Loading...
HomeMy WebLinkAbout2016 CUPA ReportBAKERSFIELD FIRE DEPARTMENT Prevention Services Division Underground Storage Tank Program 2101 H Street DW Inspection Report '* Bakersfield, CA 93301 Permission to Inspect: -- ' - Phone: 661-326-3979 Fax: 661-852-2171 Business Name: KERN CO HOUSING AUTHORITY-15-021-100043 Date:7/19/2016 Address Name: 3015 WILSON RD-CAL000409447 Inspector Name: Shane Gardner #8248557 Inspection Type: Routine Report : Final NVO = No Violation Observed OUT = Out of Compliance NA = Not Applicable UD = Undetermined COS = Corrected On Site RPT = Repeat Violation Violation Program Requirement ro- SOC Comments No 0 0 a. z 0 z File Review Facility Tank Information 2030021 Facility has a valid Permit Tank 1-300-DW-DSL to Operate from the Tank 2- CUPA - 23 CCR 16 2712(1); F-1 ❑ None Tank 3- HSC 6.7 25284 Tank 4- 2010010 UST Operating Permit Application for Facility information and Tank information 0 ED F-1 ❑ ❑ ❑ None submitted/maintained - 23 CCR 16 2711; HSC 6.7 25286(a) 2010001 Current BOE number submitted to the CUPA None and/or CERS - HSC 6.7 25286(c) 2030011 UST compliance statement and/or Designated Operator ❑ ❑ ❑ ❑ None current certification submitted - 23 CCR 16 2715(a), 2715(b) 2030046 A complete and accurate response plan has been submitted, approved and F-1 r-1 ❑ ❑ ❑ None maintained - 23 CCR 16 2632, 2634(e), 2641(h), 2712(i) 2030041 A complete and accurate plot plan has been submitted, approved and F-1 ❑ ❑ ❑ ❑ Minor maintained - 23 CCR 16 2632(d)(1)(C), 2711 )(8) 2010006 Owner/Operator has not made false statements or representation on any ED ❑ F-1 ❑ ❑ ❑ None required document - HSC 6.725299 2010003 Owner/Operator has a DO and/or informed the CUPA of any change (s) 0 ❑ ❑ ❑ ❑ ❑ None within 30 days - 23 CCR 16 2715(a) Violation Program -Requirement 4- C 0 0.0 SOC Comments No 11-- .:) < a 0 CL z 0 z oO Testing 2030002 Owner /Operator has tested and certified leak 1-1 ❑ ❑ ❑ ❑ None detection equipment annually - 23 CCR 16 2638 2030048 Secondary containment testing conducted every 36 months in accordance None with requirements - 23 CCR 16 2637 2030055 Spill buckets have been tested annually as ❑ ❑ ❑ ❑ ❑ None required - HSC 6.7 25284.2 2010009 Secondary containment test results submitted to the CUPA within 30 days None after the test - 23 CCR 16 2637(e) 2030064 CUPA was poperly notified within the prescribed number of E ❑ ❑ ❑ 1:1 ❑ None hours prior to testing - 23 CCR 16 26370, 2638(e), 2643 , 2644.1(a) (4) Install/Repair 2060009 Permits obtained to install, replace, repair, or 0 ❑ ❑ ❑ ❑ ❑ None modify part of the UST syste - 23 CCR 16 2712 UST System Observation General Monitoring 2030003 Leak detection system maintains continuous RD monitoring that activates N ❑ ❑ ❑ ❑ ❑ None ❑ an audible and visual Yes alarm - 23 CCR 16 2632, 2634, 2636, 2666 2030016 The annular space of the tank, piping and sumps are continuously RD monitored and activates None the alarm - 23 CCR 16 Yes 2631(g), 2632(c)(2)(A)&(8), 2633(c), 2636(o 2030017 Product piping outside the UDC is fail-safe and shuts down the pump or None restricts flow - 23 CCR 16 2636(1) (5) 2030018 Turbine sump monitor activates an audible and RD visual alarm or stops the ❑ ❑ ❑ None ❑ flow of at the dispenser - Yes 23 CCR 16 26360(1) Underground Storage Tank Program - DW Inspection Report v 2.0 Violation Program Requirement o SOC Comments No a o O (L IM z o z C) a o> 2030019 Monitoring system in the UDCs activates an audible and visual alarm ® ❑ ❑ ❑ ❑ ❑ None or stops the flow at the UDC - 23 CCR 16 2636 (0(1) 2030043 Leak detection