Loading...
HomeMy WebLinkAbout#775 FMC Results 7-6-16MONITORING SYSTEM CERTIFICATION For Use By All Jurisdictions Within the State of CaliforniaAuthority Cited: Chapter 6.7, Health and Safety Code; Chapter 16, Division 3, Title 23, California Code of Regulations This form must be used to document testing and servicing of monitoring equipment. A separate certification or report must be prepared for each monitoring system control panel by the technician who performs the work. A copy of this form must be provided to the tank system owner/operator. The owner/operator must submit a copy of this form to the local agency regulating UST systems within 30 days of test date. A.General Information Facility Name:Bldg. No.: Site Address:City:Zip: Facility Contact Person: Contact Phone No.: Make/Model of Monitoring System:Date of Testing/Servicing: B.Inventory of Equipment Tested/Certified Check the appropriate boxes to indicate specific equipment inspected/serviced: Tank ID:Tank ID: In-Tank Gauging Probe.Model:In-Tank Gauging Probe.Model: Annular Space or Vault Sensor.Model:Annular Space or Vault Sensor.Model: Piping Sump / Trench Sensor(s).Model:Piping Sump / Trench Sensor(s).Model: Fill Sump Sensor(s).Model:Fill Sump Sensor(s).Model: Mechanical Line Leak Detector.Model:Mechanical Line Leak Detector.Model: Electronic Line Leak Detector.Model:Electronic LineLeak Detector.Model: Tank Overfill / High-Level Sensor.Model:Tank Overfill / High-Level Sensor.Model: Other (specify equipment type and model in Section E on Page 2).Other (specify equipment type and model in Section E on Page 2). Tank ID:Tank ID: In-Tank Gauging Probe.Model:In-Tank Gauging Probe.Model: Annular Space or Vault Sensor.Model:Annular Space or Vault Sensor.Model: Piping Sump / TrenchSensor(s).Model:Piping Sump / Trench Sensor(s).Model: Fill Sump Sensor(s).Model:Fill Sump Sensor(s).Model: Mechanical Line Leak Detector.Model:Mechanical Line Leak Detector.Model: Electronic Line Leak Detector.Model:Electronic Line Leak Detector.Model: Tank Overfill / High-Level Sensor.Model:Tank Overfill / High-Level Sensor.Model: Other (specify equipment type and model in Section E on Page 2).Other (specify equipment type and model in Section E on Page 2). Dispenser ID:Dispenser ID: Dispenser Containment Sensor(s).Model:Dispenser Containment Sensor(s).Model: Shear Valve(s).Shear Valve(s). Dispenser Containment Float(s) and Chain(s).Dispenser Containment Float(s) and Chain(s). Dispenser ID:Dispenser ID: Dispenser Containment Sensor(s).Model:Dispenser Containment Sensor(s).Model: Shear Valve(s).Shear Valve(s). Dispenser Containment Float(s) and Chain(s).Dispenser Containment Float(s) and Chain(s). Dispenser ID:Dispenser ID: Dispenser Containment Sensor(s).Model:Dispenser Containment Sensor(s).Model: Shear Valve(s).Shear Valve(s). Dispenser Containment Float(s) and Chain(s).Dispenser Containment Float(s) and Chain(s). *If the facility contains more tanks or dispensers, copy this form. Include information for every tank and dispenser at the facility. C.Certification -I certify that the equipment identified in this document was inspected/serviced in accordance with the manufacturers’ guidelines. Attached to this Certification is information (e.g. manufacturers' checklists)necessary to verify that this information is correct and a Plot Plan showing the layout of monitoring equipment. For any equipment capable of generating such reports, I have also attached a copy of the report;(check all that apply):System set-up Alarm history report Technician Name (print):Signature: Certification No.:License. No.:804904 Testing Company Name:Confidence UST Services, Inc.Phone No.:(800)339-9930 Site Address:Date of Testing/Servicing: Page 1 of 3 #7775/Fastrip#19 4901SouthUnionAvenueBakersfield93307 OmeroGarcia (661)393-7000 Veeder-RootTLS-350 07/06/2016 12,000gal.Regular-1 847390-107 794390-420 794380-208 FX1V 847390-107 12,000gal.Regular-2 847390-107 794390-420 794380-208 FX1V 847390-107 12,000gal.Super 847390-107 794390-420 794380-208 FX1V 847390-107 12,000gal.Diesel 847390-107 794390-420 794380-208 FX1DV 847390-107 1-2 794380-208 3-4 794380-208 5-6 794380-208 794380-208 7-8 TransitionSump1 794380-208 TransitionSump2 794380-208 BrandonMason B34335 4901SouthUnionAvenue Bakersfield,CA93307 07/06/2016 794380-208 794380-208 794380-208 794380-208 Monitoring System Certification D.Results of Testing/Servicing Software Version Installed: Complete the following checklist: Yes No*Isthe audible alarm operational? Yes No*Is the visual alarm operational? Yes No*Were all sensors visually inspected, functionally tested, and confirmed operational? Yes No*Were all sensors installed at lowest point of secondary containment and positioned so that other equipment will not interfere with their proper operation? Yes No* N/A If alarms are relayed to a remote monitoring station, is all communications equipment (e.g., modem) operational? Yes No* N/A For pressurized piping systems, does the turbine automatically shut down if the piping secondary containment monitoring system detects a leak, fails to operate, or is electrically disconnected? If yes: which sensors initiate positive shut-down? (Check all that apply) Sump/Trench Sensors; Dispenser Containment Sensors. Did you confirm positive shut-down due to leaks and sensor failure/disconnection? Yes; No. Yes No* N/A For tank systems that utilize the monitoring system as the primary tank overfill warning device (i.e., no mechanical overfill prevention valve is installed), is the overfill warning alarm visible and audible at the tank fill point(s) and operating properly? If so, at what percent oftank capacity does the alarm trigger? % Yes*NoWas any monitoring equipment replaced? If yes, identify specific sensors, probes, or other equipment replaced and list the manufacturer name and model for all replacement parts in Section E, below. Yes*NoWas liquid found inside any secondary containment systems designed as dry systems? (Check all that apply) Product; Water. If yes, describe causes in Section E, below. Yes No*Was monitoring system set-up reviewed to ensure proper settings? Attach set up reports, if applicable Yes No*Is all monitoring equipment operational per manufacturer’s specifications? * In Section E below, describe how and when these deficiencies were or will be corrected. E.Comments: Page 2 of 3 327.04 90 Monitoring System Certification F.In-Tank Gauging / SIR Equipment: Check this box if tank gauging is used only for inventory control. Check this box if no tank gauging or SIR equipment is installed. This section must be completed if in-tank gauging equipment is used to perform leak detection monitoring. Complete the following checklist: Yes No*Has all input wiring been inspected for proper entry and termination, including testing for ground faults? Yes No*Were all tank gauging probes visually inspected for damage and residue buildup? Yes No*Was accuracy of system product level readings tested? Yes No*Was accuracy of system water level readings tested? Yes No*Were all probes reinstalled properly? Yes No*Were all items on the equipment manufacturer’s maintenance checklist completed? * In the Section H, below, describe how and when these deficiencies were or will be corrected. G.Line Leak Detectors (LLD):Check this box if LLDs are not installed. Complete the following