HomeMy WebLinkAboutFMC 2016MONITORING SYSTEM CERTIFICATION
For Use By All Jurisdictions Within the State of CaliforniaAuthority Cited: Chapter 6.7, Health and Safety Code; Chapter 16, Division 3, Title 23, California Code of Regulations
This form must be used to document testing and servicing of monitoring equipment. A separate certification or report must be prepared for each
monitoring system control panel by the technician who performs the work. A copy of this form must be provided to the tank system owner/operator.
The owner/operator must submit a copy of this form to the local agency regulating UST systems within 30 days of test date.
A.General Information
Facility Name:Bldg. No.:
Site Address:City:Zip:
Facility Contact Person: Contact Phone No.:
Make/Model of Monitoring System:Date of Testing/Servicing:
B.Inventory of Equipment Tested/Certified
Check the appropriate boxes to indicate specific equipment inspected/serviced:
Tank ID:Tank ID:
In-Tank Gauging Probe.Model:In-Tank Gauging Probe.Model:
Annular Space or Vault Sensor.Model:Annular Space or Vault Sensor.Model:
Piping Sump / Trench Sensor(s).Model:Piping Sump / Trench Sensor(s).Model:
Fill Sump Sensor(s).Model:Fill Sump Sensor(s).Model:
Mechanical Line Leak Detector.Model:Mechanical Line Leak Detector.Model:
Electronic Line Leak Detector.Model:Electronic LineLeak Detector.Model:
Tank Overfill / High-Level Sensor.Model:Tank Overfill / High-Level Sensor.Model:
Other (specify equipment type and model in Section E on Page 2).Other (specify equipment type and model in Section E on Page 2).
Tank ID:Tank ID:
In-Tank Gauging Probe.Model:In-Tank Gauging Probe.Model:
Annular Space or Vault Sensor.Model:Annular Space or Vault Sensor.Model:
Piping Sump / TrenchSensor(s).Model:Piping Sump / Trench Sensor(s).Model:
Fill Sump Sensor(s).Model:Fill Sump Sensor(s).Model:
Mechanical Line Leak Detector.Model:Mechanical Line Leak Detector.Model:
Electronic Line Leak Detector.Model:Electronic Line Leak Detector.Model:
Tank Overfill / High-Level Sensor.Model:Tank Overfill / High-Level Sensor.Model:
Other (specify equipment type and model in Section E on Page 2).Other (specify equipment type and model in Section E on Page 2).
Dispenser ID:Dispenser ID:
Dispenser Containment Sensor(s).Model:Dispenser Containment Sensor(s).Model:
Shear Valve(s).Shear Valve(s).
Dispenser Containment Float(s) and Chain(s).Dispenser Containment Float(s) and Chain(s).
Dispenser ID:Dispenser ID:
Dispenser Containment Sensor(s).Model:Dispenser Containment Sensor(s).Model:
Shear Valve(s).Shear Valve(s).
Dispenser Containment Float(s) and Chain(s).Dispenser Containment Float(s) and Chain(s).
Dispenser ID:Dispenser ID:
Dispenser Containment Sensor(s).Model:Dispenser Containment Sensor(s).Model:
Shear Valve(s).Shear Valve(s).
Dispenser Containment Float(s) and Chain(s).Dispenser Containment Float(s) and Chain(s).
*If the facility contains more tanks or dispensers, copy this form. Include information for every tank and dispenser at the facility.
C.Certification -I certify that the equipment identified in this document was inspected/serviced in accordance with the manufacturers’
guidelines. Attached to this Certification is information (e.g. manufacturers' checklists)necessary to verify that this information is
correct and a Plot Plan showing the layout of monitoring equipment. For any equipment capable of generating such reports, I have also
attached a copy of the report;(check all that apply):System set-up Alarm history report
Technician Name (print):Signature:
Certification No.:License. No.:804904
Testing Company Name:Confidence UST Services, Inc.Phone No.:(800)339-9930
Site Address:Date of Testing/Servicing:
Page 1 of 3
#3360FarrellsFastrip
6401WhiteLane Bakersfield93309
OmeroGarcia (661)393-7000
Veeder-RootTLS-350 09/16/2016
12,000gal.Regular
847390-107
794390-303
794380-208
794380-208
FX1V
847390-107
12,000gal.Super
847390-107
794390-303
794380-208
794380-208
FX1V
847390-107
12,000gal.Diesel
847390-107
794390-303
794380-208
794380-208
FX1DV
847390-107
1-2
794380-208
3-4
794380-208
5-6
794380-208 794380-208
7-8
CameronMason
B42599
6401WhiteLane Bakersfield,CA93309 09/16/2016
794380-208
794380-208
Monitoring System Certification
D.Results of Testing/Servicing
Software Version Installed:
Complete the following checklist:
Yes No*Isthe audible alarm operational?
Yes No*Is the visual alarm operational?
Yes No*Were all sensors visually inspected, functionally tested, and confirmed operational?
Yes No*Were all sensors installed at lowest point of secondary containment and positioned so that other equipment will
not interfere with their proper operation?
Yes No*
N/A
If alarms are relayed to a remote monitoring station, is all communications equipment (e.g., modem)
operational?
Yes No*
N/A
For pressurized piping systems, does the turbine automatically shut down if the piping secondary containment
monitoring system detects a leak, fails to operate, or is electrically disconnected? If yes: which sensors initiate
positive shut-down? (Check all that apply) Sump/Trench Sensors; Dispenser Containment Sensors.
Did you confirm positive shut-down due to leaks and sensor failure/disconnection? Yes; No.
Yes No*
N/A
For tank systems that utilize the monitoring system as the primary tank overfill warning device (i.e., no
mechanical overfill prevention valve is installed), is the overfill warning alarm visible and audible at the tank
fill point(s) and operating properly? If so, at what percent oftank capacity does the alarm trigger? %
Yes*NoWas any monitoring equipment replaced? If yes, identify specific sensors, probes, or other equipment replaced
and list the manufacturer name and model for all replacement parts in Section E, below.
Yes*NoWas liquid found inside any secondary containment systems designed as dry systems? (Check all that apply)
Product; Water. If yes, describe causes in Section E, below.
Yes No*Was monitoring system set-up reviewed to ensure proper settings? Attach set up reports, if applicable
Yes No*Is all monitoring equipment operational per manufacturer’s specifications?
* In Section E below, describe how and when these deficiencies were or will be corrected.
E.Comments:
Page 2 of 3
331.01
90
Monitoring System Certification
F.In-Tank Gauging / SIR Equipment: Check this box if tank gauging is used only for inventory control.
Check this box if no tank gauging or SIR equipment is installed.
This section must be completed if in-tank gauging equipment is used to perform leak detection monitoring.
Complete the following checklist:
Yes No*Has all input wiring been inspected for proper entry and termination, including testing for ground faults?
Yes No*Were all tank gauging probes visually inspected for damage and residue buildup?
Yes No*Was accuracy of system product level readings tested?
Yes No*Was accuracy of system water level readings tested?
Yes No*Were all probes reinstalled properly?
Yes No*Were all items on the equipment manufacturer’s maintenance checklist completed?
* In the Section H, below, describe how and when these deficiencies were or will be corrected.
G.Line Leak Detectors (LLD):Check this box if LLDs are not installed.
Complete the following checklist:
Yes No*
N/A
For equipment start-up or annual equipment certification, was a leak simulated to verify LLD performance?
(Check all that apply)Simulated leak rate: 3 g.p.h.; 0.1 g.p.h ; 0.2 g.p.h.
Yes No*Were all LLDs confirmed operational and accurate within regulatory requirements?
Yes No*Was the testing apparatus properly calibrated?
Yes No*
N/A
For mechanical LLDs, does the LLD restrict product flow if it detects a leak?
Yes No*
N/A
For electronic LLDs, does the turbine automatically shut off if the LLD detects a leak?
Yes No*
N/A
For electronic LLDs, does the turbine automatically shut off if any portion of the monitoring system is disabled
or disconnected?
Yes No*
N/A
For electronic LLDs, does the turbine automatically shut off if any portion of the monitoring system malfunctions
or fails a test?
Yes No*
N/A
For electronic LLDs, have all accessible wiring connections been visually inspected?
Yes No*Were all items on the equipment manufacturer’s maintenance checklist completed?
* In the Section H, below, describe how and when these deficiencies were or will be corrected.
H.Comments:
Page 3 of 3
Leak Detector Test Results Sheet
Customer Address: Work Order: Site Address:
Test Date:
Site Contact: Phone:
Technician: Phone: 800-339-9930 ICC No.:
Product Type LLD Type Model Serial No. Check
Valve
Holding
Pressure
Bleed
Off ML.
