Loading...
HomeMy WebLinkAbout#725 FMC Results 7-6-16MONITORING SYSTEM CERTIFICATION For Use By All Jurisdictions Within the State of CaliforniaAuthority Cited: Chapter 6.7, Health and Safety Code; Chapter 16, Division 3, Title 23, California Code of Regulations This form must be used to document testing and servicing of monitoring equipment. A separate certification or report must be prepared for each monitoring system control panel by the technician who performs the work. A copy of this form must be provided to the tank system owner/operator. The owner/operator must submit a copy of this form to the local agency regulating UST systems within 30 days of test date. A.General Information Facility Name:Bldg. No.: Site Address:City:Zip: Facility Contact Person: Contact Phone No.: Make/Model of Monitoring System:Date of Testing/Servicing: B.Inventory of Equipment Tested/Certified Check the appropriate boxes to indicate specific equipment inspected/serviced: Tank ID:Tank ID: In-Tank Gauging Probe.Model:In-Tank Gauging Probe.Model: Annular Space or Vault Sensor.Model:Annular Space or Vault Sensor.Model: Piping Sump / Trench Sensor(s).Model:Piping Sump / Trench Sensor(s).Model: Fill Sump Sensor(s).Model:Fill Sump Sensor(s).Model: Mechanical Line Leak Detector.Model:Mechanical Line Leak Detector.Model: Electronic Line Leak Detector.Model:Electronic LineLeak Detector.Model: Tank Overfill / High-Level Sensor.Model:Tank Overfill / High-Level Sensor.Model: Other (specify equipment type and model in Section E on Page 2).Other (specify equipment type and model in Section E on Page 2). Tank ID:Tank ID: In-Tank Gauging Probe.Model:In-Tank Gauging Probe.Model: Annular Space or Vault Sensor.Model:Annular Space or Vault Sensor.Model: Piping Sump / TrenchSensor(s).Model:Piping Sump / Trench Sensor(s).Model: Fill Sump Sensor(s).Model:Fill Sump Sensor(s).Model: Mechanical Line Leak Detector.Model:Mechanical Line Leak Detector.Model: Electronic Line Leak Detector.Model:Electronic Line Leak Detector.Model: Tank Overfill / High-Level Sensor.Model:Tank Overfill / High-Level Sensor.Model: Other (specify equipment type and model in Section E on Page 2).Other (specify equipment type and model in Section E on Page 2). Dispenser ID:Dispenser ID: Dispenser Containment Sensor(s).Model:Dispenser Containment Sensor(s).Model: Shear Valve(s).Shear Valve(s). Dispenser Containment Float(s) and Chain(s).Dispenser Containment Float(s) and Chain(s). Dispenser ID:Dispenser ID: Dispenser Containment Sensor(s).Model:Dispenser Containment Sensor(s).Model: Shear Valve(s).Shear Valve(s). Dispenser Containment Float(s) and Chain(s).Dispenser Containment Float(s) and Chain(s). Dispenser ID:Dispenser ID: Dispenser Containment Sensor(s).Model:Dispenser Containment Sensor(s).Model: Shear Valve(s).Shear Valve(s). Dispenser Containment Float(s) and Chain(s).Dispenser Containment Float(s) and Chain(s). *If the facility contains more tanks or dispensers, copy this form. Include information for every tank and dispenser at the facility. C.Certification -I certify that the equipment identified in this document was inspected/serviced in accordance with the manufacturers’ guidelines. Attached to this Certification is information (e.g. manufacturers' checklists)necessary to verify that this information is correct and a Plot Plan showing the layout of monitoring equipment. For any equipment capable of generating such reports, I have also attached a copy of the report;(check all that apply):System set-up Alarm history report Technician Name (print):Signature: Certification No.:License. No.:804904 Testing Company Name:Confidence UST Services, Inc.Phone No.:(800)339-9930 Site Address:Date of Testing/Servicing: Page 1 of 3 #7725/Fastrip#19 4901SouthUnionAvenueBakersfield93307 OmeroGarcia (661)393-7000 Veeder-RootTLS-350 07/06/2016 12,000gal.Regular 847390-107 794390-420 794380-208 FX1V 847390-107 12,000gal.Super 847390-107 794390-420 794380-208 FX1V 847390-107 12,000gal.Diesel 847390-107 794390-420 794380-208 VMI LD-2000 847390-107 9-10 794380-208 11-12 794380-208 13-14 794380-208 794380-208 15-16 BrandonMason B34335 4901SouthUnionAvenue Bakersfield,CA93307 07/06/2016 794380-208 794380-208 Monitoring System Certification D.Results of Testing/Servicing Software Version Installed: Complete the following checklist: Yes No*Isthe audible alarm operational? Yes No*Is the visual alarm operational? Yes No*Were all sensors visually inspected, functionally tested, and confirmed operational? Yes No*Were all sensors installed at lowest point of secondary containment and positioned so that other equipment will not interfere with their proper operation? Yes No* N/A If alarms are relayed to a remote monitoring station, is all communications equipment (e.g., modem) operational? Yes No* N/A For pressurized piping systems, does the turbine automatically shut down if the piping secondary containment monitoring system detects a leak, fails to operate, or is electrically disconnected? If yes: which sensors initiate positive shut-down? (Check all that apply) Sump/Trench Sensors; Dispenser Containment Sensors. Did you confirm positive shut-down due to leaks and sensor failure/disconnection? Yes; No. Yes No* N/A For tank systems that utilize the monitoring system as the primary tank overfill warning device (i.e., no mechanical overfill prevention valve is installed), is the overfill warning alarm visible and audible at the tank fill point(s) and operating properly? If so, at what percent oftank capacity does the alarm trigger? % Yes*NoWas any monitoring equipment replaced? If yes, identify specific sensors, probes, or other equipment replaced and list the manufacturer name and model for all replacement parts in Section E, below. Yes*NoWas liquid found inside any secondary containment systems designed as dry systems? (Check all that apply) Product; Water. If yes, describe causes in Section E, below. Yes No*Was monitoring system set-up reviewed to ensure proper settings? Attach set up reports, if applicable Yes No*Is all monitoring equipment operational per manufacturer’s specifications? * In Section E below, describe how and when these deficiencies were or will be corrected. E.Comments: Page 2 of 3 333.06 90 Replaced existing FX1DV LLD with new VMI LD-2000 LLD on Diesel