HomeMy WebLinkAbout2016 FMC RESULTSTAIT
RISING TO THE CHALLENGE
p;714/560/8222 www.tait.com
October 27, 2016
VIA FED EX. 7775 7359 5301
Bakersfield Fire Department
2101 H Street
Bakersfield, CA 93301
Re: Precision Line Testing
Monitoring System Certification
Spill Bucket Testing
Pacific Bell Telephone Co. dba AT&T California
1918 "M" STREET, BAKERSFIELD, CA
GEOPAR: SA004
To Whom It May Concern:
701 N. Parkcenter Drive, Santa Ana, CA 92705
Enclosed are the results for the following tests completed on October 25, 2016:
■ Precision Line Testing Report Form
■ Monitoring System Certification Report Form
■ Spill Bucket Testing Report Form
Please do not hesitate to call me if you have any questions.
Very Truly Yours,
C
C rol�os E. (Cardenas
Program Manager
CA lic# 588098 / AZ lic# 095984 / NV lic# 0049666 / TX HO CR0000041
DATA CHART FOR USE WITH PETRO TITE LINE TESTER
Job Number: ATTPLI6
Date of Test: 10125/2016
LOCATION:
1918 M Street Bakersfield California 93301
80
Street No. City State Telephone No.
OWNER:
Pacific Bell Telephone Company dba AT &T California
+.0000
Name Address Representative Position Telephone No.
OPERATOR:
Grant Armstrong Environmental Site Manager 661 - 327 -6903
80
Name Dealer, Mgr. Or Other Address (if different than location) Telephone No.
REASON FOR TEST:
Annual Compliance
TEST REQUESTED BY:
Bakersfield Fire Dept.
1115
Name Position OrderN.ov - Billing Address
SPECIAL INSTRUCTIONS:
Bakersfield Fire Dept. on site Sh Gardne
TECHNICIAN: Patrick Banbury ,o'' 90 -1413
Name - 4'/
IS A TANK TEST TO BE MADE WITH THIS LINE TEST?
MAKE AND TYPE OF PUMP OR DISPENSERS
WEATHER Mild
COVER OVER LINES Concrete / Black Top
Signature License Number
❑ Yes ® No
FE- PETRO TURBINE
TEMPERATURE IN TANKS OF °C
APPROX. BURIAL DEPTH 24"
Concrete, Black Top, Etc.
PRESSURE VOLUME
EACH LINE TIME PSI READING TEST RESULTS
AS TESTED MILITARY BEFORE AFTER BEFORE AFTER NET CHANGE CONCLUSIONS
DIESEL
1015
START
80
+.0000
SA0040001
1045
STABILIZATION
80
60
1115
START TEST
60
60
Line Tight
Bleed Bac
1130
60
60
.0295
.0295
+.0000
1145
60
60
.0295
.0295
+.0000
1146
BLEED BACK
1 60
0
.0295
.0680
+.0385
BLEED BACK
START TEST
BLEED BACK
BLEED BACK
START TEST
BLEED BACK
COMMENTS: Approximately 100 feet of 1.5" Western Fiberglass Flex Line.
G.P.H.
® YES ❑ NO
(N OK
❑ NOT OK
G.P.H.
Line Tight ❑ YES ❑ NO
Bleed Back ❑ OK
❑ NOT OK
G.P.H.
Line Tight ❑ YES ❑ NO
Bleed Back ❑ OK
❑ NOT OK
D. Results of Testing /Servicing
Software Version Installed: 123.01
Complete the following checklist:
❑7 Yes
❑ No*
- - - - -- - - -__
Is the audible alarm operational?
❑X Yes
❑ No*
Is the visual alarm operational?
0 Yes
❑ No*
Were all sensors visually inspected, functionally tested, and confirmed operational?
0 Yes
❑ No*
Were all sensors installed at lowest point of secondary containment and positioned so that other equipment
will not interfere with their
proper operation?
QX Yes
❑ No*
If alarms are relayed to a remote monitoring station, is all communications equipment (e.g. modem)
❑ N/A
operational?
❑ Yes
❑X No*
For pressurized piping systems, does the turbine automatically shut down if the piping secondary
❑ N/A
containment monitoring system detects a leak, fails to operate, or is electrically disconnected? If yes: which
sensors initiate positive shut -down? (Check all that apply)
❑ Sump /Trench Sensors; ❑ Dispenser Containment Sensors. Did you confirm positive shut-down
due to leaks and sensor failure /disconnection?