Leak
Rate
Tested:
Pass/Fail
3 gph @
10 psi
3 gph @
10 psi
3 gph @
10 psi
3 gph @
10 psi
3 gph @
10 psi
3 gph @
10 psi
3 gph @
10 psi
3 gph @
10 psi
Technician Name: Technician No.:
Signature: Date:
JacoHill
P.O.Box82515
Bakersfield,CA93380-2515
37029
09/16/2016
8174721-UT
Regular Mechanical FX1V
CameronMason
(661)393-7000OmeroGarcia
Bakersfield,CA93309
6401WhiteLane
#3360FarrellsFastrip
29 PSI200 ml Pass
FX1VMechanicalPremium 26 PSI200 ml Pass
FX1DVMechanicalDiesel 19 PSI150 ml Pass
CameronMason 8174721-UT
09/16/2016
Responses Received: 200 FASTRIP 6401 WHITE LANE BAKERSFIELD,CA 93309 AUG 16, 2016 9:14 AM TANK PRODUCT GALLONS INCHES WATER DEG F ULLAGE 1 UNL 8998 67.38 0.0 85.0 3002 2 PNL 7919 60.19 0.8 87.9 4081 3 DIESEL 6859 53.41 0.0 92.3 5141 I90500 AUG 16, 2016 9:14 AM SOFTWARE REVISION LEVEL VERSION 331.01 SOFTWARE# 346331-100-B CREATED - 11.03.22.16.28 S-MODULE# 330160-004-a SYSTEM FEATURES: PERIODIC IN-TANK TESTS ANNUAL IN-TANK TESTS ISD/APM I50500 AUG 16, 2016 9:14 AM SYSTEM TYPE AND LANGUAGE FLAG SYSTEM UNITS U.S. SYSTEM LANGUAGE ENGLISH SYSTEM DATE/TIME FORMAT MON DD YYYY HH:MM:SS xM
I50201 AUG 16, 2016 9:14 AM SHIFT TIME 1 : 7:00 AM I50202 AUG 16, 2016 9:14 AM SHIFT TIME 2 : DISABLED I50203 AUG 16, 2016 9:14 AM
SHIFT TIME 3 : DISABLED I50204 AUG 16, 2016 9:14 AM SHIFT TIME 4 : DISABLED I54600 AUG 16, 2016 9:14 AM TANK PER TST NEEDED WRN: DISABLED I54900 AUG 16, 2016 9:14 AM TANK ANN TST NEEDED WRN: DISABLED I55300 AUG 16, 2016 9:14 AM LINE RE-ENABLE METHOD PASS LINE TEST I55600 AUG 16, 2016 9:14 AM LINE PER TST NEEDED WRN: DISABLED I55900 AUG 16, 2016 9:14 AM LINE ANN TST NEEDED WRN: DISABLED
I50D00 AUG 16, 2016 9:14 AM PRINT TC VOLUMES ENABLED I50E00 AUG 16, 2016 9:14 AM TEMP COMPENSATION VALUE (DEG F ): 60.0
I60B00 AUG 16, 2016 9:14 AM STICK HEIGHT OFFSET ENABLE STATUS DISABLED I51400 AUG 16, 2016 9:14 AM H-PROTOCOL DATA FORMAT HEIGHT I51A01 AUG 16, 2016 9:14 AM DAYLIGHT SAVING TIME ENABLED ON I51B00 AUG 16, 2016 9:14 AM DAYLIGHT SAVING TIME START DATE MAR WEEK 2 SUN 2:00 AM END DATE NOV WEEK 1 SUN 2:00 AM I51600 AUG 16, 2016 9:14 AM RE-DIRECT LOCAL PRINTOUT DISABLED I50400
AUG 16, 2016 9:14 AM 232 SECURITY CODE PORT SECURITY CODE STATUS 1 000000 DISABLED 2 000000 DISABLED 3 000000 DISABLED 4 000000 DISABLED 5 000000 DISABLED 6 000000 DISABLED I21900
AUG 16, 2016 9:14 AM TANK CHART SECURITY DISABLED I5BD00 AUG 16, 2016 9:14 AM CUSTOM ALARM LABELS DISABLED I56000 AUG 16, 2016 9:14 AM MASS/DENSITY DISABLED I88101 AUG 16, 2016 9:14 AM PORT SETTINGS: COMM BOARD : 1 (RS-232) BAUD RATE : 9600 PARITY : NONE STOP BIT : 1 STOP DATA LENGTH: 8 DATA RS-232 SECURITY CODE : DISABLED I88102 AUG 16, 2016 9:14 AM PORT SETTINGS: COMM BOARD : 2 (RS-232) BAUD RATE : 9600
PARITY : NONE STOP BIT : 1 STOP DATA LENGTH: 8 DATA RS-232 SECURITY CODE : DISABLED I88103 AUG 16, 2016 9:14 AM PORT SETTINGS: COMM BOARD : 3 (EDIM ) RS-232 SECURITY CODE : DISABLED
I88104 AUG 16, 2016 9:14 AM I88105 AUG 16, 2016 9:14 AM I88106 AUG 16, 2016 9:14 AM I52000 AUG 16, 2016 9:14 AM RECEIVER AUTO DIAL TYPE & START TIME RCVR LOCATION LABEL DIAL TYPE START TIME 1 ON DATE ??? 16, 2016 DISABLED 2 ON DATE ??? 16, 2016 DISABLED 3 ON DATE ??? 16, 2016 DISABLED 4 ON DATE ??? 16, 2016 DISABLED 5 ON DATE ??? 16, 2016 DISABLED 6 ON DATE ??? 16, 2016 DISABLED 7 ON DATE ??? 16, 2016 DISABLED 8 ON DATE ??? 16, 2016 DISABLED I60100 AUG 16, 2016 9:14 AM TANK CONFIGURATION DEVICE LABEL CONFIGURED 1 UNL ON 2 PNL ON 3 DIESEL ON 4 OFF I60200
AUG 16, 2016 9:14 AM TANK PRODUCT LABEL TANK PRODUCT LABEL 1 UNL 2 PNL 3 DIESEL 4 I60300 AUG 16, 2016 9:14 AM TANK PRODUCT CODE TANK PRODUCT LABEL 1 UNL 1
2 PNL 2 3 DIESEL 3 4 4 I60900 AUG 16, 2016 9:14 AM TANK THERMAL COEFFICIENT TANK PRODUCT LABEL 1 UNL 0.000700 2 PNL 0.000700 3 DIESEL 0.000450 4 0.000000 I60700 AUG 16, 2016 9:14 AM TANK DIAMETER TANK PRODUCT LABEL INCHES 1 UNL 96.00 2 PNL 96.00 3 DIESEL 96.00 4 0.00 I60A00 AUG 16, 2016 9:14 AM TANK FULL VOLUME
TANK PRODUCT LABEL TANK PROFILE GALLONS 1 UNL 1 PT 12000 2 PNL 1 PT 12000 3 DIESEL 1 PT 12000 4 1 PT 0 I60400 AUG 16, 2016 9:14 AM TANK FULL VOLUME TANK PRODUCT LABEL GALLONS 1 UNL 12000 2 PNL 12000 3 DIESEL 12000 4 0 I60500 AUG 16, 2016 9:14 AM TANK 4 POINT VOLUMES TANK PRODUCT LABEL GALLONS 1 UNL 12000 0 0 0 2 PNL 12000 0 0 0 3 DIESEL 12000 0 0 0 4 0 0 0 0
I60600 AUG 16, 2016 9:14 AM TANK 20 POINT VOLUMES TANK PRODUCT LABEL GALLONS 1 UNL 12000 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 2 PNL 12000 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 3 DIESEL 12000 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 4 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 I61500 AUG 16, 2016 9:14 AM TANK PRODUCT LABEL METER DATA 1 UNL NO 2 PNL NO 3 DIESEL NO 4 NO I62F00 AUG 16, 2016 9:14 AM MAG PROBE FLOAT SIZE
TANK PRODUCT LABEL FLOAT SIZE: 1 UNL 4.0 IN. 2 PNL 4.0 IN. 3 DIESEL 4.0 IN. I62700 AUG 16, 2016 9:14 AM TANK HIGH WATER WARNING LIMIT TANK PRODUCT LABEL INCHES 1 UNL 2.0 2 PNL 2.0 3 DIESEL 2.0
I64200 AUG 16, 2016 9:14 AM WATER ALARM FILTER TANK PRODUCT LABEL 1 UNL LOW 2 PNL LOW 3 DIESEL LOW I62400 AUG 16, 2016 9:14 AM TANK HIGH WATER LEVEL LIMIT TANK PRODUCT LABEL INCHES 1 UNL 3.0 2 PNL 3.0 3 DIESEL 3.0 I62800 AUG 16, 2016 9:14 AM TANK MAXIMUM VOLUME LIMIT TANK PRODUCT LABEL GALLONS 1 UNL 12000 2 PNL 12000 3 DIESEL 12000 4 0 I62300 AUG 16, 2016 9:14 AM TANK OVERFILL LEVEL LIMIT TANK PRODUCT LABEL GALLONS 1 UNL 10800 2 PNL 10800 3 DIESEL 10800
4 0 I62200 AUG 16, 2016 9:14 AM TANK HIGH PRODUCT LIMIT TANK PRODUCT LABEL GALLONS 1 UNL 11400 2 PNL 11400 3 DIESEL 11400 4 0 I62900 AUG 16, 2016 9:14 AM
TANK DELIVERY REQUIRED LIMIT TANK PRODUCT LABEL GALLONS 1 UNL 1800 2 PNL 1800 3 DIESEL 1800 4 0 I62100 AUG 16, 2016 9:14 AM TANK LOW PRODUCT LIMIT TANK PRODUCT LABEL GALLONS 1 UNL 500 2 PNL 500 3 DIESEL 500 4 0 I62600 AUG 16, 2016 9:14 AM TANK LEAK ALARM LIMIT TANK PRODUCT LABEL GALLONS 1 UNL 99 2 PNL 99 3 DIESEL 99 4 99 I62500 AUG 16, 2016 9:14 AM TANK SUDDEN LOSS LIMIT TANK PRODUCT LABEL GALLONS 1 UNL 99 2 PNL 99 3 DIESEL 99 4 99
