Loading...
HomeMy WebLinkAbout2016 FMC RESULTSTAIT RISING TO THE CHALLENGE p;714/560/8222 www.tait.com October 27, 2016 VIA FED EX. 7775 7359 5301 Bakersfield Fire Department 2101 H Street Bakersfield, CA 93301 Re: Precision Line Testing Monitoring System Certification Spill Bucket Testing Pacific Bell Telephone Co. dba AT&T California 1918 "M" STREET, BAKERSFIELD, CA GEOPAR: SA004 To Whom It May Concern: 701 N. Parkcenter Drive, Santa Ana, CA 92705 Enclosed are the results for the following tests completed on October 25, 2016: ■ Precision Line Testing Report Form ■ Monitoring System Certification Report Form ■ Spill Bucket Testing Report Form Please do not hesitate to call me if you have any questions. Very Truly Yours, C C rol�os E. (Cardenas Program Manager CA lic# 588098 / AZ lic# 095984 / NV lic# 0049666 / TX HO CR0000041 DATA CHART FOR USE WITH PETRO TITE LINE TESTER Job Number: ATTPLI6 Date of Test: 10125/2016 LOCATION: 1918 M Street Bakersfield California 93301 80 Street No. City State Telephone No. OWNER: Pacific Bell Telephone Company dba AT &T California +.0000 Name Address Representative Position Telephone No. OPERATOR: Grant Armstrong Environmental Site Manager 661 - 327 -6903 80 Name Dealer, Mgr. Or Other Address (if different than location) Telephone No. REASON FOR TEST: Annual Compliance TEST REQUESTED BY: Bakersfield Fire Dept. 1115 Name Position OrderN.ov - Billing Address SPECIAL INSTRUCTIONS: Bakersfield Fire Dept. on site Sh Gardne TECHNICIAN: Patrick Banbury ,o'' 90 -1413 Name - 4'/ IS A TANK TEST TO BE MADE WITH THIS LINE TEST? MAKE AND TYPE OF PUMP OR DISPENSERS WEATHER Mild COVER OVER LINES Concrete / Black Top Signature License Number ❑ Yes ® No FE- PETRO TURBINE TEMPERATURE IN TANKS OF °C APPROX. BURIAL DEPTH 24" Concrete, Black Top, Etc. PRESSURE VOLUME EACH LINE TIME PSI READING TEST RESULTS AS TESTED MILITARY BEFORE AFTER BEFORE AFTER NET CHANGE CONCLUSIONS DIESEL 1015 START 80 +.0000 SA0040001 1045 STABILIZATION 80 60 1115 START TEST 60 60 Line Tight Bleed Bac 1130 60 60 .0295 .0295 +.0000 1145 60 60 .0295 .0295 +.0000 1146 BLEED BACK 1 60 0 .0295 .0680 +.0385 BLEED BACK START TEST BLEED BACK BLEED BACK START TEST BLEED BACK COMMENTS: Approximately 100 feet of 1.5" Western Fiberglass Flex Line. G.P.H. ® YES ❑ NO (N OK ❑ NOT OK G.P.H. Line Tight ❑ YES ❑ NO Bleed Back ❑ OK ❑ NOT OK G.P.H. Line Tight ❑ YES ❑ NO Bleed Back ❑ OK ❑ NOT OK D. Results of Testing /Servicing Software Version Installed: 123.01 Complete the following checklist: ❑7 Yes ❑ No* - - - - -- - - -__ Is the audible alarm operational? ❑X Yes ❑ No* Is the visual alarm operational? 0 Yes ❑ No* Were all sensors visually inspected, functionally tested, and confirmed operational? 