❑ Yes; ❑ No.
❑ Yes
❑ No*
For tank systems that utilize the monitoring system as the primary tank overfill warning device (i.e. no
mechanical overfill prevention valve is installed), is the overfill warning alarm visible and audible at the
0 N/A
tank fill point(s) and operating properly? If so, at what percent of tank capacity does the alarm trigger?
%
❑Yes*
0 No
Was any monitoring equipment replaced? If yes, identify specific sensors, probes, or other equipment
replaced and list the manufacturer name and model for all replacement parts in Section E, below.
❑Yes*
❑X No
Was liquid found inside any secondary containment systems designed as dry systems? (Check all that
apply) ❑ Product; ❑ Water. If yes, describe causes in Section E, below.
F-M Yes
❑ No*
Was monitoring system set -up reviewed to ensure proper settings? Attach set up reports, if applicable
QYes
❑ No*
Is all monitoring equipment operational per manufacturer's specifications?
*In Section below, describe how and when these deficiencies were or will be corrected.
E. Comments:
Other From Sensors Section B:
L4 Piping transition sump sensor 794380 - 208 /NA certified.
L5 Day tank containment sensor 794380 - 208/930304 certified.
L6 Generator room floor sensor 794380 - 208/930141 certified.
No leak detector installed. Back up generator system.
A precision line test was conducted and passed.
A mechanical drop tube overfill prevention valve is installed as primary overfill.
F. In -Tank Gauging / SIR Equipment:
0 Check this box if tank gauging is used only for inventory control.
❑ Check this box if no tank gauging or SIR equipment is installed.
This section must be completed if in -tank gauging equipment is used to perform leak detection monitoring.
*In the Section H, below, describe how and when these deficiencies were or will be correctea.
G. Line Leak Detectors (LLD): ❑X Check this box if LLD s are not installed.
!'�.. _..,. _.l ,. a,. 4L. .. �',. 11....r,.. nl�r�nlrlia t•
❑ Yes
❑ NO
For equipment start -up or annual equipment cert ification, was a leak simulated to veri fy LLD performance ?(Check
❑ N/A
all that apply) Simulated leak rate: ❑ 3 g. p.h.; ❑ 0.1 g. p. h ; ❑ 0.2 g.p.h.
❑ Yes
❑ No*
Were all LLDs confirmed operational and accurate within regulatory requirements?
ElF-1
No* Was the testing apparatus properly calibrated?
❑ Yes
F-1 No*
For mechanical LLDs, does the LLD restrict product flow if it detects a leak?
❑ N/A
❑ Yes
❑ No* For electro nic LLDs, does the turbine automatically shut off if the LLD detects a leak?
❑ N/A
F-1 Yes
F-] No*
For electronic LLDs, does the turbine automatically shut off if any portion of the monitoring system is disabled or
❑ N/A
disconnected?
❑ Yes
❑ No *
For electronic LLDs, does the turbine automatically shut off if any portion of the monitoring system malfunctions or
❑ N/A
fai is a test?
❑ Yes
❑ No*
For electronic LLDs, have all accessible wiring connections been visually inspected?
❑ N/A
❑ Yes
❑ No*
Were all items on the equipment manufacturer's maintenance checklist completed?
* In the Section H, below, describe how and when these deficiencies were or will be correctea.
H. Comments:
No leak detector installed. Back up generator system. A precision line test was conducted and passed.
Site Address : 1918 M St.
UST Monitoring Site Plan
Bakersfield
93301
Monitoring Elan Site Map
Business Nam 9:
Pacific Bell Telephone Co. dba AT&T Cal. (SA004)
8ii sin ess Address:
1918 M St Bakersfield
TLS 350 Plus on
(1st Floor)
Fuel Lines
SA (UO03
30U gal. Diesel Roof
Top
(2nd Floor) day Tank.