I60800 AUG 16, 2016 9:14 AM TANK TILT TANK PRODUCT LABEL INCHES 1 UNL 8.00 2 PNL 0.00 3 DIESEL 10.00 4 0.00 I60B00 AUG 16, 2016 9:14 AM STICK HEIGHT OFFSET ENABLE STATUS DISABLED
I60C00 AUG 16, 2016 9:14 AM TANK STICK HEIGHT OFFSET TANK PRODUCT LABEL INCHES 1 UNL 0.00 2 PNL 0.00 3 DIESEL 0.00 4 0.00 I61200 AUG 16, 2016 9:14 AM TANK MANIFOLDED PARTNERS TANK PRODUCT LABEL SIPHON MANIFOLDED TANKS LINE MANIFOLDED TANKS 1 UNL NONE NONE 2 PNL NONE NONE 3 DIESEL NONE NONE 4 NONE NONE I63600 AUG 16, 2016 9:14 AM PERIODIC LEAK TEST MIN VOLUME TANK PRODUCT LABEL GALLONS 1 UNL 120 2 PNL 120 3 DIESEL 120 4 0 I62A00 AUG 16, 2016 9:14 AM ANNUAL LEAK TEST MIN VOLUME TANK PRODUCT LABEL GALLONS 1 UNL 120 2 PNL 120
3 DIESEL 120 4 0 I62C00 AUG 16, 2016 9:14 AM TANK PERIODIC TEST TYPE TANK PRODUCT LABEL PERIODIC TEST TYPE 1 UNL STANDARD 2 PNL STANDARD 3 DIESEL STANDARD 4 STANDARD I62D00
AUG 16, 2016 9:14 AM TANK LEAK TEST FAIL ALARMS TANK PRODUCT LABEL 1 UNL GROSS TEST FAIL ALARM DISABLED PERIODIC TEST FAIL ALARM DISABLED ANNUAL TEST FAIL ALARM DISABLED 2 PNL GROSS TEST FAIL ALARM DISABLED PERIODIC TEST FAIL ALARM DISABLED ANNUAL TEST FAIL ALARM DISABLED 3 DIESEL GROSS TEST FAIL ALARM DISABLED PERIODIC TEST FAIL ALARM DISABLED ANNUAL TEST FAIL ALARM DISABLED 4 GROSS TEST FAIL ALARM DISABLED PERIODIC TEST FAIL ALARM DISABLED ANNUAL TEST FAIL ALARM DISABLED I63100 AUG 16, 2016 9:14 AM TANK LEAK TEST AVERAGING TANK PRODUCT LABEL ANNUAL PERIODIC 1 UNL OFF OFF 2 PNL OFF OFF 3 DIESEL OFF OFF 4 OFF OFF I63000 AUG 16, 2016 9:14 AM IN-TANK LEAK TEST NOTIFY TANK PRODUCT LABEL TANK TEST NOTIFY: 1 UNL OFF 2 PNL OFF
3 DIESEL OFF 4 OFF I63200 AUG 16, 2016 9:15 AM TANK TEST SIPHON BREAK TANK PRODUCT LABEL SIPHON BREAK 1 UNL OFF 2 PNL OFF 3 DIESEL OFF 4 OFF
I61000 AUG 16, 2016 9:15 AM TANK DELIVERY DELAY TANK PRODUCT LABEL 1 UNL 1 2 PNL 1 3 DIESEL 1 4 1 I63A00 AUG 16, 2016 9:15 AM LOW LEVEL PUMP THRESHOLD FOR SEQUENTIAL LINE MANIFOLD TANK PRODUCT LABEL PUMP THRESHOLD 1 UNL 10.00% 2 PNL 10.00% 3 DIESEL 10.00% 4 10.00% I61100 AUG 16, 2016 9:15 AM LEAK TEST METHOD - - - - - - - - - - - - TEST ON DATE : ALL TANK MAR 22, 2011 START TIME : DISABLED TEST RATE :0.20 GAL/HR DURATION : 2 HOURS TST EARLY STOP:DISABLED I61300 AUG 16, 2016 9:15 AM CSLD PROBABLITY OF DETECTION
I61400 AUG 16, 2016 9:15 AM CSLD CLIMATE FACTOR I61600 AUG 16, 2016 9:15 AM TANK PRODUCT LABEL CAL UPDATE 1 UNL IMMEDIATE 2 PNL IMMEDIATE 3 DIESEL IMMEDIATE 4 IMMEDIATE
I61A00 AUG 16, 2016 9:15 AM IN-TANK LEAK TEST EARLY STOP TANK PRODUCT LABEL TST EARLY STOP: 1 UNL DISABLED 2 PNL DISABLED 3 DIESEL DISABLED 4 DISABLED I61B00 AUG 16, 2016 9:15 AM IN-TANK LEAK GROSS TEST AUTO-CONFIRM I61C00 AUG 16, 2016 9:15 AM CSLD REPORT ONLY I62B00 AUG 16, 2016 9:15 AM TANK LAST ANNUAL TEST TANK PRODUCT LABEL DATE 1 UNL ??? 0, 0 2 PNL ??? 0, 0 3 DIESEL ??? 0, 0 4 ??? 0, 0 I63300 AUG 16, 2016 9:15 AM
LEAK TEST REPORT FORMAT: NORMAL I63400 AUG 16, 2016 9:15 AM RECONCILIATION WARNING LIMIT TANK PRODUCT LABEL GALLONS 1 UNL 0 2 PNL 0 3 DIESEL 0 4 0 I63500
AUG 16, 2016 9:15 AM RECONCILIATION ALARM LIMIT TANK PRODUCT LABEL GALLONS 1 UNL 1 2 PNL 1 3 DIESEL 1 4 1 I63900 AUG 16, 2016 9:15 AM ACCU CHART END SHAPE FACTOR TANK PRODUCT LABEL 1 UNL END FACTOR: NONE 2 PNL END FACTOR: NONE 3 DIESEL END FACTOR: NONE 4 END FACTOR: NONE I78000 AUG 16, 2016 9:15 AM I77700 AUG 16, 2016 9:15 AM
I77800 AUG 16, 2016 9:15 AM I78C00 AUG 16, 2016 9:15 AM I78300 AUG 16, 2016 9:15 AM I78F00 AUG 16, 2016 9:15 AM
I78700 AUG 16, 2016 9:15 AM I70200 AUG 16, 2016 9:15 AM LIQUID LABEL DEVICE LABEL 1 UNL STP 2 UNL ANN 3 UNL FILL 4 PNL STP 5 PNL FILL 6 PNL ANN 7 DIE STP 8 DIE FILL 9 10 DIS 1-2 11 DIS 3-4 12 DIS 5-6 13 DIS 7-8 14 15 16 DIE ANN I70300 AUG 16, 2016 9:15 AM LIQUID TYPE SENSOR LOCATION TYPE 1 UNL STP TRI-STATE (SINGLE FLOAT) 2 UNL ANN DUAL POINT HYDROSTATIC 3 UNL FILL TRI-STATE (SINGLE FLOAT) 4 PNL STP TRI-STATE (SINGLE FLOAT) 5 PNL FILL TRI-STATE (SINGLE FLOAT) 6 PNL ANN DUAL POINT HYDROSTATIC
7 DIE STP TRI-STATE (SINGLE FLOAT) 8 DIE FILL TRI-STATE (SINGLE FLOAT) 9 TRI-STATE (SINGLE FLOAT) 10 DIS 1-2 TRI-STATE (SINGLE FLOAT) 11 DIS 3-4 TRI-STATE (SINGLE FLOAT) 12 DIS 5-6 TRI-STATE (SINGLE FLOAT) 13 DIS 7-8 TRI-STATE (SINGLE FLOAT) 14 TRI-STATE (SINGLE FLOAT) 15 TRI-STATE (SINGLE FLOAT) 16 DIE ANN DUAL POINT HYDROSTATIC I70400 AUG 16, 2016 9:15 AM LIQUID CATEGORY
SENSOR LOCATION CATEGORY 1 UNL STP STP SUMP 2 UNL ANN ANNULAR SPACE 3 UNL FILL OTHER SENSORS 4 PNL STP STP SUMP 5 PNL FILL OTHER SENSORS 6 PNL ANN ANNULAR SPACE 7 DIE STP STP SUMP 8 DIE FILL OTHER SENSORS 9 OTHER SENSORS 10 DIS 1-2 DISPENSER PAN 11 DIS 3-4 DISPENSER PAN 12 DIS 5-6 DISPENSER PAN 13 DIS 7-8 DISPENSER PAN 14 OTHER SENSORS 15 OTHER SENSORS 16 DIE ANN ANNULAR SPACE I74200 AUG 16, 2016 9:15 AM I74300 AUG 16, 2016 9:15 AM I74400 AUG 16, 2016 9:15 AM I74700 AUG 16, 2016 9:15 AM I74800 AUG 16, 2016 9:15 AM
I74900 AUG 16, 2016 9:15 AM I7BC00 AUG 16, 2016 9:15 AM I80200 AUG 16, 2016 9:15 AM I80300 AUG 16, 2016 9:15 AM
I80400 AUG 16, 2016 9:15 AM I80700 AUG 16, 2016 9:15 AM RELAY LABEL DEVICE LABEL 1 UNL 2 PNL 3 DSL 4 OVERFILL I80900 AUG 16, 2016 9:15 AM RELAY ORIENTATION RELAY DESIGNATION ORIENTATION 1 UNL NORMALLY CLOSED 2 PNL NORMALLY CLOSED 3 DSL NORMALLY CLOSED 4 OVERFILL NORMALLY OPEN I80B00 AUG 16, 2016 9:15 AM RELAY TANK ASSIGNMENT RELAY DESIGNATION TANK 1 UNL 1 2 PNL 2 3 DSL 3 4 OVERFILL 1
I80A00 AUG 16, 2016 9:15 AM RELAY TYPE RELAY DESIGNATION TYPE 1 UNL STANDARD 2 PNL STANDARD 3 DSL STANDARD 4 OVERFILL STANDARD I80C00 AUG 16, 2016 9:15 AM
I80800 AUG 16, 2016 9:15 AM RELAY SETUP REPORT R 1:UNL TYPE: STANDARD NORMALLY CLOSED TANK #: 1 LIQUID SENSOR ALMS L 1:FUEL ALARM L10:FUEL ALARM L11:FUEL ALARM L12:FUEL ALARM L13:FUEL ALARM L 1:SENSOR OUT ALARM L10:SENSOR OUT ALARM L11:SENSOR OUT ALARM L12:SENSOR OUT ALARM L13:SENSOR OUT ALARM L 1:SHORT ALARM L10:SHORT ALARM L11:SHORT ALARM L12:SHORT ALARM L13:SHORT ALARM ISD SITE ALARMS ISD GROSS PRES FAIL ISD DEGRD PRES FAIL ISD VAPOR LEAK FAIL ISD VP PRES FAIL ISD VP STATUS FAIL ISD HOSE ALARMS ALL:GROSS COLLECT FAIL ALL:DEGRD COLLECT FAIL ALL:FLOW COLLECT FAIL R 2:PNL