0 Yes ❑ No* Were all sensors installed at lowest point of secondary containment and positioned so that other equipment will not interfere with their proper operation? QX Yes ❑ No* If alarms are relayed to a remote monitoring station, is all communications equipment (e.g. modem) ❑ N/A operational? ❑ Yes ❑X No* For pressurized piping systems, does the turbine automatically shut down if the piping secondary ❑ N/A containment monitoring system detects a leak, fails to operate, or is electrically disconnected? If yes: which sensors initiate positive shut -down? (Check all that apply) ❑ Sump /Trench Sensors; ❑ Dispenser Containment Sensors. Did you confirm positive shut-down due to leaks and sensor failure /disconnection? ❑ Yes; ❑ No. ❑ Yes ❑ No* For tank systems that utilize the monitoring system as the primary tank overfill warning device (i.e. no mechanical overfill prevention valve is installed), is the overfill warning alarm visible and audible at the 0 N/A tank fill point(s) and operating properly? If so, at what percent of tank capacity does the alarm trigger? % ❑Yes* 0 No Was any monitoring equipment replaced? If yes, identify specific sensors, probes, or other equipment replaced and list the manufacturer name and model for all replacement parts in Section E, below. ❑Yes* ❑X No Was liquid found inside any secondary containment systems designed as dry systems? (Check all that apply) ❑ Product; ❑ Water. If yes, describe causes in Section E, below. F-M Yes ❑ No* Was monitoring system set -up reviewed to ensure proper settings? Attach set up reports, if applicable QYes ❑ No* Is all monitoring equipment operational per manufacturer's specifications? *In Section below, describe how and when these deficiencies were or will be corrected. E. Comments: Other From Sensors Section B: L4 Piping transition sump sensor 794380 - 208 /NA certified. L5 Day tank containment sensor 794380 - 208/930304 certified. L6 Generator room floor sensor 794380 - 208/930141 certified. No leak detector installed. Back up generator system. A precision line test was conducted and passed. A mechanical drop tube overfill prevention valve is installed as primary overfill. F. In -Tank Gauging / SIR Equipment: 0 Check this box if tank gauging is used only for inventory control. ❑ Check this box if no tank gauging or SIR equipment is installed. This section must be completed if in -tank gauging equipment is used to perform leak detection monitoring. *In the Section H, below, describe how and when these deficiencies were or will be correctea. G. Line Leak Detectors (LLD): ❑X Check this box if LLD s are not installed. !'�.. _..,. _.l ,. a,. 4L. .. �',. 11....r,.. nl�r�nlrlia t• ❑ Yes ❑ NO For equipment start -up or annual equipment cert ification, was a leak simulated to veri fy LLD performance ?