September 8, 2016
V/A FED EX. 77718090 9046
Bakersfield Fire Department
2101 H Street
Bakersfield CA 93301
Re: Secondary Containment Testing
Pacific Bell Telephone Co. dba AT&T California
3221 S. H STREET, BAKERSFIELD, CA
GEOPAR: SA098
To Whom it May Concern:
Enclosed are the results for the following tests completed on August 31, 2016:
■ Secondary Containment Testing Report Form
Please do not hesitate to call me if you have any questions.
Sincerely,
Carlos E. Cardenas
Program Manager
CA llc# 588098 AZ lic# 095984 j NV 11,,# 0049666 TX !:<-# 'R000004 I
SWRCB, January 2002
Secondary Containment Testing Report Form
This form is intended for use by contractors performing periodic testing of UST secondary containment systems. Use the
appropriate pages of this form to report results for all components tested. The completed form, written test procedures, and
printouts from tests (f applicable), should be provided to the facility owner /operator for submittal to the local regulatory agency.
1. FACILITY INFORMATION Facili ID: SA098
Client Name: Pacific Bell Telephone Co dba ATT California Date of Testing: 8/31/2016
Facility Address: 3221 S. H St. City: Bakersfield State: CA Zip Code: 93304
Facility Contact: Grant Armstrong Phone: (661) 327 -6903 ❑ Initial ❑ Repair Test
Date Local Agency Was Notified of Testing: 8/12/2016 ❑ 6 Month FX-1 Other
Name of Local Agency Inspector (f present during testing): No One Present FRI Triennial
2. TESTING CONTRACTOR INFORMATION
Company Name: TAIT Environmental Services
Pass
Technician Conducting Test: Adolfo Aguilar
Not
Tested
Repairs
Made
Credentials: ❑X CSLB Licensed Contractor
❑ SWRCB Licensed Tank Tester
❑X ICC UST Service Technician
License Type: A B ASB C -10 HAZ
License Number: 588098
SA098UO01 Annular Space
Manufacturer
Manufacturer Training
Component(s)
Date Training Expires
ICC Technician
5238610
6/9/2018
Franklin Fueling / Incon Unit
1007483708
7/13/2018
SA0980001 Supply Sec. Line
❑
❑X
❑
❑
SA0980001 Supply Sec. Line
3_ STTMMARV OF TF,ST RESULTS
Component
Pass
Fail
Not
Tested
Repairs
Made
Component
Pass
Fail
Not
Tested
Repairs
Made
SA098UO01 Annular Space
❑❑
❑
❑
❑
❑
❑
❑
SA0980001 Supply Sec. Line
❑
❑X
❑
❑
SA0980001 Supply Sec. Line
0
❑
❑
❑X
SA0980001 Return Sec. Line
❑
❑
❑
❑
SA0980001 Return Sec. Line
❑❑
❑
❑
SA0980001 Vent Sec. Line
❑
❑❑
❑
SA0980001 Vent Sec. Line
❑X
❑
❑
❑X
SA0980001 Piping Sump
❑
❑
❑
❑
❑
❑
❑
❑
SA0980001 Fill Sump
❑❑
❑
❑
❑
❑
❑
❑
❑
❑
❑
❑
❑
❑
❑
❑
❑
❑
❑
❑
❑
❑
❑
❑
❑
❑
❑
❑
❑
❑
❑
❑
❑
❑
❑
❑
❑
❑
❑
❑
❑
❑
❑
❑
❑
❑
❑
❑
❑ I
❑ I
❑
❑
❑
❑
❑
❑
If hydrostatic testing was performed, describe what was done with the water after completion of tests:
Took Non -Haz. Test Water To TAIT Shop.
For any equipment capable of generating a print out of test results, you must attach a copy of the test report to this certification.
EX-1 System printout attached.
CERTIFICATION OF TECHNICIAN RESPONSIBLE FOR CONDUCTING THIS TESTING
To the best of my knowledge, the facts stated in this document are accurate and in full compliance with legal requirements
Technician's Signature: 14400 14Gpd= Date: 8/31/2016
SWRCB, January 2002
Comments — (include information on repairs made prior to testing, and recommended follow -up for failed tests)
Re- Installed Sensor To Lowest Point But Not Tested.
' Secondary containment systems where the continuous monitoring automatically monitors both the primary and secondary
containment, such as systems that are hydrostatically monitored or under constant vacuum, are exempt from periodic containment
testing. {California Code of Regulations, Title 23, Section 2637(a)(6)1
4. TANK ANNULAR TESTING
Test Method Developed By:
❑ Tank Manufacturer 21 Industry Standard ❑ Professional Engineer
❑ Other (Spec)
Test Method Used:
❑ Pressure
❑Vacuum
❑ Hydrostatic
❑ Other (Specify)
Test Equipment Used: 4" Dial Gauge
Equipment Resolution: .2"
SA098U001 Annular
Is Tank Exempt From Testing ?