checklist: Yes No* N/A For equipment start-up or annual equipment certification, was a leak simulated to verify LLD performance? (Check all that apply)Simulated leak rate: 3 g.p.h.; 0.1 g.p.h ; 0.2 g.p.h. Yes No*Were all LLDs confirmed operational and accurate within regulatory requirements? Yes No*Was the testing apparatus properly calibrated? Yes No* N/A For mechanical LLDs, does the LLD restrict product flow if it detects a leak? Yes No* N/A For electronic LLDs, does the turbine automatically shut off if the LLD detects a leak? Yes No* N/A For electronic LLDs, does the turbine automatically shut off if any portion of the monitoring system is disabled or disconnected? Yes No* N/A For electronic LLDs, does the turbine automatically shut off if any portion of the monitoring system malfunctions or fails a test? Yes No* N/A For electronic LLDs, have all accessible wiring connections been visually inspected? Yes No*Were all items on the equipment manufacturer’s maintenance checklist completed? * In the Section H, below, describe how and when these deficiencies were or will be corrected. H.Comments: Page 3 of 3 Leak Detector Test Results Sheet Customer Address: Work Order: Site Address: Test Date: Site Contact: Phone: Technician: Phone: 800-339-9930 ICC No.: Product Type LLD Type Model Serial No. Check Valve Holding Pressure Bleed Off ML. Leak Rate Tested: Pass/Fail 3 gph @ 10 psi 3 gph @ 10 psi 3 gph @ 10 psi 3 gph @ 10 psi 3 gph @ 10 psi 3 gph @ 10 psi 3 gph @ 10 psi 3 gph @ 10 psi Technician Name: Technician No.: Signature: Date: JamiesonHill P.O.Box82515 Bakersfield,CA93380-2515 36812 07/06/2016 5284980-UT Regular1 Mechanical FX1V BrandonMason (661)393-7000OmeroGarcia Bakersfield,CA93307 4901SouthUnionAvenue #7775/Fastrip#19 12psi50ml Pass FX1VMechanicalRegular2 12psi50ml Pass FX1VMechanicalPremium 10psi50ml Pass FX1DVMechanicalDiesel 12psi50ml Pass BrandonMason 5284980-UT 07/06/2016 Responses Received: 200 FASTRIP 775 4901 S UNION BAKERSFIELD CA93307 661-391-9387 JUL 6, 2016 9:15 AM TANK PRODUCT GALLONS INCHES WATER DEG F ULLAGE 1 UNLEADED 1 5289 43.44 0.0 82.8 6743 2 UNLEADED 2 5610 45.46 0.0 83.1 6422 3 PREMIUM 4534 38.66 1.0 83.4 7497 4 DIESEL 3134 29.47 0.0 85.6 8898 I90500 JUL 6, 2016 9:15 AM SOFTWARE REVISION LEVEL VERSION 334.00 SOFTWARE# 346334-100-A CREATED - 15.05.29.10.36 S-MODULE# 330160-004-a SYSTEM FEATURES: PERIODIC IN-TANK TESTS ANNUAL IN-TANK TESTS ISD/APM I50500 JUL 6, 2016 9:15 AM SYSTEM TYPE AND LANGUAGE FLAG SYSTEM UNITS U.S. SYSTEM LANGUAGE ENGLISH SYSTEM DATE/TIME FORMAT MON DD YYYY HH:MM:SS xM I50201 JUL 6, 2016 9:15 AM SHIFT TIME 1 : 6:00 AM I50202 JUL 6, 2016 9:15 AM SHIFT TIME 2 : DISABLED I50203 JUL 6, 2016 9:15 AM SHIFT TIME 3 : DISABLED I50204 JUL 6, 2016 9:15 AM SHIFT TIME 4 : DISABLED I54600 JUL 6, 2016 9:15 AM TANK PER TST NEEDED WRN: DISABLED I54900 JUL 6, 2016 9:15 AM TANK ANN TST NEEDED WRN: DISABLED I55300 JUL 6, 2016 9:15 AM LINE RE-ENABLE METHOD PASS LINE TEST I55600 JUL 6, 2016 9:15 AM LINE PER TST NEEDED WRN: DISABLED I55900 JUL 6, 2016 9:15 AM LINE ANN TST NEEDED WRN: DISABLED I50D00 JUL 6, 2016 9:15 AM PRINT TC VOLUMES ENABLED I50E00 JUL 6, 2016 9:15 AM TEMP COMPENSATION VALUE (DEG F ): 60.0 I60B00 JUL 6, 2016 9:15 AM STICK HEIGHT OFFSET ENABLE STATUS DISABLED I51400 JUL 6, 2016 9:15 AM H-PROTOCOL DATA FORMAT HEIGHT I51A01 JUL 6, 2016 9:15 AM DAYLIGHT SAVING TIME ENABLED ON I51B00 JUL 6, 2016 9:15 AM DAYLIGHT SAVING TIME START DATE APR WEEK 1 SUN 2:00 AM END DATE OCT WEEK 6 SUN 2:00 AM I51600 JUL 6, 2016 9:15 AM RE-DIRECT LOCAL PRINTOUT DISABLED I50400 JUL 6, 2016 9:15 AM 232 SECURITY CODE PORT SECURITY CODE STATUS 1 000000 DISABLED 2 000000 DISABLED 3 000000 DISABLED 4 000000 DISABLED 5 000000 DISABLED 6 000000 DISABLED I21900 JUL 6, 2016 9:15 AM TANK CHART SECURITY DISABLED I5BD00 JUL 6, 2016 9:15 AM CUSTOM ALARM LABELS DISABLED I56000 JUL 6, 2016 9:15 AM MASS/DENSITY DISABLED I88101 JUL 6, 2016 9:15 AM PORT SETTINGS: COMM BOARD : 1 (EDIM ) RS-232 SECURITY CODE : DISABLED I88102 JUL 6, 2016 9:15 AM PORT SETTINGS: COMM BOARD : 2 (RS-232) BAUD RATE : 9600 PARITY : NONE STOP BIT : 1 STOP DATA LENGTH: 8 DATA RS-232 SECURITY CODE : DISABLED I88103 JUL 6, 2016 9:15 AM PORT SETTINGS: COMM BOARD : 3 (RS-232) BAUD RATE : 9600 PARITY : NONE STOP BIT : 2 STOP DATA LENGTH: 8 DATA RS-232 SECURITY CODE : DISABLED I88104 JUL 6, 2016 9:15 AM I88105 JUL 6, 2016 9:15 AM I88106 JUL 6, 2016 9:15 AM I52000 JUL 6, 2016 9:15 AM RECEIVER AUTO DIAL TYPE & START TIME RCVR LOCATION LABEL DIAL TYPE START TIME 1 ON DATE APR 8, 2016 DISABLED 2 ON DATE APR 8, 2016 DISABLED 3 ON DATE APR 8, 2016 DISABLED 4 ON DATE APR 8, 2016 DISABLED 5 ON DATE APR 8, 2016 DISABLED 6 ON DATE APR 8, 2016 DISABLED 7 ON DATE APR 8, 2016 DISABLED 8 ON DATE APR 8, 2016 DISABLED I60100 JUL 6, 2016 9:15 AM TANK CONFIGURATION DEVICE LABEL CONFIGURED 1 UNLEADED 1 ON 2 UNLEADED 2 ON 3 PREMIUM ON 4 DIESEL ON I60200 JUL 6, 2016 9:16 AM TANK PRODUCT LABEL TANK PRODUCT LABEL 1 UNLEADED 1 2 UNLEADED 2 3 PREMIUM 4 DIESEL I60300 JUL 6, 2016 9:16 AM TANK PRODUCT CODE TANK PRODUCT LABEL 1 UNLEADED 1 1 2 UNLEADED 2 2 3 PREMIUM 3 4 DIESEL 4 I60900 JUL 6, 2016 9:16 AM TANK THERMAL COEFFICIENT TANK PRODUCT LABEL 1 UNLEADED 1 0.000700 2 UNLEADED 2 0.000700 3 PREMIUM 0.000700 4 DIESEL 0.000450 I60700 JUL 6, 2016 9:16 AM TANK DIAMETER TANK PRODUCT LABEL INCHES 1 UNLEADED 1 96.00 2 UNLEADED 2 96.00 3 PREMIUM 96.00 4 DIESEL 96.00 I60A00 JUL 6, 2016 9:16 AM TANK FULL VOLUME TANK PRODUCT LABEL TANK PROFILE GALLONS 1 UNLEADED 1 1 PT 12032 2 UNLEADED 2 1 PT 12032 3 PREMIUM 1 PT 12031 4 DIESEL 1 PT 12032 I60400 JUL 6, 2016 9:16 AM TANK FULL VOLUME TANK PRODUCT LABEL GALLONS 1 UNLEADED 1 12032 2 UNLEADED 2 12032 3 PREMIUM 12031 4 DIESEL 12032 I60500 JUL 6, 2016 9:16 AM TANK 4 POINT VOLUMES TANK PRODUCT LABEL GALLONS 1 UNLEADED 1 12032 0 0 0 2 UNLEADED 2 12032 0 0 0 3 PREMIUM 12031 0 0 0 4 DIESEL 12032 0 0 0 I60600 JUL 6, 2016 9:16 AM TANK 20 POINT VOLUMES TANK PRODUCT LABEL GALLONS 1 UNLEADED 1 12032 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 2 UNLEADED 2 12032 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 3 PREMIUM 12031 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 4 DIESEL 12032 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 I61500 JUL 6, 2016 9:16 AM TANK PRODUCT LABEL METER DATA 1 UNLEADED 1 NO 2 UNLEADED 2 NO 3 PREMIUM NO 4 DIESEL NO I62F00 JUL 6, 2016 9:16 AM MAG PROBE FLOAT SIZE TANK PRODUCT LABEL FLOAT SIZE: 1 UNLEADED 1 4.0 IN. 2 UNLEADED 2 4.0 IN. 3 PREMIUM 4.0 IN. 4 DIESEL 4.0 IN. I62700 JUL 6, 2016 9:16 AM TANK HIGH WATER WARNING LIMIT TANK PRODUCT LABEL INCHES 1 UNLEADED 1 2.0 2 UNLEADED 2 2.0 3 PREMIUM 2.0 4 DIESEL 2.0 I64200 JUL 6, 2016 9:16 AM WATER ALARM FILTER TANK PRODUCT LABEL 1 UNLEADED 1 LOW 2 UNLEADED 2 LOW 3 PREMIUM LOW 4 DIESEL LOW I62400 JUL 6, 2016 9:16 AM TANK HIGH WATER LEVEL LIMIT TANK PRODUCT LABEL INCHES 1 UNLEADED 1 3.0 2 UNLEADED 2 3.0 3 PREMIUM 3.0 4 DIESEL 3.0 I62800 JUL 6, 2016 9:16 AM TANK MAXIMUM VOLUME LIMIT TANK PRODUCT LABEL GALLONS 1 UNLEADED 1 12032 2 UNLEADED 2 12032 3 PREMIUM 12031 4 DIESEL 12032 I62300 JUL 6, 2016 9:16 AM TANK OVERFILL LEVEL LIMIT TANK PRODUCT LABEL GALLONS 1 UNLEADED 1 10829 2 UNLEADED 2 10829 3 PREMIUM 10828 4 DIESEL 10829 I62200 JUL 6, 2016 9:16 AM TANK HIGH PRODUCT LIMIT TANK PRODUCT LABEL GALLONS 1 UNLEADED 1 11430 2 UNLEADED 2 11430 3 PREMIUM 11429 4 