equipment properly programmed or RD properly operated - 23 ® ❑ ❑ ❑ ❑ ❑ None ❑ CCR 16 2632, 2634, 2636, Yes 2666 2060005 System constructed with a monitoring system capable of detecting entry ® ❑ ❑ ❑ ❑ ❑ None into secondary containment - HSC 6.7 25291(b) 2060014 Correct leak detection equipment installed for RD the type of system ® ❑ ❑ ❑ ❑ ❑ None ❑ present - 23 CCR 16 2638; Yes HSC 6.7 25290.1, 25290.2, 25291 2060015 Sensor located in the RD proper position /location - ® ❑ ❑ ❑ ❑ ❑ None ❑ 23 CCR 16 2630(d), 2641(a) Yes 2030062 Facility is in compliance with not tampering with or RD disabling leak detection ® ❑ ❑ ❑ ❑ ❑ None ❑ devices or alarms - HSC Yes 6.7 25299 a 9 2060022 System constructed with a monitoring system capable of detecting entry ® ❑ ❑ ❑ ❑ ❑ None into secondary containment - HSC 6.7 25290.2(d) 2030034 Tag /sticker on affixed monitoring equipment being certified, repaired, ® ❑ ❑ ❑ ❑ ❑ None or replaced - 23 CCR 16 26380 VPH Monitoring VPH 2030065 Interstitial monitoring of the annular spaces of the RD UST is properly ® ❑ ❑ ❑ ❑ ❑ None ❑ maintained - HSC 6.7 Yes 25290.1(e 2060023 System constructed with a monitoring system capable of detecting entry into secondary ® ❑ ❑ ❑ ❑ ❑ None containment - HSC 6.7 25290.1(d) Underground Storage Tank Program - DW Inspection Report v 2.0 Violation Program Requirement o SOC Comments No p = Q o O a �c Z O z Line Leak Detector 2060012 Line leak detector installed on pressurized RD piping system - HSC 6.7 ❑ ❑ ® ❑ ❑ ❑ None F] 25290.1(h), 25290.2(8), Yes 252910, 25292(e), 26360 (2) 2030026 Line leak detectors detect a 3 gph leak and /or RD audible and visual alarm ❑ ❑ ® ❑ ❑ ❑ None ❑ function properly - 23 Yes CCR 16 26360(6), 2666(c) 2030027 Turbine shuts down when a leak is detected or RD when line leak detector is ❑ ❑ ® ❑ ❑ ❑ None ❑ disconnected - 23 CCR 16 Yes 2666(c) 2030025 Pressurized piping able to detect a 3.0 gph leak RD within an hour, and ❑ ❑ ® ❑ ❑ ❑ None ❑ restricts the flow or Yes alarms - 23 CCR 16 26360 (2 Secondary Containment 2060010 UST storing a hazardous RD substance has secondary ® ❑ ❑ ❑ ❑ ❑ None ❑ containment - HSC 6.7 Yes 25292 Underground Storage Tank Program - DW Inspection Report v 2.0 Violation Program Requirement 0.0 SOC Comments No p _ o O a Q)0 Z o z D 0 a 0.- 2030008 UDC, sumps, and /or other secondary containment in good ® ❑ ❑ ❑ ❑ ❑ None condition and /or are free of debris /liquid - HSC 6.7 25290.1, 25290.2, 25291 2030040 Secondarily contained RD piping maintained to allow ❑ ❑ ❑ ❑ ❑ None ❑ liquid to drain into sump - Yes 23 CCR 16 2630(d), 2641 a 2060006 Secondary containment piping slopes back to the ® ❑ ❑ ❑ ❑ ❑ None collection sump - 23 CCR 16 263 c 2030047 Secondary containment maintained tight and has been confirmed by testing ® ❑ ❑ ❑ ❑ ❑ None - 23 CCR 16 2662, HSC 6.7 25290. 1 (c) (2), 25290.2(c) (2), 25291(a), 25292(e) 2030060 Entry fittings in secondary containment for UST system maintained ® ❑ ❑ ❑ ❑ ❑ None tight/sealed - 23 CCR 16 2630, 2635(d), 2636(c), 2666 2060020 Spill bucket is installed and has a functional drain RP valve or other means to ® ❑ ❑ ❑ ❑ ❑ None ❑ remove liquid - 23 CCR 16 Yes 2635(b), 2665 2030054 Spill bucket maintained in RP good condition and free of ® ❑ ❑ ❑ ❑ ❑ None ❑ debris and /or liquid - 23 Yes CCR 16 2635(b), 2715(c)(2) 2060019 Spill bucket to has a minimum capacity of five ® ❑ ❑ ❑ ❑ ❑ None gallons - 23 CCR 16 2635(b), 2665 Overfill 2030035 UST system is operated to prevent unauthorized RP release, including spills ® ❑ ❑ ❑ ❑ ❑ None ❑ and overfills - HSC 6.7 Yes 25292.1 a 2030036 Overfill