(Check ❑ N/A all that apply) Simulated leak rate: ❑ 3 g. p.h.; ❑ 0.1 g. p. h ; ❑ 0.2 g.p.h. ❑ Yes ❑ No* Were all LLDs confirmed operational and accurate within regulatory requirements? ElF-1 No* Was the testing apparatus properly calibrated? ❑ Yes F-1 No* For mechanical LLDs, does the LLD restrict product flow if it detects a leak? ❑ N/A ❑ Yes ❑ No* For electro nic LLDs, does the turbine automatically shut off if the LLD detects a leak? ❑ N/A F-1 Yes F-] No* For electronic LLDs, does the turbine automatically shut off if any portion of the monitoring system is disabled or ❑ N/A disconnected? ❑ Yes ❑ No * For electronic LLDs, does the turbine automatically shut off if any portion of the monitoring system malfunctions or ❑ N/A fai is a test? ❑ Yes ❑ No* For electronic LLDs, have all accessible wiring connections been visually inspected? ❑ N/A ❑ Yes ❑ No* Were all items on the equipment manufacturer's maintenance checklist completed? * In the Section H, below, describe how and when these deficiencies were or will be correctea. H. Comments: No leak detector installed. Back up generator system. A precision line test was conducted and passed. Site Address : 1918 M St. UST Monitoring Site Plan Bakersfield 93301 Monitoring Elan Site Map Business Nam 9: Pacific Bell Telephone Co. dba AT&T Cal. (SA004) 8ii sin ess Address: 1918 M St Bakersfield TLS 350 Plus on (1st Floor) Fuel Lines SA (UO03 30U gal. Diesel Roof Top (2nd Floor) day Tank. Day Tank Room Floor Sensor (LS) 794380 -208 N W E S Drawing NOT to Scale L(6) Engine Room Floor Sensor 794380 -2D8 Overfill Alarm t Annular Sensor Transition Sump Vent Riser f (i 1179 90 -420 w/ Sensor (L4) Fill Sump Sensor 794380 -208 _ E Vent Line .i�. _�j w/ [U) 79i3W208, Spill Fuel Lines � � 1 Bucket & ATG 1 E t 3 SA01MU041 L_ 2DK UST [diesel t Piping Sump girl SensorfL3) 7943W -208 Date map was drawn: 10/25/2016 Instructions If you already have a diagram that shows all required information, you may include it, rather than this page, with your Monitoring System Certification. On your site plan, show the general layout of tanks and piping. Clearly identify locations of the following equipment, if installed: monitoring system control panels; sensors monitoring tank annular spaces, sumps, dispenser pans, spill containers, or other secondary containment areas; mechanical or electronic line leak detectors; and in -tank liquid level probes (if used for leak detection). In the space provided, note the date this Site Plan was prepared. SWRCB, January 2006 Spill Bucket Testing Report Form This form is intended for use by contractors performing annual testing of UST spill containment structures. The completed form and printouts from tests (if applicable), should be provided to the facility owner /operator for submittal to the local regulatory agency. 