DIESEL 11430 I62900 JUL 6, 2016 9:16 AM TANK DELIVERY REQUIRED LIMIT TANK PRODUCT LABEL GALLONS 1 UNLEADED 1 1805 2 UNLEADED 2 1805 3 PREMIUM 1805 4 DIESEL 1805 I62100 JUL 6, 2016 9:16 AM TANK LOW PRODUCT LIMIT TANK PRODUCT LABEL GALLONS 1 UNLEADED 1 500 2 UNLEADED 2 500 3 PREMIUM 500 4 DIESEL 500 I62600 JUL 6, 2016 9:16 AM TANK LEAK ALARM LIMIT TANK PRODUCT LABEL GALLONS 1 UNLEADED 1 99 2 UNLEADED 2 99 3 PREMIUM 99 4 DIESEL 99 I62500 JUL 6, 2016 9:16 AM TANK SUDDEN LOSS LIMIT TANK PRODUCT LABEL GALLONS 1 UNLEADED 1 99 2 UNLEADED 2 99 3 PREMIUM 99 4 DIESEL 99 I60800 JUL 6, 2016 9:16 AM TANK TILT TANK PRODUCT LABEL INCHES 1 UNLEADED 1 7.33 2 UNLEADED 2 0.00 3 PREMIUM 2.67 4 DIESEL 3.75 I60B00 JUL 6, 2016 9:16 AM STICK HEIGHT OFFSET ENABLE STATUS DISABLED I60C00 JUL 6, 2016 9:16 AM TANK STICK HEIGHT OFFSET TANK PRODUCT LABEL INCHES 1 UNLEADED 1 0.00 2 UNLEADED 2 0.00 3 PREMIUM 0.00 4 DIESEL 0.00 I61200 JUL 6, 2016 9:16 AM TANK MANIFOLDED PARTNERS TANK PRODUCT LABEL SIPHON MANIFOLDED TANKS LINE MANIFOLDED TANKS 1 UNLEADED 1 2 NONE 2 UNLEADED 2 1 NONE 3 PREMIUM NONE NONE 4 DIESEL NONE NONE I63600 JUL 6, 2016 9:16 AM PERIODIC LEAK TEST MIN VOLUME TANK PRODUCT LABEL GALLONS 1 UNLEADED 1 120 2 UNLEADED 2 120 3 PREMIUM 120 4 DIESEL 120 I62A00 JUL 6, 2016 9:16 AM ANNUAL LEAK TEST MIN VOLUME TANK PRODUCT LABEL GALLONS 1 UNLEADED 1 120 2 UNLEADED 2 120 3 PREMIUM 120 4 DIESEL 120 I62C00 JUL 6, 2016 9:16 AM TANK PERIODIC TEST TYPE TANK PRODUCT LABEL PERIODIC TEST TYPE 1 UNLEADED 1 STANDARD 2 UNLEADED 2 STANDARD 3 PREMIUM STANDARD 4 DIESEL STANDARD I62D00 JUL 6, 2016 9:16 AM TANK LEAK TEST FAIL ALARMS TANK PRODUCT LABEL 1 UNLEADED 1 GROSS TEST FAIL ALARM DISABLED PERIODIC TEST FAIL ALARM DISABLED ANNUAL TEST FAIL ALARM DISABLED 2 UNLEADED 2 GROSS TEST FAIL ALARM DISABLED PERIODIC TEST FAIL ALARM DISABLED ANNUAL TEST FAIL ALARM DISABLED 3 PREMIUM GROSS TEST FAIL ALARM DISABLED PERIODIC TEST FAIL ALARM DISABLED ANNUAL TEST FAIL ALARM DISABLED 4 DIESEL GROSS TEST FAIL ALARM DISABLED PERIODIC TEST FAIL ALARM DISABLED ANNUAL TEST FAIL ALARM DISABLED I63100 JUL 6, 2016 9:16 AM TANK LEAK TEST AVERAGING TANK PRODUCT LABEL ANNUAL PERIODIC 1 UNLEADED 1 OFF OFF 2 UNLEADED 2 OFF OFF 3 PREMIUM OFF OFF 4 DIESEL OFF OFF I63000 JUL 6, 2016 9:16 AM IN-TANK LEAK TEST NOTIFY TANK PRODUCT LABEL TANK TEST NOTIFY: 1 UNLEADED 1 OFF 2 UNLEADED 2 OFF 3 PREMIUM OFF 4 DIESEL OFF I63200 JUL 6, 2016 9:16 AM TANK TEST SIPHON BREAK TANK PRODUCT LABEL SIPHON BREAK 1 UNLEADED 1 OFF 2 UNLEADED 2 OFF 3 PREMIUM OFF 4 DIESEL OFF I61000 JUL 6, 2016 9:16 AM TANK DELIVERY DELAY TANK PRODUCT LABEL 1 UNLEADED 1 1 2 UNLEADED 2 1 3 PREMIUM 1 4 DIESEL 1 I63A00 JUL 6, 2016 9:16 AM LOW LEVEL PUMP THRESHOLD FOR SEQUENTIAL LINE MANIFOLD TANK PRODUCT LABEL PUMP THRESHOLD 1 UNLEADED 1 10.00% 2 UNLEADED 2 10.00% 3 PREMIUM 10.00% 4 DIESEL 10.00% I61100 JUL 6, 2016 9:16 AM LEAK TEST METHOD - - - - - - - - - - - - TEST ON DATE : ALL TANK APR 8, 2016 START TIME : DISABLED TEST RATE :0.20 GAL/HR DURATION : 2 HOURS TST EARLY STOP:DISABLED I61300 JUL 6, 2016 9:16 AM CSLD PROBABLITY OF DETECTION I61400 JUL 6, 2016 9:16 AM CSLD CLIMATE FACTOR I61600 JUL 6, 2016 9:16 AM TANK PRODUCT LABEL CAL UPDATE 1 UNLEADED 1 IMMEDIATE 2 UNLEADED 2 IMMEDIATE 3 PREMIUM IMMEDIATE 4 DIESEL IMMEDIATE I61A00 JUL 6, 2016 9:16 AM IN-TANK LEAK TEST EARLY STOP TANK PRODUCT LABEL TST EARLY STOP: 1 UNLEADED 1 DISABLED 2 UNLEADED 2 DISABLED 3 PREMIUM DISABLED 4 DIESEL DISABLED I61B00 JUL 6, 2016 9:16 AM IN-TANK LEAK GROSS TEST AUTO-CONFIRM I61C00 JUL 6, 2016 9:16 AM CSLD REPORT ONLY I62B00 JUL 6, 2016 9:16 AM TANK LAST ANNUAL TEST TANK PRODUCT LABEL DATE 1 UNLEADED 1 ??? 0, 0 2 UNLEADED 2 ??? 0, 0 3 PREMIUM ??? 0, 0 4 DIESEL ??? 0, 0 I63300 JUL 6, 2016 9:16 AM LEAK TEST REPORT FORMAT: NORMAL I63400 JUL 6, 2016 9:16 AM RECONCILIATION WARNING LIMIT TANK PRODUCT LABEL GALLONS 1 UNLEADED 1 0 2 UNLEADED 2 0 3 PREMIUM 0 4 DIESEL 0 I63500 JUL 6, 2016 9:16 AM RECONCILIATION ALARM LIMIT TANK PRODUCT LABEL GALLONS 1 UNLEADED 1 1 2 UNLEADED 2 1 3 PREMIUM 1 4 DIESEL 1 I63900 JUL 6, 2016 9:16 AM ACCU CHART END SHAPE FACTOR TANK PRODUCT LABEL 1 UNLEADED 1 END FACTOR: NONE 2 UNLEADED 2 END FACTOR: NONE 3 PREMIUM END FACTOR: NONE 4 DIESEL END FACTOR: NONE I78000 JUL 6, 2016 9:16 AM I77700 JUL 6, 2016 9:16 AM I77800 JUL 6, 2016 9:16 AM I78C00 JUL 6, 2016 9:16 AM I78300 JUL 6, 2016 9:16 AM I78F00 JUL 6, 2016 9:16 AM I78700 JUL 6, 2016 9:16 AM I70200 JUL 6, 2016 9:16 AM LIQUID LABEL DEVICE LABEL 1 UNL 1 STP 2 UNL 1 ANN 3 UNL 2 STP 4 UNL 2 ANN 5 PNL STP 6 PNL ANN 7 DSL STP 8 DSL ANN 9 DISP 1-2 10 DISP 3-4 11 DISP 5-6 12 DISP 7-8 13 N. TRANS SUMP 14 S. TRANS SUMP 15 16 I70300 JUL 6, 2016 9:16 AM LIQUID TYPE SENSOR LOCATION TYPE 1 UNL 1 STP TRI-STATE (SINGLE FLOAT) 2 UNL 1 ANN TRI-STATE (SINGLE FLOAT) 3 UNL 2 STP TRI-STATE (SINGLE FLOAT) 4 UNL 2 ANN TRI-STATE (SINGLE FLOAT) 5 PNL STP TRI-STATE (SINGLE FLOAT) 6 PNL ANN TRI-STATE (SINGLE FLOAT) 7 DSL STP TRI-STATE (SINGLE FLOAT) 8 DSL ANN TRI-STATE (SINGLE FLOAT) 9 DISP 1-2 TRI-STATE (SINGLE FLOAT) 10 DISP 3-4 TRI-STATE (SINGLE FLOAT) 11 DISP 5-6 TRI-STATE (SINGLE FLOAT) 12 DISP 7-8 TRI-STATE (SINGLE FLOAT) 13 N. TRANS SUMP TRI-STATE (SINGLE FLOAT) 14 S. TRANS SUMP TRI-STATE (SINGLE FLOAT) 15 TRI-STATE (SINGLE FLOAT) 16 TRI-STATE (SINGLE FLOAT) I70400 JUL 6, 2016 9:16 AM LIQUID CATEGORY SENSOR LOCATION CATEGORY 1 UNL 1 STP STP SUMP 2 UNL 1 ANN ANNULAR SPACE 3 UNL 2 STP STP SUMP 4 UNL 2 ANN ANNULAR SPACE 5 PNL STP STP SUMP 6 PNL ANN ANNULAR SPACE 7 DSL STP STP SUMP 8 DSL ANN ANNULAR SPACE 9 DISP 1-2 DISPENSER PAN 10 DISP 3-4 OTHER SENSORS 11 DISP 5-6 DISPENSER PAN 12 DISP 7-8 DISPENSER PAN 13 N. TRANS SUMP PIPING SUMP 14 S. TRANS SUMP PIPING SUMP 15 OTHER SENSORS 16 OTHER SENSORS I74200 JUL 6, 2016 9:16 AM I74300 JUL 6, 2016 9:16 AM I74400 JUL 6, 2016 9:16 AM I74700 JUL 6, 2016 9:16 AM I74800 JUL 6, 2016 9:16 AM I74900 JUL 6, 2016 9:16 AM I7BC00 JUL 6, 2016 9:16 AM I80200 JUL 6, 2016 9:16 AM I80300 JUL 6, 2016 9:16 AM I80400 JUL 6, 2016 9:16 AM I80700 JUL 6, 2016 9:16 AM RELAY LABEL DEVICE LABEL 1 OVERFILL 2 OVERFILL 3 PNL 4 5 UNL 1 6 PNL 7 DSL 8 I80900 JUL 6, 2016 9:16 AM RELAY ORIENTATION RELAY DESIGNATION ORIENTATION 1 OVERFILL NORMALLY OPEN 2 OVERFILL NORMALLY OPEN 3 PNL NORMALLY CLOSED 4 NORMALLY OPEN 5 UNL 1 NORMALLY CLOSED 6 PNL NORMALLY CLOSED 7 DSL NORMALLY CLOSED 8 NORMALLY OPEN I80B00 JUL 6, 2016 9:16 AM RELAY TANK ASSIGNMENT RELAY DESIGNATION TANK 1 OVERFILL NONE 2 OVERFILL NONE 3 PNL NONE 4 NONE 5 UNL 1 1 6 PNL NONE 7 DSL NONE 8 NONE I80A00 JUL 6, 2016 9:16 AM RELAY TYPE RELAY DESIGNATION TYPE 1 OVERFILL STANDARD 2 OVERFILL STANDARD 3 PNL STANDARD 4 STANDARD 5 UNL 1 STANDARD 6 PNL STANDARD 7 DSL STANDARD 8 STANDARD I80C00 JUL 6, 2016 9:16 AM I80800 JUL 6, 2016 9:16 AM RELAY SETUP REPORT R 1:OVERFILL TYPE: STANDARD NORMALLY OPEN TANK #: NONE IN-TANK ALARMS ALL:LEAK ALARM ALL:OVERFILL ALARM ALL:HIGH PRODUCT ALARM R 2:OVERFILL TYPE: STANDARD NORMALLY OPEN TANK #: NONE IN-TANK ALARMS ALL:OVERFILL ALARM ALL:HIGH PRODUCT ALARM R 3:PNL TYPE: STANDARD NORMALLY CLOSED TANK #: NONE LIQUID SENSOR ALMS L 5:FUEL ALARM L 9:FUEL ALARM L10:FUEL ALARM L11:FUEL ALARM L12:FUEL ALARM L 6:SENSOR OUT ALARM L 9:SENSOR OUT ALARM L10:SENSOR OUT ALARM L11:SENSOR OUT ALARM L12:SENSOR OUT ALARM L 6:SHORT ALARM L 9:SHORT ALARM L10:SHORT ALARM L11:SHORT ALARM L12:SHORT ALARM ISD SITE ALARMS ISD GROSS PRES