prevention system RP has not been overridden and meets overfill ® ❑ ❑ ❑ ❑ ❑ None ❑ requirements - 23 CCR 16 Yes 2635(b)(2), 2665 Underground Storage Tank Program - DW Inspection Report v 2.0 Violation Program Requirement a°, o SOC Comments No p_ a o O a d� 00 z O z M On Site Records Certifications 2030023 Required designated operators or contractors maintain a proper and ® ❑ ❑ ❑ ❑ ❑ None current ICC certification - 23 CCR 16 2715 2030024 Service technician, installer, and/ or employee maintain a ® ❑ ❑ ❑ ❑ ❑ None proper license - 23 CCR 162715 2030031 Employee or contractor obtained and maintained proper manufacturer ® ❑ ❑ ❑ ❑ ❑ None certification - 23 CCR 16 2715 2010007 Submit/maintain current Certificate of Financial Responsibility /mechanism of financial assurance - ® ❑ ❑ ❑ ❑ ❑ None 23 CCR 16 2711; 23 CCR 18 2808.1, 2809 - 2809.2; HSC 6.7 25292.2; HSC 6.75 25299.30- 25299.34 Designated Operator 2010004 Copies of DO inspections for last 12 months and list of trained employees ® ❑ ❑ ❑ ❑ ❑ None maintained - 23 CCR 16 2715 2030013 Designated operator properly conducted the monthly inspection and ® ❑ ❑ ❑ ❑ ❑ None the reports are complete - 23 CCR 16 2715 2030010 DO notified operator of any condition observed during the monthly ® ❑ ❑ ❑ [� None inspection that may require action - 23 CCR 16 2715(d) 2030012 DO employee training performed, current for at least one employee on ® ❑ ❑ ❑ ❑ ❑ None site, and a log kept - 23 CCR 16 2715(c)(6), 2715(0 Underground Storage Tank Program - DW Inspection Report v 2.0 Violation Program Requirement o SOC Comments No O Q p O a d o Z O Z p U W p> Logs 2030001 Leak detection alarm logs, maintenance and RD records of appropriate ® ❑ ❑ ❑ ❑ ❑ None ❑ follow -up actions Yes maintained - 23 CCR 16 2632, 2634, 2712(b) Maintenance/Tests 2010008 Monitoring, maintenance, repairs, linings, and RD upgrade records ® ❑ ❑ ❑ ❑ ❑ None ❑ maintained for the proper Yes time period - 23 CCR 16 2712(b) Documentation 2030033 Failure to maintain on site an approved monitoring ® ❑ ❑ ❑ ❑ ❑ None plan - 23 CCR 16 2632, 2634, 2711, 2712(1) 2030037 Written agreement between the tank owner and tank operator to monitor the tank system ® ❑ ❑ ❑ ❑ ❑ None is maintained - 23 CCR 16 2620(b); HSC 6.7 25284 (a) (3) 2030061 Suspected or actual unauthorized release RD reported in appropriate ❑ ❑ ® ❑ ❑ ❑ None ❑ time frame - HSC 6.7 Yes 29294, 29295 General Operating Requirements Permit Condition /Approval 2030039 Compliance with all operating permit ® EJ ❑ ❑ ❑ ❑ None conditions - 23 CCR 16 2712, HSC 6.7 25299 2030059 UST system maintained in accordance with exclusion /exemption ® ❑ ❑ ❑ ❑ ❑ None status - HSC 6.7 25281.6, 25283.5 2030014 Owner /Operator received approval and has implemented a training ❑ ❑ ® ❑ ❑ ❑ None program at an unstaffed facility - 23 CCR 16 27150(2) 2030015 Facility exhibited that the method used to monitor the tank meets the monitoring methods in ® ❑ ❑ ❑ ❑ ❑ None 2643(f - 23 CCR 16 2643 Underground Storage Tank Program - DW Inspection Report v 2.0 Violation Program Requirement m o SOC Comments No Oj D a o O n. 0o z O z M 0 W of Red Tag 2030045 Red Tag information is legible and has not been ❑ ❑ ® ❑ ❑ ❑ None tampered with - 23 CCR 16 2717. 