1 F A C'TT ,TTV TNF(IRMATTON Facilitv ID: SA004 Facility Name: Pacific Bell Telephone Co dba ATT California Date of Testing: 10/25/2016 Facility Address: 1918 M St. Bakersfield CA 93301 Facility Contact: Grant Armstrong I Phone: (661) 327 -6903 Date Local Agency Was Notified of Testing: 10/5/2016 Name of Local Agency Inspector (rf present during testing): Sean Gardner I. TF.CTTNC CONTRACTOR INFORMATION Company Name: TAIT Environmental Services Technician Conducting Test: Pat Banbury Credentials': ❑x CSLB Contractor 0 ICC Service Tech. ❑ SWRCB Tank Tester ❑ Other (Specify) License Number(s): A B ASB C -10 HAZ, 588098 ICC 5254955 3 SPILL BUCKET TESTING INFORMATION Test Method Used: OHydrostatic ❑Vacuum ❑Other Test Equipment Used: Tape Measure Equipment Resolution 1/16th Inch 77777 7, 2 SA0040001 Retest 3 4 Identify Spill Bucket (By Tank Number, Stored Product, etc.) 1 SA0040001 Bucket Installation Type: ❑Direct Bury RContained in Sump [I On Top of AST F1 Direct Bury OContained in Sump El On Top of AST ❑Direct Bury ❑Contained in Sump El On Top of AST ❑Direct Bury ❑Contained in Sump ❑On Top of AST Bucket Diameter: Bucket Depth: 13" 13" Wait time between applying vacuum /water and start of test: 1 Min 15 Min Test Start Time (Tj): 9:00 AM 10:25 AM Initial Reading (Rj): 11.50" Test End Time (TF): 11:25 Am Final Reading (RF): 11.50" Test Duration (TF — Tj): One Hour Change in Reading (RF - Rj): 0.00" Pass/Fail Threshold or Criteria: 0.00" Test Result: ❑ Pass ZFail 0 Pass ❑ Fail ❑ Pass ❑ Fail ❑ Pass ❑ Fail Comments —(include information on repairs made prior to testing, and recommended follow -up for failed tests) First test failed torn spill bucket gasket. Install new gasket and retest. CERTIFICATION OF TECHNICIAN RESPONSIBLE FOR CONDUCTING THIS TESTING I hereby certify that all the information contained in this report is true, accurate, and in full compliance with legal requirements. Technician's Signature: Date: 10/25/2016 ' State laws and regulations do not currently require testing to be performed by a qualified contractor. However, local requirements may be more stringent. 150301 OCT 27, 2016 12 :33 PM # 1:BKFDCAI2 SA004 S -S L I50302 OCT 27, 2016 12:33 PM # 2:1918 M ST. L I50303 OCT 27, 2016 12:33 PM # 3:BAKERSFIELD,CA 93301 L I50304 OCT 27, 2016 12:33 PM # 4:661- 631 -2540 L I51700 OCT 27, 2016 12:33 PM SYSTEM TYPE AND LANGUAGE FLAG SYSTEM UNITS U.S. SYSTEM LANGUAGE ENGLISH SYSTEM DATE /TIME FORMAT MON DD YYYY HH:MM:SS xM L 150F00 OCT 27, 2016 12:33 PM MON DD YYYY HH:MM:SS xM I10200 OCT 27, 2016 12:33 PM BKFDCA12 SA004 S -S 1918 M ST. BAKERSFIELD,CA 93301 661- 631 -2540 SYSTEM CONFIGURATION SLOT BOARD TYPE POWER ON RESET CURRENT 