FAIL ISD DEGRD PRES FAIL ISD VAPOR LEAK FAIL ISD VP PRES FAIL ISD VP STATUS FAIL ISD HOSE ALARMS ALL:GROSS COLLECT FAIL ALL:DEGRD COLLECT FAIL ALL:FLOW COLLECT FAIL R 4: TYPE: STANDARD NORMALLY OPEN TANK #: NONE - NO ALARM ASSIGNMENTS - R 5:UNL 1 TYPE: STANDARD NORMALLY CLOSED TANK #: 1 LIQUID SENSOR ALMS L 1:FUEL ALARM L 3:FUEL ALARM L 9:FUEL ALARM L10:FUEL ALARM L11:FUEL ALARM L12:FUEL ALARM L 1:SENSOR OUT ALARM L 3:SENSOR OUT ALARM L 9:SENSOR OUT ALARM L10:SENSOR OUT ALARM L11:SENSOR OUT ALARM L12:SENSOR OUT ALARM L 1:SHORT ALARM L 3:SHORT ALARM L 9:SHORT ALARM L10:SHORT ALARM L11:SHORT ALARM L12:SHORT ALARM L13:SHORT ALARM ISD SITE ALARMS ISD GROSS PRES FAIL ISD DEGRD PRES FAIL ISD VAPOR LEAK FAIL ISD VP PRES FAIL ISD VP STATUS FAIL ISD SETUP FAIL ISD HOSE ALARMS ALL:GROSS COLLECT FAIL ALL:DEGRD COLLECT FAIL ALL:FLOW COLLECT FAIL PMC ALARMS VP PRESSURE FAIL VP DUTY CYCLE FAIL PMC SETUP FAIL R 6:PNL TYPE: STANDARD NORMALLY CLOSED TANK #: NONE LIQUID SENSOR ALMS L 5:FUEL ALARM L 9:FUEL ALARM L10:FUEL ALARM L11:FUEL ALARM L12:FUEL ALARM L 6:SENSOR OUT ALARM L 9:SENSOR OUT ALARM L10:SENSOR OUT ALARM L11:SENSOR OUT ALARM L12:SENSOR OUT ALARM L 6:SHORT ALARM L 9:SHORT ALARM L10:SHORT ALARM L11:SHORT ALARM L12:SHORT ALARM ISD SITE ALARMS ISD GROSS PRES FAIL ISD DEGRD PRES FAIL ISD VAPOR LEAK FAIL ISD VP PRES FAIL ISD VP STATUS FAIL ISD HOSE ALARMS ALL:GROSS COLLECT FAIL ALL:DEGRD COLLECT FAIL ALL:FLOW COLLECT FAIL PMC ALARMS VP EMISSIONS FAIL VP PRESSURE FAIL VP DUTY CYCLE FAIL PMC SETUP FAIL R 7:DSL TYPE: STANDARD NORMALLY CLOSED TANK #: NONE LIQUID SENSOR ALMS L 7:FUEL ALARM L 9:FUEL ALARM L10:FUEL ALARM L11:FUEL ALARM L12:FUEL ALARM L13:FUEL ALARM L14:FUEL ALARM L 7:SENSOR OUT ALARM L 9:SENSOR OUT ALARM L10:SENSOR OUT ALARM L11:SENSOR OUT ALARM L12:SENSOR OUT ALARM L13:SENSOR OUT ALARM L 7:SHORT ALARM L 9:SHORT ALARM L10:SHORT ALARM L11:SHORT ALARM L12:SHORT ALARM L13:SHORT ALARM ISD SITE ALARMS ISD GROSS PRES FAIL ISD DEGRD PRES FAIL ISD VAPOR LEAK FAIL ISD VP PRES FAIL ISD VP STATUS FAIL ISD HOSE ALARMS ALL:GROSS COLLECT FAIL ALL:DEGRD COLLECT FAIL ALL:FLOW COLLECT FAIL PMC ALARMS VP EMISSIONS FAIL VP PRESSURE FAIL VP DUTY CYCLE FAIL PMC SETUP FAIL R 8: TYPE: STANDARD NORMALLY OPEN TANK #: NONE - NO ALARM ASSIGNMENTS - I79000 JUL 6, 2016 9:17 AM EDIM:1 VR:349634-003-C TD:06.05.11.11.15 I79100 JUL 6, 2016 9:17 AM I72300 JUL 6, 2016 9:17 AM FASTRIP 775 4901 S UNION BAKERSFIELD CA93307 661-391-9387 SMARTSENSOR ASSIGNMENT DEVICE LABEL CATEGORY 01 PS 3-4 VAPOR PRESSURE 02 FM 1-2 AIR FLOW METER 03 FM 3-4 AIR FLOW METER 04 FM 5-6 AIR FLOW METER 05 FM 7-8 AIR FLOW METER 06 UNKNOWN 07 UNKNOWN 08 UNKNOWN 09 UNKNOWN 10 UNKNOWN 11 UNKNOWN 12 UNKNOWN 13 UNKNOWN 14 UNKNOWN 15 UNKNOWN 16 UNKNOWN 17 UNKNOWN 18 UNKNOWN 19 UNKNOWN 20 UNKNOWN 21 UNKNOWN 22 UNKNOWN 23 UNKNOWN 24 UNKNOWN 25 UNKNOWN 26 UNKNOWN 27 UNKNOWN 28 UNKNOWN 29 UNKNOWN 30 UNKNOWN 31 UNKNOWN 32 UNKNOWN 33 UNKNOWN 34 UNKNOWN 35 UNKNOWN 36 UNKNOWN 37 UNKNOWN 38 UNKNOWN 39 UNKNOWN 40 UNKNOWN IV4E00 JUL 6, 2016 9:17 AM FASTRIP 775 4901 S UNION BAKERSFIELD CA93307 661-391-9387 EVR/ISD SETUP TYPE: VACUUM ASSIST VACUUM ASSIST TYPE: HEALY VAC IV4F00 JUL 6, 2016 9:17 AM FASTRIP 775 4901 S UNION BAKERSFIELD CA93307 661-391-9387 NOZZLE A/L RANGE A/L RATIO: 0.95 - 1.15 IV4000 JUL 6, 2016 9:17 AM FASTRIP 775 4901 S UNION BAKERSFIELD CA93307 661-391-9387 VAPOR PROCESSOR TYPE NONE IV4700 JUL 6, 2016 9:17 AM FASTRIP 775 4901 S UNION BAKERSFIELD CA93307 661-391-9387 ASSESSMENT TIME START TIME: 11:59 PM TIME DELAY MINUTES: 1 IV5200 JUL 6, 2016 9:17 AM FASTRIP 775 4901 S UNION BAKERSFIELD CA93307 661-391-9387 ACCEPT HIGH ORVR: NO IV4A00 JUL 6, 2016 9:17 AM FASTRIP 775 4901 S UNION BAKERSFIELD CA93307 661-391-9387 ISD HOSE TABLE HOSE FP FP AFM REL HOSE ID ID LABEL ID ID LABEL 01 01 01 01 07 BLEND3 02 02 02 01 07 BLEND3 03 03 03 02 07 BLEND3 04 04 04 02 07 BLEND3 05 05 05 03 07 BLEND3 06 06 06 03 07 BLEND3 07 07 07 04 07 BLEND3 08 08 08 04 07 BLEND3 IV4B00 JUL 6, 2016 9:17 AM FASTRIP 775 4901 S UNION BAKERSFIELD CA93307 661-391-9387 PRODUCT/HOSE MAP TABLE FP AFID M1/H1 M2/H2 M3/H3 M4/H4 01 01 02/01 09/01 03/01 xx/xx 02 01 02/02 03/02 09/02 xx/xx 03 02 02/03 03/03 09/03 xx/xx 04 02 02/04 03/04 09/04 xx/xx 05 03 02/05 03/05 09/05 xx/xx 06 03 02/06 03/06 09/06 xx/xx 07 04 02/07 03/07 09/07 xx/xx 08 04 02/08 03/08 09/08 xx/xx IV4900 JUL 6, 2016 9:17 AM FASTRIP 775 4901 S UNION BAKERSFIELD CA93307 661-391-9387 LABEL TABLE ID LABEL 01 UNASSIGNED 02 BLEND3 03 REGULAR 04 MID GRADE 05 PREMIUM 06 GOLD 07 BRONZE 08 SILVER 09 BLEND2 10 BLEND4 IV1000 JUL 6, 2016 9:17 AM ISD VERSION: 01.05 PRE MONITOR CERT Responses Received: 200 FASTRIP 775 4901 S UNION BAKERSFIELD CA93307 661-391-9387 JUL 6, 2016 9:15 AM TANK PRODUCT GALLONS INCHES WATER DEG F ULLAGE 1 UNLEADED 1 5289 43.44 0.0 82.8 6743 2 UNLEADED 2 5610 45.46 0.0 83.1 6422 3 PREMIUM 4534 38.66 1.0 83.4 7497 4 DIESEL 3134 29.47 0.0 85.6 8898 I90500 JUL 6, 2016 9:15 AM SOFTWARE REVISION LEVEL VERSION 334.00 SOFTWARE# 346334-100-A CREATED - 15.05.29.10.36 S-MODULE# 330160-004-a SYSTEM FEATURES: PERIODIC IN-TANK TESTS ANNUAL IN-TANK TESTS ISD/APM I50500 JUL 6, 2016 9:15 AM SYSTEM TYPE AND LANGUAGE FLAG SYSTEM UNITS U.S. SYSTEM LANGUAGE ENGLISH SYSTEM DATE/TIME FORMAT MON DD YYYY HH:MM:SS xM I50201 JUL 6, 2016 9:15 AM SHIFT TIME 1 : 6:00 AM I50202 JUL 6, 2016 9:15 AM SHIFT TIME 2 : DISABLED I50203 JUL 6, 2016 9:15 AM SHIFT TIME 3 : DISABLED I50204 JUL 6, 2016 9:15 AM SHIFT TIME 4 : DISABLED I54600 JUL 6, 2016 9:15 AM TANK PER TST NEEDED WRN: DISABLED I54900 JUL 6, 2016 9:15 AM TANK ANN TST NEEDED WRN: DISABLED I55300 JUL 6, 2016 9:15 AM LINE RE-ENABLE METHOD PASS LINE TEST I55600 JUL 6, 2016 9:15 AM LINE PER TST NEEDED WRN: DISABLED I55900 JUL 6, 2016 9:15 AM LINE ANN TST NEEDED WRN: DISABLED I50D00 JUL 6, 2016 9:15 AM PRINT TC VOLUMES ENABLED I50E00 JUL 6, 2016 9:15 AM TEMP COMPENSATION VALUE (DEG F ): 60.0 I60B00 JUL 6, 2016 9:15 AM STICK HEIGHT OFFSET ENABLE STATUS DISABLED I51400 JUL 6, 2016 9:15 AM H-PROTOCOL DATA FORMAT HEIGHT I51A01 JUL 6, 2016 9:15 AM DAYLIGHT SAVING TIME ENABLED ON I51B00 JUL 6, 2016 9:15 AM DAYLIGHT SAVING TIME START DATE APR WEEK 1 SUN 2:00 AM END DATE OCT WEEK 6 SUN 2:00 AM I51600 JUL 6, 2016 9:15 AM RE-DIRECT LOCAL PRINTOUT DISABLED I50400 JUL 6, 2016 9:15 AM 232 SECURITY CODE PORT SECURITY CODE STATUS 1 000000 DISABLED 2 000000 DISABLED 3 000000 DISABLED 4 000000 DISABLED 5 000000 DISABLED 6 000000 DISABLED I21900 JUL 6, 2016 9:15 AM TANK CHART SECURITY DISABLED I5BD00 JUL 6, 2016 9:15 AM CUSTOM ALARM LABELS DISABLED I56000 JUL 6, 2016 9:15 AM MASS/DENSITY DISABLED I88101 JUL 6, 2016 9:15 AM PORT SETTINGS: COMM BOARD : 1 (EDIM ) RS-232 SECURITY CODE : DISABLED I88102 JUL 6, 2016 9:15 AM PORT SETTINGS: COMM BOARD : 2 (RS-232) BAUD RATE : 9600 PARITY : NONE STOP BIT : 1 STOP DATA LENGTH: 8 DATA RS-232 SECURITY CODE : DISABLED I88103 JUL 6, 2016 9:15 AM PORT SETTINGS: COMM BOARD : 3 (RS-232) BAUD RATE : 9600 PARITY : NONE STOP BIT : 2 STOP DATA LENGTH: 8 DATA RS-232 SECURITY CODE : DISABLED I88104 JUL 6, 2016 9:15 AM I88105 JUL 6, 2016 9:15 AM I88106 JUL 6, 2016 9:15 AM I52000 JUL 6, 2016 9:15 AM RECEIVER AUTO DIAL TYPE & START TIME RCVR LOCATION LABEL DIAL TYPE START TIME 1 ON DATE APR 8, 2016 DISABLED 2 ON DATE APR 8, 2016 DISABLED 3 ON DATE APR 8, 2016 DISABLED 4 ON DATE APR 8, 2016 DISABLED 5 ON DATE APR 8, 2016 DISABLED 