted within allowable
time frame. Most recent testing results submitted and indicate
passing results. 40 CFR 280.33, 280.40, 280.41, 280.44; T23 CCR 2636(f),
2643(b)(3), (c)(3), (d) (e)
16 Repaired tanks/piping are tightness tested within 30 days of RD RD RD RD
the repair. 40 CFR 280.33; T23 CCR 2661
17 ELD test conducted within allowable time frame. Most recent
test results submitted and passing results achieved. T23 CCR
2644.1
18 The corrosion protection system is checked by a corrosion
specialist within six months of instal lation/repair and at least
every three years thereafter; results show protection to be RP RP RP RID
adequate. Impressed current inspected every 60-calendar
days. 40 CFR 280.31, 280.70; T23 CCR 2635(a)(2)
19 Tank Lining recertification is current (within 10 years of lining
and every 5 years thereafter) and compliant. 40 CFR280.21(b)(1)(fi,); RP RP RP RPT23CCR2663(h)
Bakersfield Fire Department — Prevention Services Division, 2101 H Street, Bakersfield, CA 93301 (661) 326-3979
C_
UNDERGROUND STORAGE TANK COMPLIANCE INSPECTION REPORT
Facilitv Name: Date:
R1 On-Site Review I
This Inspection is being conducted during the annual
monitoring certification. X YES L7 NO siz'3 41-9s-'a 6X"
The service technician has provided ICC Certification and 83 'y33 S" 5-lzql
manufacturers training documentation, and possesses a tank 25-6&
tester's license or works under a CSLB contractor's license.
YES L7 NO
D43-4 [X Interstitial monitoring conducted properly. 40 CFR 280.40(a)(2), RD RD RD RD
280.43(g)(1)&(2); T23 CCR 2632 (c)(2); 2634(d)(1) I I
35 VPH monitorinq conducted properly. HSC 25290.1 RD RD I RD I RD
0 SIR I I I
36 SIR and Biennial 0.1 gph tank test performed properly. 40 CFR RD RD RD RD280,41, 280.43, T23 CCR 2643, 2646.1
37 Non-passing SIR monitoring report results are reported and RD RD RD RD
investiqated Properly. 40 CFR 280.4 1 (a), 280.43(h) (1), (2); T23 CCR 2646.1 1
Bakersfield Fire Department — Prevention Services Division, 2101 H Street, Bakersfield, CA 93301 (661) 326-3979
General
020 Tank systems meet current construction standards as required
for type of system. HSC 25288
Y21 Hazardous substance tanks have secondary containment. 40 RP RP RP RP
CFR 280.42(b); T23 CCR 2631
822 Electronic monitoring system has audible and visual alarm in
operating condition. T23 CCR 2632, 2634, 2636
923 Monitor console programmed appropriately for monitoring F-1
option used. T23 CCR 2638, 2643, 2643.1
24 Tank systems in temporary closure meet requirements. 40 CFR RD RD RD RD 19
280.70; T23 CCR 2670 & 2671
K25 Overfill Prevention mechanism present and operational
according to type: JgFlapper valve Audible-visual alarm RP RP RP RP Iballfloat. A/V alarm and Ball Float 40 CFR 280.20(c)(I)(li),
280.21(d); T23 CCR 2635(b)(2), 2631(d)(4)
D26 Spill prevention device is present and functional (in good
condition and drain mechanism operational if applicable). 40 CFR RP RP RP RP 1280.20(c)(1)(1), 280.21(d); T23 CCR 2635(P)(1);2665
W27 Piping and piping penetration boots within sumps/UDC are in
ciood condition. HSC 25288(a), 25292.1
28 All sumps, spill buckets, and UDC's free from debris and liquid.
HSC 25291(e), 25290.1, 25290.2; T23 CCR 2635(b)(1)(C) 7r-
929 Areas around vents appear to be free from signs of liquid
releases. HSC 25288(a), 25290.1, 25290.2, 25295.5
X30 Release Detection methods are present and meet performance RD RD RD RD
standards. See LG -113. 40 CFR 280.40(a)(3)
431 All sensors are correct for the type of system and operational. RD RD RD RD
40 CFR 280. g40(a)(2), 280.43(g) (1)&( ); HSC 25290.1 (e), 25290.2, 25291; T23 CCR 2638
932 All sensors are located in the proper position/location. 40 CFR
280.40(a)(2), 280.43(g)(1)&(2); HSC 25290.1, 25290.2, 25291; T23 CCR 2630(d); RD RD RD RD El
2632(c);26 1(a)
ja33 All secondary containment, including UDC shall be equipped
with a continuous monitoring system that either activates an
A/V alarm or stops the flow of product at the dispenser when it
detects a leak. T23 CCR 2636 (0(1)
Tank Monitoring
D43-4 [X Interstitial monitoring conducted properly. 40 CFR 280.40(a)(2), RD RD RD RD
280.43(g)(1)&(2); T23 CCR 2632 (c)(2); 2634(d)(1) I I
35 VPH monitorinq conducted properly. HSC 25290.1 RD RD I RD I RD
0 SIR I I I
36 SIR and Biennial 0.1 gph tank test performed properly. 40 CFR RD RD RD RD280,41, 280.43, T23 CCR 2643, 2646.1
37 Non-passing SIR monitoring report results are reported and RD RD RD RD
investiqated Properly. 40 CFR 280.4 1 (a), 280.43(h) (1), (2); T23 CCR 2646.1 1
Bakersfield Fire Department — Prevention Services Division, 2101 H Street, Bakersfield, CA 93301 (661) 326-3979
UNDERGROUND STORAGE TANK COMPLIANCE INSPECTION REPORT
Facility Name- Date:
Bakersfield Fire Department — Prevention Services Division, 2101 H Street, Bakersfield, CA 93301 (661) 326 -3979
UNDERGROUND STORAGE TANK COMPLIANCE INSPECTION REPORT
Facilitv Name: Date:
177153 SW conventional suction system: inspections conducted for
RP RP RP RP
presence of air in the pipeline. Daily monitoring records are
059
kept. T23 CCR 2643(d)
054 SW gravity flow piping: biennial 0.1 gph integrity test or overfill
RP RP RP RP
tank integrity test is conducted within allowable time frames.