Day Tank Room
Floor Sensor (LS)
794380 -208
N
W E
S
Drawing NOT to Scale
L(6) Engine Room
Floor Sensor
794380 -2D8
Overfill Alarm
t
Annular Sensor
Transition Sump Vent Riser f
(i 1179 90 -420
w/ Sensor (L4)
Fill Sump Sensor
794380 -208 _ E
Vent Line .i�. _�j
w/
[U) 79i3W208, Spill
Fuel Lines � �
1 Bucket & ATG
1
E t
3 SA01MU041
L_
2DK UST [diesel
t
Piping Sump girl
SensorfL3)
7943W -208
Date map was drawn: 10/25/2016
Instructions
If you already have a diagram that shows all required information, you may include it, rather than this page, with your Monitoring System
Certification. On your site plan, show the general layout of tanks and piping. Clearly identify locations of the following equipment, if
installed: monitoring system control panels; sensors monitoring tank annular spaces, sumps, dispenser pans, spill containers, or other
secondary containment areas; mechanical or electronic line leak detectors; and in -tank liquid level probes (if used for leak detection). In the
space provided, note the date this Site Plan was prepared.
SWRCB, January 2006
Spill Bucket Testing Report Form
This form is intended for use by contractors performing annual testing of UST spill containment structures. The completed form and
printouts from tests (if applicable), should be provided to the facility owner /operator for submittal to the local regulatory agency.
1 F A C'TT ,TTV TNF(IRMATTON Facilitv ID: SA004
Facility Name: Pacific Bell Telephone Co dba ATT California
Date of Testing: 10/25/2016
Facility Address: 1918 M St. Bakersfield CA 93301
Facility Contact: Grant Armstrong
I Phone: (661) 327 -6903
Date Local Agency Was Notified of Testing: 10/5/2016
Name of Local Agency Inspector (rf present during testing): Sean Gardner
I. TF.CTTNC CONTRACTOR INFORMATION
Company Name: TAIT Environmental Services
Technician Conducting Test: Pat Banbury
Credentials': ❑x CSLB Contractor 0 ICC Service Tech. ❑ SWRCB Tank Tester ❑ Other (Specify)
License Number(s): A B ASB C -10 HAZ, 588098 ICC 5254955
3 SPILL BUCKET TESTING INFORMATION
Test Method Used: OHydrostatic ❑Vacuum ❑Other
Test Equipment Used: Tape Measure
Equipment Resolution 1/16th Inch
77777 7,
2 SA0040001 Retest
3
4
Identify Spill Bucket (By Tank
Number, Stored Product, etc.)
1 SA0040001
Bucket Installation Type:
❑Direct Bury
RContained in Sump
[I On Top of AST
F1 Direct Bury
OContained in Sump
El On Top of AST
❑Direct Bury
❑Contained in Sump
El On Top of AST
❑Direct Bury
❑Contained in Sump
❑On Top of AST
Bucket Diameter:
Bucket Depth:
13"
13"
Wait time between applying
vacuum /water and start of test:
1 Min
15 Min
Test Start Time (Tj):
9:00 AM
10:25 AM
Initial Reading (Rj):
11.50"
Test End Time (TF):
11:25 Am
Final Reading (RF):
11.50"
Test Duration (TF — Tj):
One Hour
Change in Reading (RF - Rj):
0.00"
Pass/Fail Threshold or
Criteria:
0.00"
Test Result:
❑ Pass ZFail
0 Pass ❑ Fail
❑ Pass ❑ Fail
❑ Pass ❑ Fail
Comments —(include information on repairs made prior to testing, and recommended follow -up for failed tests)
First test failed torn spill bucket gasket. Install new gasket and retest.
CERTIFICATION OF TECHNICIAN RESPONSIBLE FOR CONDUCTING THIS TESTING
I hereby certify that all the information contained in this report is true, accurate, and in full compliance with legal requirements.
Technician's Signature:
Date: 10/25/2016
' State laws and regulations do not currently require testing to be performed by a qualified contractor. However, local requirements
may be more stringent.
150301
OCT 27, 2016 12 :33 PM
# 1:BKFDCAI2 SA004 S -S
L
I50302
OCT 27, 2016 12:33 PM
# 2:1918 M ST.
L
I50303
OCT 27, 2016 12:33 PM
# 3:BAKERSFIELD,CA 93301
L
I50304
OCT 27, 2016 12:33 PM
# 4:661- 631 -2540
L
I51700
OCT 27, 2016 12:33 PM
SYSTEM TYPE AND LANGUAGE FLAG
SYSTEM UNITS
U.S.