1 4 PROBE / G.T. 163858 162876 2 INTERSTITIAL BD 201571 200899 3 UNUSED 9807749 9728695 4 UNUSED 9779270 9722957 5 UNUSED 9773701 9725585 6 UNUSED 9777894 9731256 7 UNUSED 9762690 9725651 8 UNUSED 9771838 9730359 9 COMBO I/O BOARD 9933 9950 10 COMBO I/O BOARD 9955 9972 11 UNUSED 9777370 9734249 12 UNUSED 9766698 9726892 13 UNUSED 9769260 9730483 14 UNUSED 9767566 9723169 15 UNUSED 9766910 9730702 16 UNUSED 9765364 9725118 COMM 1 FAXMODEM BOARD 40262 40258 COMM 2 UNUSED 9774427 9742285 COMM 3 UNUSED 9760324 9728030 COMM 4 UNUSED 9766571 9734578 COMM 5 UNUSED 9764941 9726082 COMM 6 UNUSED 9764496 9728819 160100 OCT 27, 2016 12:34 PM TANK CONFIGURATION DEVICE LABEL CONFIGURED 1 DIESEL TK #SA004U001 ON 2 OFF 3 OFF 4 OFF 160200 OCT 27, 2016 12:34 PM TANK PRODUCT LABEL TANK PRODUCT LABEL 1 DIESEL TK #SA004U001 2 3 4 I60300 OCT 27, 2016 12:34 PM TANK PRODUCT CODE TANK PRODUCT LABEL 1 DIESEL TK #SA004U001 1 2 2 3 3 4 4 I60400 OCT 27, 2016 12:34 PM TANK FULL VOLUME TANK PRODUCT LABEL GALLONS 1 DIESEL TK #SA004U001 20149 2 0 3 0 4 0 L 160700 OCT 27, 2016 12:34 PM TANK DIAMETER TANK PRODUCT LABEL INCHES 1 DIESEL TK #SA004U001 114.00 2 0.00 3 0.00 4 0.00 L 160900 OCT 27, 2016 12:34 PM TANK THERMAL COEFFICIENT TANK PRODUCT LABEL 1 DIESEL TK #SA004U001 0.000450 2 0.000000 3 0.000000 4 0.000000 L I61200 OCT 27, 2016 12:34 PM TANK MANIFOLDED PARTNERS TANK PRODUCT LABEL SIPHON MANIFOLDED TANKS 1 DIESEL TK #SA004U001 NONE 2 NONE 3 NONE 4 NONE L I62100 OCT 27, 2016 12:34 PM LINE MANIFOLDED TANKS NONE NONE NONE NONE TANK LOW PRODUCT LIMIT TANK PRODUCT LABEL GALLONS 1 DIESEL TK #SA004U001 12000 2 0 3 0 4 0 I62200 OCT 27, 2016 12:34 PM TANK HIGH PRODUCT LIMIT TANK PRODUCT LABEL GALLONS 1 DIESEL TK4SA004U001 19141 2 0 3 0 4 0 162300 OCT 27, 2016 12:34 PM TANK OVERFILL LEVEL LIMIT TANK PRODUCT LABEL GALLONS 1 DIESEL TKOSA004UO01 18134 2 0 3 0 4 0 162400 OCT 27, 2016 12:34 PM TANK HIGH WATER LEVEL LIMIT TANK PRODUCT LABEL INCHES 1 DIESEL TKOSA004UO01 2.0 L I62800 OCT 27, 2016 12:34 PM TANK MAXIMUM VOLUME LIMIT TANK PRODUCT LABEL GALLONS 1 DIESEL TK #SA004U001 20149 2 0 3 0 4 0 L 162900 OCT 27, 2016 12:34 PM TANK DELIVERY REQUIRED LIMIT TANK PRODUCT LABEL GALLONS 1 DIESEL TK #SA004U001 12000 2 0 3 0 4 0 L 170300 OCT 27, 2016 12:35 PM LIQUID TYPE SENSOR LOCATION TYPE 1 ANNULAR SPACE TRI -STATE (SINGLE FLOAT) 2 FILL SUMP TRI -STATE (SINGLE FLOAT) 3 PIPING SUMP TRI -STATE (SINGLE FLOAT) 4 TRANSITION SUMP TRI -STATE (SINGLE FLOAT) 5 DAY TANK CONTAINMENT TRI -STATE (SINGLE FLOAT) 6 GEN ROOM FLOOR TRI -STATE (SINGLE FLOAT) 7 TRI -STATE (SINGLE FLOAT) 8 TRI -STATE (SINGLE FLOAT) L I90200 OCT 27, 2016 12:35 PM SOFTWARE REVISION LEVEL VERSION 123.01 SOFTWARE# 346123 -100 -B CREATED - 02.06.21.13.00 S- MODULE# 330160 -002 -A SYSTEM