product. Monitoring System Certification F.In-Tank Gauging / SIR Equipment: Check this box if tank gauging is used only for inventory control. Check this box if no tank gauging or SIR equipment is installed. This section must be completed if in-tank gauging equipment is used to perform leak detection monitoring. Complete the following checklist: Yes No*Has all input wiring been inspected for proper entry and termination, including testing for ground faults? Yes No*Were all tank gauging probes visually inspected for damage and residue buildup? Yes No*Was accuracy of system product level readings tested? Yes No*Was accuracy of system water level readings tested? Yes No*Were all probes reinstalled properly? Yes No*Were all items on the equipment manufacturer’s maintenance checklist completed? * In the Section H, below, describe how and when these deficiencies were or will be corrected. G.Line Leak Detectors (LLD):Check this box if LLDs are not installed. Complete the following checklist: Yes No* N/A For equipment start-up or annual equipment certification, was a leak simulated to verify LLD performance? (Check all that apply)Simulated leak rate: 3 g.p.h.; 0.1 g.p.h ; 0.2 g.p.h. Yes No*Were all LLDs confirmed operational and accurate within regulatory requirements? Yes No*Was the testing apparatus properly calibrated? Yes No* N/A For mechanical LLDs, does the LLD restrict product flow if it detects a leak? Yes No* N/A For electronic LLDs, does the turbine automatically shut off if the LLD detects a leak? Yes No* N/A For electronic LLDs, does the turbine automatically shut off if any portion of the monitoring system is disabled or disconnected? Yes No* N/A For electronic LLDs, does the turbine automatically shut off if any portion of the monitoring system malfunctions or fails a test? Yes No* N/A For electronic LLDs, have all accessible wiring connections been visually inspected? Yes No*Were all items on the equipment manufacturer’s maintenance checklist completed? * In the Section H, below, describe how and when these deficiencies were or will be corrected. H.Comments: Page 3 of 3 Replaced existing FX1DV LLD with new VMI LD-2000 LLD on Diesel product. Leak Detector Test Results Sheet Customer Address: Work Order: Site Address: Test Date: Site Contact: Phone: Technician: Phone: 800-339-9930 ICC No.: Product Type LLD Type Model Serial No. Check Valve Holding Pressure Bleed Off ML. Leak Rate Tested: Pass/Fail 3 gph @ 10 psi 3 gph @ 10 psi 3 gph @ 10 psi 3 gph @ 10 psi 3 gph @ 10 psi 3 gph @ 10 psi 3 gph @ 10 psi 3 gph @ 10 psi Technician Name: Technician No.: Signature: Date: JamiesonHill P.O.Box82515 Bakersfield,CA93380-2515 36811 07/06/2016 5284980-UT Regular Mechanical FX1V BrandonMason (661)393-7000OmeroGarcia Bakersfield,CA93307 4901SouthUnionAvenue #7725/Fastrip#19 12psi40ml Pass FX1VMechanicalPremium 12psi40ml Pass VMI LD-2000MechanicalDiesel 1602137824psi40ml Pass BrandonMason 5284980-UT 07/06/2016 Responses Received: 200 FASTRIP 7725 4901 S UNION BAKERSFIELD CA 661-397-9387 JUL 6, 2016 9:07 AM TANK PRODUCT GALLONS INCHES WATER DEG F ULLAGE 1 UNLEADED 7234 55.79 0.0 85.0 4766 2 PREMIUM 5109 42.39 1.1 84.9 6891 3 DIESEL 6044 48.27 1.1 88.5 5956 I90500 JUL 6, 2016 9:07 AM SOFTWARE REVISION LEVEL VERSION 333.06 SOFTWARE# 346333-100-G CREATED - 14.10.01.16.35 S-MODULE# 330160-004-a SYSTEM FEATURES: PERIODIC IN-TANK TESTS ANNUAL IN-TANK TESTS ISD/APM I50500 JUL 6, 2016 9:07 AM SYSTEM TYPE AND LANGUAGE FLAG SYSTEM UNITS U.S. SYSTEM LANGUAGE ENGLISH SYSTEM DATE/TIME FORMAT MON DD YYYY HH:MM:SS xM I50201 JUL 6, 2016 9:07 AM SHIFT TIME 1 : 12:00 AM I50202 JUL 6, 2016 9:07 AM SHIFT TIME 2 : DISABLED I50203 JUL 6, 2016 9:07 AM SHIFT TIME 3 : DISABLED I50204 JUL 6, 2016 9:07 AM SHIFT TIME 4 : DISABLED I54600 JUL 6, 2016 9:07 AM TANK PER TST NEEDED WRN: DISABLED I54900 JUL 6, 2016 9:07 AM TANK ANN TST NEEDED WRN: DISABLED I55300 JUL 6, 2016 9:07 AM LINE RE-ENABLE METHOD PASS LINE TEST I55600 JUL 6, 2016 9:07 AM LINE PER TST NEEDED WRN: DISABLED I55900 JUL 6, 2016 9:07 AM LINE ANN TST NEEDED WRN: DISABLED I50D00 JUL 6, 2016 9:07 AM PRINT TC VOLUMES ENABLED I50E00 JUL 6, 2016 9:07 AM TEMP COMPENSATION VALUE (DEG F ): 60.0 I60B00 JUL 6, 2016 9:07 AM STICK HEIGHT OFFSET ENABLE STATUS DISABLED I51400 JUL 6, 2016 9:07 AM H-PROTOCOL DATA FORMAT HEIGHT I51A01 JUL 6, 2016 9:07 AM DAYLIGHT SAVING TIME ENABLED ON I51B00 JUL 6, 2016 9:07 AM DAYLIGHT SAVING TIME START DATE MAR WEEK 1 SUN 2:00 AM END DATE NOV WEEK 1 SUN 2:00 AM I51600 JUL 6, 2016 9:07 AM RE-DIRECT LOCAL PRINTOUT DISABLED I50400 JUL 6, 2016 9:07 AM 232 SECURITY CODE PORT SECURITY CODE STATUS 1 000000 DISABLED 2 000000 DISABLED 3 000000 DISABLED 4 000000 DISABLED 5 000000 DISABLED 6 000000 DISABLED I21900 JUL 6, 2016 9:08 AM TANK CHART SECURITY DISABLED I5BD00 JUL 6, 2016 9:08 AM CUSTOM ALARM LABELS DISABLED I56000 JUL 6, 2016 9:08 AM MASS/DENSITY DISABLED I88101 JUL 6, 2016 9:08 AM PORT SETTINGS: COMM BOARD : 1 (EDIM ) RS-232 SECURITY CODE : DISABLED I88102 JUL 6, 2016 9:08 AM PORT SETTINGS: COMM BOARD : 2 (RS-232) BAUD RATE : 9600 PARITY : NONE STOP BIT : 1 STOP DATA LENGTH: 8 DATA RS-232 SECURITY CODE : DISABLED I88103 JUL 6, 2016 9:08 AM PORT SETTINGS: COMM BOARD : 3 (RS-232) BAUD RATE : 9600 PARITY : NONE STOP BIT : 1 STOP DATA LENGTH: 8 DATA RS-232 SECURITY CODE : DISABLED I88104 JUL 6, 2016 9:08 AM I88105 JUL 6, 2016 9:08 AM I88106 JUL 6, 2016 9:08 AM I52000 JUL 6, 2016 9:08 AM RECEIVER AUTO DIAL TYPE & START TIME RCVR LOCATION LABEL DIAL TYPE START TIME 1 ON DATE JAN 18, 2014 DISABLED 2 ON DATE JAN 18, 2014 DISABLED 3 ON DATE JAN 18, 2014 DISABLED 4 ON DATE JAN 18, 2014 DISABLED 5 ON DATE JAN 18, 2014 DISABLED 6 ON DATE JAN 18, 2014 DISABLED 7 ON DATE JAN 18, 2014 DISABLED 8 ON DATE JAN 18, 2014 DISABLED I60100 JUL 6, 2016 9:08 AM TANK CONFIGURATION DEVICE LABEL CONFIGURED 1 UNLEADED ON 2 PREMIUM ON 3 DIESEL ON 4 OFF I60200 JUL 6, 2016 9:08 AM TANK PRODUCT LABEL TANK PRODUCT LABEL 1 UNLEADED 2 PREMIUM 3 DIESEL 4 I60300 JUL 6, 2016 9:08 AM TANK PRODUCT CODE TANK PRODUCT LABEL 1 UNLEADED 1 2 PREMIUM 2 3 DIESEL 3 4 4 I60900 JUL 6, 2016 9:08 AM TANK THERMAL COEFFICIENT TANK PRODUCT LABEL 1 UNLEADED 0.000700 2 PREMIUM 0.000700 3 DIESEL 0.000450 4 0.000000 I60700 JUL 6, 2016 9:08 AM TANK DIAMETER TANK PRODUCT LABEL INCHES 1 UNLEADED 96.00 2 