❑Yes ONo
❑Yes ❑No
❑ Yes F-1 No
❑ Yes ❑ No
Tank Capacity:
6,016 Gallons
Tank Material:
Steel Clad
Tank Manufacturer:
Modern Welding
Product Stored:
Diesel
Wait time between applying
pressure /vacuum /water and
15 Minutes
starting test:
Test Start Time:
9:30 AM
Initial Reading (RI):
- 10.0" HG
Test End Time:
10:30 AM
Final Reading (RF):
10.0" HG
Test Duration:
1 Hour
Change in Reading (RF -RI):
0.0" HG
Pass /Fail Threshold or Criteria:
0.0" HG
Test Result:
❑X Pass ❑Fail
❑ Pass ❑Fail
❑ Pass ''❑ Fail
❑ Pass ❑ Fail
Was sensor removed for testing?
❑ Yes ❑No ❑NA
F-1 Yes F-1 No El NA
1:1 Yes 0 N El NA
El Yes ❑No ❑NA
Was sensor properly replaced and
❑Yes 0No DNA
❑ Yes ❑No ❑NA
❑ Yes ❑No ❑NA
❑Yes ❑No ❑NA
verified functional after testing?
Comments — (include information on repairs made prior to testing, and recommended follow -up for failed tests)
Re- Installed Sensor To Lowest Point But Not Tested.
' Secondary containment systems where the continuous monitoring automatically monitors both the primary and secondary
containment, such as systems that are hydrostatically monitored or under constant vacuum, are exempt from periodic containment
testing. {California Code of Regulations, Title 23, Section 2637(a)(6)1
SWRCB, January 2002
5. SECONDARY PIPE TESTING
Test Method Developed By:
❑ Piping Manufacturer
FX-1 Industry Standard ❑ Professional Engineer
❑ Other (Specify)
Test Method Used:
FX--1 Pressure
❑ Vacuum ❑ Hydrostatic
❑ Other (Specify)
Test Equipment Used: 4" Dial Pressure
Equipment Resolution:.1"
EMEM
SA0980001 Vent Sec.
SA0980001 Vent Sec.
Piping Material:
Fiberglass
Fiberglass
Piping Manufacturer:
A.O. Smith
A.O. Smith
Piping Diameter:
3"
3"
Length of Piping Run:
35'
35'
Product Stored:
Diesel
Diesel
Method and location of
Test Boot / Piping Sump
Test Boot / Piping Sump
piping-run isolation:
Wait time between applying
pressure /vacuum /water and
Visual Failure
15 Minutes
starting test:
Test Start Time:
11:20 AM
Initial Reading (R,):
5 PSI
Test End Time:
12:20 PM
Final Reading (RF):
5 PSI
Test Duration:
1 Hour
Change in Reading (RF -RI):
0.0 PSI
Pass/Fail Threshold or
0.0 PSI
0.0 PSI
Criteria:
Test Result:
❑ Pass 0 Fail -.
E Pass
❑ Fail
❑ Pass El Fail
❑ Pass ❑ Fail
Comments — (include information on repairs made prior to testing, and recommended follow -up for failed tests)
Replaced Vent Sec. Line Test Boot In Piping Sump, After Repairs Tested & Passed.
SWRCB, January 2002
6. PIPING SUMP TESTING
Test Method Developed By: ❑ Sump Manufacturer Industry Standard ❑ Professional Engineer
❑ Other (Spec)
Test Method Used: ❑ Pressure ❑ Vacuum 0 Hydrostatic
❑ Other (Specify)
Test Equipment Used: Incon TS -STS
Equipment Resolution: .0006"
SA0980001 Piping
Sump Diameter:
48"
Sump Depth:
51"
Sump Material:
Fiberglass
Height from Tank Top to Top of
Highest Piping Penetration:
2211
Height from Tank Top to Lowest
Electrical Penetration:
15"
Condition of sump prior to testing:
Poor
Portion of Sump Tested'
Visual Failure
Does turbine shut down when
sump sensor detects liquid (both
product and water) ?*
0Yes [--]No LENA
❑Yes ❑No ❑NA
❑Yes ❑No ❑NA
❑Yes ❑No ❑NA
Turbine shutdown response time
N/A
Is system programmed for fail -safe
shutdown ?*
❑Yes ❑No QNA
❑Yes ❑No ❑NA
❑Yes ❑No ❑NA
❑Yes ❑No ❑NA
Was fail -safe verified to be
operational ?*
❑Yes ❑No ❑NA
❑ Yes ❑No ❑NA
Dyes ❑No ❑NA
❑Yes ❑No DNA
Wait time between applying
pressure /vacuum /water and starting
test:
Visual Failure
Test Start Time:
Initial Reading (RI):
Test End Time:
Final Reading (RF):
Test Duration:
Change in Reading (RF -R,):
Pass/Fail Threshold or Criteria:
Test Result:
❑ Pass 0 Fail
F-1 Pass ❑ Fail
❑Pass " ❑Fail
❑ Pass ❑Fail
Was sensor removed for testing?