SYSTEM LANGUAGE
ENGLISH
SYSTEM DATE /TIME FORMAT
MON DD YYYY HH:MM:SS xM
L
150F00
OCT 27, 2016 12:33 PM
MON DD YYYY HH:MM:SS xM
I10200
OCT 27, 2016 12:33 PM
BKFDCA12 SA004 S -S
1918 M ST.
BAKERSFIELD,CA 93301
661- 631 -2540
SYSTEM CONFIGURATION
SLOT BOARD TYPE
POWER ON RESET
CURRENT
1 4 PROBE / G.T.
163858
162876
2 INTERSTITIAL BD
201571
200899
3 UNUSED
9807749
9728695
4 UNUSED
9779270
9722957
5 UNUSED
9773701
9725585
6 UNUSED
9777894
9731256
7 UNUSED
9762690
9725651
8 UNUSED
9771838
9730359
9 COMBO I/O BOARD
9933
9950
10 COMBO I/O BOARD
9955
9972
11 UNUSED
9777370
9734249
12 UNUSED
9766698
9726892
13 UNUSED
9769260
9730483
14 UNUSED
9767566
9723169
15 UNUSED
9766910
9730702
16 UNUSED
9765364
9725118
COMM 1 FAXMODEM BOARD
40262
40258
COMM 2 UNUSED
9774427
9742285
COMM 3 UNUSED
9760324
9728030
COMM 4 UNUSED
9766571
9734578
COMM 5 UNUSED
9764941
9726082
COMM 6 UNUSED
9764496
9728819
160100
OCT 27, 2016 12:34 PM
TANK CONFIGURATION
DEVICE LABEL CONFIGURED
1 DIESEL TK #SA004U001 ON
2 OFF
3 OFF
4 OFF
160200
OCT 27, 2016 12:34 PM
TANK PRODUCT LABEL
TANK PRODUCT LABEL
1 DIESEL TK #SA004U001
2
3
4
I60300
OCT 27, 2016 12:34 PM
TANK PRODUCT CODE
TANK PRODUCT LABEL
1 DIESEL TK #SA004U001 1
2 2
3 3
4 4
I60400
OCT 27, 2016 12:34 PM
TANK FULL VOLUME
TANK PRODUCT LABEL GALLONS
1 DIESEL TK #SA004U001 20149
2 0
3 0
4 0
L
160700
OCT 27, 2016 12:34 PM
TANK DIAMETER
TANK PRODUCT LABEL INCHES
1 DIESEL TK #SA004U001 114.00
2 0.00
3 0.00
4 0.00
L
160900
OCT 27, 2016 12:34 PM
TANK THERMAL COEFFICIENT
TANK PRODUCT LABEL
1 DIESEL TK #SA004U001 0.000450
2 0.000000
3 0.000000
4 0.000000
L
I61200
OCT 27, 2016 12:34 PM
TANK MANIFOLDED PARTNERS
TANK PRODUCT LABEL SIPHON MANIFOLDED TANKS
1 DIESEL TK #SA004U001 NONE
2 NONE
3 NONE
4 NONE
L
I62100
OCT 27, 2016 12:34 PM
LINE MANIFOLDED TANKS
NONE
NONE
NONE
NONE
TANK LOW PRODUCT LIMIT
TANK PRODUCT LABEL GALLONS
1 DIESEL TK #SA004U001 12000
2 0
3 0
4 0
I62200
OCT 27, 2016 12:34 PM
TANK HIGH PRODUCT LIMIT
TANK PRODUCT LABEL GALLONS
1 DIESEL TK4SA004U001 19141
2 0
3 0
4 0
162300
OCT 27, 2016 12:34 PM
TANK OVERFILL LEVEL LIMIT
TANK PRODUCT LABEL GALLONS
1 DIESEL TKOSA004UO01 18134
2 0
3 0
4 0
162400
OCT 27, 2016 12:34 PM
TANK HIGH WATER LEVEL LIMIT
TANK PRODUCT LABEL INCHES
1 DIESEL TKOSA004UO01 2.0
L
I62800
OCT 27, 2016 12:34 PM
TANK MAXIMUM VOLUME LIMIT
TANK PRODUCT LABEL GALLONS
1 DIESEL TK #SA004U001 20149
2 0
3 0
4 0
L
162900
OCT 27, 2016 12:34 PM
TANK DELIVERY REQUIRED LIMIT
TANK PRODUCT LABEL GALLONS
1 DIESEL TK #SA004U001 12000
2 0
3 0
4 0
L
170300
OCT 27, 2016 12:35 PM
LIQUID TYPE
SENSOR
LOCATION
TYPE
1
ANNULAR SPACE
TRI -STATE
(SINGLE
FLOAT)
2
FILL SUMP
TRI -STATE
(SINGLE
FLOAT)
3
PIPING SUMP
TRI -STATE
(SINGLE
FLOAT)
4
TRANSITION SUMP
TRI -STATE
(SINGLE
FLOAT)
5
DAY TANK CONTAINMENT
TRI -STATE
(SINGLE
FLOAT)
6
GEN ROOM FLOOR
TRI -STATE
(SINGLE
FLOAT)
7
TRI -STATE
(SINGLE
FLOAT)
8
TRI -STATE
(SINGLE
FLOAT)
L
I90200
OCT 27, 2016 12:35 PM
SOFTWARE REVISION LEVEL
VERSION 123.01
SOFTWARE# 346123 -100 -B
CREATED - 02.06.21.13.00
S- MODULE# 330160 -002 -A
SYSTEM FEATURES:
PERIODIC IN -TANK TESTS
ANNUAL IN -TANK TESTS
CSLD
111100
OCT
27, 2016
12:35 PM
BKFDCAI2 SA004 S -S
1918 M ST.
BAKERSFIELD,CA 93301
661- 631 -2540
PRIORITY ALARM HISTORY
ID
CATEGORY
DESCRIPTION
ALARM TYPE
STATE
DATE
TIME
L 5
OTHER
DAY TANK CONTAINMENT
FUEL ALARM
CLEAR
10 -25 -16
9:57AM
L 5
OTHER
DAY TANK CONTAINMENT
FUEL ALARM
ALARM
10 -25 -16
9:56AM
L 6
OTHER
GEN ROOM FLOOR
FUEL ALARM
CLEAR
10 -25 -16
9:54AM
L 6
OTHER
GEN ROOM FLOOR
FUEL ALARM
ALARM
10 -25 -16
9:51AM
L 4
OTHER
TRANSITION SUMP
FUEL ALARM
CLEAR
10 -25 -16
9:49AM
L 4
OTHER
TRANSITION SUMP
FUEL ALARM
ALARM
10 -25 -16
9:41AM
L 3
STP SUMP
PIPING SUMP
FUEL ALARM
CLEAR
10 -25 -16
9:40AM
L 3
STP SUMP
PIPING SUMP
FUEL ALARM
ALARM
10 -25 -16
9:38AM
L 2
OTHER
FILL SUMP
FUEL ALARM
CLEAR
10 -25 -16
9:37AM
L 2
OTHER
FILL SUMP
FUEL ALARM
ALARM
10 -25 -16
9:33AM
L 1
ANNULAR
ANNULAR SPACE
FUEL ALARM
CLEAR
10 -25 -16
9:33AM
L 1
ANNULAR
ANNULAR SPACE
FUEL ALARM
ALARM
10 -25 -16
9:27AM
T 1
TANK
DIESEL TK #SA004U001
HIGH WATER ALARM
CLEAR
10 -25 -16
9:24AM
T 1
TANK
DIESEL TK #SA004U001
PROBE OUT
CLEAR
10 -25 -16
9:23AM
T 1
TANK
DIESEL TK4SA004U001
OVERFILL ALARM
CLEAR
10 -25 -16
9:23AM
T 1
TANK
DIESEL TK #SA004U001
PROBE OUT
ALARM
10 -25 -16
9:23AM
T 1
TANK
DIESEL TK #SA004U001
OVERFILL ALARM
ALARM
10 -25 -16
9:19AM
T 1
TANK
DIESEL TK4SA004U001
LOW PRODUCT ALARM
CLEAR
10 -25 -16
9:19AM
T 1
TANK
DIESEL TK #SA004U001
HIGH WATER ALARM
ALARM
10 -25 -16
9:16AM
T 1
TANK
DIESEL TK #SA004U001
LOW PRODUCT ALARM
ALARM
10 -25 -16
9:09AM
T 1
TANK
DIESEL TK #SA004U001
PROBE OUT
CLEAR
10 -25 -16
9:08AM
T 1
TANK
DIESEL TK #SA004U001
PROBE OUT
ALARM
10 -25 -16
9:07AM
I 3
INPUT
GEN RUN
EXTERN INPUT
ALARM
CLEAR
10 -18 -16
8:42PM
I 3
INPUT
GEN RUN
EXTERN INPUT
ALARM
ALARM
10 -18 -16
8:1OPM
I 2
INPUT
PUMP RUN
EXTERN INPUT
ALARM
CLEAR
10 -18 -16
8:06PM
13
INPUT
GEN RUN
EXTERN INPUT
ALARM
CLEAR
10 -18 -16
7:03PM
I 2
INPUT
PUMP RUN
EXTERN INPUT
ALARM
ALARM
10 -18 -16
5:16PM
I 3
INPUT
GEN RUN
EXTERN INPUT
ALARM
ALARM
10 -18 -16
4:52PM
13
INPUT
GEN RUN
EXTERN INPUT
ALARM
CLEAR
10 -18 -16
4:15PM
13
INPUT