PREMIUM 96.00 3 DIESEL 96.00 4 0.00 I60A00 JUL 6, 2016 9:08 AM TANK FULL VOLUME TANK PRODUCT LABEL TANK PROFILE GALLONS 1 UNLEADED 1 PT 12000 2 PREMIUM 1 PT 12000 3 DIESEL 1 PT 12000 4 1 PT 0 I60400 JUL 6, 2016 9:08 AM TANK FULL VOLUME TANK PRODUCT LABEL GALLONS 1 UNLEADED 12000 2 PREMIUM 12000 3 DIESEL 12000 4 0 I60500 JUL 6, 2016 9:08 AM TANK 4 POINT VOLUMES TANK PRODUCT LABEL GALLONS 1 UNLEADED 12000 0 0 0 2 PREMIUM 12000 0 0 0 3 DIESEL 12000 0 0 0 4 0 0 0 0 I60600 JUL 6, 2016 9:08 AM TANK 20 POINT VOLUMES TANK PRODUCT LABEL GALLONS 1 UNLEADED 12000 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 2 PREMIUM 12000 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 3 DIESEL 12000 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 4 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 I61500 JUL 6, 2016 9:08 AM TANK PRODUCT LABEL METER DATA 1 UNLEADED NO 2 PREMIUM NO 3 DIESEL NO 4 NO I62F00 JUL 6, 2016 9:08 AM MAG PROBE FLOAT SIZE TANK PRODUCT LABEL FLOAT SIZE: 1 UNLEADED 4.0 IN. 2 PREMIUM 4.0 IN. 3 DIESEL 4.0 IN. I62700 JUL 6, 2016 9:08 AM TANK HIGH WATER WARNING LIMIT TANK PRODUCT LABEL INCHES 1 UNLEADED 2.0 2 PREMIUM 2.0 3 DIESEL 2.0 I64200 JUL 6, 2016 9:08 AM WATER ALARM FILTER TANK PRODUCT LABEL 1 UNLEADED LOW 2 PREMIUM LOW 3 DIESEL LOW I62400 JUL 6, 2016 9:08 AM TANK HIGH WATER LEVEL LIMIT TANK PRODUCT LABEL INCHES 1 UNLEADED 3.0 2 PREMIUM 3.0 3 DIESEL 3.0 I62800 JUL 6, 2016 9:08 AM TANK MAXIMUM VOLUME LIMIT TANK PRODUCT LABEL GALLONS 1 UNLEADED 12000 2 PREMIUM 12000 3 DIESEL 12000 4 0 I62300 JUL 6, 2016 9:08 AM TANK OVERFILL LEVEL LIMIT TANK PRODUCT LABEL GALLONS 1 UNLEADED 10800 2 PREMIUM 10800 3 DIESEL 10800 4 0 I62200 JUL 6, 2016 9:08 AM TANK HIGH PRODUCT LIMIT TANK PRODUCT LABEL GALLONS 1 UNLEADED 11400 2 PREMIUM 11400 3 DIESEL 11400 4 0 I62900 JUL 6, 2016 9:08 AM TANK DELIVERY REQUIRED LIMIT TANK PRODUCT LABEL GALLONS 1 UNLEADED 1200 2 PREMIUM 1200 3 DIESEL 1200 4 0 I62100 JUL 6, 2016 9:08 AM TANK LOW PRODUCT LIMIT TANK PRODUCT LABEL GALLONS 1 UNLEADED 1200 2 PREMIUM 1200 3 DIESEL 1200 4 0 I62600 JUL 6, 2016 9:08 AM TANK LEAK ALARM LIMIT TANK PRODUCT LABEL GALLONS 1 UNLEADED 99 2 PREMIUM 99 3 DIESEL 99 4 99 I62500 JUL 6, 2016 9:08 AM TANK SUDDEN LOSS LIMIT TANK PRODUCT LABEL GALLONS 1 UNLEADED 99 2 PREMIUM 99 3 DIESEL 99 4 99 I60800 JUL 6, 2016 9:08 AM TANK TILT TANK PRODUCT LABEL INCHES 1 UNLEADED 0.00 2 PREMIUM 0.00 3 DIESEL 0.00 4 0.00 I60B00 JUL 6, 2016 9:08 AM STICK HEIGHT OFFSET ENABLE STATUS DISABLED I60C00 JUL 6, 2016 9:08 AM TANK STICK HEIGHT OFFSET TANK PRODUCT LABEL INCHES 1 UNLEADED 0.00 2 PREMIUM 0.00 3 DIESEL 0.00 4 0.00 I61200 JUL 6, 2016 9:08 AM TANK MANIFOLDED PARTNERS TANK PRODUCT LABEL SIPHON MANIFOLDED TANKS LINE MANIFOLDED TANKS 1 UNLEADED NONE NONE 2 PREMIUM NONE NONE 3 DIESEL NONE NONE 4 NONE NONE I63600 JUL 6, 2016 9:08 AM PERIODIC LEAK TEST MIN VOLUME TANK PRODUCT LABEL GALLONS 1 UNLEADED 120 2 PREMIUM 120 3 DIESEL 120 4 0 I62A00 JUL 6, 2016 9:08 AM ANNUAL LEAK TEST MIN VOLUME TANK PRODUCT LABEL GALLONS 1 UNLEADED 120 2 PREMIUM 120 3 DIESEL 120 4 0 I62C00 JUL 6, 2016 9:08 AM TANK PERIODIC TEST TYPE TANK PRODUCT LABEL PERIODIC TEST TYPE 1 UNLEADED STANDARD 2 PREMIUM STANDARD 3 DIESEL STANDARD 4 STANDARD I62D00 JUL 6, 2016 9:08 AM TANK LEAK TEST FAIL ALARMS TANK PRODUCT LABEL 1 UNLEADED GROSS TEST FAIL ALARM DISABLED PERIODIC TEST FAIL ALARM DISABLED ANNUAL TEST FAIL ALARM DISABLED 2 PREMIUM GROSS TEST FAIL ALARM DISABLED PERIODIC TEST FAIL ALARM DISABLED ANNUAL TEST FAIL ALARM DISABLED 3 DIESEL GROSS TEST FAIL ALARM DISABLED PERIODIC TEST FAIL ALARM DISABLED ANNUAL TEST FAIL ALARM DISABLED 4 GROSS TEST FAIL ALARM DISABLED PERIODIC TEST FAIL ALARM DISABLED ANNUAL TEST FAIL ALARM DISABLED I63100 JUL 6, 2016 9:08 AM TANK LEAK TEST AVERAGING TANK PRODUCT LABEL ANNUAL PERIODIC 1 UNLEADED OFF OFF 2 PREMIUM OFF OFF 3 DIESEL OFF OFF 4 OFF OFF I63000 JUL 6, 2016 9:08 AM IN-TANK LEAK TEST NOTIFY TANK PRODUCT LABEL TANK TEST NOTIFY: 1 UNLEADED OFF 2 PREMIUM OFF 3 DIESEL OFF 4 OFF I63200 JUL 6, 2016 9:08 AM TANK TEST SIPHON BREAK TANK PRODUCT LABEL SIPHON BREAK 1 UNLEADED OFF 2 PREMIUM OFF 3 DIESEL OFF 4 OFF I61000 JUL 6, 2016 9:08 AM TANK DELIVERY DELAY TANK PRODUCT LABEL 1 UNLEADED 1 2 PREMIUM 1 3 DIESEL 1 4 1 I63A00 JUL 6, 2016 9:08 AM LOW LEVEL PUMP THRESHOLD FOR SEQUENTIAL LINE MANIFOLD TANK PRODUCT LABEL PUMP THRESHOLD 1 UNLEADED 10.00% 2 PREMIUM 10.00% 3 DIESEL 10.00% 4 10.00% I61100 JUL 6, 2016 9:08 AM LEAK TEST METHOD - - - - - - - - - - - - TEST ON DATE : ALL TANK OCT 1, 2014 START TIME : DISABLED TEST RATE :0.20 GAL/HR DURATION : 2 HOURS TST EARLY STOP:DISABLED I61300 JUL 6, 2016 9:08 AM CSLD PROBABLITY OF DETECTION I61400 JUL 6, 2016 9:08 AM CSLD CLIMATE FACTOR I61600 JUL 6, 2016 9:08 AM TANK PRODUCT LABEL CAL UPDATE 1 UNLEADED IMMEDIATE 2 PREMIUM IMMEDIATE 3 DIESEL IMMEDIATE 4 IMMEDIATE I61A00 JUL 6, 2016 9:08 AM IN-TANK LEAK TEST EARLY STOP TANK PRODUCT LABEL TST EARLY STOP: 1 UNLEADED DISABLED 2 PREMIUM DISABLED 3 DIESEL DISABLED 4 DISABLED I61B00 JUL 6, 2016 9:08 AM IN-TANK LEAK GROSS TEST AUTO-CONFIRM I61C00 JUL 6, 2016 9:08 AM CSLD REPORT ONLY I62B00 JUL 6, 2016 9:08 AM TANK LAST ANNUAL TEST TANK PRODUCT LABEL DATE 1 UNLEADED ??? 0, 0 2 PREMIUM ??? 0, 0 3 DIESEL ??? 0, 0 4 ??? 0, 0 I63300 JUL 6, 2016 9:08 AM LEAK TEST REPORT FORMAT: NORMAL I63400 JUL 6, 2016 9:08 AM RECONCILIATION WARNING LIMIT TANK PRODUCT LABEL GALLONS 1 UNLEADED 0 2 PREMIUM 0 3 DIESEL 0 4 0 I63500 JUL 6, 2016 9:08 AM RECONCILIATION ALARM LIMIT TANK PRODUCT LABEL GALLONS 1 UNLEADED 1 2 PREMIUM 1 3 DIESEL 1 4 1 I63900 JUL 6, 2016 9:08 AM ACCU CHART END SHAPE FACTOR TANK PRODUCT LABEL 1 UNLEADED END FACTOR: NONE 2 PREMIUM END FACTOR: NONE 3 DIESEL END FACTOR: NONE 4 END FACTOR: NONE I78000 JUL 6, 2016 9:08 AM I77700 JUL 6, 2016 9:08 AM I77800 JUL 6, 2016 9:08 AM I78C00 JUL 6, 2016 9:08 AM I78300 JUL 6, 2016 9:08 AM I78F00 JUL 6, 2016 9:08 AM I78700 JUL 6, 2016 9:08 AM I70200 JUL 6, 2016 9:08 AM LIQUID LABEL DEVICE LABEL 1 UNL STP 2 UNL ANN 3 PREM STP 4 PREM ANN 5 DSL STP 6 DSL ANN 7 DISP 9-10 8 DISP11-12 9 DISP 13-14 10 DISP 15-16 11 12 13 14 15 16 I70300 JUL 6, 2016 9:08 AM LIQUID TYPE SENSOR LOCATION TYPE 1 UNL STP TRI-STATE (SINGLE FLOAT) 2 UNL ANN TRI-STATE (SINGLE FLOAT) 3 PREM STP TRI-STATE (SINGLE FLOAT) 4 PREM ANN TRI-STATE (SINGLE FLOAT) 5 DSL STP