FEATURES: PERIODIC IN -TANK TESTS ANNUAL IN -TANK TESTS CSLD 111100 OCT 27, 2016 12:35 PM BKFDCAI2 SA004 S -S 1918 M ST. BAKERSFIELD,CA 93301 661- 631 -2540 PRIORITY ALARM HISTORY ID CATEGORY DESCRIPTION ALARM TYPE STATE DATE TIME L 5 OTHER DAY TANK CONTAINMENT FUEL ALARM CLEAR 10 -25 -16 9:57AM L 5 OTHER DAY TANK CONTAINMENT FUEL ALARM ALARM 10 -25 -16 9:56AM L 6 OTHER GEN ROOM FLOOR FUEL ALARM CLEAR 10 -25 -16 9:54AM L 6 OTHER GEN ROOM FLOOR FUEL ALARM ALARM 10 -25 -16 9:51AM L 4 OTHER TRANSITION SUMP FUEL ALARM CLEAR 10 -25 -16 9:49AM L 4 OTHER TRANSITION SUMP FUEL ALARM ALARM 10 -25 -16 9:41AM L 3 STP SUMP PIPING SUMP FUEL ALARM CLEAR 10 -25 -16 9:40AM L 3 STP SUMP PIPING SUMP FUEL ALARM ALARM 10 -25 -16 9:38AM L 2 OTHER FILL SUMP FUEL ALARM CLEAR 10 -25 -16 9:37AM L 2 OTHER FILL SUMP FUEL ALARM ALARM 10 -25 -16 9:33AM L 1 ANNULAR ANNULAR SPACE FUEL ALARM CLEAR 10 -25 -16 9:33AM L 1 ANNULAR ANNULAR SPACE FUEL ALARM ALARM 10 -25 -16 9:27AM T 1 TANK DIESEL TK #SA004U001 HIGH WATER ALARM CLEAR 10 -25 -16 9:24AM T 1 TANK DIESEL TK #SA004U001 PROBE OUT CLEAR 10 -25 -16 9:23AM T 1 TANK DIESEL TK4SA004U001 OVERFILL ALARM CLEAR 10 -25 -16 9:23AM T 1 TANK DIESEL TK #SA004U001 PROBE OUT ALARM 10 -25 -16 9:23AM T 1 TANK DIESEL TK #SA004U001 OVERFILL ALARM ALARM 10 -25 -16 9:19AM T 1 TANK DIESEL TK4SA004U001 LOW PRODUCT ALARM CLEAR 10 -25 -16 9:19AM T 1 TANK DIESEL TK #SA004U001 HIGH WATER ALARM ALARM 10 -25 -16 9:16AM T 1 TANK DIESEL TK #SA004U001 LOW PRODUCT ALARM ALARM 10 -25 -16 9:09AM T 1 TANK DIESEL TK #SA004U001 PROBE OUT CLEAR 10 -25 -16 9:08AM T 1 TANK DIESEL TK #SA004U001 PROBE OUT ALARM 10 -25 -16 9:07AM I 3 INPUT GEN RUN EXTERN INPUT ALARM CLEAR 10 -18 -16 8:42PM I 3 INPUT GEN RUN EXTERN INPUT ALARM ALARM 10 -18 -16 8:1OPM I 2 INPUT PUMP RUN EXTERN INPUT ALARM CLEAR 10 -18 -16 8:06PM 13 INPUT GEN RUN EXTERN INPUT ALARM CLEAR 10 -18 -16 7:03PM I 2 INPUT PUMP RUN EXTERN INPUT ALARM ALARM 10 -18 -16 5:16PM I 3 INPUT GEN RUN EXTERN INPUT ALARM ALARM 10 -18 -16 4:52PM 13 INPUT GEN RUN EXTERN INPUT ALARM CLEAR 10 -18 -16 4:15PM 13 INPUT GEN RUN EXTERN INPUT ALARM ALARM 10 -18 -16 4:10PM I 3 INPUT GEN RUN EXTERN INPUT ALARM CLEAR 10 -18 -16 4:07PM 13 INPUT GEN RUN EXTERN INPUT ALARM ALARM 10 -18 -16 4:06PM I 3 INPUT GEN RUN EXTERN INPUT ALARM CLEAR 10 -13 -16 4:37PM I 3 INPUT GEN RUN EXTERN INPUT ALARM ALARM 10 -13 -16 4:11PM I 3 INPUT GEN RUN EXTERN INPUT ALARM CLEAR 10 -12 -16 7:40PM I 3 INPUT GEN RUN EXTERN INPUT ALARM ALARM 10 -12 -16 7:09PM I 3 INPUT GEN RUN EXTERN INPUT ALARM CLEAR 10 -12 -16 4:37PM I 3 INPUT GEN RUN EXTERN INPUT ALARM ALARM 10 -12 -16 4:07PM I 3 INPUT GEN RUN EXTERN INPUT ALARM CLEAR 10 -10 -16 4:07PM I 3 INPUT GEN RUN EXTERN INPUT ALARM ALARM 10 -10 -16 4:062M I 3 INPUT GEN RUN EXTERN