GEN RUN
EXTERN INPUT
ALARM
ALARM
10 -18 -16
4:10PM
I 3
INPUT
GEN RUN
EXTERN INPUT
ALARM
CLEAR
10 -18 -16
4:07PM
13
INPUT
GEN RUN
EXTERN INPUT
ALARM
ALARM
10 -18 -16
4:06PM
I 3
INPUT
GEN RUN
EXTERN INPUT
ALARM
CLEAR
10 -13 -16
4:37PM
I 3
INPUT
GEN RUN
EXTERN INPUT
ALARM
ALARM
10 -13 -16
4:11PM
I 3
INPUT
GEN RUN
EXTERN INPUT
ALARM
CLEAR
10 -12 -16
7:40PM
I 3
INPUT
GEN RUN
EXTERN INPUT
ALARM
ALARM
10 -12 -16
7:09PM
I 3
INPUT
GEN RUN
EXTERN INPUT
ALARM
CLEAR
10 -12 -16
4:37PM
I 3
INPUT
GEN RUN
EXTERN INPUT
ALARM
ALARM
10 -12 -16
4:07PM
I 3
INPUT
GEN RUN
EXTERN INPUT
ALARM
CLEAR
10 -10 -16
4:07PM
I 3
INPUT
GEN RUN
EXTERN INPUT
ALARM
ALARM
10 -10 -16
4:062M
I 3
INPUT
GEN RUN
EXTERN INPUT
ALARM
CLEAR
10 -10 -16
3:42PM
I 3
INPUT
GEN RUN
EXTERN INPUT
ALARM
ALARM
10 -10 -16
3:42PM
T 1
TANK
DIESEL TK #SA004U001
LOW PRODUCT ALARM
CLEAR
6 -22 -16
8:38AM
T 1
TANK
DIESEL TK #SA004U001
LOW PRODUCT ALARM
ALARM
6 -21 -16
11:54AM
T 1
TANK
DIESEL TK #SA004U001
PROBE OUT
CLEAR
6 -21 -16
11:53AM
T 1
TANK
DIESEL TK #SA004U001
PROBE OUT
ALARM
6 -21 -16
5:57AM
T 1
TANK
DIESEL TK4SA004U001
PROBE OUT
CLEAR
6 -20 -16
2:31PM
T 1
TANK
DIESEL TK #SA004U001
PROBE OUT
ALARM
6 -20 -16
9:48AM
I 3
INPUT
GEN RUN
EXTERN INPUT
ALARM
CLEAR
4 -12 -16
6:17AM
I 3
INPUT
GEN RUN
EXTERN INPUT
ALARM
ALARM
4 -12 -16
5:11AM
I11200
OCT 27, 2016 12:36 PM
BKFDCAI2 SA004 S -S
1918 M ST.
BAKERSFIELD,CA 93301
661- 631 -2540
NON - PRIORITY ALARM HISTORY
ID CATEGORY DESCRIPTION ALARM TYPE STATE DATE TIME
SYSTEM PRINTER ERROR CLEAR 10 -25 -16 10:36AM
SYSTEM PRINTER ERROR ALARM 10 -25 -16 10:36AM
T 1 TANK
DIESEL
TK #SA004U001
T 1 TANK
DIESEL
TK #SA004U001
T 1 TANK
DIESEL
TK #SA004U001
T 1 TANK
DIESEL
TK #SA004U001
T 1 TANK
DIESEL
TK #SA004U001
T 1 TANK
DIESEL
TK #SA004U001
T 1 TANK
DIESEL
TK4SA004U001
T 1 TANK
DIESEL
TK #SA004U001
SYSTEM
SYSTEM
SYSTEM
SYSTEM
T 1 TANK
DIESEL
TK #SA004U001
T 1 TANK
DIESEL
TK #SA004U001
SYSTEM
SYSTEM
T 1 TANK
DIESEL
TK #SA004U001
T 1 TANK
DIESEL
TK #SA004U001
T 1 TANK
DIESEL
TK #SA004U001
T 1 TANK
DIESEL
TK #SA004U001
T 1 TANK
DIESEL
TK #SA004U001
T 1 TANK