TRI-STATE (SINGLE FLOAT) 6 DSL ANN TRI-STATE (SINGLE FLOAT) 7 DISP 9-10 TRI-STATE (SINGLE FLOAT) 8 DISP11-12 TRI-STATE (SINGLE FLOAT) 9 DISP 13-14 TRI-STATE (SINGLE FLOAT) 10 DISP 15-16 NORMALLY CLOSED 11 TRI-STATE (SINGLE FLOAT) 12 TRI-STATE (SINGLE FLOAT) 13 TRI-STATE (SINGLE FLOAT) 14 TRI-STATE (SINGLE FLOAT) 15 TRI-STATE (SINGLE FLOAT) 16 TRI-STATE (SINGLE FLOAT) I70400 JUL 6, 2016 9:08 AM LIQUID CATEGORY SENSOR LOCATION CATEGORY 1 UNL STP STP SUMP 2 UNL ANN ANNULAR SPACE 3 PREM STP STP SUMP 4 PREM ANN ANNULAR SPACE 5 DSL STP STP SUMP 6 DSL ANN ANNULAR SPACE 7 DISP 9-10 DISPENSER PAN 8 DISP11-12 DISPENSER PAN 9 DISP 13-14 DISPENSER PAN 10 DISP 15-16 DISPENSER PAN 11 OTHER SENSORS 12 OTHER SENSORS 13 OTHER SENSORS 14 OTHER SENSORS 15 OTHER SENSORS 16 OTHER SENSORS I74200 JUL 6, 2016 9:08 AM I74300 JUL 6, 2016 9:08 AM I74400 JUL 6, 2016 9:08 AM I74700 JUL 6, 2016 9:08 AM I74800 JUL 6, 2016 9:08 AM I74900 JUL 6, 2016 9:08 AM I7BC00 JUL 6, 2016 9:08 AM I80200 JUL 6, 2016 9:08 AM I80300 JUL 6, 2016 9:08 AM I80400 JUL 6, 2016 9:08 AM I80700 JUL 6, 2016 9:08 AM RELAY LABEL DEVICE LABEL 1 UNL 2 PNL 3 DSL 4 OVERFILL ALARM I80900 JUL 6, 2016 9:08 AM RELAY ORIENTATION RELAY DESIGNATION ORIENTATION 1 UNL NORMALLY CLOSED 2 PNL NORMALLY CLOSED 3 DSL NORMALLY CLOSED 4 OVERFILL ALARM NORMALLY OPEN I80B00 JUL 6, 2016 9:08 AM RELAY TANK ASSIGNMENT RELAY DESIGNATION TANK 1 UNL 1 2 PNL 2 3 DSL 3 4 OVERFILL ALARM NONE I80A00 JUL 6, 2016 9:08 AM RELAY TYPE RELAY DESIGNATION TYPE 1 UNL STANDARD 2 PNL STANDARD 3 DSL STANDARD 4 OVERFILL ALARM STANDARD I80C00 JUL 6, 2016 9:08 AM I80800 JUL 6, 2016 9:08 AM RELAY SETUP REPORT R 1:UNL TYPE: STANDARD NORMALLY CLOSED TANK #: 1 LIQUID SENSOR ALMS L 1:FUEL ALARM L 7:FUEL ALARM L 8:FUEL ALARM L 9:FUEL ALARM L10:FUEL ALARM L 1:SENSOR OUT ALARM L 7:SENSOR OUT ALARM L 8:SENSOR OUT ALARM L 9:SENSOR OUT ALARM L10:SENSOR OUT ALARM L 1:SHORT ALARM L 7:SHORT ALARM L 8:SHORT ALARM L 9:SHORT ALARM L10:SHORT ALARM ISD SITE ALARMS ISD GROSS PRES FAIL ISD DEGRD PRES FAIL ISD VAPOR LEAK FAIL ISD VP PRES FAIL ISD VP STATUS FAIL ISD SETUP FAIL ISD SENSOR OUT FAIL PC-ISD FAILURE ISD HOSE ALARMS ALL:GROSS COLLECT FAIL ALL:DEGRD COLLECT FAIL ALL:FLOW COLLECT FAIL R 2:PNL TYPE: STANDARD NORMALLY CLOSED TANK #: 2 LIQUID SENSOR ALMS L 3:FUEL ALARM L 7:FUEL ALARM L 8:FUEL ALARM L 9:FUEL ALARM L10:FUEL ALARM L 3:SENSOR OUT ALARM L 7:SENSOR OUT ALARM L 8:SENSOR OUT ALARM L 9:SENSOR OUT ALARM L10:SENSOR OUT ALARM L 3:SHORT ALARM L 7:SHORT ALARM L 8:SHORT ALARM L 9:SHORT ALARM L10:SHORT ALARM ISD SITE ALARMS ISD GROSS PRES FAIL ISD DEGRD PRES FAIL ISD VAPOR LEAK FAIL ISD VP PRES FAIL ISD VP STATUS FAIL ISD SETUP FAIL ISD SENSOR OUT FAIL PC-ISD FAILURE ISD HOSE ALARMS ALL:GROSS COLLECT FAIL ALL:DEGRD COLLECT FAIL ALL:FLOW COLLECT FAIL R 3:DSL TYPE: STANDARD NORMALLY CLOSED TANK #: 3 LIQUID SENSOR ALMS L 5:FUEL ALARM L 7:FUEL ALARM L 8:FUEL ALARM L 9:FUEL ALARM L10:FUEL ALARM L 5:SENSOR OUT ALARM L 7:SENSOR OUT ALARM L 8:SENSOR OUT ALARM L 9:SENSOR OUT ALARM L10:SENSOR OUT ALARM L 5:SHORT ALARM L 7:SHORT ALARM L 8:SHORT ALARM L 9:SHORT ALARM L10:SHORT ALARM R 4:OVERFILL ALARM TYPE: STANDARD NORMALLY OPEN TANK #: NONE IN-TANK ALARMS ALL:OVERFILL ALARM ALL:HIGH PRODUCT ALARM ALL:MAX PRODUCT ALARM I79000 JUL 6, 2016 9:09 AM EDIM:1 VR:349634-003-C TD:06.05.11.11.15 I79100 JUL 6, 2016 9:09 AM I72300 JUL 6, 2016 9:09 AM FASTRIP 7725 4901 S UNION BAKERSFIELD CA 661-397-9387 SMARTSENSOR ASSIGNMENT DEVICE LABEL CATEGORY 01 VP 11-12 VAPOR PRESSURE 02 FM 9-10 AIR FLOW METER 03 FM 11-12 AIR FLOW METER 04 FM 13-14 AIR FLOW METER 05 FM 15-16 AIR FLOW METER 06 UNKNOWN 07 UNKNOWN 08 UNKNOWN 09 UNKNOWN 10 UNKNOWN 11 UNKNOWN 12 UNKNOWN 13 UNKNOWN 14 UNKNOWN 15 UNKNOWN 16 UNKNOWN 17 UNKNOWN 18 UNKNOWN 19 UNKNOWN 20 UNKNOWN 21 UNKNOWN 22 UNKNOWN 23 UNKNOWN 24 UNKNOWN 25 UNKNOWN 26 UNKNOWN 27 UNKNOWN 28 UNKNOWN 29 UNKNOWN 30 UNKNOWN 31 UNKNOWN 32 UNKNOWN 33 UNKNOWN 34 UNKNOWN 35 UNKNOWN 36 UNKNOWN 37 UNKNOWN 38 UNKNOWN 39 UNKNOWN 40 UNKNOWN IV4E00 JUL 6, 2016 9:09 AM FASTRIP 7725 4901 S UNION BAKERSFIELD CA 661-397-9387 EVR/ISD SETUP TYPE: VACUUM ASSIST VACUUM ASSIST TYPE: HEALY VAC IV4F00 JUL 6, 2016 9:09 AM FASTRIP 7725 4901 S UNION BAKERSFIELD CA 661-397-9387 NOZZLE A/L RANGE A/L RATIO: 0.95 - 1.15 IV4000 JUL 6, 2016 9:09 AM FASTRIP 7725 4901 S UNION BAKERSFIELD CA 661-397-9387 VAPOR PROCESSOR TYPE NONE IV4700 JUL 6, 2016 9:09 AM FASTRIP 7725 4901 S UNION BAKERSFIELD CA 661-397-9387 ASSESSMENT TIME START TIME: 10:00 AM TIME DELAY MINUTES: 1 IV5200 JUL 6, 2016 9:09 AM FASTRIP 7725 4901 S UNION BAKERSFIELD CA 661-397-9387 ACCEPT HIGH ORVR: NO IV4A00 JUL 6, 2016 9:09 AM FASTRIP 7725 4901 S UNION BAKERSFIELD CA 661-397-9387 ISD HOSE TABLE HOSE FP FP AFM REL HOSE ID ID LABEL ID ID LABEL 01 09 01 01 02 BLEND3 02 10 02 01 02 BLEND3 03 11 03 02 02 BLEND3 04 12 04 02 02 BLEND3 05 17 05 03 02 BLEND3 06 18 06 03 02 BLEND3 07 19 07 04 02 BLEND3 08 20 08 04 02 BLEND3 IV4B00 JUL 6, 2016 9:09 AM FASTRIP 7725 4901 S UNION BAKERSFIELD CA 661-397-9387 PRODUCT/HOSE MAP TABLE FP AFID M1/H1 M2/H2 M3/H3 M4/H4 09 01 02/01 03/01 09/01 xx/xx 10 01 02/02 03/02 09/02 xx/xx 11 02 02/03 03/03 09/03 xx/xx 12 02 02/04 03/04 09/04 xx/xx 17 03 02/05 03/05 09/05 xx/xx 18 03 02/06 03/06 09/06 xx/xx 19 04 02/07 03/07 09/07 xx/xx 20 04 02/08 03/08 09/08 xx/xx IV4900 JUL 6, 2016 9:09 AM FASTRIP 7725 4901 S UNION BAKERSFIELD CA 661-397-9387 LABEL TABLE ID LABEL 01 UNASSIGNED 02 BLEND3 03 REGULAR 04 MID GRADE 05 PREMIUM 06 GOLD 07 BRONZE 08 SILVER 09 BLEND2 10 BLEND4 IV1000 JUL 6, 2016 9:09 AM ISD VERSION: 01.05 PRE MONITOR CERT Responses Received: I10200 JUL 6, 2016 9:10 AM FASTRIP 7725 4901 S UNION BAKERSFIELD CA 661-397-9387 SYSTEM CONFIGURATION SLOT BOARD TYPE POWER ON RESET CURRENT 1 8SMARTSENSOR BD 39955 39387 2 4 PROBE / G.T. 164948 163700 3 INTERSTITIAL BD 203214 201929 4 INTERSTITIAL BD 203171 201795 5 UNUSED 9872648 9486298 6 UNUSED 9821355 9467249 7 UNUSED 9805808 9472998 8 UNUSED 9790138 9477138 9 RELAY BOARD 15028 15014 10 UNUSED 9802609 9479447 11 UNUSED 9790789 9469580 12 UNUSED 9790810 9476466 13 UNUSED 9774542 9472905 14 UNUSED 9779422 9466813 15 UNUSED 9780617 9477881 16 UNUSED 9778208 9468808 COMM 1 ELEC DISP INT. 101334 101198 COMM 2 RS232 SERIAL BD 15007 14992 COMM 3 RS232 SERIAL BD 14987 14992 COMM 4 UNUSED 9796658 9482171 COMM 