TYPE: STANDARD NORMALLY CLOSED TANK #: 2 LIQUID SENSOR ALMS L 4:FUEL ALARM L10:FUEL ALARM L11:FUEL ALARM L12:FUEL ALARM L13:FUEL ALARM L 4:SENSOR OUT ALARM L10:SENSOR OUT ALARM L11:SENSOR OUT ALARM L12:SENSOR OUT ALARM L13:SENSOR OUT ALARM
L 4:SHORT ALARM L10:SHORT ALARM L11:SHORT ALARM L12:SHORT ALARM L13:SHORT ALARM ISD SITE ALARMS ISD GROSS PRES FAIL ISD DEGRD PRES FAIL ISD VAPOR LEAK FAIL ISD VP PRES FAIL ISD VP STATUS FAIL ISD HOSE ALARMS ALL:GROSS COLLECT FAIL ALL:DEGRD COLLECT FAIL ALL:FLOW COLLECT FAIL R 3:DSL TYPE: STANDARD NORMALLY CLOSED TANK #: 3 LIQUID SENSOR ALMS L 7:FUEL ALARM L10:FUEL ALARM L12:FUEL ALARM L 7:SENSOR OUT ALARM L10:SENSOR OUT ALARM L12:SENSOR OUT ALARM L 7:SHORT ALARM L10:SHORT ALARM L12:SHORT ALARM R 4:OVERFILL TYPE: STANDARD NORMALLY OPEN TANK #: 1
IN-TANK ALARMS ALL:OVERFILL ALARM ALL:HIGH PRODUCT ALARM ALL:MAX PRODUCT ALARM I79000 AUG 16, 2016 9:15 AM EDIM:1 VR:349634-003-C TD:06.05.11.11.15
I79100 AUG 16, 2016 9:15 AM I72300 AUG 16, 2016 9:15 AM FASTRIP 6401 WHITE LANE BAKERSFIELD,CA 93309 SMARTSENSOR ASSIGNMENT DEVICE LABEL CATEGORY 01 VP SENSOR DIS 3-4 VAPOR PRESSURE 02 FM DIS 1-2 AIR FLOW METER 03 FM DIS 3-4 AIR FLOW METER 04 FM DIS 5-6 AIR FLOW METER 05 FM DIS 7-8 AIR FLOW METER 06 UNKNOWN 07 UNKNOWN 08 UNKNOWN 09 UNKNOWN 10 UNKNOWN 11 UNKNOWN 12 UNKNOWN 13 UNKNOWN 14 UNKNOWN 15 UNKNOWN 16 UNKNOWN 17 UNKNOWN 18 UNKNOWN 19 UNKNOWN 20 UNKNOWN 21 UNKNOWN 22 UNKNOWN 23 UNKNOWN 24 UNKNOWN 25 UNKNOWN 26 UNKNOWN 27 UNKNOWN 28 UNKNOWN
29 UNKNOWN 30 UNKNOWN 31 UNKNOWN 32 UNKNOWN 33 UNKNOWN 34 UNKNOWN 35 UNKNOWN 36 UNKNOWN 37 UNKNOWN 38 UNKNOWN 39 UNKNOWN 40 UNKNOWN IV4E00 AUG 16, 2016 9:15 AM
FASTRIP 6401 WHITE LANE BAKERSFIELD,CA 93309 EVR/ISD SETUP TYPE: VACUUM ASSIST VACUUM ASSIST TYPE: HEALY VAC IV4F00 AUG 16, 2016 9:15 AM FASTRIP 6401 WHITE LANE BAKERSFIELD,CA 93309 NOZZLE A/L RANGE A/L RATIO: 0.95 - 1.15 IV4000 AUG 16, 2016 9:15 AM FASTRIP 6401 WHITE LANE BAKERSFIELD,CA 93309 VAPOR PROCESSOR TYPE NONE IV4700 AUG 16, 2016 9:15 AM FASTRIP 6401 WHITE LANE BAKERSFIELD,CA 93309
ASSESSMENT TIME START TIME: 10:05 AM TIME DELAY MINUTES: 1 IV5200 AUG 16, 2016 9:16 AM FASTRIP 6401 WHITE LANE BAKERSFIELD,CA 93309 ACCEPT HIGH ORVR: NO IV4A00
AUG 16, 2016 9:16 AM FASTRIP 6401 WHITE LANE BAKERSFIELD,CA 93309 ISD HOSE TABLE HOSE FP FP AFM HOSE ID ID LABEL ID LABEL 01 01 01 01 BLEND3 02 02 02 01 BLEND3 03 03 03 02 BLEND3 04 04 04 02 BLEND3 05 05 05 03 BLEND3 06 06 06 03 BLEND3 07 07 07 04 BLEND3 08 08 08 04 BLEND3 IV4B00 AUG 16, 2016 9:16 AM FASTRIP 6401 WHITE LANE BAKERSFIELD,CA 93309 PRODUCT/HOSE MAP TABLE FP AFID M1/H1 M2/H2 M3/H3 M4/H4 01 01 02/01 03/01 09/01 xx/xx 02 01 02/02 03/02 09/02 xx/xx 03 02 02/03 03/03 09/03 xx/xx 04 02 02/04 03/04 09/04 xx/xx 05 03 02/05 03/05 09/05 xx/xx 06 03 02/06 03/06 09/06 xx/xx 07 04 02/07 03/07 09/07 xx/xx 08 04 02/08 03/08 09/08 xx/xx IV4900
AUG 16, 2016 9:16 AM FASTRIP 6401 WHITE LANE BAKERSFIELD,CA 93309 LABEL TABLE ID LABEL 01 UNASSIGNED 02 BLEND3 03 REGULAR 04 MID GRADE 05 PREMIUM 06 GOLD 07 BRONZE 08 SILVER 09 BLEND2
10 BLEND4 IV1000 AUG 16, 2016 9:16 AM ISD VERSION: 01.04
Responses Received: I10200 AUG 16, 2016 9:17 AM FASTRIP 6401 WHITE LANE BAKERSFIELD,CA 93309 SYSTEM CONFIGURATION SLOT BOARD TYPE POWER ON RESET CURRENT 1 8SMARTSENSOR BD 39680 39501 2 4 PROBE / G.T. 164579 163950 3 INTERSTITIAL BD 203255 202659 4 INTERSTITIAL BD 202902 202156 5 UNUSED 9885416 9794589 6 UNUSED 9868181 9781523 7 UNUSED 9867504 9778952 8 UNUSED 9859248 9779457 9 STP SENSE BOARD 33066 33028 10 RELAY BOARD 15022 15029 11 UNUSED 9867737 9782155 12 UNUSED 9863722 9776415 13 UNUSED 9859368 9780433 14 UNUSED 9851630 9783877 15 UNUSED 9852984 9786380 16 UNUSED 9862977 9779836 COMM 1 RS232 SERIAL BD 14999 15029 COMM 2 RS232 SERIAL BD 15067 15076 COMM 3 ELEC DISP INT. 101804 101629 COMM 4 UNUSED 9865977 9784979 COMM 5 UNUSED 9855623 9781719 COMM 6 UNUSED 9852465 9786885 I90200 AUG 16, 2016 9:17 AM SOFTWARE REVISION LEVEL VERSION 331.01 SOFTWARE# 346331-100-B CREATED - 11.03.22.16.28
S-MODULE# 330160-004-a SYSTEM FEATURES: PERIODIC IN-TANK TESTS ANNUAL IN-TANK TESTS ISD/APM I11100 AUG 16, 2016 9:17 AM FASTRIP 6401 WHITE LANE BAKERSFIELD,CA 93309 PRIORITY ALARM HISTORY ID CATEGORY DESCRIPTION ALARM TYPE STATE DATE TIME
T 1 TANK UNL PROBE OUT CLEAR 8-16-16 9:11AM T 1 TANK UNL PROBE OUT ALARM 8-16-16 9:10AM T 2 TANK PNL PROBE OUT CLEAR 8-16-16 9:09AM T 2 TANK PNL PROBE OUT ALARM 8-16-16 9:08AM T 3 TANK DIESEL PROBE OUT CLEAR 8-16-16 9:07AM T 3 TANK DIESEL PROBE OUT ALARM 8-16-16 9:06AM T 3 TANK DIESEL PROBE OUT CLEAR 8-08-16 10:22AM L 6 ANNULAR PNL ANN SENSOR OUT ALARM CLEAR 8-08-16 10:17AM L 2 ANNULAR UNL ANN SENSOR OUT ALARM CLEAR 8-08-16 10:17AM L 7 STP SUMP DIE STP SENSOR OUT ALARM CLEAR 8-08-16 10:17AM L 1 STP SUMP UNL STP SENSOR OUT ALARM CLEAR 8-08-16 10:17AM L 4 STP SUMP PNL STP SENSOR OUT ALARM CLEAR 8-08-16 10:17AM L 5 OTHER PNL FILL SENSOR OUT ALARM CLEAR 8-08-16 10:17AM L 3 OTHER UNL FILL SENSOR OUT ALARM CLEAR 8-08-16 10:17AM L 8 OTHER DIE FILL SENSOR OUT ALARM CLEAR 8-08-16 10:17AM L12 DISP PAN DIS 5-6 SENSOR OUT ALARM CLEAR 8-08-16 10:17AM L11 DISP PAN DIS 3-4 SENSOR OUT ALARM CLEAR 8-08-16 10:17AM L10 DISP PAN DIS 1-2 SENSOR OUT ALARM CLEAR 8-08-16 10:17AM L16 ANNULAR DIE ANN SENSOR OUT ALARM CLEAR 8-08-16 10:17AM L13 DISP PAN DIS 7-8 SENSOR OUT ALARM CLEAR 8-08-16 10:17AM L10 DISP PAN DIS 1-2 SENSOR OUT ALARM ALARM 8-08-16 10:15AM L 7 STP SUMP DIE STP SENSOR OUT ALARM ALARM 8-08-16 10:15AM L 2 ANNULAR UNL ANN SENSOR OUT ALARM ALARM 8-08-16 10:15AM L16 ANNULAR DIE ANN SENSOR OUT ALARM ALARM 8-08-16 10:15AM L13 DISP PAN DIS 7-8 SENSOR OUT ALARM ALARM 8-08-16 10:15AM L 6 ANNULAR PNL ANN SENSOR OUT ALARM ALARM 8-08-16 10:15AM L12 DISP PAN DIS 5-6 SENSOR OUT ALARM ALARM 8-08-16 10:15AM L 5 OTHER PNL FILL SENSOR OUT ALARM ALARM 8-08-16 10:15AM L 4 STP SUMP PNL STP SENSOR OUT ALARM ALARM 8-08-16 10:15AM L11 DISP PAN DIS 3-4 SENSOR OUT ALARM ALARM 8-08-16 10:15AM L 3 OTHER UNL FILL SENSOR OUT ALARM ALARM 8-08-16 