6 ON DATE APR 8, 2016 DISABLED 7 ON DATE APR 8, 2016 DISABLED 8 ON DATE APR 8, 2016 DISABLED I60100 JUL 6, 2016 9:15 AM TANK CONFIGURATION DEVICE LABEL CONFIGURED 1 UNLEADED 1 ON 2 UNLEADED 2 ON 3 PREMIUM ON 4 DIESEL ON I60200 JUL 6, 2016 9:16 AM TANK PRODUCT LABEL TANK PRODUCT LABEL 1 UNLEADED 1 2 UNLEADED 2 3 PREMIUM 4 DIESEL I60300 JUL 6, 2016 9:16 AM TANK PRODUCT CODE TANK PRODUCT LABEL 1 UNLEADED 1 1 2 UNLEADED 2 2 3 PREMIUM 3 4 DIESEL 4 I60900 JUL 6, 2016 9:16 AM TANK THERMAL COEFFICIENT TANK PRODUCT LABEL 1 UNLEADED 1 0.000700 2 UNLEADED 2 0.000700 3 PREMIUM 0.000700 4 DIESEL 0.000450 I60700 JUL 6, 2016 9:16 AM TANK DIAMETER TANK PRODUCT LABEL INCHES 1 UNLEADED 1 96.00 2 UNLEADED 2 96.00 3 PREMIUM 96.00 4 DIESEL 96.00 I60A00 JUL 6, 2016 9:16 AM TANK FULL VOLUME TANK PRODUCT LABEL TANK PROFILE GALLONS 1 UNLEADED 1 1 PT 12032 2 UNLEADED 2 1 PT 12032 3 PREMIUM 1 PT 12031 4 DIESEL 1 PT 12032 I60400 JUL 6, 2016 9:16 AM TANK FULL VOLUME TANK PRODUCT LABEL GALLONS 1 UNLEADED 1 12032 2 UNLEADED 2 12032 3 PREMIUM 12031 4 DIESEL 12032 I60500 JUL 6, 2016 9:16 AM TANK 4 POINT VOLUMES TANK PRODUCT LABEL GALLONS 1 UNLEADED 1 12032 0 0 0 2 UNLEADED 2 12032 0 0 0 3 PREMIUM 12031 0 0 0 4 DIESEL 12032 0 0 0 I60600 JUL 6, 2016 9:16 AM TANK 20 POINT VOLUMES TANK PRODUCT LABEL GALLONS 1 UNLEADED 1 12032 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 2 UNLEADED 2 12032 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 3 PREMIUM 12031 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 4 DIESEL 12032 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 I61500 JUL 6, 2016 9:16 AM TANK PRODUCT LABEL METER DATA 1 UNLEADED 1 NO 2 UNLEADED 2 NO 3 PREMIUM NO 4 DIESEL NO I62F00 JUL 6, 2016 9:16 AM MAG PROBE FLOAT SIZE TANK PRODUCT LABEL FLOAT SIZE: 1 UNLEADED 1 4.0 IN. 2 UNLEADED 2 4.0 IN. 3 PREMIUM 4.0 IN. 4 DIESEL 4.0 IN. I62700 JUL 6, 2016 9:16 AM TANK HIGH WATER WARNING LIMIT TANK PRODUCT LABEL INCHES 1 UNLEADED 1 2.0 2 UNLEADED 2 2.0 3 PREMIUM 2.0 4 DIESEL 2.0 I64200 JUL 6, 2016 9:16 AM WATER ALARM FILTER TANK PRODUCT LABEL 1 UNLEADED 1 LOW 2 UNLEADED 2 LOW 3 PREMIUM LOW 4 DIESEL LOW I62400 JUL 6, 2016 9:16 AM TANK HIGH WATER LEVEL LIMIT TANK PRODUCT LABEL INCHES 1 UNLEADED 1 3.0 2 UNLEADED 2 3.0 3 PREMIUM 3.0 4 DIESEL 3.0 I62800 JUL 6, 2016 9:16 AM TANK MAXIMUM VOLUME LIMIT TANK PRODUCT LABEL GALLONS 1 UNLEADED 1 12032 2 UNLEADED 2 12032 3 PREMIUM 12031 4 DIESEL 12032 I62300 JUL 6, 2016 9:16 AM TANK OVERFILL LEVEL LIMIT TANK PRODUCT LABEL GALLONS 1 UNLEADED 1 10829 2 UNLEADED 2 10829 3 PREMIUM 10828 4 DIESEL 10829 I62200 JUL 6, 2016 9:16 AM TANK HIGH PRODUCT LIMIT TANK PRODUCT LABEL GALLONS 1 UNLEADED 1 11430 2 UNLEADED 2 11430 3 PREMIUM 11429 4 DIESEL 11430 I62900 JUL 6, 2016 9:16 AM TANK DELIVERY REQUIRED LIMIT TANK PRODUCT LABEL GALLONS 1 UNLEADED 1 1805 2 UNLEADED 2 1805 3 PREMIUM 1805 4 DIESEL 1805 I62100 JUL 6, 2016 9:16 AM TANK LOW PRODUCT LIMIT TANK PRODUCT LABEL GALLONS 1 UNLEADED 1 500 2 UNLEADED 2 500 3 PREMIUM 500 4 DIESEL 500 I62600 JUL 6, 2016 9:16 AM TANK LEAK ALARM LIMIT TANK PRODUCT LABEL GALLONS 1 UNLEADED 1 99 2 UNLEADED 2 99 3 PREMIUM 99 4 DIESEL 99 I62500 JUL 6, 2016 9:16 AM TANK SUDDEN LOSS LIMIT TANK PRODUCT LABEL GALLONS 1 UNLEADED 1 99 2 UNLEADED 2 99 3 PREMIUM 99 4 DIESEL 99 I60800 JUL 6, 2016 9:16 AM TANK TILT TANK PRODUCT LABEL INCHES 1 UNLEADED 1 7.33 2 UNLEADED 2 0.00 3 PREMIUM 2.67 4 DIESEL 3.75 I60B00 JUL 6, 2016 9:16 AM STICK HEIGHT OFFSET ENABLE STATUS DISABLED I60C00 JUL 6, 2016 9:16 AM TANK STICK HEIGHT OFFSET TANK PRODUCT LABEL INCHES 1 UNLEADED 1 0.00 2 UNLEADED 2 0.00 3 PREMIUM 0.00 4 DIESEL 0.00 I61200 JUL 6, 2016 9:16 AM TANK MANIFOLDED PARTNERS TANK PRODUCT LABEL SIPHON MANIFOLDED TANKS LINE MANIFOLDED TANKS 1 UNLEADED 1 2 NONE 2 UNLEADED 2 1 NONE 3 PREMIUM NONE NONE 4 DIESEL NONE NONE I63600 JUL 6, 2016 9:16 AM PERIODIC LEAK TEST MIN VOLUME TANK PRODUCT LABEL GALLONS 1 UNLEADED 1 120 2 UNLEADED 2 120 3 PREMIUM 120 4 DIESEL 120 I62A00 JUL 6, 2016 9:16 AM ANNUAL LEAK TEST MIN VOLUME TANK PRODUCT LABEL GALLONS 1 UNLEADED 1 120 2 UNLEADED 2 120 3 PREMIUM 120 4 DIESEL 120 I62C00 JUL 6, 2016 9:16 AM TANK PERIODIC TEST TYPE TANK PRODUCT LABEL PERIODIC TEST TYPE 1 UNLEADED 1 STANDARD 2 UNLEADED 2 STANDARD 3 PREMIUM STANDARD 4 DIESEL STANDARD I62D00 JUL 6, 2016 9:16 AM TANK LEAK TEST FAIL ALARMS TANK PRODUCT LABEL 1 UNLEADED 1 GROSS TEST FAIL ALARM DISABLED PERIODIC TEST FAIL ALARM DISABLED ANNUAL TEST FAIL ALARM DISABLED 2 UNLEADED 2 GROSS TEST FAIL ALARM DISABLED PERIODIC TEST FAIL ALARM DISABLED ANNUAL TEST FAIL ALARM DISABLED 3 PREMIUM GROSS TEST FAIL ALARM DISABLED PERIODIC TEST FAIL ALARM DISABLED ANNUAL TEST FAIL ALARM DISABLED 4 DIESEL GROSS TEST FAIL ALARM DISABLED PERIODIC TEST FAIL ALARM DISABLED ANNUAL TEST FAIL ALARM DISABLED I63100 JUL 6, 2016 9:16 AM TANK LEAK TEST AVERAGING TANK PRODUCT LABEL ANNUAL PERIODIC 1 UNLEADED 1 OFF OFF 2 UNLEADED 2 OFF OFF 3 PREMIUM OFF OFF 4 DIESEL OFF OFF I63000 JUL 6, 2016 9:16 AM IN-TANK LEAK TEST NOTIFY TANK PRODUCT LABEL TANK TEST NOTIFY: 1 UNLEADED 1 OFF 2 UNLEADED 2 OFF 3 PREMIUM OFF 4 DIESEL OFF I63200 JUL 6, 2016 9:16 AM TANK TEST SIPHON BREAK TANK PRODUCT LABEL SIPHON BREAK 1 UNLEADED 1 OFF 2 UNLEADED 2 OFF 3 PREMIUM OFF 4 DIESEL OFF I61000 JUL 6, 2016 9:16 AM TANK DELIVERY DELAY TANK PRODUCT LABEL 1 UNLEADED 1 1 2 UNLEADED 2 1 3 PREMIUM 1 4 DIESEL 1 I63A00 JUL 6, 2016 9:16 AM LOW LEVEL PUMP THRESHOLD FOR SEQUENTIAL LINE MANIFOLD TANK PRODUCT LABEL PUMP THRESHOLD 1 UNLEADED 1 10.00% 2 UNLEADED 2 10.00% 3 PREMIUM 10.00% 4 DIESEL 10.00% I61100 JUL 6, 2016 9:16 AM LEAK TEST METHOD - - - - - - - - - - - - TEST ON DATE : ALL TANK APR 8, 2016 START TIME : DISABLED TEST RATE :0.20 GAL/HR DURATION : 2 HOURS TST EARLY STOP:DISABLED I61300 JUL 6, 2016 9:16 AM CSLD PROBABLITY OF DETECTION I61400 JUL 6, 2016 9:16 AM CSLD CLIMATE FACTOR I61600 JUL 6, 2016 9:16 AM TANK PRODUCT LABEL CAL UPDATE 1 UNLEADED 1 IMMEDIATE 2 UNLEADED 2 IMMEDIATE 3 PREMIUM IMMEDIATE 4 DIESEL IMMEDIATE I61A00 JUL 6, 2016 9:16 AM IN-TANK LEAK TEST EARLY STOP TANK PRODUCT LABEL TST EARLY STOP: 1 UNLEADED 1 DISABLED 2 UNLEADED 2 DISABLED 3 PREMIUM DISABLED 4 DIESEL DISABLED I61B00 JUL 6, 2016 9:16 AM IN-TANK LEAK GROSS TEST AUTO-CONFIRM I61C00 JUL 6, 2016 9:16 AM CSLD REPORT ONLY I62B00 JUL 6, 2016 9:16 AM TANK LAST ANNUAL TEST TANK PRODUCT LABEL DATE 1 UNLEADED 1 ??? 0, 0 2 UNLEADED 2 ??? 0, 0 3 PREMIUM ??? 0, 0 4 DIESEL ??? 