5 UNUSED 9777899 9469773 COMM 6 UNUSED 9775901 9477173 I90200 JUL 6, 2016 9:10 AM SOFTWARE REVISION LEVEL VERSION 333.06 SOFTWARE# 346333-100-G CREATED - 14.10.01.16.35 S-MODULE# 330160-004-a SYSTEM FEATURES: PERIODIC IN-TANK TESTS ANNUAL IN-TANK TESTS ISD/APM I11100 JUL 6, 2016 9:10 AM FASTRIP 7725 4901 S UNION BAKERSFIELD CA 661-397-9387 PRIORITY ALARM HISTORY ID CATEGORY DESCRIPTION ALARM TYPE STATE DATE TIME L 3 STP SUMP PREM STP FUEL ALARM CLEAR 7-01-16 3:16PM L 3 STP SUMP PREM STP FUEL ALARM ALARM 7-01-16 2:55PM L 3 STP SUMP PREM STP FUEL ALARM CLEAR 7-01-16 2:45PM L 3 STP SUMP PREM STP FUEL ALARM ALARM 7-01-16 2:40PM L 7 DISP PAN DISP 9-10 SENSOR OUT ALARM CLEAR 6-27-16 10:36AM L 3 STP SUMP PREM STP SENSOR OUT ALARM CLEAR 6-27-16 10:36AM L 6 ANNULAR DSL ANN SENSOR OUT ALARM CLEAR 6-27-16 10:36AM L 4 ANNULAR PREM ANN SENSOR OUT ALARM CLEAR 6-27-16 10:36AM L 8 DISP PAN DISP11-12 SENSOR OUT ALARM CLEAR 6-27-16 10:36AM L 5 STP SUMP DSL STP SENSOR OUT ALARM CLEAR 6-27-16 10:36AM L 2 ANNULAR UNL ANN SENSOR OUT ALARM CLEAR 6-27-16 10:36AM L 1 STP SUMP UNL STP SENSOR OUT ALARM CLEAR 6-27-16 10:36AM L 3 STP SUMP PREM STP SENSOR OUT ALARM ALARM 6-27-16 10:36AM L 6 ANNULAR DSL ANN SENSOR OUT ALARM ALARM 6-27-16 10:36AM L 5 STP SUMP DSL STP SENSOR OUT ALARM ALARM 6-27-16 10:36AM L 4 ANNULAR PREM ANN SENSOR OUT ALARM ALARM 6-27-16 10:36AM L 2 ANNULAR UNL ANN SENSOR OUT ALARM ALARM 6-27-16 10:36AM L 8 DISP PAN DISP11-12 SENSOR OUT ALARM ALARM 6-27-16 10:36AM L 1 STP SUMP UNL STP SENSOR OUT ALARM ALARM 6-27-16 10:36AM L 7 DISP PAN DISP 9-10 SENSOR OUT ALARM ALARM 6-27-16 10:36AM L10 DISP PAN DISP 15-16 FUEL ALARM CLEAR 6-27-16 10:35AM L 9 DISP PAN DISP 13-14 SENSOR OUT ALARM CLEAR 6-27-16 10:35AM L10 DISP PAN DISP 15-16 FUEL ALARM ALARM 6-27-16 10:35AM L 9 DISP PAN DISP 13-14 SENSOR OUT ALARM ALARM 6-27-16 10:35AM T 3 TANK DIESEL LOW PRODUCT ALARM CLEAR 6-27-16 10:03AM T 3 TANK DIESEL LOW PRODUCT ALARM ALARM 6-27-16 10:03AM T 3 TANK DIESEL PROBE OUT CLEAR 6-27-16 10:02AM T 3 TANK DIESEL PROBE OUT ALARM 6-27-16 10:02AM T 3 TANK DIESEL OVERFILL ALARM CLEAR 6-27-16 10:01AM T 3 TANK DIESEL OVERFILL ALARM ALARM 6-27-16 10:01AM T 3 TANK DIESEL PROBE OUT CLEAR 6-27-16 10:01AM T 1 TANK UNLEADED LOW PRODUCT ALARM CLEAR 6-27-16 10:01AM T 1 TANK UNLEADED LOW PRODUCT ALARM ALARM 6-27-16 10:01AM T 3 TANK DIESEL OVERFILL ALARM CLEAR 6-27-16 10:01AM T 3 TANK DIESEL PROBE OUT ALARM 6-27-16 10:01AM T 1 TANK UNLEADED PROBE OUT CLEAR 6-27-16 10:01AM T 2 TANK PREMIUM PROBE OUT CLEAR 6-27-16 10:00AM T 1 TANK UNLEADED PROBE OUT ALARM 6-27-16 10:00AM T 2 TANK PREMIUM OVERFILL ALARM CLEAR 6-27-16 10:00AM T 2 TANK PREMIUM PROBE OUT ALARM 6-27-16 10:00AM T 3 TANK DIESEL OVERFILL ALARM ALARM 6-27-16 9:59AM T 2 TANK PREMIUM OVERFILL ALARM ALARM 6-27-16 9:58AM T 3 TANK DIESEL PROBE OUT CLEAR 6-27-16 9:57AM T 2 TANK PREMIUM PROBE OUT CLEAR 6-27-16 9:57AM T 3 TANK DIESEL PROBE OUT ALARM 6-27-16 9:56AM T 2 TANK PREMIUM PROBE OUT ALARM 6-27-16 9:56AM T 1 TANK UNLEADED PROBE OUT CLEAR 6-27-16 9:56AM T 1 TANK UNLEADED PROBE OUT ALARM 6-27-16 9:55AM L 7 DISP PAN DISP 9-10 FUEL ALARM CLEAR 6-27-16 9:54AM L 7 DISP PAN DISP 9-10 FUEL ALARM ALARM 6-27-16 9:53AM I11200 JUL 6, 2016 9:10 AM FASTRIP 7725 4901 S UNION BAKERSFIELD CA 661-397-9387 NON-PRIORITY ALARM HISTORY ID CATEGORY DESCRIPTION ALARM TYPE STATE DATE TIME T 3 TANK DIESEL INVALID FUEL LEVEL CLEAR 6-27-16 10:03AM T 3 TANK DIESEL DELIVERY NEEDED CLEAR 6-27-16 10:03AM T 3 TANK DIESEL DELIVERY NEEDED ALARM 6-27-16 10:03AM T 3 TANK DIESEL INVALID FUEL LEVEL ALARM 6-27-16 10:02AM T 3 TANK DIESEL HIGH PRODUCT ALARM CLEAR 6-27-16 10:02AM T 3 TANK DIESEL HIGH PRODUCT ALARM ALARM 6-27-16 10:02AM T 1 TANK UNLEADED INVALID FUEL LEVEL CLEAR 6-27-16 10:01AM T 1 TANK UNLEADED DELIVERY NEEDED CLEAR 6-27-16 10:01AM T 1 TANK UNLEADED DELIVERY NEEDED ALARM 6-27-16 10:01AM T 2 TANK PREMIUM LOW TEMP WARNING CLEAR 6-27-16 10:01AM T 1 TANK UNLEADED INVALID FUEL LEVEL ALARM 6-27-16 10:01AM T 2 TANK PREMIUM LOW TEMP WARNING ALARM 6-27-16 10:01AM T 3 TANK DIESEL HIGH PRODUCT ALARM CLEAR 6-27-16 10:00AM T 3 TANK DIESEL HIGH PRODUCT ALARM ALARM 6-27-16 9:59AM T 1 TANK UNLEADED HIGH PRODUCT ALARM CLEAR 6-27-16 9:58AM T 1 TANK UNLEADED HIGH PRODUCT ALARM ALARM 6-27-16 9:58AM SYSTEM PRINTER ERROR CLEAR 6-15-16 6:42PM SYSTEM PAPER OUT CLEAR 6-15-16 6:42PM SYSTEM PAPER OUT ALARM 6-15-16 6:42PM SYSTEM PRINTER ERROR ALARM 6-15-16 6:41PM SYSTEM PRINTER ERROR CLEAR 6-15-16 6:40PM SYSTEM PRINTER ERROR ALARM 6-15-16 6:40PM SYSTEM PRINTER ERROR CLEAR 6-15-16 6:39PM SYSTEM PAPER OUT CLEAR 6-15-16 6:39PM SYSTEM PRINTER ERROR ALARM 6-15-16 6:17PM SYSTEM PAPER OUT ALARM 6-15-16 6:17PM T 2 TANK PREMIUM DELIVERY NEEDED CLEAR 6-04-16 4:33AM T 2 TANK PREMIUM DELIVERY NEEDED ALARM 6-03-16 8:45PM T 3 TANK DIESEL DELIVERY NEEDED CLEAR 5-26-16 10:04PM T 3 TANK DIESEL DELIVERY NEEDED ALARM 5-26-16 5:50PM T 1 TANK UNLEADED DELIVERY NEEDED CLEAR 5-14-16 4:46AM T 1 TANK UNLEADED DELIVERY NEEDED ALARM 5-14-16 4:15AM T 1 TANK UNLEADED DELIVERY NEEDED CLEAR 5-07-16 11:43AM T 1 TANK UNLEADED INVALID FUEL LEVEL CLEAR 5-07-16 11:42AM T 1 TANK UNLEADED INVALID FUEL LEVEL ALARM 5-07-16 11:01AM T 1 TANK UNLEADED DELIVERY NEEDED ALARM 5-07-16 9:41AM OTHER ISD VAPOR LEAK WARN CLEAR 5-03-16 10:00AM OTHER ISD VAPOR LEAK WARN ALARM 5-02-16 10:01AM T 1 TANK UNLEADED DELIVERY NEEDED CLEAR 4-22-16 7:22AM T 1 TANK UNLEADED INVALID FUEL LEVEL CLEAR 4-22-16 7:21AM T 1 TANK UNLEADED INVALID FUEL LEVEL ALARM 4-22-16 6:05AM T 1 TANK UNLEADED DELIVERY NEEDED ALARM 4-21-16 8:38PM SYSTEM PRINTER ERROR CLEAR 4-08-16 2:23PM SYSTEM PAPER OUT CLEAR 4-08-16 2:23PM SYSTEM PRINTER ERROR ALARM 4-08-16 2:14PM SYSTEM PAPER OUT ALARM 4-08-16 2:14PM T 1 TANK UNLEADED DELIVERY NEEDED CLEAR 4-03-16 11:55PM T 1 TANK UNLEADED DELIVERY NEEDED ALARM 4-03-16 8:56PM T 1 TANK UNLEADED DELIVERY NEEDED CLEAR 3-14-16 2:34AM T 1 TANK UNLEADED DELIVERY NEEDED ALARM 3-13-16 9:20PM I20600 JUL 6, 2016 9:10 AM FASTRIP 7725 4901 S UNION BAKERSFIELD CA 661-397-9387 TANK ALARM HISTORY TANK 1 UNLEADED OVERFILL ALARM JUN 7, 2016 9:16 PM MAY 18, 2016 6:32 AM APR 13, 2016 2:48 AM LOW PRODUCT ALARM JUN 27, 2016 10:01 AM MAY 14, 2016 4:15 AM MAY 7, 2016 9:41 AM HIGH PRODUCT ALARM JUN 27, 2016 9:58 AM JAN 17, 2016 5:12 AM DEC 25, 2015 6:48 AM INVALID FUEL LEVEL JUN 27, 2016 10:01 AM MAY 