10:15AM L 8 OTHER DIE FILL SENSOR OUT ALARM ALARM 8-08-16 10:15AM L 1 STP SUMP UNL STP SENSOR OUT ALARM ALARM 8-08-16 10:15AM L13 DISP PAN DIS 7-8 FUEL ALARM CLEAR 8-08-16 10:09AM L13 DISP PAN DIS 7-8 FUEL ALARM ALARM 8-08-16 10:07AM L12 DISP PAN DIS 5-6 FUEL ALARM CLEAR 8-08-16 10:07AM L12 DISP PAN DIS 5-6 FUEL ALARM ALARM 8-08-16 10:06AM L11 DISP PAN DIS 3-4 FUEL ALARM CLEAR 8-08-16 10:06AM L11 DISP PAN DIS 3-4 FUEL ALARM ALARM 8-08-16 10:06AM L10 DISP PAN DIS 1-2 FUEL ALARM CLEAR 8-08-16 10:05AM L10 DISP PAN DIS 1-2 FUEL ALARM ALARM 8-08-16 10:04AM L16 ANNULAR DIE ANN HIGH LIQUID ALARM CLEAR 8-08-16 10:03AM L16 ANNULAR DIE ANN LOW LIQUID ALARM CLEAR 8-08-16 10:01AM L16 ANNULAR DIE ANN HIGH LIQUID ALARM ALARM 8-08-16 10:01AM L16 ANNULAR DIE ANN LOW LIQUID ALARM ALARM 8-08-16 10:01AM L 8 OTHER DIE FILL FUEL ALARM CLEAR 8-08-16 10:01AM T 3 TANK DIESEL PROBE OUT ALARM 8-08-16 10:01AM L 8 OTHER DIE FILL FUEL ALARM ALARM 8-08-16 10:00AM T 2 TANK PNL PROBE OUT CLEAR 8-08-16 10:00AM T 2 TANK PNL PROBE OUT ALARM 8-08-16 10:00AM I11200 AUG 16, 2016 9:17 AM FASTRIP 6401 WHITE LANE BAKERSFIELD,CA 93309 NON-PRIORITY ALARM HISTORY ID CATEGORY DESCRIPTION ALARM TYPE STATE DATE TIME
T 2 TANK PNL INVALID FUEL LEVEL CLEAR 8-16-16 9:09AM T 2 TANK PNL INVALID FUEL LEVEL ALARM 8-16-16 9:09AM SYSTEM PRINTER ERROR CLEAR 8-15-16 3:22AM SYSTEM PAPER OUT CLEAR 8-15-16 3:22AM SYSTEM PRINTER ERROR ALARM 8-15-16 3:22AM SYSTEM PAPER OUT ALARM 8-15-16 3:22AM T 2 TANK PNL LOW TEMP WARNING CLEAR 8-08-16 10:00AM T 2 TANK PNL LOW TEMP WARNING ALARM 8-08-16 10:00AM T 1 TANK UNL LOW TEMP WARNING CLEAR 8-08-16 9:58AM T 1 TANK UNL LOW TEMP WARNING ALARM 8-08-16 9:57AM T 1 TANK UNL HIGH PRODUCT ALARM CLEAR 8-08-16 9:55AM T 1 TANK UNL HIGH PRODUCT ALARM ALARM 8-08-16 9:54AM T 1 TANK UNL HIGH PRODUCT ALARM CLEAR 8-08-16 9:53AM T 1 TANK UNL HIGH PRODUCT ALARM ALARM 8-08-16 9:52AM T 3 TANK DIESEL HIGH PRODUCT ALARM CLEAR 8-08-16 9:51AM T 3 TANK DIESEL HIGH PRODUCT ALARM ALARM 8-08-16 9:51AM T 3 TANK DIESEL HIGH PRODUCT ALARM CLEAR 8-08-16 9:47AM T 3 TANK DIESEL HIGH PRODUCT ALARM ALARM 8-08-16 9:47AM T 2 TANK PNL HIGH WATER WARNING CLEAR 8-08-16 9:27AM T 2 TANK PNL INVALID FUEL LEVEL CLEAR 8-08-16 9:23AM T 2 TANK PNL DELIVERY NEEDED CLEAR 8-08-16 9:23AM T 2 TANK PNL HIGH WATER WARNING ALARM 8-08-16 9:20AM T 2 TANK PNL DELIVERY NEEDED ALARM 8-08-16 9:16AM T 2 TANK PNL INVALID FUEL LEVEL ALARM 8-08-16 9:16AM SYSTEM PRINTER ERROR CLEAR 7-06-16 4:10PM SYSTEM PAPER OUT CLEAR 7-06-16 4:10PM SYSTEM PRINTER ERROR ALARM 7-06-16 4:10PM SYSTEM PAPER OUT ALARM 7-06-16 4:10PM SYSTEM PRINTER ERROR CLEAR 7-06-16 4:03PM SYSTEM PAPER OUT CLEAR 7-06-16 4:03PM SYSTEM PRINTER ERROR ALARM 7-06-16 4:03PM SYSTEM PAPER OUT ALARM 7-06-16 4:03PM SYSTEM PRINTER ERROR CLEAR 7-06-16 4:03PM SYSTEM PAPER OUT CLEAR 7-06-16 4:03PM SYSTEM PRINTER ERROR ALARM 7-06-16 4:03PM SYSTEM PAPER OUT ALARM 7-06-16 4:03PM SYSTEM PRINTER ERROR CLEAR 7-06-16 4:03PM SYSTEM PAPER OUT CLEAR 7-06-16 4:03PM SYSTEM PRINTER ERROR ALARM 7-06-16 4:03PM SYSTEM PAPER OUT ALARM 7-06-16 4:03PM OTHER ISD VAPOR LEAK WARN CLEAR 6-30-16 10:05AM OTHER ISD VAPOR LEAK WARN ALARM 6-29-16 10:06AM T 1 TANK UNL DELIVERY NEEDED CLEAR 6-28-16 7:57PM T 1 TANK UNL INVALID FUEL LEVEL CLEAR 6-28-16 7:56PM T 1 TANK UNL INVALID FUEL LEVEL ALARM 6-28-16 6:28PM
T 1 TANK UNL DELIVERY NEEDED ALARM 6-28-16 5:20PM T 1 TANK UNL DELIVERY NEEDED CLEAR 6-27-16 3:05PM T 1 TANK UNL INVALID FUEL LEVEL CLEAR 6-27-16 3:04PM T 1 TANK UNL INVALID FUEL LEVEL ALARM 6-27-16 2:02PM T 1 TANK UNL DELIVERY NEEDED ALARM 6-27-16 12:38PM I20600 AUG 16, 2016 9:18 AM FASTRIP 6401 WHITE LANE BAKERSFIELD,CA 93309 TANK ALARM HISTORY
TANK 1 UNL OVERFILL ALARM AUG 8, 2016 9:55 AM AUG 31, 2015 8:27 AM AUG 30, 2015 3:47 PM HIGH PRODUCT ALARM AUG 8, 2016 9:54 AM AUG 8, 2016 9:52 AM AUG 31, 2015 8:29 AM INVALID FUEL LEVEL JUN 28, 2016 6:28 PM JUN 27, 2016 2:02 PM JUN 23, 2016 11:38 AM PROBE OUT AUG 16, 2016 9:10 AM AUG 8, 2016 9:56 AM AUG 8, 2016 9:14 AM DELIVERY NEEDED JUN 28, 2016 5:20 PM JUN 27, 2016 12:38 PM JUN 24, 2016 11:46 AM MAX PRODUCT ALARM AUG 8, 2016 9:55 AM AUG 13, 2015 9:46 AM LOW TEMP WARNING AUG 8, 2016 9:57 AM AUG 7, 2015 9:55 AM AUG 14, 2014 9:16 AM TANK 2 PNL HIGH WATER ALARM AUG 8, 2016 9:20 AM OVERFILL ALARM AUG 8, 2016 9:46 AM JUL 12, 2016 3:41 PM JUL 12, 2016 3:33 PM HIGH PRODUCT ALARM AUG 13, 2015 9:50 AM AUG 7, 2015 9:58 AM INVALID FUEL LEVEL AUG 16, 2016 9:09 AM AUG 8, 2016 9:16 AM JUL 25, 2014 9:26 AM
PROBE OUT AUG 16, 2016 9:08 AM AUG 8, 2016 10:00 AM AUG 8, 2016 9:16 AM HIGH WATER WARNING AUG 8, 2016 9:20 AM DELIVERY NEEDED AUG 8, 2016 9:16 AM MAY 4, 2016 4:11 PM APR 27, 2016 8:11 PM LOW TEMP WARNING AUG 8, 2016 10:00 AM AUG 13, 2015 9:51 AM AUG 13, 2015 9:49 AM TANK 3 DIESEL OVERFILL ALARM AUG 8, 2016 9:47 AM AUG 13, 2015 9:54 AM
AUG 7, 2015 10:05 AM HIGH PRODUCT ALARM AUG 8, 2016 9:51 AM AUG 8, 2016 9:47 AM AUG 13, 2015 9:54 AM INVALID FUEL LEVEL FEB 19, 2016 5:42 PM FEB 12, 2016 1:28 PM JAN 26, 2016 3:28 PM PROBE OUT AUG 16, 2016 9:06 AM AUG 8, 2016 10:01 AM AUG 8, 2016 9:49 AM DELIVERY NEEDED FEB 19, 2016 8:13 AM FEB 12, 2016 8:16 AM JAN 31, 2016 12:50 AM LOW TEMP WARNING JUL 25, 2014 9:24 AM AUG 14, 2013 1:37 PM AUG 14, 2013 1:05 PM I38200 AUG 16, 2016 9:18 AM I30200 AUG 16, 2016 9:18 AM FASTRIP 6401 WHITE LANE BAKERSFIELD,CA 93309 LIQUID ALARM HISTORY REPORT SENSOR LOCATION 1 UNL STP AUG 8, 2016 10:15 AM SENSOR OUT ALARM AUG 8, 2016 9:27 AM FUEL ALARM JUN 3, 2016 10:34 AM FUEL ALARM
2 UNL ANN AUG 8, 2016 10:15 AM SENSOR OUT ALARM AUG 8, 2016 9:31 AM LOW LIQUID ALARM AUG 8, 2016 9:31 AM HIGH LIQUID ALARM 3 UNL FILL AUG 8, 2016 10:15 AM SENSOR OUT ALARM AUG 8, 2016 9:32 AM FUEL ALARM MAY 5, 2016 8:02 PM FUEL ALARM 4 PNL STP AUG 8, 2016 10:15 AM SENSOR OUT ALARM AUG 8, 2016 9:33 AM FUEL ALARM JUL 11, 2016 10:03 AM FUEL ALARM 5 PNL FILL AUG 8, 2016 10:15 AM SENSOR OUT ALARM AUG 8, 2016 9:34 AM FUEL ALARM JUL 1, 2016 11:54 AM SENSOR OUT ALARM 6 PNL ANN AUG 8, 2016 10:15 AM SENSOR OUT ALARM