0, 0 I63300 JUL 6, 2016 9:16 AM LEAK TEST REPORT FORMAT: NORMAL I63400 JUL 6, 2016 9:16 AM RECONCILIATION WARNING LIMIT TANK PRODUCT LABEL GALLONS 1 UNLEADED 1 0 2 UNLEADED 2 0 3 PREMIUM 0 4 DIESEL 0 I63500 JUL 6, 2016 9:16 AM RECONCILIATION ALARM LIMIT TANK PRODUCT LABEL GALLONS 1 UNLEADED 1 1 2 UNLEADED 2 1 3 PREMIUM 1 4 DIESEL 1 I63900 JUL 6, 2016 9:16 AM ACCU CHART END SHAPE FACTOR TANK PRODUCT LABEL 1 UNLEADED 1 END FACTOR: NONE 2 UNLEADED 2 END FACTOR: NONE 3 PREMIUM END FACTOR: NONE 4 DIESEL END FACTOR: NONE I78000 JUL 6, 2016 9:16 AM I77700 JUL 6, 2016 9:16 AM I77800 JUL 6, 2016 9:16 AM I78C00 JUL 6, 2016 9:16 AM I78300 JUL 6, 2016 9:16 AM I78F00 JUL 6, 2016 9:16 AM I78700 JUL 6, 2016 9:16 AM I70200 JUL 6, 2016 9:16 AM LIQUID LABEL DEVICE LABEL 1 UNL 1 STP 2 UNL 1 ANN 3 UNL 2 STP 4 UNL 2 ANN 5 PNL STP 6 PNL ANN 7 DSL STP 8 DSL ANN 9 DISP 1-2 10 DISP 3-4 11 DISP 5-6 12 DISP 7-8 13 N. TRANS SUMP 14 S. TRANS SUMP 15 16 I70300 JUL 6, 2016 9:16 AM LIQUID TYPE SENSOR LOCATION TYPE 1 UNL 1 STP TRI-STATE (SINGLE FLOAT) 2 UNL 1 ANN TRI-STATE (SINGLE FLOAT) 3 UNL 2 STP TRI-STATE (SINGLE FLOAT) 4 UNL 2 ANN TRI-STATE (SINGLE FLOAT) 5 PNL STP TRI-STATE (SINGLE FLOAT) 6 PNL ANN TRI-STATE (SINGLE FLOAT) 7 DSL STP TRI-STATE (SINGLE FLOAT) 8 DSL ANN TRI-STATE (SINGLE FLOAT) 9 DISP 1-2 TRI-STATE (SINGLE FLOAT) 10 DISP 3-4 TRI-STATE (SINGLE FLOAT) 11 DISP 5-6 TRI-STATE (SINGLE FLOAT) 12 DISP 7-8 TRI-STATE (SINGLE FLOAT) 13 N. TRANS SUMP TRI-STATE (SINGLE FLOAT) 14 S. TRANS SUMP TRI-STATE (SINGLE FLOAT) 15 TRI-STATE (SINGLE FLOAT) 16 TRI-STATE (SINGLE FLOAT) I70400 JUL 6, 2016 9:16 AM LIQUID CATEGORY SENSOR LOCATION CATEGORY 1 UNL 1 STP STP SUMP 2 UNL 1 ANN ANNULAR SPACE 3 UNL 2 STP STP SUMP 4 UNL 2 ANN ANNULAR SPACE 5 PNL STP STP SUMP 6 PNL ANN ANNULAR SPACE 7 DSL STP STP SUMP 8 DSL ANN ANNULAR SPACE 9 DISP 1-2 DISPENSER PAN 10 DISP 3-4 OTHER SENSORS 11 DISP 5-6 DISPENSER PAN 12 DISP 7-8 DISPENSER PAN 13 N. TRANS SUMP PIPING SUMP 14 S. TRANS SUMP PIPING SUMP 15 OTHER SENSORS 16 OTHER SENSORS I74200 JUL 6, 2016 9:16 AM I74300 JUL 6, 2016 9:16 AM I74400 JUL 6, 2016 9:16 AM I74700 JUL 6, 2016 9:16 AM I74800 JUL 6, 2016 9:16 AM I74900 JUL 6, 2016 9:16 AM I7BC00 JUL 6, 2016 9:16 AM I80200 JUL 6, 2016 9:16 AM I80300 JUL 6, 2016 9:16 AM I80400 JUL 6, 2016 9:16 AM I80700 JUL 6, 2016 9:16 AM RELAY LABEL DEVICE LABEL 1 OVERFILL 2 OVERFILL 3 PNL 4 5 UNL 1 6 PNL 7 DSL 8 I80900 JUL 6, 2016 9:16 AM RELAY ORIENTATION RELAY DESIGNATION ORIENTATION 1 OVERFILL NORMALLY OPEN 2 OVERFILL NORMALLY OPEN 3 PNL NORMALLY CLOSED 4 NORMALLY OPEN 5 UNL 1 NORMALLY CLOSED 6 PNL NORMALLY CLOSED 7 DSL NORMALLY CLOSED 8 NORMALLY OPEN I80B00 JUL 6, 2016 9:16 AM RELAY TANK ASSIGNMENT RELAY DESIGNATION TANK 1 OVERFILL NONE 2 OVERFILL NONE 3 PNL NONE 4 NONE 5 UNL 1 1 6 PNL NONE 7 DSL NONE 8 NONE I80A00 JUL 6, 2016 9:16 AM RELAY TYPE RELAY DESIGNATION TYPE 1 OVERFILL STANDARD 2 OVERFILL STANDARD 3 PNL STANDARD 4 STANDARD 5 UNL 1 STANDARD 6 PNL STANDARD 7 DSL STANDARD 8 STANDARD I80C00 JUL 6, 2016 9:16 AM I80800 JUL 6, 2016 9:16 AM RELAY SETUP REPORT R 1:OVERFILL TYPE: STANDARD NORMALLY OPEN TANK #: NONE IN-TANK ALARMS ALL:LEAK ALARM ALL:OVERFILL ALARM ALL:HIGH PRODUCT ALARM R 2:OVERFILL TYPE: STANDARD NORMALLY OPEN TANK #: NONE IN-TANK ALARMS ALL:OVERFILL ALARM ALL:HIGH PRODUCT ALARM R 3:PNL TYPE: STANDARD NORMALLY CLOSED TANK #: NONE LIQUID SENSOR ALMS L 5:FUEL ALARM L 9:FUEL ALARM L10:FUEL ALARM L11:FUEL ALARM L12:FUEL ALARM L 6:SENSOR OUT ALARM L 9:SENSOR OUT ALARM L10:SENSOR OUT ALARM L11:SENSOR OUT ALARM L12:SENSOR OUT ALARM L 6:SHORT ALARM L 9:SHORT ALARM L10:SHORT ALARM L11:SHORT ALARM L12:SHORT ALARM ISD SITE ALARMS ISD GROSS PRES FAIL ISD DEGRD PRES FAIL ISD VAPOR LEAK FAIL ISD VP PRES FAIL ISD VP STATUS FAIL ISD HOSE ALARMS ALL:GROSS COLLECT FAIL ALL:DEGRD COLLECT FAIL ALL:FLOW COLLECT FAIL R 4: TYPE: STANDARD NORMALLY OPEN TANK #: NONE - NO ALARM ASSIGNMENTS - R 5:UNL 1 TYPE: STANDARD NORMALLY CLOSED TANK #: 1 LIQUID SENSOR ALMS L 1:FUEL ALARM L 3:FUEL ALARM L 9:FUEL ALARM L10:FUEL ALARM L11:FUEL ALARM L12:FUEL ALARM L 1:SENSOR OUT ALARM L 3:SENSOR OUT ALARM L 9:SENSOR OUT ALARM L10:SENSOR OUT ALARM L11:SENSOR OUT ALARM L12:SENSOR OUT ALARM L 1:SHORT ALARM L 3:SHORT ALARM L 9:SHORT ALARM L10:SHORT ALARM L11:SHORT ALARM L12:SHORT ALARM L13:SHORT ALARM ISD SITE ALARMS ISD GROSS PRES FAIL ISD DEGRD PRES FAIL ISD VAPOR LEAK FAIL ISD VP PRES FAIL ISD VP STATUS FAIL ISD SETUP FAIL ISD HOSE ALARMS ALL:GROSS COLLECT FAIL ALL:DEGRD COLLECT FAIL ALL:FLOW COLLECT FAIL PMC ALARMS VP PRESSURE FAIL VP DUTY CYCLE FAIL PMC SETUP FAIL R 6:PNL TYPE: STANDARD NORMALLY CLOSED TANK #: NONE LIQUID SENSOR ALMS L 5:FUEL ALARM L 9:FUEL ALARM L10:FUEL ALARM L11:FUEL ALARM L12:FUEL ALARM L 6:SENSOR OUT ALARM L 9:SENSOR OUT ALARM L10:SENSOR OUT ALARM L11:SENSOR OUT ALARM L12:SENSOR OUT ALARM L 6:SHORT ALARM L 9:SHORT ALARM L10:SHORT ALARM L11:SHORT ALARM L12:SHORT ALARM ISD SITE ALARMS ISD GROSS PRES FAIL ISD DEGRD PRES FAIL ISD VAPOR LEAK FAIL ISD VP PRES FAIL ISD VP STATUS FAIL ISD HOSE ALARMS ALL:GROSS COLLECT FAIL ALL:DEGRD COLLECT FAIL ALL:FLOW COLLECT FAIL PMC ALARMS VP EMISSIONS FAIL VP PRESSURE FAIL VP DUTY CYCLE FAIL PMC SETUP FAIL R 7:DSL TYPE: STANDARD NORMALLY CLOSED TANK #: NONE LIQUID SENSOR ALMS L 7:FUEL ALARM L 9:FUEL ALARM L10:FUEL ALARM L11:FUEL ALARM L12:FUEL ALARM L13:FUEL ALARM L14:FUEL ALARM L 7:SENSOR OUT ALARM L 9:SENSOR OUT ALARM L10:SENSOR OUT ALARM L11:SENSOR OUT ALARM L12:SENSOR OUT ALARM L13:SENSOR OUT ALARM L 7:SHORT ALARM L 9:SHORT ALARM L10:SHORT ALARM L11:SHORT ALARM L12:SHORT ALARM L13:SHORT ALARM ISD SITE ALARMS ISD GROSS PRES FAIL ISD DEGRD PRES FAIL ISD VAPOR LEAK FAIL ISD VP PRES FAIL ISD VP STATUS FAIL ISD HOSE ALARMS ALL:GROSS COLLECT FAIL ALL:DEGRD COLLECT FAIL ALL:FLOW COLLECT FAIL PMC ALARMS VP EMISSIONS FAIL VP PRESSURE FAIL VP DUTY CYCLE FAIL PMC SETUP FAIL R 8: TYPE: STANDARD NORMALLY OPEN TANK #: NONE - NO ALARM ASSIGNMENTS - I79000 JUL 6, 2016 9:17 AM EDIM:1 VR:349634-003-C TD:06.05.11.11.15 I79100 JUL 6, 2016 9:17 AM I72300 JUL 6, 2016 9:17 AM FASTRIP 775 4901 S UNION BAKERSFIELD CA93307 661-391-9387 SMARTSENSOR ASSIGNMENT DEVICE LABEL CATEGORY 01 PS 3-4 VAPOR PRESSURE 02 FM 1-2 AIR FLOW METER 03 FM 3-4 AIR FLOW METER 04 FM 5-6 AIR FLOW METER 05 FM 7-8 AIR FLOW METER 06 UNKNOWN 07 UNKNOWN 08 UNKNOWN 09 UNKNOWN 10 UNKNOWN 11 UNKNOWN 12 UNKNOWN 13 UNKNOWN 14 UNKNOWN 15 UNKNOWN 16 UNKNOWN 17 UNKNOWN 18 UNKNOWN 19 UNKNOWN 20 UNKNOWN 21 UNKNOWN 22 UNKNOWN 23 UNKNOWN 24 UNKNOWN 25 UNKNOWN 26 UNKNOWN 27 UNKNOWN 28 UNKNOWN 29 UNKNOWN 30 UNKNOWN 31 UNKNOWN 32 UNKNOWN 33 UNKNOWN 34 UNKNOWN 35 UNKNOWN 36 UNKNOWN 37 UNKNOWN 38 UNKNOWN 39 UNKNOWN 40 UNKNOWN IV4E00 JUL 6, 2016 9:17 AM FASTRIP 775 4901 S UNION BAKERSFIELD CA93307 661-391-9387 EVR/ISD SETUP TYPE: VACUUM ASSIST VACUUM ASSIST TYPE: HEALY VAC IV4F00 JUL 6, 2016 9:17 AM FASTRIP 775 4901 S UNION BAKERSFIELD CA93307 661-391-9387 NOZZLE A/L RANGE A/L RATIO: 0.95 - 1.15 IV4000 JUL 6, 2016 9:17 AM FASTRIP 775 4901 S UNION BAKERSFIELD CA93307 661-391-9387 VAPOR PROCESSOR TYPE NONE IV4700 JUL 6, 2016 9:17 AM FASTRIP 775 4901 S UNION BAKERSFIELD CA93307 661-391-9387 ASSESSMENT TIME START TIME: 11:59 PM TIME DELAY MINUTES: 1 IV5200 JUL 6, 2016 9:17 AM FASTRIP 775 4901 S UNION BAKERSFIELD CA93307 661-391-9387 ACCEPT HIGH ORVR: NO IV4A00 JUL 6, 2016 9:17 AM FASTRIP 775 4901 S UNION BAKERSFIELD CA93307 661-391-9387 ISD HOSE TABLE HOSE FP FP AFM REL HOSE ID ID LABEL ID ID LABEL 01 01 01 01 07 BLEND3 02 02 02 01 07 BLEND3 03 03 03 02 07 BLEND3 04 04 04 02 07 BLEND3 05 05 05 03 07 BLEND3 06 06 06 03 07 BLEND3 07 07 07 04 07 BLEND3 08 08 08 04 07 BLEND3 IV4B00 JUL 6, 2016 9:17 AM FASTRIP 775 4901 S UNION BAKERSFIELD CA93307 661-391-9387 PRODUCT/HOSE MAP TABLE FP AFID M1/H1 M2/H2 M3/H3 M4/H4 01 01 02/01 09/01 03/01 xx/xx 02 01 02/02 03/02 09/02 xx/xx 03 02 02/03 03/03 09/03 xx/xx 04 02 02/04 03/04 09/04 xx/xx 05 03 02/05 03/05 09/05 xx/xx 06 03 02/06 03/06 09/06 xx/xx 07 04 02/07 03/07 09/07 xx/xx 08 04 02/08 03/08 09/08 xx/xx IV4900 JUL 6, 2016 9:17 AM FASTRIP 775 4901 S UNION BAKERSFIELD CA93307 661-391-9387 LABEL TABLE ID LABEL 01 UNASSIGNED 02 BLEND3 03 REGULAR 04 MID GRADE 05 PREMIUM 06 GOLD 07 BRONZE 08 SILVER 09 BLEND2 10 BLEND4 IV1000 JUL 6, 2016 9:17 AM ISD VERSION: 01.05 POST MONITOR CERT Responses Received: I10200 JUL 6, 2016 3:39 PM