7, 2016 11:01 AM APR 22, 2016 6:05 AM PROBE OUT JUN 27, 2016 10:00 AM JUN 27, 2016 9:55 AM JUL 10, 2015 12:05 PM DELIVERY NEEDED JUN 27, 2016 10:01 AM MAY 14, 2016 4:15 AM MAY 7, 2016 9:41 AM LOW TEMP WARNING JUN 29, 2015 2:02 PM TANK 2 PREMIUM OVERFILL ALARM JUN 27, 2016 9:58 AM MAR 27, 2016 10:33 AM MAR 20, 2016 6:25 AM LOW PRODUCT ALARM JUN 3, 2016 8:45 PM JUN 29, 2015 1:08 PM INVALID FUEL LEVEL JUN 29, 2015 1:09 PM PROBE OUT JUN 27, 2016 10:00 AM JUN 27, 2016 9:56 AM JUL 10, 2015 12:16 PM DELIVERY NEEDED JUN 3, 2016 8:45 PM JUN 29, 2015 1:08 PM LOW TEMP WARNING JUN 27, 2016 10:01 AM JUN 29, 2015 2:00 PM TANK 3 DIESEL OVERFILL ALARM JUN 27, 2016 10:01 AM JUN 27, 2016 9:59 AM JUL 10, 2015 12:17 PM LOW PRODUCT ALARM JUN 27, 2016 10:03 AM MAY 26, 2016 5:50 PM FEB 18, 2016 8:37 AM HIGH PRODUCT ALARM JUN 27, 2016 10:02 AM JUN 27, 2016 9:59 AM JUN 29, 2015 1:56 PM INVALID FUEL LEVEL JUN 27, 2016 10:02 AM PROBE OUT JUN 27, 2016 10:02 AM JUN 27, 2016 10:01 AM JUN 27, 2016 9:56 AM DELIVERY NEEDED JUN 27, 2016 10:03 AM MAY 26, 2016 5:50 PM FEB 18, 2016 8:37 AM LOW TEMP WARNING JUN 29, 2015 1:58 PM TANK 5 TANK 6 TANK 7 TANK 8 TANK 9 TANK 10 TANK 11 TANK 12 TANK 13 TANK 14 TANK 15 TANK 16 I38200 JUL 6, 2016 9:11 AM I30200 JUL 6, 2016 9:11 AM FASTRIP 7725 4901 S UNION BAKERSFIELD CA 661-397-9387 LIQUID ALARM HISTORY REPORT SENSOR LOCATION 1 UNL STP JUN 27, 2016 10:36 AM SENSOR OUT ALARM JUN 27, 2016 9:46 AM FUEL ALARM MAY 31, 2016 4:19 AM FUEL ALARM 2 UNL ANN JUN 27, 2016 10:36 AM SENSOR OUT ALARM JUN 27, 2016 9:46 AM FUEL ALARM JUL 10, 2015 12:02 PM FUEL ALARM 3 PREM STP JUL 1, 2016 2:55 PM FUEL ALARM JUL 1, 2016 2:40 PM FUEL ALARM JUN 27, 2016 10:36 AM SENSOR OUT ALARM 4 PREM ANN JUN 27, 2016 10:36 AM SENSOR OUT ALARM JUN 27, 2016 9:48 AM FUEL ALARM JUL 10, 2015 12:02 PM FUEL ALARM 5 DSL STP JUN 27, 2016 10:36 AM SENSOR OUT ALARM JUN 27, 2016 9:48 AM FUEL ALARM MAY 9, 2016 6:38 AM FUEL ALARM 6 DSL ANN JUN 27, 2016 10:36 AM SENSOR OUT ALARM JUN 27, 2016 9:49 AM FUEL ALARM MAY 9, 2016 11:06 AM FUEL ALARM 7 DISP 9-10 JUN 27, 2016 10:36 AM SENSOR OUT ALARM JUN 27, 2016 9:53 AM FUEL ALARM JUL 10, 2015 11:53 AM FUEL ALARM 8 DISP11-12 JUN 27, 2016 10:36 AM SENSOR OUT ALARM JUN 27, 2016 9:50 AM FUEL ALARM JUL 10, 2015 11:55 AM FUEL ALARM 9 DISP 13-14 JUN 27, 2016 10:35 AM SENSOR OUT ALARM JUN 27, 2016 9:52 AM FUEL ALARM NOV 12, 2015 7:41 AM FUEL ALARM 10 DISP 15-16 JUN 27, 2016 10:35 AM FUEL ALARM JUN 27, 2016 9:51 AM FUEL ALARM JUL 10, 2015 12:00 PM FUEL ALARM I31600 JUL 6, 2016 9:11 AM FASTRIP 7725 4901 S UNION BAKERSFIELD CA 661-397-9387 SMART SENSOR ALARM HISTORY REPORT SENSOR LOCATION 1 VP 11-12 2 FM 9-10 3 FM 11-12 MAR 30, 2015 10:29 AM COMMUNICATION ALARM MAR 26, 2015 7:12 PM COMMUNICATION ALARM MAR 26, 2015 7:06 PM COMMUNICATION ALARM 4 FM 13-14 JAN 18, 2014 4:28 AM COMMUNICATION ALARM 5 FM 15-16 JAN 18, 2014 4:28 AM COMMUNICATION ALARM I40200 JUL 6, 2016 9:11 AM I40300 JUL 6, 2016 9:11 AM I34200 JUL 6, 2016 9:11 AM I34700 JUL 6, 2016 9:11 AM IV0100 JUL 6, 2016 9:11 AM FASTRIP 7725 4901 S UNION BAKERSFIELD CA 661-397-9387 ISD ALARM STATUS REPORT EVR TYPE: VACUUM ASSIST ISD TYPE: 01.05 VAPOR PROCESSOR TYPE: NONE OVERALL STATUS :PASS EVR VAPOR COLLECTION :PASS EVR VAPOR CONTAINMENT :PASS ISD MONITOR UP-TIME :100% EVR/ISD PASS TIME :100% WARNING ALARMS DATE TIME DESCRIPTION READING VALUE 16-05-02 10:01:09 VAPOR CONTAINMENT LEAKAGE CFH@2 INCHES WC 11.49 15-11-23 10:01:37 CONTAINMENT GROSS OVER PRESSURE WEEKLY 95% 2.69 15-09-10 10:01:09 VAPOR CONTAINMENT LEAKAGE CFH@2 INCHES WC 17.48 15-08-27 10:01:11 SENSOR OUT SELFTEST CHECK VAPOR FLOW METER f 4:FM 15-16 15-08-27 10:01:11 A/L RATIO GROSS BLOCKAGE FP 7 BLEND3 BLKD 15-08-26 10:01:09 SENSOR OUT SELFTEST CHECK VAPOR FLOW METER f 4:FM 15-16 15-06-22 10:01:09 VAPOR CONTAINMENT LEAKAGE CFH@2 INCHES WC 18.57 15-04-02 10:01:09 VAPOR CONTAINMENT LEAKAGE CFH@2 INCHES WC 51.38 15-04-01 10:01:09 VAPOR CONTAINMENT LEAKAGE CFH@2 INCHES WC 13.18 15-03-31 10:01:09 VAPOR CONTAINMENT LEAKAGE CFH@2 INCHES WC 13.18 FAILURE ALARMS DATE TIME DESCRIPTION READING VALUE SHUTDOWN & MISCELLANEOUS EVENTS DATE TIME DESCRIPTION ACTION/NAME 16-07-05 10:01:30 READINESS ISD:PP EVR:NP EVR READINESS PENDING 16-07-04 10:02:07 READINESS ISD:PP EVR:NP EVR READINESS PENDING 16-07-03 10:01:52 READINESS ISD:PP EVR:NP EVR READINESS PENDING 16-07-03 09:25:33 READINESS ISD:PP EVR:NN EVR READINESS PENDING 16-07-03 09:25:33 ISD STARTUP 16-07-03 09:25:28 ISD SHUTDOWN 16-07-03 01:32:39 READINESS ISD:PP EVR:NN EVR READINESS PENDING 16-07-03 01:32:39 ISD STARTUP 16-07-03 01:32:33 ISD SHUTDOWN 16-07-03 01:03:10 READINESS ISD:PP EVR:NN EVR READINESS PENDING POST MONITOR CERT Responses Received: I10200 JUL 6, 2016 3:48 PM FASTRIP 7725 4901 S UNION BAKERSFIELD CA 661-397-9387 SYSTEM CONFIGURATION SLOT BOARD TYPE POWER ON RESET CURRENT 1 8SMARTSENSOR BD 39955 39411 2 4 PROBE / G.T. 164948 163609 3 INTERSTITIAL BD 203214 201818 4 INTERSTITIAL BD 203171 201728 5 UNUSED 9872648 9481665 6 UNUSED 9821355 9457375 7 UNUSED 9805808 9463990 8 UNUSED 9790138 9472366 9 RELAY BOARD 15028 15028 10 UNUSED 9802609 9473109 11 UNUSED 9790789 9463960 12 UNUSED 9790810 9461125 13 UNUSED 9774542 9465055 14 UNUSED 9779422 9453565 15 UNUSED 9780617 9468921 16 UNUSED 9778208 9457989 COMM 1 ELEC DISP INT. 101334 101098 COMM 2 RS232 SERIAL BD 15007 15007 COMM 3 RS232 SERIAL BD 14987 15028 COMM 4 UNUSED 9796658 9469436 COMM 5 UNUSED 9777899 9458333 COMM 6 UNUSED 9775901 9468104 I90200 JUL 6, 2016 3:48 PM SOFTWARE REVISION LEVEL VERSION 333.06 SOFTWARE# 346333-100-G CREATED - 14.10.01.16.35 S-MODULE# 330160-004-a SYSTEM FEATURES: PERIODIC IN-TANK TESTS ANNUAL IN-TANK TESTS ISD/APM I11100 JUL 6, 2016 3:48 PM FASTRIP 7725 4901 S UNION BAKERSFIELD CA 661-397-9387 PRIORITY ALARM HISTORY ID CATEGORY DESCRIPTION ALARM TYPE STATE DATE TIME T 1 TANK UNLEADED PROBE OUT CLEAR 7-06-16 11:35AM T 1 TANK UNLEADED PROBE OUT ALARM 7-06-16 11:34AM T 2 TANK PREMIUM PROBE OUT CLEAR 7-06-16 11:33AM T 2 TANK PREMIUM PROBE OUT ALARM 7-06-16 11:33AM T 3 TANK DIESEL PROBE OUT CLEAR 7-06-16 11:32AM T 3 TANK DIESEL PROBE OUT ALARM 7-06-16 11:31AM T 3 TANK DIESEL OVERFILL ALARM CLEAR 7-06-16 11:21AM T 3 TANK DIESEL OVERFILL ALARM ALARM 7-06-16 11:19AM T 2 TANK PREMIUM OVERFILL ALARM CLEAR 7-06-16 11:19AM T 2 TANK PREMIUM OVERFILL ALARM ALARM 7-06-16 