AUG 8, 2016 9:37 AM LOW LIQUID ALARM AUG 8, 2016 9:37 AM HIGH LIQUID ALARM 7 DIE STP AUG 8, 2016 10:15 AM SENSOR OUT ALARM AUG 8, 2016 9:56 AM FUEL ALARM AUG 8, 2016 9:53 AM SENSOR OUT ALARM 8 DIE FILL AUG 8, 2016 10:15 AM SENSOR OUT ALARM AUG 8, 2016 10:00 AM FUEL ALARM JUL 1, 2016 11:59 AM SENSOR OUT ALARM 10 DIS 1-2 AUG 8, 2016 10:15 AM SENSOR OUT ALARM AUG 8, 2016 10:04 AM FUEL ALARM FEB 16, 2016 2:54 PM SENSOR OUT ALARM 11 DIS 3-4 AUG 8, 2016 10:15 AM SENSOR OUT ALARM AUG 8, 2016 10:06 AM FUEL ALARM FEB 16, 2016 2:55 PM SENSOR OUT ALARM 12 DIS 5-6 AUG 8, 2016 10:15 AM SENSOR OUT ALARM AUG 8, 2016 10:06 AM FUEL ALARM FEB 16, 2016 2:52 PM SENSOR OUT ALARM 13 DIS 7-8 AUG 8, 2016 10:15 AM SENSOR OUT ALARM AUG 8, 2016 10:07 AM FUEL ALARM AUG 13, 2015 9:56 AM SENSOR OUT ALARM 16 DIE ANN AUG 8, 2016 10:15 AM SENSOR OUT ALARM AUG 8, 2016 10:01 AM HIGH LIQUID ALARM AUG 8, 2016 10:01 AM LOW LIQUID ALARM I31600 AUG 16, 2016 9:18 AM FASTRIP 6401 WHITE LANE BAKERSFIELD,CA 93309 SMART SENSOR ALARM HISTORY REPORT SENSOR LOCATION 1 VP SENSOR DIS 3-4
2 FM DIS 1-2 3 FM DIS 3-4 4 FM DIS 5-6 5 FM DIS 7-8 I40200 AUG 16, 2016 9:18 AM I40300 AUG 16, 2016 9:18 AM I34200
AUG 16, 2016 9:18 AM I34700 AUG 16, 2016 9:18 AM IV0100 AUG 16, 2016 9:18 AM FASTRIP 6401 WHITE LANE BAKERSFIELD,CA 93309 ISD ALARM STATUS REPORT EVR TYPE: VACUUM ASSIST ISD TYPE: 01.04 VAPOR PROCESSOR TYPE: NONE OVERALL STATUS :PASS EVR VAPOR COLLECTION :PASS EVR VAPOR CONTAINMENT :PASS ISD MONITOR UP-TIME :100% EVR/ISD PASS TIME :100% WARNING ALARMS DATE TIME DESCRIPTION READING VALUE 16-06-29 10:06:09 VAPOR CONTAINMENT LEAKAGE CFH@2 INCHES WC 51.07 16-06-20 10:06:09 A/L RATIO DEGRADATION FP 6 BLEND3 0.80 16-06-07 10:06:09 VAPOR CONTAINMENT LEAKAGE CFH@2 INCHES WC 9.22 16-06-06 10:06:09 VAPOR CONTAINMENT LEAKAGE CFH@2 INCHES WC 9.22 16-06-05 10:06:09 VAPOR CONTAINMENT LEAKAGE CFH@2 INCHES WC 9.22 16-06-04 10:06:09 VAPOR CONTAINMENT LEAKAGE CFH@2 INCHES WC 10.45 16-02-28 10:07:48 CONTAINMENT GROSS OVER PRESSURE WEEKLY 95% 2.50 16-02-21 10:07:51 CONTAINMENT GROSS OVER PRESSURE WEEKLY 95% 2.84 16-02-14 10:09:05 CONTAINMENT GROSS OVER PRESSURE WEEKLY 95% 2.00 16-01-11 10:07:59 CONTAINMENT GROSS OVER PRESSURE WEEKLY 95% 2.93 FAILURE ALARMS DATE TIME DESCRIPTION READING VALUE 15-12-27 10:07:23 A/L RATIO DEGRADATION FP 5 BLEND3 0.76 11-10-02 10:02:09 A/L RATIO GROSS BLOCKAGE FP 2 BLEND3 BLKD
11-10-02 10:02:09 A/L RATIO GROSS BLOCKAGE FP 1 BLEND3 BLKD 11-09-12 10:04:11 A/L RATIO GROSS BLOCKAGE FP 1 BLEND3 BLKD 11-09-08 10:03:18 CONTAINMENT GROSS OVER PRESSURE WEEKLY 95% 2.72 11-08-22 00:01:32 A/L RATIO GROSS BLOCKAGE FP 4 BLEND3 BLKD 11-08-22 00:01:32 A/L RATIO GROSS BLOCKAGE FP 3 BLEND3 BLKD 10-12-27 10:01:40 A/L RATIO GROSS BLOCKAGE FP 8 BLEND3 BLKD 10-12-27 10:01:40 A/L RATIO GROSS BLOCKAGE FP 7 BLEND3 BLKD 10-12-26 10:01:25 A/L RATIO GROSS BLOCKAGE FP 7 BLEND3 BLKD SHUTDOWN & MISCELLANEOUS EVENTS DATE TIME DESCRIPTION ACTION/NAME 16-08-11 10:07:23 READINESS ISD:PP EVR:PP ISD & EVR READY 16-08-10 10:06:09 READINESS ISD:PP EVR:NP EVR READINESS PENDING 16-08-09 10:06:09 READINESS ISD:PP EVR:NP EVR READINESS PENDING 16-08-08 10:20:18 READINESS ISD:PP EVR:NN EVR READINESS PENDING 16-08-08 10:20:18 ISD STARTUP 16-08-08 10:20:12 ISD SHUTDOWN 16-06-07 16:52:36 CONTAINMENT VAPOR LEAKAGE TEST MANUALLY CLEARED
16-03-13 03:00:00 TIME CHANGE DETECTED AT: 16-03-13 02:00:13 16-02-28 10:13:27 CONTAINMENT GROSS & DEGRD TEST MANUALLY CLEARED 16-02-21 10:08:56 CONTAINMENT GROSS & DEGRD TEST MANUALLY CLEARED
Responses Received: I10200 AUG 16, 2016 10:55 AM FASTRIP 6401 WHITE LANE BAKERSFIELD,CA 93309 SYSTEM CONFIGURATION SLOT BOARD TYPE POWER ON RESET CURRENT 1 8SMARTSENSOR BD 39680 39568 2 4 PROBE / G.T. 164579 164137 3 INTERSTITIAL BD 203255 202842 4 INTERSTITIAL BD 202902 202364 5 UNUSED 9885416 9818005 6 UNUSED 9868181 9804957 7 UNUSED 9867504 9803214 8 UNUSED 9859248 9805209 9 STP SENSE BOARD 33066 33058 10 RELAY BOARD 15022 15014 11 UNUSED 9867737 9810726 12 UNUSED 9863722 9802585 13 UNUSED 9859368 9801782 14 UNUSED 9851630 9799191 15 UNUSED 9852984 9805910 16 UNUSED 9862977 9801599 COMM 1 RS232 SERIAL BD 14999 15014 COMM 2 RS232 SERIAL BD 15067 15083 COMM 3 ELEC DISP INT. 101804 101757 COMM 4 UNUSED 9865977 9808777 COMM 5 UNUSED 9855623 9800865 COMM 6 UNUSED 9852465 9798411 I90200 AUG 16, 2016 10:55 AM SOFTWARE REVISION LEVEL VERSION 331.01 SOFTWARE# 346331-100-B CREATED - 11.03.22.16.28
S-MODULE# 330160-004-a SYSTEM FEATURES: PERIODIC IN-TANK TESTS ANNUAL IN-TANK TESTS ISD/APM I11100 AUG 16, 2016 10:55 AM FASTRIP 6401 WHITE LANE BAKERSFIELD,CA 93309 PRIORITY ALARM HISTORY ID CATEGORY DESCRIPTION ALARM TYPE STATE DATE TIME
T 3 TANK DIESEL PROBE OUT CLEAR 8-16-16 10:03AM T 3 TANK DIESEL OVERFILL ALARM CLEAR 8-16-16 10:02AM T 3 TANK DIESEL PROBE OUT ALARM 8-16-16 10:02AM T 3 TANK DIESEL OVERFILL ALARM ALARM 8-16-16 10:02AM T 2 TANK PNL PROBE OUT CLEAR 8-16-16 10:00AM T 2 TANK PNL OVERFILL ALARM CLEAR 8-16-16 10:00AM T 2 TANK PNL PROBE OUT ALARM 8-16-16 10:00AM T 2 TANK PNL OVERFILL ALARM ALARM 8-16-16 10:00AM T 1 TANK UNL PROBE OUT CLEAR 8-16-16 9:57AM T 1 TANK UNL OVERFILL ALARM CLEAR 8-16-16 9:57AM T 1 TANK UNL PROBE OUT ALARM 8-16-16 9:57AM T 1 TANK UNL OVERFILL ALARM ALARM 8-16-16 9:56AM L 2 ANNULAR UNL ANN SENSOR OUT ALARM CLEAR 8-16-16 9:53AM L 8 OTHER DIE FILL SENSOR OUT ALARM CLEAR 8-16-16 9:53AM L 1 STP SUMP UNL STP SENSOR OUT ALARM CLEAR 8-16-16 9:53AM L 7 STP SUMP DIE STP SENSOR OUT ALARM CLEAR 8-16-16 9:53AM L 4 STP SUMP PNL STP SENSOR OUT ALARM CLEAR 8-16-16 9:53AM L 6 ANNULAR PNL ANN SENSOR OUT ALARM CLEAR 8-16-16 9:53AM L12 DISP PAN DIS 5-6 SENSOR OUT ALARM CLEAR 8-16-16 9:53AM L 3 OTHER UNL FILL SENSOR OUT ALARM CLEAR 8-16-16 9:53AM L13 DISP PAN DIS 7-8 SENSOR OUT ALARM CLEAR 8-16-16 9:53AM L11 DISP PAN DIS 3-4 SENSOR OUT ALARM CLEAR 8-16-16 9:53AM L 5 OTHER PNL FILL SENSOR OUT ALARM CLEAR 8-16-16 9:53AM L10 DISP PAN DIS 1-2 SENSOR OUT ALARM CLEAR 8-16-16 9:53AM L16 ANNULAR DIE ANN SENSOR OUT ALARM CLEAR 8-16-16 9:53AM L10 DISP PAN DIS 1-2 SENSOR OUT ALARM ALARM 8-16-16 9:50AM L16 ANNULAR