❑Yes ❑ No ❑NA
❑Yes ❑No ❑NA
❑Yes ❑No DNA
❑Yes ❑No ❑NA
Was sensor properly replaced and
verified functional after testing?
❑Yes ❑No ❑ NA
❑Yes ❑No ❑NA
❑Yes ❑No ❑NA
❑Yes ❑No ❑NA
Comments — (include information on repairs made prior to testing, and recommended follow -up for failed tests)
Visual Failure: Piping Sump Penetration Termination Boots (Sump Cuff Boots) Are Torn On Vent and Supply /Return, Repairs Needed.
' If the entire depth of the sump is not tested, specify how much was tested. If the answer to anX of the questions indicated with an
asterisk (") is "NO" or "NA ", the entire sump must be tested. (See SWRCB LG -160)
SWRCB, January 2002
S. FILL RISER CONTAINMENT SUMP TESTING
Facility is Not Equipped With Fill Riser Containment Sumps ❑
Fill Riser Containment Sumps are Present, but were Not Tested ❑
Test Method Developed By: ❑ Sump Manufacturer ❑Industry Standard ❑ Professional Engineer
❑ Other (Specify)
Test Method Used: ❑ Pressure ❑ Vacuum 0 Hydrostatic
❑ Other (Specify)
Test Equipment Used: Incon TS -STS
Equipment Resolution: .0006"
SA0980001 Fill
Sump Diameter: _
48"
Sump Depth:
50"
Height from Tank Top to Top of
Highest Piping Penetration:
N/A
Height from Tank Top to Lowest
Electrical Penetration:
12"
Condition of sump prior to
testing:
Good
Portion of Sump Tested
2" Above Highest Pentr
Sump Material:
Fiberglass
Wait time between applying
pressure /vacuum /water and
starting test:
15 Minutes
Test Start Time:
9:18 AM
9:33 AM
Initial Reading (RI):
3.5636"
3.5635"
Test End Time:
9:33 AM
9:48 AM
Final Reading (RF):
3.5634"
3.5635"
Test Duration:
15 Min.
15 Min.
Change in Reading (RF -RI):
.0002"
.0000"
Pass/Fail Threshold or Criteria:
.002"
.002"
Test Result:
El Pass ❑ Fail
❑ Pass: ❑Fail
❑ Pass ❑ Fail
❑ Pass ❑ Fail
Is there a sensor in the sump?
[Z]Yes ❑ No
❑ Yes ❑ No
❑ Yes ❑ No
❑ Yes ❑ No
Does the sensor alarm when
either product or water is
detected?
❑Yes ❑ No ❑NA
❑Yes ❑No ❑NA
❑Yes ❑No NA
❑
Yes
❑ ❑No ❑NA
Was sensor removed for testing?
❑ Yes [—]No ❑NA
❑ Yes ❑No ❑NA
❑ Yes ❑No ❑ NA
❑ Yes ❑No ❑NA
Was sensor properly replaced and
verified functional after testing?
❑Yes ❑No ❑NA
❑ �'es ❑No ❑NA
❑Yes ❑No ❑NA
Dyes ❑No ❑NA
Comments — (include information on repairs made prior to testing, and recommended follow -up for failed tests)
Re- Installed Sensor To Lowest Point But Not Tested.
AT -T SA098
3221 S. H ST,
BAKERSFIELD
CALIFORNIA
TAIT ENVIRONMENTAL
0'3! /31/ 2016 9: 33 AM
SUMP LEAK TEST REPORT
FILL
TEST STARTED 9 :18 AM
TEST STARTED 08/31/2016
BEGIN LEVEL 3,5636 IN
END TIME 9 :33 AM
END DATE 08/31/2016
END LEVEL 3.5634 IN
LEAK: 'THRESHOLD 0, 002 IN
TEST RESULT PASSED
AT -T SA098
3221 S. H ST,
BAKERSFIELD
CALIFORNIA
TAIT ENVIRONMENTAL
08/31/2016 9 :48 AM
SUMP LEAK TEST REPORT
FILL
TEST STARTED 9 :33 AM
TEST STARTED 08 /31/2016
EEGIN LEVEL 3,5635 IN
END TIME 9 :48 AM
END DATE 08 /31/2016
END LEVEL 3.5635 IN
LEAK THRESHOLD 0,002 IN
TEST RESULT PASSED
AT &T, SA098 3221 S. H Street, Bakersfield, CA 8/31/2016 Page 1 of 1