11:17AM T 1 TANK UNLEADED OVERFILL ALARM CLEAR 7-06-16 11:17AM T 1 TANK UNLEADED OVERFILL ALARM ALARM 7-06-16 11:15AM T 1 TANK UNLEADED PROBE OUT CLEAR 7-06-16 10:07AM T 1 TANK UNLEADED PROBE OUT ALARM 7-06-16 10:07AM T 2 TANK PREMIUM PROBE OUT CLEAR 7-06-16 10:04AM L10 DISP PAN DISP 15-16 FUEL ALARM CLEAR 7-06-16 10:04AM L 9 DISP PAN DISP 13-14 SENSOR OUT ALARM CLEAR 7-06-16 10:04AM L 3 STP SUMP PREM STP SENSOR OUT ALARM CLEAR 7-06-16 10:04AM L 2 ANNULAR UNL ANN SENSOR OUT ALARM CLEAR 7-06-16 10:04AM L 8 DISP PAN DISP11-12 SENSOR OUT ALARM CLEAR 7-06-16 10:04AM L 7 DISP PAN DISP 9-10 SENSOR OUT ALARM CLEAR 7-06-16 10:04AM L 6 ANNULAR DSL ANN SENSOR OUT ALARM CLEAR 7-06-16 10:04AM L 1 STP SUMP UNL STP SENSOR OUT ALARM CLEAR 7-06-16 10:04AM L 4 ANNULAR PREM ANN SENSOR OUT ALARM CLEAR 7-06-16 10:04AM L 5 STP SUMP DSL STP SENSOR OUT ALARM CLEAR 7-06-16 10:04AM L 3 STP SUMP PREM STP SENSOR OUT ALARM ALARM 7-06-16 10:04AM L 1 STP SUMP UNL STP SENSOR OUT ALARM ALARM 7-06-16 10:04AM L 6 ANNULAR DSL ANN SENSOR OUT ALARM ALARM 7-06-16 10:03AM L 5 STP SUMP DSL STP SENSOR OUT ALARM ALARM 7-06-16 10:03AM L 8 DISP PAN DISP11-12 SENSOR OUT ALARM ALARM 7-06-16 10:03AM L 4 ANNULAR PREM ANN SENSOR OUT ALARM ALARM 7-06-16 10:03AM L 7 DISP PAN DISP 9-10 SENSOR OUT ALARM ALARM 7-06-16 10:03AM L 2 ANNULAR UNL ANN SENSOR OUT ALARM ALARM 7-06-16 10:03AM L10 DISP PAN DISP 15-16 FUEL ALARM ALARM 7-06-16 10:03AM L 9 DISP PAN DISP 13-14 SENSOR OUT ALARM ALARM 7-06-16 10:03AM T 2 TANK PREMIUM PROBE OUT ALARM 7-06-16 10:02AM L 7 DISP PAN DISP 9-10 FUEL ALARM CLEAR 7-06-16 10:00AM L 7 DISP PAN DISP 9-10 FUEL ALARM ALARM 7-06-16 9:59AM L 9 DISP PAN DISP 13-14 FUEL ALARM CLEAR 7-06-16 9:59AM L 9 DISP PAN DISP 13-14 FUEL ALARM ALARM 7-06-16 9:59AM L10 DISP PAN DISP 15-16 FUEL ALARM CLEAR 7-06-16 9:58AM L10 DISP PAN DISP 15-16 FUEL ALARM ALARM 7-06-16 9:58AM L 8 DISP PAN DISP11-12 FUEL ALARM CLEAR 7-06-16 9:58AM L 8 DISP PAN DISP11-12 FUEL ALARM ALARM 7-06-16 9:57AM L 6 ANNULAR DSL ANN FUEL ALARM CLEAR 7-06-16 9:57AM L 6 ANNULAR DSL ANN FUEL ALARM ALARM 7-06-16 9:56AM L 5 STP SUMP DSL STP FUEL ALARM CLEAR 7-06-16 9:56AM L 5 STP SUMP DSL STP FUEL ALARM ALARM 7-06-16 9:56AM L 4 ANNULAR PREM ANN FUEL ALARM CLEAR 7-06-16 9:56AM L 4 ANNULAR PREM ANN FUEL ALARM ALARM 7-06-16 9:55AM I11200 JUL 6, 2016 3:48 PM FASTRIP 7725 4901 S UNION BAKERSFIELD CA 661-397-9387 NON-PRIORITY ALARM HISTORY ID CATEGORY DESCRIPTION ALARM TYPE STATE DATE TIME T 1 TANK UNLEADED LOW TEMP WARNING CLEAR 7-06-16 11:37AM T 3 TANK DIESEL HIGH WATER WARNING CLEAR 7-06-16 11:36AM T 1 TANK UNLEADED LOW TEMP WARNING ALARM 7-06-16 11:35AM T 2 TANK PREMIUM INVALID FUEL LEVEL CLEAR 7-06-16 11:34AM T 2 TANK PREMIUM INVALID FUEL LEVEL ALARM 7-06-16 11:33AM T 3 TANK DIESEL INVALID FUEL LEVEL CLEAR 7-06-16 11:32AM T 3 TANK DIESEL INVALID FUEL LEVEL ALARM 7-06-16 11:32AM T 3 TANK DIESEL HIGH WATER WARNING ALARM 7-06-16 10:33AM T 1 TANK UNLEADED LOW TEMP WARNING CLEAR 7-06-16 10:08AM T 1 TANK UNLEADED LOW TEMP WARNING ALARM 7-06-16 10:08AM T 3 TANK DIESEL INVALID FUEL LEVEL CLEAR 6-27-16 10:03AM T 3 TANK DIESEL DELIVERY NEEDED CLEAR 6-27-16 10:03AM T 3 TANK DIESEL DELIVERY NEEDED ALARM 6-27-16 10:03AM T 3 TANK DIESEL INVALID FUEL LEVEL ALARM 6-27-16 10:02AM T 3 TANK DIESEL HIGH PRODUCT ALARM CLEAR 6-27-16 10:02AM T 3 TANK DIESEL HIGH PRODUCT ALARM ALARM 6-27-16 10:02AM T 1 TANK UNLEADED INVALID FUEL LEVEL CLEAR 6-27-16 10:01AM T 1 TANK UNLEADED DELIVERY NEEDED CLEAR 6-27-16 10:01AM T 1 TANK UNLEADED DELIVERY NEEDED ALARM 6-27-16 10:01AM T 2 TANK PREMIUM LOW TEMP WARNING CLEAR 6-27-16 10:01AM T 1 TANK UNLEADED INVALID FUEL LEVEL ALARM 6-27-16 10:01AM T 2 TANK PREMIUM LOW TEMP WARNING ALARM 6-27-16 10:01AM T 3 TANK DIESEL HIGH PRODUCT ALARM CLEAR 6-27-16 10:00AM T 3 TANK DIESEL HIGH PRODUCT ALARM ALARM 6-27-16 9:59AM T 1 TANK UNLEADED HIGH PRODUCT ALARM CLEAR 6-27-16 9:58AM T 1 TANK UNLEADED HIGH PRODUCT ALARM ALARM 6-27-16 9:58AM SYSTEM PRINTER ERROR CLEAR 6-15-16 6:42PM SYSTEM PAPER OUT CLEAR 6-15-16 6:42PM SYSTEM PAPER OUT ALARM 6-15-16 6:42PM SYSTEM PRINTER ERROR ALARM 6-15-16 6:41PM SYSTEM PRINTER ERROR CLEAR 6-15-16 6:40PM SYSTEM PRINTER ERROR ALARM 6-15-16 6:40PM SYSTEM PRINTER ERROR CLEAR 6-15-16 6:39PM SYSTEM PAPER OUT CLEAR 6-15-16 6:39PM SYSTEM PRINTER ERROR ALARM 6-15-16 6:17PM SYSTEM PAPER OUT ALARM 6-15-16 6:17PM T 2 TANK PREMIUM DELIVERY NEEDED CLEAR 6-04-16 4:33AM T 2 TANK PREMIUM DELIVERY NEEDED ALARM 6-03-16 8:45PM T 3 TANK DIESEL DELIVERY NEEDED CLEAR 5-26-16 10:04PM T 3 TANK DIESEL DELIVERY NEEDED ALARM 5-26-16 5:50PM T 1 TANK UNLEADED DELIVERY NEEDED CLEAR 5-14-16 4:46AM T 1 TANK UNLEADED DELIVERY NEEDED ALARM 5-14-16 4:15AM T 1 TANK UNLEADED DELIVERY NEEDED CLEAR 5-07-16 11:43AM T 1 TANK UNLEADED INVALID FUEL LEVEL CLEAR 5-07-16 11:42AM T 1 TANK UNLEADED INVALID FUEL LEVEL ALARM 5-07-16 11:01AM T 1 TANK UNLEADED DELIVERY NEEDED ALARM 5-07-16 9:41AM OTHER ISD VAPOR LEAK WARN CLEAR 5-03-16 10:00AM OTHER ISD VAPOR LEAK WARN ALARM 5-02-16 10:01AM T 1 TANK UNLEADED DELIVERY NEEDED CLEAR 4-22-16 7:22AM T 1 TANK UNLEADED INVALID FUEL LEVEL CLEAR 4-22-16 7:21AM I20600 JUL 6, 2016 3:48 PM FASTRIP 7725 4901 S UNION BAKERSFIELD CA 661-397-9387 TANK ALARM HISTORY TANK 1 UNLEADED OVERFILL ALARM JUL 6, 2016 11:15 AM JUN 7, 2016 9:16 PM MAY 18, 2016 6:32 AM LOW PRODUCT ALARM JUN 27, 2016 10:01 AM MAY 14, 2016 4:15 AM MAY 7, 2016 9:41 AM HIGH PRODUCT ALARM JUN 27, 2016 9:58 AM JAN 17, 2016 5:12 AM DEC 25, 2015 6:48 AM INVALID FUEL LEVEL JUN 27, 2016 10:01 AM MAY 7, 2016 11:01 AM APR 22, 2016 6:05 AM PROBE OUT JUL 6, 2016 11:34 AM JUL 6, 2016 10:07 AM JUN 27, 2016 10:00 AM DELIVERY NEEDED JUN 27, 2016 10:01 AM MAY 14, 2016 4:15 AM MAY 7, 2016 9:41 AM LOW TEMP WARNING JUL 6, 2016 11:35 AM JUL 6, 2016 10:08 AM JUN 29, 2015 2:02 PM TANK 2 PREMIUM OVERFILL ALARM JUL 6, 2016 11:17 AM JUN 27, 2016 9:58 AM MAR 27, 2016 10:33 AM LOW PRODUCT ALARM JUN 3, 2016 8:45 PM JUN 29, 2015 1:08 PM INVALID FUEL LEVEL JUL 6, 2016 11:33 AM JUN 29, 2015 1:09 PM PROBE OUT JUL 6, 2016 11:33 AM JUL 6, 2016 10:02 AM JUN 27, 2016 10:00 AM DELIVERY NEEDED JUN 3, 2016 8:45 PM JUN 29, 2015 1:08 PM LOW TEMP WARNING JUN 27, 2016 10:01 AM JUN 29, 2015 2:00 PM TANK 3 DIESEL OVERFILL ALARM JUL 6, 2016 11:19 AM JUN 27, 2016 10:01 AM JUN 27, 2016 9:59 AM LOW PRODUCT ALARM JUN 27, 2016 10:03 AM