060
T23 CCR 2643(e)
O Safe Suction (SS) System
RP RP RP RP
055 Piping meets the SS requirements. 40 CFR 280.41; T23 CCR 2636(x)(3) RD RD RD RD
061
A -D
RP RP RP RP
O LLD for Pressurized Piping
56 LLD's installed, annually tested and operational on SW
962
pressurized piping. Pump shuts down when a leak occurs and RD RD RD RD(
El
when the LLD fails or is disconnected. T23 CCR 2666
057 LLD's installed, annually tested, and operational on SW
emergency generator systems; LLD is connected to an AN
64
alarm. 40 CFR 280.40(a)(2), 280.43(g)(1),(2), 280.44(a); T23 CCR 2666
Corrosion Protection
58 Metal Tanks and piping components have corrosion protection, RP RP RP RPorareisolatedfromthebackfill. 40 CFR 280.20, 280.21
059 Corrosion protection equipment turned on, functioning properly
and provides continuous protection. 40 CFR 280.31(a),(b)(1); T23 CCR RP RP RP RP
2635
060 Cathodic protection system is tested within 6 months of
installation and then every 3 years. 40 CFR 280.31(x) & (b)(1); T23 CCR RP RP RP RP
2635 a (2
061 Impressed current systems checked every 60- calendar days RP RP RP RP
and records are up-to-date. 40 CFR 280.31(c); T23 CCR 2635(x)(2)
On -site Paperwork
962 Permit and conditions available on -site. Facility is operated El
accordin to permit and conditions. HsC 25293; 25299; T23 CCR 2712(1)
Q3 Monitoring and response plans are on -site and are the
approved version. T23 CCR 2712(i); 2632 ;2634; 2641
64 Site plan depicts current site conditions and has all required
elements. T23 CCR 2632(d)
X65 All release detection records for monitoring method are
available, up -to -date, and appropriate for leak detection RD RD RD RD
method. 40 CFR 280.41, 280.45
Z66 All monitoring /testing records /documents are available for the,rt;
required timeframe. (3 years, 6 Y2 years, five years, life oftank) T23 CCR coxJ 7-0" 0-1FA-1-1 —C-5i j2712
1967 Equipment maintenance records/logs available. T23 CCR 2712(b)
J468 Alarm logs /tapes available and appropriate follow -up actions
occurred. T23 CCR 2712(b); 2632; 2634
1969 Visual observation logs available, up -to -date, and appropriate
follow-up actions to problems occurred. T23 CCR 2712(b); 2642
X70 Designated UST Operator monthly reports available and
complete. T23 CCR 2715
W1 Employee training records available and training appropriate
and up-to-date. T23 CCR 2715
X2 Suspected or actual unauthorized releases are recorded
and /or reported within allowed timeframes, including non- RD RD RD RD
passing test results. Leak and Spill Logs available. 40 CFR 280.50;
T23 CCR, 2650, 2652
W3 Financial Responsibility Certificate and mechanisms (CFO
Letter, etc.) on -site and up -to -date. HsC 25292.2, 25299.30- 25299.34; T23
CCR 2711; T23 2808.1; 2809 - 2809.2
Bakersfield Fire Department — Prevention Services Division, 2101 H Street, Bakersfield, CA 93301 (661) 326 -3979
UNDERGROUND STORAGE TANK COMPLIANCE INSPECTION REPORT
Facility Name: Date:
On -Site Observation ofPeriodic Testing
074 Spill- bucket testing conducted appropriately and a passing test
achieved.
075 Secondary Containment testing conducted appropriately and a F-1passingtestachieved.
SOC AND RED TAG
a
gs, eJ op
a. This facility is in compliance with Release Detection (RD) requirements only. (No
violations in boxes marked RD, but one or more in boxes marked RP.)
b. This facility is in compliance with Release Prevention (RP) requirements only. (No
violations in boxes marked RP, but one or more in boxes marked RD.)
c. This facility is in compliance with BOTH Release Detection (RD) and Release
Prevention (RP) requirements. No violations in boxes marked RD or RP.)
d. This facility is NOT in compliance with both Release Detection (RD) and Release
Prevention (RP) requirements. (One or more violations marked in (both) boxes RD
and RP.)
Y$Y'vY' P.,. L4:y2. #` 411f ' "'r. "' '.ir:. sit' toN 4 : S.Y fr`+:s:P #. `^:. S i5`r" rs. 4s a. * a4 '"yi+.,
r_ c, ,.</;r?./5.11';;, ..< • i E " i k`... Y x:.„ >s,. a. r '., vT a '. k' r ,t . ?''uc 1 "! ,.; : a:: -:
Jat. x .u.. xt :xim. ,:.
5..._,.u d,..v.,.L &
A Red Tag was issued to this facility based on the results of this inspection.
Red Tag #
Reason for Red Tag (Choose one):
1. Violation that causes or threatens to cause a liquid release. CCR 2717(a)(1)
2. Violation that impairs the ability of an UST system to detect a leak. CCR 2717(a)(2)
3. Chronic violation or committed by a recalcitrant violator. CCR 2717(a)(3)
Item I Inspection Comments:
Bakersfield Fire Department — Prevention Services Division, 2101 H Street, Bakersfield, CA 93301 (661) 326 -3979