1 g 2030044 Facility did not allow for deposit of petroleum into a UST that has a red tag ❑ ❑ ® ❑ ❑ ❑ None affixed to the fill - 23 CCR 16 2717.1( Install /Repair 2060024 UST system is made of or lined with materials that are compatible with the ® ❑ ❑ ❑ ❑ ❑ None substance stored - 23 CCR 16 2631.1 2060021 Striker plate installed and positioned correctly - 23 ® ❑ ❑ ❑ ❑ ❑ None CCR 16 2631(c), 2662(d) ® There were no violations noted for this inspection. ❑This report shall serve as a "NOTICE TO COMPLY" for Minor Violations, and a "NOTICE OF VIOLATION" for Major violations. You are, hereby, ordered to correct the above noted violations within 30 days, or according to correction summaries provided. Formal enforcement and /or penalty assessment may be initiated for any violations noted, and for those not corrected in a timely manner. (NOTE: If this is a preliminary report, a final report will follow.) Inspectors Signature. -- Date: Inspector: Enter # of Violations: RD: RP: Check one box for facility Significant Operational Status (SOC) to be reported to SWRCB and US EPA: ❑ SOC with both Release Detection and Release Detection (Facility has no Release Prevention and no Release Prevention Violations) ❑ Not in SOC (Facility has both Release Prevention and Release Detection Violations) ❑SOC with Release Detection only (Facility has no Release Detection violations but one or more Release Prevention violations) ❑ SOC with Release Prevention only (Facility has no Release Prevention violations but one or more Release Detection violations) Underground Storage Tank Program - DW Inspection Report v 2.0 FACILITY NAME INSPECTION DATE, INSPECTION TIME ,✓ APPROPRIATE PERMIT ON HAND (BMC:15.65.080) ADDRESS PHONE NO. NO OF EMPLOYEES BUSINESS PLAN CONTACT INFORMATION ACCURATE (CCR: 2729.1) 1010008 FACILITY CONTACT BUSINESS ID NUMBER VISIBLE ADDRESS (CFC: 505.1, BMC: 15.52.020) Consent to Inspect Name /Title ,A Y.... ., , � k .... _ ,. X'r: s.. F �i .. <S. <,., ..ny. a :.5. .. . .... �.0 , .. .. - .St^'+ ,., .. .. o. .9 k..✓?...7. , � F .. ..:. � �. ���s. <r. ....2, ..,'a• .. �, :fi ��...^3� „3..,,�`i .s� nr '2. :n .�... ..�.., 3 .,� n.. �.. r3 n �� -. o �'��r�i. �a. e. ..... ..�. _ F., X. x `�'s +u.i, <+Y f.:. :,e 4�. _?f.. k.:c � (,� . rt <e. a -n , ,,,. L, ,.. . as3u. 9..,.: a� 7a.&. n .i� . � <a. ^eivA :C:?r, � 4:k• 4 .,,+,\ .z huv. ,:n. ,..<, •,.. -.., ., �` i,.�. �x ., t .S:uS.... ,. .� aC �. ; .. l".": s., k �<? .. t� E, ?r }Y .. w �a: �. .. S�J x, ?�A( s ❑ ROUTINE 'ff COMBINED ❑ JOINTAGENCY ❑. MULTI- AGENCY ❑ COMPLAINT ❑ RE- INSPECTION C V C=Compliance OPERATION V =Violation; 1,11 Minor CERS Violation COMMENT APPROPRIATE PERMIT ON HAND (BMC:15.65.080) 3010001 BUSINESS PLAN CONTACT INFORMATION ACCURATE (CCR: 2729.1) 1010008 VISIBLE ADDRESS (CFC: 505.1, BMC: 15.52.020) ` CORRECT OCCUPANCY (CBC:401) VERIFICATION OF INVENTORY MATERIALS (CCR: 2729.3) 1010004 VERIFICATION OF QUANTITIES (CCR: 2729.4) 1010006 VERIFICATION OF LOCATION (CCR: 2729.2) PROPER SEGREGATION OF MATERIAL (CFC: 2704.1) VERIFICATION OF SDS AVAILABILITY (CCR: 2729.2(3)(b)) VERIFICATION OF HAZ MAT TRAINING (CCR: 2732) 1020002 VERIFICATION OF ABATEMENT SUPPLIES & PROCEDURES (CCR: 2731(c)) EMERGENCY PROCEDURES ADEQUATE (CCR: 2731) 1010010 CONTAINERS PROPERLY LABELED (CCR: 66262.34(f , CFC: 2703.5) 3030007 HOUSEKEEPING (CFC: 304.1) FIRE PROTECTION (CFC: 903 & 906) 3030032 SITE DIAGRAM ADEQUATE & ON HAND (CCR: 2729.2) 1010005 NY HAZARDOUS WASTE ON SITE? ❑ YES „"9 10 Signature ofRecei t Explain:., Inspector:, POST INSPECTION INSTRUCTIONS: • Correct the violation(s) noted above by �=- • Within 5 days of correcting all of the violations, sign and return a copy of this page to: Signature (that all violations have been corrected as noted) Bakersfield Fire Dept., Prevention Services, 2.101 H Street, California 93301 Date I White Business Copy Yellow — Station Copy " Pirik .Prevenb6n Services FD2155 (Rev 8H14)