DIE ANN SENSOR OUT ALARM ALARM 8-16-16 9:50AM L 6 ANNULAR PNL ANN SENSOR OUT ALARM ALARM 8-16-16 9:50AM L12 DISP PAN DIS 5-6 SENSOR OUT ALARM ALARM 8-16-16 9:50AM L11 DISP PAN DIS 3-4 SENSOR OUT ALARM ALARM 8-16-16 9:50AM L 4 STP SUMP PNL STP SENSOR OUT ALARM ALARM 8-16-16 9:50AM L 3 OTHER UNL FILL SENSOR OUT ALARM ALARM 8-16-16 9:50AM L 2 ANNULAR UNL ANN SENSOR OUT ALARM ALARM 8-16-16 9:50AM L13 DISP PAN DIS 7-8 SENSOR OUT ALARM ALARM 8-16-16 9:50AM L 8 OTHER DIE FILL SENSOR OUT ALARM ALARM 8-16-16 9:50AM L 7 STP SUMP DIE STP SENSOR OUT ALARM ALARM 8-16-16 9:50AM L 5 OTHER PNL FILL SENSOR OUT ALARM ALARM 8-16-16 9:50AM L 1 STP SUMP UNL STP SENSOR OUT ALARM ALARM 8-16-16 9:50AM L13 DISP PAN DIS 7-8 FUEL ALARM CLEAR 8-16-16 9:43AM L13 DISP PAN DIS 7-8 FUEL ALARM ALARM 8-16-16 9:43AM L12 DISP PAN DIS 5-6 FUEL ALARM CLEAR 8-16-16 9:43AM L12 DISP PAN DIS 5-6 FUEL ALARM ALARM 8-16-16 9:42AM L11 DISP PAN DIS 3-4 FUEL ALARM CLEAR 8-16-16 9:42AM L11 DISP PAN DIS 3-4 FUEL ALARM ALARM 8-16-16 9:42AM L10 DISP PAN DIS 1-2 FUEL ALARM CLEAR 8-16-16 9:41AM
L10 DISP PAN DIS 1-2 FUEL ALARM ALARM 8-16-16 9:41AM L16 ANNULAR DIE ANN LOW LIQUID ALARM CLEAR 8-16-16 9:40AM L16 ANNULAR DIE ANN LOW LIQUID ALARM ALARM 8-16-16 9:40AM L16 ANNULAR DIE ANN HIGH LIQUID ALARM CLEAR 8-16-16 9:40AM L16 ANNULAR DIE ANN LOW LIQUID ALARM CLEAR 8-16-16 9:40AM I11200 AUG 16, 2016 10:56 AM FASTRIP 6401 WHITE LANE BAKERSFIELD,CA 93309 NON-PRIORITY ALARM HISTORY ID CATEGORY DESCRIPTION ALARM TYPE STATE DATE TIME
T 3 TANK DIESEL LOW TEMP WARNING CLEAR 8-16-16 10:03AM T 3 TANK DIESEL LOW TEMP WARNING ALARM 8-16-16 10:03AM T 1 TANK UNL HIGH PRODUCT ALARM CLEAR 8-16-16 9:55AM T 1 TANK UNL HIGH PRODUCT ALARM ALARM 8-16-16 9:54AM SYSTEM PRINTER ERROR CLEAR 8-16-16 9:53AM SYSTEM PAPER OUT CLEAR 8-16-16 9:53AM SYSTEM PRINTER ERROR ALARM 8-16-16 9:52AM SYSTEM PAPER OUT ALARM 8-16-16 9:52AM SYSTEM PRINTER ERROR CLEAR 8-16-16 9:52AM SYSTEM PAPER OUT CLEAR 8-16-16 9:52AM SYSTEM PRINTER ERROR ALARM 8-16-16 9:52AM SYSTEM PAPER OUT ALARM 8-16-16 9:52AM SYSTEM PRINTER ERROR CLEAR 8-16-16 9:52AM SYSTEM PAPER OUT CLEAR 8-16-16 9:52AM SYSTEM PRINTER ERROR ALARM 8-16-16 9:52AM SYSTEM PAPER OUT ALARM 8-16-16 9:52AM SYSTEM PRINTER ERROR CLEAR 8-16-16 9:52AM SYSTEM PAPER OUT CLEAR 8-16-16 9:52AM SYSTEM PAPER OUT ALARM 8-16-16 9:50AM SYSTEM PRINTER ERROR ALARM 8-16-16 9:50AM T 2 TANK PNL INVALID FUEL LEVEL CLEAR 8-16-16 9:09AM T 2 TANK PNL INVALID FUEL LEVEL ALARM 8-16-16 9:09AM SYSTEM PRINTER ERROR CLEAR 8-15-16 3:22AM SYSTEM PAPER OUT CLEAR 8-15-16 3:22AM SYSTEM PRINTER ERROR ALARM 8-15-16 3:22AM SYSTEM PAPER OUT ALARM 8-15-16 3:22AM T 2 TANK PNL LOW TEMP WARNING CLEAR 8-08-16 10:00AM T 2 TANK PNL LOW TEMP WARNING ALARM 8-08-16 10:00AM T 1 TANK UNL LOW TEMP WARNING CLEAR 8-08-16 9:58AM T 1 TANK UNL LOW TEMP WARNING ALARM 8-08-16 9:57AM T 1 TANK UNL HIGH PRODUCT ALARM CLEAR 8-08-16 9:55AM T 1 TANK UNL HIGH PRODUCT ALARM ALARM 8-08-16 9:54AM T 1 TANK UNL HIGH PRODUCT ALARM CLEAR 8-08-16 9:53AM T 1 TANK UNL HIGH PRODUCT ALARM ALARM 8-08-16 9:52AM T 3 TANK DIESEL HIGH PRODUCT ALARM CLEAR 8-08-16 9:51AM T 3 TANK DIESEL HIGH PRODUCT ALARM ALARM 8-08-16 9:51AM T 3 TANK DIESEL HIGH PRODUCT ALARM CLEAR 8-08-16 9:47AM T 3 TANK DIESEL HIGH PRODUCT ALARM ALARM 8-08-16 9:47AM T 2 TANK PNL HIGH WATER WARNING CLEAR 8-08-16 9:27AM T 2 TANK PNL INVALID FUEL LEVEL CLEAR 8-08-16 9:23AM T 2 TANK PNL DELIVERY NEEDED CLEAR 8-08-16 9:23AM T 2 TANK PNL HIGH WATER WARNING ALARM 8-08-16 9:20AM T 2 TANK PNL DELIVERY NEEDED ALARM 8-08-16 9:16AM T 2 TANK PNL INVALID FUEL LEVEL ALARM 8-08-16 9:16AM SYSTEM PRINTER ERROR CLEAR 7-06-16 4:10PM
SYSTEM PAPER OUT CLEAR 7-06-16 4:10PM SYSTEM PRINTER ERROR ALARM 7-06-16 4:10PM SYSTEM PAPER OUT ALARM 7-06-16 4:10PM SYSTEM PRINTER ERROR CLEAR 7-06-16 4:03PM SYSTEM PAPER OUT CLEAR 7-06-16 4:03PM I20600 AUG 16, 2016 10:56 AM FASTRIP 6401 WHITE LANE BAKERSFIELD,CA 93309 TANK ALARM HISTORY
TANK 1 UNL OVERFILL ALARM AUG 16, 2016 9:56 AM AUG 8, 2016 9:55 AM AUG 31, 2015 8:27 AM HIGH PRODUCT ALARM AUG 16, 2016 9:54 AM AUG 8, 2016 9:54 AM AUG 8, 2016 9:52 AM INVALID FUEL LEVEL JUN 28, 2016 6:28 PM JUN 27, 2016 2:02 PM JUN 23, 2016 11:38 AM PROBE OUT AUG 16, 2016 9:57 AM AUG 16, 2016 9:10 AM AUG 8, 2016 9:56 AM DELIVERY NEEDED JUN 28, 2016 5:20 PM JUN 27, 2016 12:38 PM JUN 24, 2016 11:46 AM MAX PRODUCT ALARM AUG 8, 2016 9:55 AM AUG 13, 2015 9:46 AM LOW TEMP WARNING AUG 8, 2016 9:57 AM AUG 7, 2015 9:55 AM AUG 14, 2014 9:16 AM TANK 2 PNL HIGH WATER ALARM AUG 8, 2016 9:20 AM OVERFILL ALARM AUG 16, 2016 10:00 AM AUG 8, 2016 9:46 AM JUL 12, 2016 3:41 PM HIGH PRODUCT ALARM AUG 13, 2015 9:50 AM AUG 7, 2015 9:58 AM INVALID FUEL LEVEL AUG 16, 2016 9:09 AM AUG 8, 2016 9:16 AM JUL 25, 2014 9:26 AM
PROBE OUT AUG 16, 2016 10:00 AM AUG 16, 2016 9:08 AM AUG 8, 2016 10:00 AM HIGH WATER WARNING AUG 8, 2016 9:20 AM DELIVERY NEEDED AUG 8, 2016 9:16 AM MAY 4, 2016 4:11 PM APR 27, 2016 8:11 PM LOW TEMP WARNING AUG 8, 2016 10:00 AM AUG 13, 2015 9:51 AM AUG 13, 2015 9:49 AM TANK 3 DIESEL OVERFILL ALARM AUG 16, 2016 10:02 AM AUG 8, 2016 9:47 AM
AUG 13, 2015 9:54 AM HIGH PRODUCT ALARM AUG 8, 2016 9:51 AM AUG 8, 2016 9:47 AM AUG 13, 2015 9:54 AM INVALID FUEL LEVEL FEB 19, 2016 5:42 PM FEB 12, 2016 1:28 PM JAN 26, 2016 3:28 PM PROBE OUT AUG 16, 2016 10:02 AM AUG 16, 2016 9:06 AM AUG 8, 2016 10:01 AM DELIVERY NEEDED FEB 19, 2016 8:13 AM FEB 12, 2016 8:16 AM JAN 31, 2016 12:50 AM LOW TEMP WARNING AUG 16, 2016 10:03 AM JUL 25, 2014 9:24 AM AUG 14, 2013 1:37 PM I38200 AUG 16, 2016 10:56 AM I30200 AUG 16, 2016 10:56 AM FASTRIP 6401 WHITE LANE BAKERSFIELD,CA 93309 LIQUID ALARM HISTORY REPORT SENSOR LOCATION 1 UNL STP AUG 16, 2016 9:50 AM SENSOR OUT ALARM AUG 16, 2016 9:34 AM FUEL ALARM AUG 8, 2016 10:15 AM SENSOR OUT ALARM
2 UNL ANN AUG 16, 2016 9:50 AM SENSOR OUT ALARM AUG 16, 2016 9:38 AM LOW LIQUID ALARM AUG 16, 2016 9:38 AM HIGH LIQUID ALARM 3 UNL FILL AUG 16, 2016 9:50 AM SENSOR OUT ALARM AUG 16, 2016 9:36 AM FUEL ALARM AUG 8, 2016 10:15 AM SENSOR OUT ALARM 4 PNL STP AUG 16, 2016 9:50 AM SENSOR OUT ALARM AUG 16, 2016 9:35 AM FUEL ALARM AUG 8, 2016 10:15 AM SENSOR OUT ALARM 5 PNL FILL AUG 16, 2016 9:50 AM SENSOR OUT ALARM AUG 16, 2016 9:37 AM FUEL ALARM AUG 8, 2016 10:15 AM SENSOR OUT ALARM 6 PNL ANN AUG 16, 2016 9:50 AM SENSOR OUT ALARM