DIESEL
TK #SA004U001
T 1 TANK
DIESEL
TK #SA004U001
T 1 TANK
DIESEL
TK #SA004U001
SYSTEM
SYSTEM
SYSTEM
SYSTEM
SYSTEM
SYSTEM
SYSTEM
SYSTEM
SYSTEM
SYSTEM
SYSTEM
SYSTEM
SYSTEM
SYSTEM
T 1 TANK
DIESEL
TK #SA004U001
T 1 TANK
DIESEL
TK #SA004U001
T 1 TANK
DIESEL
TK #SA004U001
T 1 TANK
DIESEL
TK #SA004U001
T 1 TANK
DIESEL
TK #SA004U001
T 1 TANK
DIESEL
TK4SA004U001
T 1 TANK
DIESEL
TK #SA004U001
T 1 TANK
DIESEL
TK #SA004U001
T 1 TANK
DIESEL
TK #SA004U001
T 1 TANK
DIESEL
TK #SA004U001
120600
OCT 27, 2016 12:37 PM
BKFDCA12 SA004 S -S
1918 M ST.
BAKERSFIELD,CA 93301
661- 631 -2540
TANK ALARM HISTORY
TANK 1 DIESEL TK #SA004U001
HIGH WATER ALARM
OVERFILL ALARM
LOW PRODUCT ALARM
HIGH PRODUCT ALARM
INVALID FUEL LEVEL
PROBE OUT
HIGH WATER WARNING
HIGH WATER WARNING
DELIVERY NEEDED
HIGH WATER WARNING
DELIVERY NEEDED
DELIVERY NEEDED
INVALID FUEL LEVEL
DELIVERY NEEDED
INVALID FUEL LEVEL
PRINTER ERROR
PRINTER ERROR
PRINTER ERROR
PRINTER ERROR
LOW TEMP WARNING
LOW TEMP WARNING
PRINTER ERROR
PRINTER ERROR
LOW TEMP WARNING
LOW TEMP WARNING
HIGH WATER WARNING
HIGH PRODUCT ALARM
HIGH PRODUCT ALARM
DELIVERY NEEDED
HIGH WATER WARNING
DELIVERY NEEDED
PRINTER ERROR
PAPER OUT
PRINTER ERROR
PAPER OUT
PRINTER ERROR
PAPER OUT
PAPER OUT
PRINTER ERROR
PRINTER ERROR
PAPER OUT
PAPER OUT
PRINTER ERROR
PRINTER ERROR
PRINTER ERROR
HIGH WATER WARNING
LOW TEMP WARNING
LOW TEMP WARNING
HIGH PRODUCT ALARM
HIGH PRODUCT ALARM
DELIVERY NEEDED
HIGH WATER WARNING
DELIVERY NEEDED
LOW TEMP WARNING
LOW TEMP WARNING
OCT 25, 2016 9:16 AM
NOV 11, 2015 9:37 AM
MAR 2, 2015 8:48 AM
OCT 25,
2016
9:19 AM
NOV 11,
2015
9:50 AM
MAR 2,
2015
9:11 AM
OCT 25,
2016
9:09 AM
JUN 21,
2016
11:54 AM
NOV 11,
2015
9:34 AM
NOV 11, 2015 9:51 AM
MAR 2, 2015 9:11 AM
DEC 2, 2014 10:29 AM
JUN 21,
2016
11:53 AM
DEC 12,
2013
9:45 AM
AUG 29,
2012
3:13 AM
OCT 25,
2016
9:23 AM
OCT 25,
2016
9:07 AM
JUN 21,
2016
5:57 AM
OCT 25, 2016 9:16 AM
CLEAR 10 -25 -16 9:24AM
CLEAR 10 -25 -16 9:19AM
ALARM 10 -25 -16 9:16AM
ALARM 10 -25 -16 9:09AM
CLEAR 6 -22 -16 8:38AM
CLEAR 6 -22 -16 5:43AM
ALARM 6 -21 -16 11:54AM
ALARM 6 -21 -16 11:53AM