MAY 26, 2016 5:50 PM FEB 18, 2016 8:37 AM HIGH PRODUCT ALARM JUN 27, 2016 10:02 AM JUN 27, 2016 9:59 AM JUN 29, 2015 1:56 PM INVALID FUEL LEVEL JUL 6, 2016 11:32 AM JUN 27, 2016 10:02 AM PROBE OUT JUL 6, 2016 11:31 AM JUN 27, 2016 10:02 AM JUN 27, 2016 10:01 AM HIGH WATER WARNING JUL 6, 2016 10:33 AM DELIVERY NEEDED JUN 27, 2016 10:03 AM MAY 26, 2016 5:50 PM FEB 18, 2016 8:37 AM LOW TEMP WARNING JUN 29, 2015 1:58 PM TANK 5 TANK 6 TANK 7 TANK 8 TANK 9 TANK 10 TANK 11 TANK 12 TANK 13 TANK 14 TANK 15 TANK 16 I38200 JUL 6, 2016 3:48 PM I30200 JUL 6, 2016 3:48 PM FASTRIP 7725 4901 S UNION BAKERSFIELD CA 661-397-9387 LIQUID ALARM HISTORY REPORT SENSOR LOCATION 1 UNL STP JUL 6, 2016 10:04 AM SENSOR OUT ALARM JUL 6, 2016 9:54 AM FUEL ALARM JUN 27, 2016 10:36 AM SENSOR OUT ALARM 2 UNL ANN JUL 6, 2016 10:03 AM SENSOR OUT ALARM JUL 6, 2016 9:54 AM FUEL ALARM JUN 27, 2016 10:36 AM SENSOR OUT ALARM 3 PREM STP JUL 6, 2016 10:04 AM SENSOR OUT ALARM JUL 6, 2016 9:55 AM FUEL ALARM JUL 1, 2016 2:55 PM FUEL ALARM 4 PREM ANN JUL 6, 2016 10:03 AM SENSOR OUT ALARM JUL 6, 2016 9:55 AM FUEL ALARM JUN 27, 2016 10:36 AM SENSOR OUT ALARM 5 DSL STP JUL 6, 2016 10:03 AM SENSOR OUT ALARM JUL 6, 2016 9:56 AM FUEL ALARM JUN 27, 2016 10:36 AM SENSOR OUT ALARM 6 DSL ANN JUL 6, 2016 10:03 AM SENSOR OUT ALARM JUL 6, 2016 9:56 AM FUEL ALARM JUN 27, 2016 10:36 AM SENSOR OUT ALARM 7 DISP 9-10 JUL 6, 2016 10:03 AM SENSOR OUT ALARM JUL 6, 2016 9:59 AM FUEL ALARM JUN 27, 2016 10:36 AM SENSOR OUT ALARM 8 DISP11-12 JUL 6, 2016 10:03 AM SENSOR OUT ALARM JUL 6, 2016 9:57 AM FUEL ALARM JUN 27, 2016 10:36 AM SENSOR OUT ALARM 9 DISP 13-14 JUL 6, 2016 10:03 AM SENSOR OUT ALARM JUL 6, 2016 9:59 AM FUEL ALARM JUN 27, 2016 10:35 AM SENSOR OUT ALARM 10 DISP 15-16 JUL 6, 2016 10:03 AM FUEL ALARM JUL 6, 2016 9:58 AM FUEL ALARM JUN 27, 2016 10:35 AM FUEL ALARM I31600 JUL 6, 2016 3:48 PM FASTRIP 7725 4901 S UNION BAKERSFIELD CA 661-397-9387 SMART SENSOR ALARM HISTORY REPORT SENSOR LOCATION 1 VP 11-12 2 FM 9-10 3 FM 11-12 MAR 30, 2015 10:29 AM COMMUNICATION ALARM MAR 26, 2015 7:12 PM COMMUNICATION ALARM MAR 26, 2015 7:06 PM COMMUNICATION ALARM 4 FM 13-14 JAN 18, 2014 4:28 AM COMMUNICATION ALARM 5 FM 15-16 JAN 18, 2014 4:28 AM COMMUNICATION ALARM I40200 JUL 6, 2016 3:48 PM I40300 JUL 6, 2016 3:48 PM I34200 JUL 6, 2016 3:48 PM I34700 JUL 6, 2016 3:48 PM IV0100 JUL 6, 2016 3:48 PM FASTRIP 7725 4901 S UNION BAKERSFIELD CA 661-397-9387 ISD ALARM STATUS REPORT EVR TYPE: VACUUM ASSIST ISD TYPE: 01.05 VAPOR PROCESSOR TYPE: NONE OVERALL STATUS :PASS EVR VAPOR COLLECTION :PASS EVR VAPOR CONTAINMENT :PASS ISD MONITOR UP-TIME :100% EVR/ISD PASS TIME :100% WARNING ALARMS DATE TIME DESCRIPTION READING VALUE 16-05-02 10:01:09 VAPOR CONTAINMENT LEAKAGE CFH@2 INCHES WC 11.49 15-11-23 10:01:37 CONTAINMENT GROSS OVER PRESSURE WEEKLY 95% 2.69 15-09-10 10:01:09 VAPOR CONTAINMENT LEAKAGE CFH@2 INCHES WC 17.48 15-08-27 10:01:11 SENSOR OUT SELFTEST CHECK VAPOR FLOW METER f 4:FM 15-16 15-08-27 10:01:11 A/L RATIO GROSS BLOCKAGE FP 7 BLEND3 BLKD 15-08-26 10:01:09 SENSOR OUT SELFTEST CHECK VAPOR FLOW METER f 4:FM 15-16 15-06-22 10:01:09 VAPOR CONTAINMENT LEAKAGE CFH@2 INCHES WC 18.57 15-04-02 10:01:09 VAPOR CONTAINMENT LEAKAGE CFH@2 INCHES WC 51.38 15-04-01 10:01:09 VAPOR CONTAINMENT LEAKAGE CFH@2 INCHES WC 13.18 15-03-31 10:01:09 VAPOR CONTAINMENT LEAKAGE CFH@2 INCHES WC 13.18 FAILURE ALARMS DATE TIME DESCRIPTION READING VALUE SHUTDOWN & MISCELLANEOUS EVENTS DATE TIME DESCRIPTION ACTION/NAME 16-07-06 10:04:57 READINESS ISD:PP EVR:NN EVR READINESS PENDING 16-07-06 10:04:57 ISD STARTUP 16-07-06 10:04:43 ISD SHUTDOWN 16-07-06 10:01:42 READINESS ISD:PP EVR:PP ISD & EVR READY 16-07-05 10:01:30 READINESS ISD:PP EVR:NP EVR READINESS PENDING 16-07-04 10:02:07 READINESS ISD:PP EVR:NP EVR READINESS PENDING 16-07-03 10:01:52 READINESS ISD:PP EVR:NP EVR READINESS PENDING 16-07-03 09:25:33 READINESS ISD:PP EVR:NN EVR READINESS PENDING 16-07-03 09:25:33 ISD STARTUP 16-07-03 09:25:28 ISD SHUTDOWN SWRCB, January 2006 Spill Bucket Testing Report Form This form is intended for use by contractors performing annual testing of UST spill containment structures. The completed form and printouts from tests (if applicable), should be provided to the facility owner/operator forsubmittal to the local regulatory agency. 1.FACILITY INFORMATION Facility Name:Date of Testing: Facility Address: Facility Contact:Phone: Date Local Agency Was Notified of Testing : Name of Local Agency Inspector (if present during testing): 2.TESTING CONTRACTOR INFORMATION Company Name:Confidence UST Services, Inc. Technician Conducting Test: Credentials1:CSLB Contractor ICC Service Tech. SWRCB Tank Tester Other (Specify) License Number(s):CSLB#804904 ICC# 3.SPILL BUCKET TESTING INFORMATION Test Method Used:Hydrostatic Vacuum Other Test Equipment Used:Lake TestEquipment Resolution:0.0625” Identify Spill Bucket (By Tank Number, Stored Product, etc.) 1234 Bucket Installation Type: Direct Bury Contained in Sump Direct Bury Contained in Sump Direct Bury Contained in Sump Direct Bury Contained in Sump Bucket Diameter: Bucket Depth: Wait time between applying vacuum/water and start of test: Test Start Time (TI): Initial Reading (RI): Test End Time (TF): Final Reading (RF): Test Duration (TF – TI): Change in Reading (RF -RI): Pass/Fail Threshold or Criteria: Test Result: Pass Fail Pass Fail Pass Fail Pass Fail Comments –(include information on repairs made prior to testing, and recommended follow-up for failed tests) CERTIFICATION OF TECHNICIAN RESPONSIBLE FOR CONDUCTING THIS TESTING I hereby certify that all the information contained in this report is true, accurate, and in full compliance with legal requirements. Technician’s Signature:________________________________________________ Date:_________ 1 State laws and regulations do not currently require testing to be performed by a qualified contractor. However, local requirements may be more stringent. #7725/Fastrip#19 07/06/2016 4901SouthUnionAvenue Bakersfield,CA93307 OmeroGarcia(661)393-7000 06/14/2016 Kris Karns BrandonMason 5284980-UT Regular 12.00" 14.50" 5min. 9:00 am 7.25" 10:00 am 7.25" 1hour 0.00" 0.0625" Super 12.00" 13.75" 5min. 9:00 am 7.50" 10:00 am 7.50" 1hour 0.00" 0.0625"0.0625" Diesel 12.00" 15.00" 5min. 9:00 am 7.50" 10:00 am 7.50" 1hour 0.00" 07/06/2016