INPUT ALARM CLEAR 10 -10 -16 3:42PM I 3 INPUT GEN RUN EXTERN INPUT ALARM ALARM 10 -10 -16 3:42PM T 1 TANK DIESEL TK #SA004U001 LOW PRODUCT ALARM CLEAR 6 -22 -16 8:38AM T 1 TANK DIESEL TK #SA004U001 LOW PRODUCT ALARM ALARM 6 -21 -16 11:54AM T 1 TANK DIESEL TK #SA004U001 PROBE OUT CLEAR 6 -21 -16 11:53AM T 1 TANK DIESEL TK #SA004U001 PROBE OUT ALARM 6 -21 -16 5:57AM T 1 TANK DIESEL TK4SA004U001 PROBE OUT CLEAR 6 -20 -16 2:31PM T 1 TANK DIESEL TK #SA004U001 PROBE OUT ALARM 6 -20 -16 9:48AM I 3 INPUT GEN RUN EXTERN INPUT ALARM CLEAR 4 -12 -16 6:17AM I 3 INPUT GEN RUN EXTERN INPUT ALARM ALARM 4 -12 -16 5:11AM I11200 OCT 27, 2016 12:36 PM BKFDCAI2 SA004 S -S 1918 M ST. BAKERSFIELD,CA 93301 661- 631 -2540 NON - PRIORITY ALARM HISTORY ID CATEGORY DESCRIPTION ALARM TYPE STATE DATE TIME SYSTEM PRINTER ERROR CLEAR 10 -25 -16 10:36AM SYSTEM PRINTER ERROR ALARM 10 -25 -16 10:36AM T 1 TANK DIESEL TK #SA004U001 T 1 TANK DIESEL TK #SA004U001 T 1 TANK DIESEL TK #SA004U001 T 1 TANK DIESEL TK #SA004U001 T 1 TANK DIESEL TK #SA004U001 T 1 TANK DIESEL TK #SA004U001 T 1 TANK DIESEL TK4SA004U001 T 1 TANK DIESEL TK #SA004U001 SYSTEM SYSTEM SYSTEM SYSTEM T 1 TANK DIESEL TK #SA004U001 T 1 TANK DIESEL TK #SA004U001 SYSTEM SYSTEM T 1 TANK DIESEL TK #SA004U001 T 1 TANK DIESEL TK #SA004U001 T 1 TANK DIESEL TK #SA004U001 T 1 TANK DIESEL TK #SA004U001 T 1 TANK DIESEL TK #SA004U001 T 1 TANK DIESEL TK #SA004U001 T 1 TANK DIESEL TK #SA004U001 T 1 TANK DIESEL TK #SA004U001 SYSTEM SYSTEM SYSTEM SYSTEM SYSTEM SYSTEM SYSTEM SYSTEM SYSTEM SYSTEM SYSTEM SYSTEM SYSTEM SYSTEM T 1 TANK DIESEL TK #SA004U001 T 1 TANK DIESEL TK #SA004U001 T 1 TANK DIESEL TK #SA004U001 T 1 TANK DIESEL TK #SA004U001 T 1 TANK DIESEL TK #SA004U001 T 1 TANK DIESEL TK4SA004U001 T 1 TANK DIESEL TK #SA004U001 T 1 TANK DIESEL TK #SA004U001 T 1 TANK DIESEL TK #SA004U001 T 1 TANK DIESEL TK #SA004U001 120600 OCT 27, 2016 12:37 PM BKFDCA12 SA004 S -S 1918 M ST. BAKERSFIELD,CA 93301 661- 631 -2540 TANK ALARM HISTORY TANK 1 DIESEL TK #SA004U001 HIGH WATER ALARM OVERFILL ALARM LOW PRODUCT ALARM HIGH PRODUCT ALARM INVALID FUEL LEVEL PROBE OUT HIGH WATER WARNING HIGH WATER WARNING DELIVERY NEEDED HIGH WATER WARNING DELIVERY NEEDED DELIVERY NEEDED INVALID FUEL LEVEL DELIVERY NEEDED INVALID FUEL LEVEL PRINTER ERROR PRINTER ERROR PRINTER ERROR PRINTER ERROR LOW TEMP WARNING LOW TEMP WARNING PRINTER ERROR PRINTER ERROR LOW TEMP WARNING LOW TEMP WARNING HIGH WATER WARNING HIGH PRODUCT ALARM HIGH PRODUCT ALARM DELIVERY NEEDED HIGH WATER WARNING DELIVERY NEEDED PRINTER ERROR PAPER OUT PRINTER ERROR PAPER OUT PRINTER ERROR PAPER OUT PAPER OUT PRINTER ERROR PRINTER ERROR PAPER OUT PAPER OUT PRINTER ERROR PRINTER ERROR PRINTER ERROR HIGH WATER WARNING LOW TEMP WARNING LOW TEMP WARNING HIGH PRODUCT