CLEAR 6 -21 -16 6:04AM
ALARM 6 -21 -16 6:03AM
CLEAR 6 -20 -16 2:47PM
ALARM 6 -20 -16 2:47PM
CLEAR 6 -20 -16 2:33PM
ALARM 6 -20 -16 2:32PM
CLEAR 6 -20 -16 9:16AM
ALARM 6 -20 -16 9:15AM
CLEAR 2 -02 -16 8:40AM
ALARM 2 -02 -16 8:38AM
CLEAR 11 -11 -15 9:58AM
CLEAR 11 -11 -15 9:56AM
ALARM 11 -11 -15 9:51AM
CLEAR 11 -11 -15 9:50AM
ALARM 11 -11 -15 9:37AM
ALARM 11 -11 -15 9:34AM
CLEAR 10 -16 -15 12:50PM
CLEAR 10 -16 -15 12:50PM
ALARM 10 -16 -15 12:49PM
ALARM 10 -16 -15 12:49PM
CLEAR 10 -16 -15 12:49PM
CLEAR 10 -16 -15 12:49PM
ALARM 10 -16 -15 12:48PM
ALARM 10 -16 -15 12:48PM
CLEAR 10 -16 -15 12:48PM
CLEAR 10 -16 -15 12:48PM
ALARM 10 -16 -15 12:48PM
ALARM 10 -16 -15 12:47PM
CLEAR 10 -16 -15 12:47PM
ALARM 10 -16 -15 12:46PM
CLEAR 3 -02 -15 9:16AM
CLEAR 3 -02 -15 9:15AM
ALARM 3 -02 -15 9:13AM
CLEAR 3 -02 -15 9:13AM
ALARM 3 -02 -15 9:11AM
CLEAR 3 -02 -15 9:10AM
ALARM 3 -02 -15 8:48AM
ALARM 3 -02 -15 8:40AM
CLEAR 12 -02 -14 10:51AM
ALARM 12 -02 -14 10:48AM
NOV 11,
MAR 2,
DELIVERY NEEDED OCT 25,
JUN 21,
NOV 11,
MAX PRODUCT ALARM NOV 11,
MAR 2,
JAN 30,
LOW TEMP WARNING JUN 20,
FEB 2,
MAR 2,
L
2015 9:37 AM
2015 8:48 AM
2016 9:09 AM
2016 11:54 AM
2015 9:34 AM
2015 9:52 AM
2015 9:11 AM
2013 3:27 PM
2016 2:32 PM
2016 8:38 AM
2015 9:13 AM
I30200
OCT 27,
2016
12:37
PM
BKFDCA12
SA004
S -S
1918 M
ST.
BAKERSFIELD,CA
93301
661 - 631
-2540
LIQUID
ALARM
HISTORY
REPORT
SENSOR
LOCATION
1
ANNULAR
SPACE
OCT
25,
2016
9:27 AM
FUEL
ALARM
NOV
11,
2015
9:03 AM
FUEL
ALARM
DEC
2,
2014
9:58 AM
FUEL
ALARM
2
FILL
SUMP
OCT
25,
2016
9:33 AM
FUEL
ALARM
NOV
11,
2015
9:08 AM
FUEL
ALARM
DEC
2,
2014
10:04 AM
FUEL
ALARM
3
PIPING
SUMP
OCT
25,
2016
9:38 AM
FUEL
ALARM
NOV
11,
2015
9:12 AM
FUEL
ALARM
DEC
2,
2014
10:07 AM
FUEL
ALARM
4
TRANSITION
SUMP
OCT
25,
2016
9:41 AM
FUEL
ALARM
NOV
11,
2015
9:17 AM
FUEL
ALARM
DEC
2,
2014
10:11 AM
FUEL
ALARM
5
DAY
TANK CONTAINMENT
OCT
25,
2016
9:56 AM
FUEL
ALARM
NOV
11,
2015
9:40 AM
FUEL
ALARM
NOV
11,
2015
9:23 AM
FUEL
ALARM
6
GEN
ROOM FLOOR
OCT
25,
2016
9:51 AM
FUEL
ALARM
NOV
11,
2015
9:28 AM
FUEL
ALARM
DEC
2,
2014
10:17 AM
FUEL
ALARM
L