FASTRIP 775 4901 S UNION BAKERSFIELD CA93307 661-391-9387 SYSTEM CONFIGURATION SLOT BOARD TYPE POWER ON RESET CURRENT 1 8SMARTSENSOR BD 39334 39176 2 4 PROBE / G.T. 163624 163036 3 INTERSTITIAL BD 202241 201650 4 INTERSTITIAL BD 201618 201260 5 UNUSED 10065686 9827770 6 UNUSED 10026804 9817437 7 UNUSED 10019950 9810365 8 UNUSED 10013054 9809241 9 RELAY BOARD 14936 14918 10 RELAY BOARD 14957 14941 11 UNUSED 10031584 9821125 12 UNUSED 10015933 9807796 13 UNUSED 10001969 9809338 14 UNUSED 10004553 9815661 15 UNUSED 10003934 9811607 16 UNUSED 9996247 9805108 COMM 1 ELEC DISP INT. 101008 101079 COMM 2 RS232 SERIAL BD 15000 15007 COMM 3 RS232 SERIAL BD 14936 14918 COMM 4 UNUSED 10014994 9825818 COMM 5 UNUSED 10008845 9814846 COMM 6 UNUSED 10002439 9810131 I90200 JUL 6, 2016 3:39 PM SOFTWARE REVISION LEVEL VERSION 334.00 SOFTWARE# 346334-100-A CREATED - 15.05.29.10.36 S-MODULE# 330160-004-a SYSTEM FEATURES: PERIODIC IN-TANK TESTS ANNUAL IN-TANK TESTS ISD/APM I11100 JUL 6, 2016 3:39 PM FASTRIP 775 4901 S UNION BAKERSFIELD CA93307 661-391-9387 PRIORITY ALARM HISTORY ID CATEGORY DESCRIPTION ALARM TYPE STATE DATE TIME T 2 TANK UNLEADED 2 PROBE OUT CLEAR 7-06-16 3:38PM T 2 TANK UNLEADED 2 PROBE OUT ALARM 7-06-16 3:38PM T 2 TANK UNLEADED 2 HIGH WATER ALARM CLEAR 7-06-16 3:37PM T 2 TANK UNLEADED 2 MAX PRODUCT ALARM CLEAR 7-06-16 3:33PM T 2 TANK UNLEADED 2 OVERFILL ALARM CLEAR 7-06-16 3:33PM T 2 TANK UNLEADED 2 MAX PRODUCT ALARM ALARM 7-06-16 3:31PM T 2 TANK UNLEADED 2 OVERFILL ALARM ALARM 7-06-16 3:31PM T 2 TANK UNLEADED 2 HIGH WATER ALARM ALARM 7-06-16 3:30PM T 2 TANK UNLEADED 2 HIGH WATER ALARM CLEAR 7-06-16 3:23PM T 2 TANK UNLEADED 2 HIGH WATER ALARM ALARM 7-06-16 3:20PM T 2 TANK UNLEADED 2 HIGH WATER ALARM CLEAR 7-06-16 3:19PM T 2 TANK UNLEADED 2 PROBE OUT CLEAR 7-06-16 3:17PM T 2 TANK UNLEADED 2 PROBE OUT ALARM 7-06-16 3:15PM T 2 TANK UNLEADED 2 HIGH WATER ALARM ALARM 7-06-16 3:07PM T 2 TANK UNLEADED 2 PROBE OUT CLEAR 7-06-16 3:04PM T 1 TANK UNLEADED 1 PROBE OUT CLEAR 7-06-16 3:04PM T 1 TANK UNLEADED 1 PROBE OUT ALARM 7-06-16 3:03PM T 2 TANK UNLEADED 2 PROBE OUT ALARM 7-06-16 3:03PM T 2 TANK UNLEADED 2 HIGH WATER ALARM CLEAR 7-06-16 3:00PM T 2 TANK UNLEADED 2 HIGH WATER ALARM ALARM 7-06-16 2:57PM T 2 TANK UNLEADED 2 HIGH WATER ALARM CLEAR 7-06-16 2:57PM T 2 TANK UNLEADED 2 PROBE OUT CLEAR 7-06-16 2:56PM T 2 TANK UNLEADED 2 PROBE OUT ALARM 7-06-16 2:53PM T 2 TANK UNLEADED 2 HIGH WATER ALARM ALARM 7-06-16 2:49PM T 2 TANK UNLEADED 2 PROBE OUT CLEAR 7-06-16 2:44PM L 8 ANNULAR DSL ANN SENSOR OUT ALARM CLEAR 7-06-16 12:54PM L 7 STP SUMP DSL STP SENSOR OUT ALARM CLEAR 7-06-16 12:54PM L 6 ANNULAR PNL ANN SENSOR OUT ALARM CLEAR 7-06-16 12:54PM L 5 STP SUMP PNL STP SENSOR OUT ALARM CLEAR 7-06-16 12:54PM L 4 ANNULAR UNL 2 ANN SENSOR OUT ALARM CLEAR 7-06-16 12:54PM L 3 STP SUMP UNL 2 STP SENSOR OUT ALARM CLEAR 7-06-16 12:54PM L 2 ANNULAR UNL 1 ANN SENSOR OUT ALARM CLEAR 7-06-16 12:54PM L12 DISP PAN DISP 7-8 SENSOR OUT ALARM CLEAR 7-06-16 12:54PM L11 DISP PAN DISP 5-6 SENSOR OUT ALARM CLEAR 7-06-16 12:54PM L 1 STP SUMP UNL 1 STP SENSOR OUT ALARM CLEAR 7-06-16 12:54PM L10 OTHER DISP 3-4 SENSOR OUT ALARM CLEAR 7-06-16 12:54PM L 9 DISP PAN DISP 1-2 SENSOR OUT ALARM CLEAR 7-06-16 12:54PM L14 PIPE S. TRANS SUMP SENSOR OUT ALARM CLEAR 7-06-16 12:54PM L13 PIPE N. TRANS SUMP SENSOR OUT ALARM CLEAR 7-06-16 12:54PM L 4 ANNULAR UNL 2 ANN SENSOR OUT ALARM ALARM 7-06-16 12:54PM L 3 STP SUMP UNL 2 STP SENSOR OUT ALARM ALARM 7-06-16 12:54PM L 8 ANNULAR DSL ANN SENSOR OUT ALARM ALARM 7-06-16 12:54PM L 7 STP SUMP DSL STP SENSOR OUT ALARM ALARM 7-06-16 12:54PM L 2 ANNULAR UNL 1 ANN SENSOR OUT ALARM ALARM 7-06-16 12:53PM L 1 STP SUMP UNL 1 STP SENSOR OUT ALARM ALARM 7-06-16 12:53PM L12 DISP PAN DISP 7-8 SENSOR OUT ALARM ALARM 7-06-16 12:53PM L 6 ANNULAR PNL ANN SENSOR OUT ALARM ALARM 7-06-16 12:53PM L11 DISP PAN DISP 5-6 SENSOR OUT ALARM ALARM 7-06-16 12:53PM L 5 STP SUMP PNL STP SENSOR OUT ALARM ALARM 7-06-16 12:53PM L10 OTHER DISP 3-4 SENSOR OUT ALARM ALARM 7-06-16 12:53PM I11200 JUL 6, 2016 3:39 PM FASTRIP 775 4901 S UNION BAKERSFIELD CA93307 661-391-9387 NON-PRIORITY ALARM HISTORY ID CATEGORY DESCRIPTION ALARM TYPE STATE DATE TIME T 2 TANK UNLEADED 2 LOW TEMP WARNING CLEAR 7-06-16 3:38PM T 2 TANK UNLEADED 2 LOW TEMP WARNING ALARM 7-06-16 3:38PM T 2 TANK UNLEADED 2 HIGH WATER WARNING CLEAR 7-06-16 3:37PM T 2 TANK UNLEADED 2 HIGH PRODUCT ALARM CLEAR 7-06-16 3:33PM T 2 TANK UNLEADED 2 HIGH PRODUCT ALARM ALARM 7-06-16 3:31PM T 2 TANK UNLEADED 2 HIGH WATER WARNING ALARM 7-06-16 3:30PM T 2 TANK UNLEADED 2 HIGH WATER WARNING CLEAR 7-06-16 3:23PM T 2 TANK UNLEADED 2 HIGH WATER WARNING ALARM 7-06-16 3:20PM T 2 TANK UNLEADED 2 HIGH WATER WARNING CLEAR 7-06-16 3:19PM T 2 TANK UNLEADED 2 HIGH WATER WARNING ALARM 7-06-16 3:07PM T 1 TANK UNLEADED 1 INVALID FUEL LEVEL CLEAR 7-06-16 3:04PM T 1 TANK UNLEADED 1 INVALID FUEL LEVEL ALARM 7-06-16 3:04PM T 2 TANK UNLEADED 2 HIGH WATER WARNING CLEAR 7-06-16 3:00PM T 2 TANK UNLEADED 2 HIGH WATER WARNING ALARM 7-06-16 2:57PM T 2 TANK UNLEADED 2 HIGH WATER WARNING CLEAR 7-06-16 2:57PM T 2 TANK UNLEADED 2 HIGH WATER WARNING ALARM 7-06-16 2:49PM T 2 TANK UNLEADED 2 DELIVERY NEEDED CLEAR 7-06-16 2:45PM T 2 TANK UNLEADED 2 INVALID FUEL LEVEL CLEAR 7-06-16 2:45PM T 2 TANK UNLEADED 2 INVALID FUEL LEVEL ALARM 7-06-16 2:45PM T 2 TANK UNLEADED 2 DELIVERY NEEDED ALARM 7-06-16 2:45PM T 4 TANK DIESEL DELIVERY NEEDED CLEAR 7-06-16 12:45PM T 4 TANK DIESEL DELIVERY NEEDED ALARM 7-06-16 12:44PM T 4 TANK DIESEL INVALID FUEL LEVEL CLEAR 7-06-16 12:44PM T 4 TANK DIESEL INVALID FUEL LEVEL ALARM 7-06-16 12:44PM T 3 TANK PREMIUM INVALID FUEL LEVEL CLEAR 7-06-16 12:42PM T 3 TANK PREMIUM INVALID FUEL LEVEL ALARM 7-06-16 12:42PM T 1 TANK UNLEADED 1 INVALID FUEL LEVEL CLEAR 7-06-16 12:39PM T 4 TANK DIESEL HIGH PRODUCT ALARM CLEAR 7-06-16 12:39PM T 1 TANK UNLEADED 1 INVALID FUEL LEVEL ALARM 7-06-16 12:39PM T 4 TANK DIESEL HIGH PRODUCT ALARM ALARM 7-06-16 12:39PM T 2 TANK UNLEADED 2 HIGH WATER WARNING CLEAR 7-06-16 12:38PM T 3 TANK PREMIUM HIGH PRODUCT ALARM CLEAR 7-06-16 12:37PM T 3 TANK PREMIUM HIGH PRODUCT ALARM ALARM 7-06-16 12:37PM T 2 TANK UNLEADED 2 HIGH PRODUCT ALARM CLEAR 7-06-16 12:36PM T 2 TANK UNLEADED 2 HIGH PRODUCT ALARM ALARM 7-06-16 12:36PM T 1 TANK UNLEADED 1 HIGH PRODUCT ALARM CLEAR 7-06-16 12:32PM T 1 TANK UNLEADED 1 HIGH PRODUCT ALARM ALARM 7-06-16 12:32PM T 2 TANK UNLEADED 2 HIGH WATER WARNING ALARM 7-06-16 12:30PM T 4 TANK DIESEL DELIVERY NEEDED CLEAR 7-06-16 12:25PM T 3 TANK PREMIUM DELIVERY NEEDED CLEAR 7-06-16 12:25PM T 4 TANK DIESEL INVALID FUEL LEVEL CLEAR 7-06-16 12:25PM T 3 TANK PREMIUM DELIVERY NEEDED ALARM 7-06-16 12:24PM T 4 TANK DIESEL INVALID FUEL LEVEL ALARM 7-06-16 12:23PM T 4 TANK DIESEL DELIVERY NEEDED ALARM 7-06-16 12:22PM OTHER ISD VAPOR LEAK WARN CLEAR 7-05-16 12:45PM OTHER ISD VAPOR LEAK WARN ALARM 7-04-16 12:00AM T 2 TANK UNLEADED 2 HIGH WATER WARNING CLEAR 7-03-16 9:17PM T 2 TANK UNLEADED 2 HIGH WATER WARNING ALARM 7-02-16 7:41PM T 1 TANK UNLEADED 1 DELIVERY NEEDED CLEAR 7-02-16 7:35PM T 1 TANK UNLEADED 1 DELIVERY NEEDED ALARM 7-02-16 5:51PM I20600 JUL 6, 2016 3:39 PM FASTRIP 775 4901 S UNION BAKERSFIELD CA93307 661-391-9387 TANK ALARM HISTORY TANK 1 UNLEADED 1 HIGH WATER ALARM JUN 3, 2016 1:07 PM OVERFILL ALARM JUN 27, 2016 1:10 PM HIGH PRODUCT ALARM JUL 6, 2016 12:32 PM INVALID FUEL LEVEL JUL 6, 2016 3:04 PM