ALARM HIGH PRODUCT ALARM DELIVERY NEEDED HIGH WATER WARNING DELIVERY NEEDED LOW TEMP WARNING LOW TEMP WARNING OCT 25, 2016 9:16 AM NOV 11, 2015 9:37 AM MAR 2, 2015 8:48 AM OCT 25, 2016 9:19 AM NOV 11, 2015 9:50 AM MAR 2, 2015 9:11 AM OCT 25, 2016 9:09 AM JUN 21, 2016 11:54 AM NOV 11, 2015 9:34 AM NOV 11, 2015 9:51 AM MAR 2, 2015 9:11 AM DEC 2, 2014 10:29 AM JUN 21, 2016 11:53 AM DEC 12, 2013 9:45 AM AUG 29, 2012 3:13 AM OCT 25, 2016 9:23 AM OCT 25, 2016 9:07 AM JUN 21, 2016 5:57 AM OCT 25, 2016 9:16 AM CLEAR 10 -25 -16 9:24AM CLEAR 10 -25 -16 9:19AM ALARM 10 -25 -16 9:16AM ALARM 10 -25 -16 9:09AM CLEAR 6 -22 -16 8:38AM CLEAR 6 -22 -16 5:43AM ALARM 6 -21 -16 11:54AM ALARM 6 -21 -16 11:53AM CLEAR 6 -21 -16 6:04AM ALARM 6 -21 -16 6:03AM CLEAR 6 -20 -16 2:47PM ALARM 6 -20 -16 2:47PM CLEAR 6 -20 -16 2:33PM ALARM 6 -20 -16 2:32PM CLEAR 6 -20 -16 9:16AM ALARM 6 -20 -16 9:15AM CLEAR 2 -02 -16 8:40AM ALARM 2 -02 -16 8:38AM CLEAR 11 -11 -15 9:58AM CLEAR 11 -11 -15 9:56AM ALARM 11 -11 -15 9:51AM CLEAR 11 -11 -15 9:50AM ALARM 11 -11 -15 9:37AM ALARM 11 -11 -15 9:34AM CLEAR 10 -16 -15 12:50PM CLEAR 10 -16 -15 12:50PM ALARM 10 -16 -15 12:49PM ALARM 10 -16 -15 12:49PM CLEAR 10 -16 -15 12:49PM CLEAR 10 -16 -15 12:49PM ALARM 10 -16 -15 12:48PM ALARM 10 -16 -15 12:48PM CLEAR 10 -16 -15 12:48PM CLEAR 10 -16 -15 12:48PM ALARM 10 -16 -15 12:48PM ALARM 10 -16 -15 12:47PM CLEAR 10 -16 -15 12:47PM ALARM 10 -16 -15 12:46PM CLEAR 3 -02 -15 9:16AM CLEAR 3 -02 -15 9:15AM ALARM 3 -02 -15 9:13AM CLEAR 3 -02 -15 9:13AM ALARM 3 -02 -15 9:11AM CLEAR 3 -02 -15 9:10AM ALARM 3 -02 -15 8:48AM ALARM 3 -02 -15 8:40AM CLEAR 12 -02 -14 10:51AM ALARM 12 -02 -14 10:48AM NOV 11, MAR 2, DELIVERY NEEDED OCT 25, JUN 21, NOV 11, MAX PRODUCT ALARM NOV 11, MAR 2, JAN 30, LOW TEMP WARNING JUN 20, FEB 2, MAR 2, L 2015 9:37 AM 2015 8:48 AM 2016 9:09 AM 2016 11:54 AM 2015 9:34 AM 2015 9:52 AM 2015 9:11 AM 2013 3:27 PM 2016 2:32 PM 2016 8:38 AM 2015 9:13 AM I30200 OCT 27, 2016 12:37 PM BKFDCA12 SA004 S -S 1918 M ST. BAKERSFIELD,CA 93301 661 - 631 -2540 LIQUID ALARM HISTORY REPORT SENSOR LOCATION 1 ANNULAR SPACE OCT 25, 2016 9:27 AM FUEL ALARM NOV 11, 2015 9:03 AM FUEL ALARM DEC 2, 2014 9:58 AM FUEL ALARM 2 FILL SUMP OCT 25, 2016 9:33 AM FUEL ALARM NOV 11, 2015 9:08 AM FUEL ALARM DEC 2, 2014 10:04 AM FUEL ALARM 3 PIPING SUMP OCT 25, 2016 9:38 AM FUEL ALARM NOV 11, 2015 9:12 AM FUEL ALARM DEC 2, 2014 10:07 AM FUEL ALARM 4 TRANSITION SUMP OCT 25, 2016 9:41 AM FUEL ALARM NOV 11, 2015 9:17 AM FUEL ALARM DEC 2, 2014 10:11 AM FUEL ALARM 5 DAY TANK CONTAINMENT OCT 25, 2016 9:56 AM FUEL ALARM NOV 11, 2015 9:40 AM FUEL ALARM NOV 11, 2015 9:23 AM FUEL ALARM 6 GEN ROOM FLOOR OCT 25, 2016 9:51 AM FUEL ALARM NOV 11, 2015 9:28 AM FUEL ALARM DEC 2, 2014 10:17 AM FUEL ALARM L