AUG 16, 2016 9:39 AM HIGH LIQUID ALARM AUG 16, 2016 9:38 AM LOW LIQUID ALARM 7 DIE STP AUG 16, 2016 9:50 AM SENSOR OUT ALARM AUG 16, 2016 9:36 AM FUEL ALARM AUG 8, 2016 10:15 AM SENSOR OUT ALARM 8 DIE FILL AUG 16, 2016 9:50 AM SENSOR OUT ALARM AUG 16, 2016 9:37 AM FUEL ALARM AUG 8, 2016 10:15 AM SENSOR OUT ALARM 10 DIS 1-2 AUG 16, 2016 9:50 AM SENSOR OUT ALARM AUG 16, 2016 9:41 AM FUEL ALARM AUG 8, 2016 10:15 AM SENSOR OUT ALARM 11 DIS 3-4 AUG 16, 2016 9:50 AM SENSOR OUT ALARM AUG 16, 2016 9:42 AM FUEL ALARM AUG 8, 2016 10:15 AM SENSOR OUT ALARM 12 DIS 5-6 AUG 16, 2016 9:50 AM SENSOR OUT ALARM AUG 16, 2016 9:42 AM FUEL ALARM AUG 8, 2016 10:15 AM SENSOR OUT ALARM 13 DIS 7-8 AUG 16, 2016 9:50 AM SENSOR OUT ALARM AUG 16, 2016 9:43 AM FUEL ALARM AUG 8, 2016 10:15 AM SENSOR OUT ALARM 16 DIE ANN AUG 16, 2016 9:50 AM SENSOR OUT ALARM AUG 16, 2016 9:40 AM LOW LIQUID ALARM AUG 16, 2016 9:40 AM HIGH LIQUID ALARM I31600 AUG 16, 2016 10:56 AM FASTRIP 6401 WHITE LANE BAKERSFIELD,CA 93309 SMART SENSOR ALARM HISTORY REPORT SENSOR LOCATION 1 VP SENSOR DIS 3-4
2 FM DIS 1-2 3 FM DIS 3-4 4 FM DIS 5-6 5 FM DIS 7-8 I40200 AUG 16, 2016 10:56 AM I40300 AUG 16, 2016 10:56 AM I34200
AUG 16, 2016 10:56 AM I34700 AUG 16, 2016 10:56 AM IV0100 AUG 16, 2016 10:56 AM FASTRIP 6401 WHITE LANE BAKERSFIELD,CA 93309 ISD ALARM STATUS REPORT EVR TYPE: VACUUM ASSIST ISD TYPE: 01.04 VAPOR PROCESSOR TYPE: NONE OVERALL STATUS :PASS EVR VAPOR COLLECTION :PASS EVR VAPOR CONTAINMENT :PASS ISD MONITOR UP-TIME : 99% EVR/ISD PASS TIME :100% WARNING ALARMS DATE TIME DESCRIPTION READING VALUE 16-06-29 10:06:09 VAPOR CONTAINMENT LEAKAGE CFH@2 INCHES WC 51.07 16-06-20 10:06:09 A/L RATIO DEGRADATION FP 6 BLEND3 0.80 16-06-07 10:06:09 VAPOR CONTAINMENT LEAKAGE CFH@2 INCHES WC 9.22 16-06-06 10:06:09 VAPOR CONTAINMENT LEAKAGE CFH@2 INCHES WC 9.22 16-06-05 10:06:09 VAPOR CONTAINMENT LEAKAGE CFH@2 INCHES WC 9.22 16-06-04 10:06:09 VAPOR CONTAINMENT LEAKAGE CFH@2 INCHES WC 10.45 16-02-28 10:07:48 CONTAINMENT GROSS OVER PRESSURE WEEKLY 95% 2.50 16-02-21 10:07:51 CONTAINMENT GROSS OVER PRESSURE WEEKLY 95% 2.84 16-02-14 10:09:05 CONTAINMENT GROSS OVER PRESSURE WEEKLY 95% 2.00 16-01-11 10:07:59 CONTAINMENT GROSS OVER PRESSURE WEEKLY 95% 2.93 FAILURE ALARMS DATE TIME DESCRIPTION READING VALUE 15-12-27 10:07:23 A/L RATIO DEGRADATION FP 5 BLEND3 0.76 11-10-02 10:02:09 A/L RATIO GROSS BLOCKAGE FP 2 BLEND3 BLKD
11-10-02 10:02:09 A/L RATIO GROSS BLOCKAGE FP 1 BLEND3 BLKD 11-09-12 10:04:11 A/L RATIO GROSS BLOCKAGE FP 1 BLEND3 BLKD 11-09-08 10:03:18 CONTAINMENT GROSS OVER PRESSURE WEEKLY 95% 2.72 11-08-22 00:01:32 A/L RATIO GROSS BLOCKAGE FP 4 BLEND3 BLKD 11-08-22 00:01:32 A/L RATIO GROSS BLOCKAGE FP 3 BLEND3 BLKD 10-12-27 10:01:40 A/L RATIO GROSS BLOCKAGE FP 8 BLEND3 BLKD 10-12-27 10:01:40 A/L RATIO GROSS BLOCKAGE FP 7 BLEND3 BLKD 10-12-26 10:01:25 A/L RATIO GROSS BLOCKAGE FP 7 BLEND3 BLKD SHUTDOWN & MISCELLANEOUS EVENTS DATE TIME DESCRIPTION ACTION/NAME 16-08-16 10:06:09 READINESS ISD:PP EVR:PP ISD & EVR READY 16-08-16 09:47:49 READINESS ISD:PP EVR:NN EVR READINESS PENDING 16-08-16 09:47:49 ISD STARTUP 16-08-16 09:47:22 ISD SHUTDOWN 16-08-11 10:07:23 READINESS ISD:PP EVR:PP ISD & EVR READY 16-08-10 10:06:09 READINESS ISD:PP EVR:NP EVR READINESS PENDING 16-08-09 10:06:09 READINESS ISD:PP EVR:NP EVR READINESS PENDING
16-08-08 10:20:18 READINESS ISD:PP EVR:NN EVR READINESS PENDING 16-08-08 10:20:18 ISD STARTUP 16-08-08 10:20:12 ISD SHUTDOWN
SWRCB, January 2006
Spill Bucket Testing Report Form
This form is intended for use by contractors performing annual testing of UST spill containment structures. The completed form and
printouts from tests (if applicable), should be provided to the facility owner/operator forsubmittal to the local regulatory agency.
1.FACILITY INFORMATION
Facility Name:Date of Testing:
Facility Address:
Facility Contact:Phone:
Date Local Agency Was Notified of Testing :
Name of Local Agency Inspector (if present during testing):
2.TESTING CONTRACTOR INFORMATION
Company Name:Confidence UST Services, Inc.
Technician Conducting Test:
Credentials1:CSLB Contractor ICC Service Tech. SWRCB Tank Tester Other (Specify)
License Number(s):CSLB#804904 ICC#
3.SPILL BUCKET TESTING INFORMATION
Test Method Used:Hydrostatic Vacuum Other
Test Equipment Used:Lake TestEquipment Resolution:0.0625”
Identify Spill Bucket (By Tank
Number, Stored Product, etc.)
1234
Bucket Installation Type: Direct Bury
Contained in Sump
Direct Bury
Contained in Sump
Direct Bury
Contained in Sump
Direct Bury
Contained in Sump
Bucket Diameter:
Bucket Depth:
Wait time between applying
vacuum/water and start of test:
Test Start Time (TI):
Initial Reading (RI):
Test End Time (TF):
Final Reading (RF):
Test Duration (TF – TI):
Change in Reading (RF -RI):
Pass/Fail Threshold or
Criteria:
Test Result: Pass Fail Pass Fail Pass Fail Pass Fail
Comments –(include information on repairs made prior to testing, and recommended follow-up for failed tests)
CERTIFICATION OF TECHNICIAN RESPONSIBLE FOR CONDUCTING THIS TESTING
I hereby certify that all the information contained in this report is true, accurate, and in full compliance with legal requirements.
Technician’s Signature:________________________________________________ Date:_________
1 State laws and regulations do not currently require testing to be performed by a qualified contractor. However, local requirements
may be more stringent.
#3360Farrell'sFastrip 09/16/2016
6401WhiteLane Bakersfield,CA93309
OmeroGarcia(661)393-7000
07/14/2016
Shane Gardner
CameronMason
8174721-UT
Regular
12.00"
14.00"
5min.
9:00 am
10.00"
10:00 am
10.00"
1hour
0.00"
0.0625"
Super
12.00"
14.00"
5min.
9:00 am
10.00"
10:00 am
10.00"
1hour
0.00"
0.0625"0.0625"
Diesel
12.00"
14.00"
5min.
9:00 am
10.00"
10:00 am
10.00"
1hour
0.00"
09/16/2016