JUL 6, 2016 12:39 PM JUN 10, 2016 6:11 AM PROBE OUT JUL 6, 2016 3:03 PM JUL 6, 2016 12:38 PM JUL 6, 2016 12:27 PM HIGH WATER WARNING JUN 3, 2016 1:07 PM DELIVERY NEEDED JUL 2, 2016 5:51 PM JUN 21, 2016 3:57 PM JUN 10, 2016 3:00 AM LOW TEMP WARNING JUN 27, 2016 2:06 PM TANK 2 UNLEADED 2 HIGH WATER ALARM JUL 6, 2016 3:30 PM JUL 6, 2016 3:20 PM JUL 6, 2016 3:07 PM OVERFILL ALARM JUL 6, 2016 3:31 PM HIGH PRODUCT ALARM JUL 6, 2016 3:31 PM JUL 6, 2016 12:36 PM JUN 27, 2016 1:12 PM INVALID FUEL LEVEL JUL 6, 2016 2:45 PM JUN 27, 2016 3:36 PM PROBE OUT JUL 6, 2016 3:38 PM JUL 6, 2016 3:15 PM JUL 6, 2016 3:03 PM HIGH WATER WARNING JUL 6, 2016 3:30 PM JUL 6, 2016 3:20 PM JUL 6, 2016 3:07 PM DELIVERY NEEDED JUL 6, 2016 2:45 PM MAX PRODUCT ALARM JUL 6, 2016 3:31 PM JUN 27, 2016 1:12 PM LOW TEMP WARNING JUL 6, 2016 3:38 PM TANK 3 PREMIUM HIGH PRODUCT ALARM JUL 6, 2016 12:37 PM JUN 27, 2016 1:13 PM INVALID FUEL LEVEL JUL 6, 2016 12:42 PM APR 27, 2016 10:38 PM PROBE OUT JUL 6, 2016 12:41 PM JUL 6, 2016 12:24 PM JUN 27, 2016 2:03 PM DELIVERY NEEDED JUL 6, 2016 12:24 PM JUN 27, 2016 1:08 PM APR 30, 2016 5:40 AM TANK 4 DIESEL HIGH PRODUCT ALARM JUL 6, 2016 12:39 PM JUN 27, 2016 1:14 PM INVALID FUEL LEVEL JUL 6, 2016 12:44 PM JUL 6, 2016 12:23 PM MAY 5, 2016 5:56 PM PROBE OUT JUL 6, 2016 12:42 PM JUL 6, 2016 12:22 PM JUN 27, 2016 2:01 PM DELIVERY NEEDED JUL 6, 2016 12:44 PM JUL 6, 2016 12:22 PM JUN 27, 2016 1:09 PM TANK 5 TANK 6 TANK 7 TANK 8 TANK 9 TANK 10 TANK 11 TANK 12 TANK 13 TANK 14 TANK 15 TANK 16 I38200 JUL 6, 2016 3:39 PM I30200 JUL 6, 2016 3:39 PM FASTRIP 775 4901 S UNION BAKERSFIELD CA93307 661-391-9387 LIQUID ALARM HISTORY REPORT SENSOR LOCATION 1 UNL 1 STP JUL 6, 2016 12:53 PM SENSOR OUT ALARM JUL 6, 2016 12:45 PM FUEL ALARM JUN 27, 2016 12:55 PM SENSOR OUT ALARM 2 UNL 1 ANN JUL 6, 2016 12:53 PM SENSOR OUT ALARM JUL 6, 2016 12:47 PM FUEL ALARM JUN 27, 2016 12:55 PM SENSOR OUT ALARM 3 UNL 2 STP JUL 6, 2016 12:54 PM SENSOR OUT ALARM JUL 6, 2016 12:45 PM FUEL ALARM JUN 27, 2016 12:55 PM SENSOR OUT ALARM 4 UNL 2 ANN JUL 6, 2016 12:54 PM SENSOR OUT ALARM JUL 6, 2016 12:47 PM FUEL ALARM JUN 27, 2016 12:55 PM SENSOR OUT ALARM 5 PNL STP JUL 6, 2016 12:53 PM SENSOR OUT ALARM JUL 6, 2016 12:45 PM FUEL ALARM JUN 27, 2016 12:55 PM SENSOR OUT ALARM 6 PNL ANN JUL 6, 2016 12:53 PM SENSOR OUT ALARM JUL 6, 2016 12:47 PM FUEL ALARM JUN 27, 2016 12:55 PM SENSOR OUT ALARM 7 DSL STP JUL 6, 2016 12:54 PM SENSOR OUT ALARM JUL 6, 2016 12:46 PM FUEL ALARM JUN 27, 2016 12:55 PM SENSOR OUT ALARM 8 DSL ANN JUL 6, 2016 12:54 PM SENSOR OUT ALARM JUL 6, 2016 12:46 PM FUEL ALARM JUN 27, 2016 12:55 PM SENSOR OUT ALARM 9 DISP 1-2 JUL 6, 2016 12:53 PM SENSOR OUT ALARM JUL 6, 2016 12:50 PM FUEL ALARM JUN 27, 2016 12:55 PM SENSOR OUT ALARM 10 DISP 3-4 JUL 6, 2016 12:53 PM SENSOR OUT ALARM JUL 6, 2016 12:49 PM FUEL ALARM JUN 27, 2016 12:55 PM SENSOR OUT ALARM 11 DISP 5-6 JUL 6, 2016 12:53 PM SENSOR OUT ALARM JUL 6, 2016 12:52 PM FUEL ALARM JUN 27, 2016 12:55 PM SENSOR OUT ALARM 12 DISP 7-8 JUL 6, 2016 12:53 PM SENSOR OUT ALARM JUL 6, 2016 12:48 PM FUEL ALARM JUN 27, 2016 12:55 PM SENSOR OUT ALARM 13 N. TRANS SUMP JUL 6, 2016 12:53 PM SENSOR OUT ALARM JUL 6, 2016 12:51 PM FUEL ALARM JUN 27, 2016 12:55 PM SENSOR OUT ALARM 14 S. TRANS SUMP JUL 6, 2016 12:53 PM SENSOR OUT ALARM JUL 6, 2016 12:50 PM FUEL ALARM JUN 27, 2016 12:55 PM SENSOR OUT ALARM I31600 JUL 6, 2016 3:40 PM FASTRIP 775 4901 S UNION BAKERSFIELD CA93307 661-391-9387 SMART SENSOR ALARM HISTORY REPORT SENSOR LOCATION 1 PS 3-4 APR 8, 2016 4:33 PM COMMUNICATION ALARM 2 FM 1-2 APR 8, 2016 4:33 PM COMMUNICATION ALARM 3 FM 3-4 APR 8, 2016 4:33 PM COMMUNICATION ALARM 4 FM 5-6 APR 8, 2016 4:33 PM COMMUNICATION ALARM 5 FM 7-8 APR 8, 2016 4:34 PM COMMUNICATION ALARM I40200 JUL 6, 2016 3:40 PM I40300 JUL 6, 2016 3:40 PM I34200 JUL 6, 2016 3:40 PM I34700 JUL 6, 2016 3:40 PM IV0100 JUL 6, 2016 3:40 PM FASTRIP 775 4901 S UNION BAKERSFIELD CA93307 661-391-9387 ISD ALARM STATUS REPORT EVR TYPE: VACUUM ASSIST ISD TYPE: 01.05 VAPOR PROCESSOR TYPE: NONE OVERALL STATUS :PASS EVR VAPOR COLLECTION :PASS EVR VAPOR CONTAINMENT :PASS ISD MONITOR UP-TIME :100% EVR/ISD PASS TIME :100% WARNING ALARMS DATE TIME DESCRIPTION READING VALUE 16-07-05 00:00:29 VAPOR CONTAINMENT LEAKAGE CFH@2 INCHES WC 20.04 16-07-04 00:00:37 VAPOR CONTAINMENT LEAKAGE CFH@2 INCHES WC 14.33 FAILURE ALARMS DATE TIME DESCRIPTION READING VALUE SHUTDOWN & MISCELLANEOUS EVENTS DATE TIME DESCRIPTION ACTION/NAME 16-07-06 15:35:38 READINESS ISD:PP EVR:NN EVR READINESS PENDING 16-07-06 15:35:38 ISD STARTUP 16-07-06 15:35:28 ISD SHUTDOWN 16-07-06 12:55:02 READINESS ISD:PP EVR:NN EVR READINESS PENDING 16-07-06 12:55:02 ISD STARTUP 16-07-06 12:54:52 ISD SHUTDOWN 16-07-06 00:00:09 READINESS ISD:PP EVR:NP EVR READINESS PENDING 16-07-05 12:45:26 CONTAINMENT VAPOR LEAKAGE TEST MANUALLY CLEARED 16-07-05 00:00:29 READINESS ISD:PP EVR:PF CHECK EVR SYSTEM 16-07-04 00:00:37 READINESS ISD:PP EVR:PF CHECK EVR SYSTEM SWRCB, January 2006 Spill Bucket Testing Report Form This form is intended for use by contractors performing annual testing of UST spill containment structures. The completed form and printouts from tests (if applicable), should be provided to the facility owner/operator forsubmittal to the local regulatory agency. 1.FACILITY INFORMATION Facility Name:Date of Testing: Facility Address: Facility Contact:Phone: Date Local Agency Was Notified of Testing : Name of Local Agency Inspector (if present during testing): 2.TESTING CONTRACTOR INFORMATION Company Name:Confidence UST Services, Inc. Technician Conducting Test: Credentials1:CSLB Contractor ICC Service Tech. SWRCB Tank Tester Other (Specify) License Number(s):CSLB#804904 ICC# 3.SPILL BUCKET TESTING INFORMATION Test Method Used:Hydrostatic Vacuum Other Test Equipment Used:Lake TestEquipment Resolution:0.0625” Identify Spill Bucket (By Tank Number, Stored Product, etc.) 1234 Bucket Installation Type: Direct Bury Contained in Sump Direct Bury Contained in Sump Direct Bury Contained in Sump Direct Bury Contained in Sump Bucket Diameter: Bucket Depth: Wait time between applying vacuum/water and start of test: Test Start Time (TI): Initial Reading (RI): Test End Time (TF): Final Reading (RF): Test Duration (TF – TI): Change in Reading (RF -RI): Pass/Fail Threshold or Criteria: Test Result: Pass Fail Pass Fail Pass Fail Pass Fail Comments –(include information on repairs made prior to testing, and recommended follow-up for failed tests) CERTIFICATION OF TECHNICIAN RESPONSIBLE FOR CONDUCTING THIS TESTING I hereby certify that all the information contained in this report is true, accurate, and in full compliance with legal requirements. Technician’s Signature:________________________________________________ Date:_________ 1 State laws and regulations do not currently require testing to be performed by a qualified contractor. However, local requirements may be more stringent. #7775/Fastrip#19 07/06/2016 4901SouthUnionAvenue Bakersfield,CA93307 OmeroGarcia(661)393-7000 06/14/2016 Kris Karns BrandonMason 5284980-UT Regular1 12.00" 13.50" 5min. 12:30 pm 8.00" 1:30 pm 8.00" 1hour 0.00" 0.0625" Regular2 12.00" 14.00" 5min. 2:30 pm 7.75" 3:30 pm 7.75" 1hour 0.00" 0.0625"0.0625" Super 12.00" 14.00" 5min. 12:30 pm 8.00" 1:30 pm 8.00" 1hour 0.00" Diesel 12.00" 14.50" 5min. 12:30 pm 7.50" 1:30 pm 7.50" 1hour 0.00" 0.0625" 07/06/2016