Loading...
HomeMy WebLinkAboutFMC Results 2016 (South)MONITORING SYSTEM CERTIFICATION For Use By All Jurisdictions Within the State of CaliforniaAuthority Cited: Chapter 6.7, Health and Safety Code; Chapter 16, Division 3, Title 23, California Code of Regulations This form must be used to document testing and servicing of monitoring equipment. A separate certification or report must be prepared for each monitoring system control panel by the technician who performs the work. A copy of this form must be provided to the tank system owner/operator. The owner/operator must submit a copy of this form to the local agency regulating UST systems within 30 days of test date. A.General Information Facility Name:Bldg. No.: Site Address:City:Zip: Facility Contact Person: Contact Phone No.: Make/Model of Monitoring System:Date of Testing/Servicing: B.Inventory of Equipment Tested/Certified Check the appropriate boxes to indicate specific equipment inspected/serviced: Tank ID:Tank ID: In-Tank Gauging Probe.Model:In-Tank Gauging Probe.Model: Annular Space or Vault Sensor.Model:Annular Space or Vault Sensor.Model: Piping Sump / Trench Sensor(s).Model:Piping Sump / Trench Sensor(s).Model: Fill Sump Sensor(s).Model:Fill Sump Sensor(s).Model: Mechanical Line Leak Detector.Model:Mechanical Line Leak Detector.Model: Electronic Line Leak Detector.Model:Electronic LineLeak Detector.Model: Tank Overfill / High-Level Sensor.Model:Tank Overfill / High-Level Sensor.Model: Other (specify equipment type and model in Section E on Page 2).Other (specify equipment type and model in Section E on Page 2). Tank ID:Tank ID: In-Tank Gauging Probe.Model:In-Tank Gauging Probe.Model: Annular Space or Vault Sensor.Model:Annular Space or Vault Sensor.Model: Piping Sump / TrenchSensor(s).Model:Piping Sump / Trench Sensor(s).Model: Fill Sump Sensor(s).Model:Fill Sump Sensor(s).Model: Mechanical Line Leak Detector.Model:Mechanical Line Leak Detector.Model: Electronic Line Leak Detector.Model:Electronic Line Leak Detector.Model: Tank Overfill / High-Level Sensor.Model:Tank Overfill / High-Level Sensor.Model: Other (specify equipment type and model in Section E on Page 2).Other (specify equipment type and model in Section E on Page 2). Dispenser ID:Dispenser ID: Dispenser Containment Sensor(s).Model:Dispenser Containment Sensor(s).Model: Shear Valve(s).Shear Valve(s). Dispenser Containment Float(s) and Chain(s).Dispenser Containment Float(s) and Chain(s). Dispenser ID:Dispenser ID: Dispenser Containment Sensor(s).Model:Dispenser Containment Sensor(s).Model: Shear Valve(s).Shear Valve(s). Dispenser Containment Float(s) and Chain(s).Dispenser Containment Float(s) and Chain(s). Dispenser ID:Dispenser ID: Dispenser Containment Sensor(s).Model:Dispenser Containment Sensor(s).Model: Shear Valve(s).Shear Valve(s). Dispenser Containment Float(s) and Chain(s).Dispenser Containment Float(s) and Chain(s). *If the facility contains more tanks or dispensers, copy this form. Include information for every tank and dispenser at the facility. C.Certification -I certify that the equipment identified in this document was inspected/serviced in accordance with the manufacturers’ guidelines. Attached to this Certification is information (e.g. manufacturers' checklists)necessary to verify that this information is correct and a Plot Plan showing the layout of monitoring equipment. For any equipment capable of generating such reports, I have also attached a copy of the report;(check all that apply):System set-up Alarm history report Technician Name (print):Signature: Certification No.:License. No.:804904 Testing Company Name:Confidence UST Services, Inc.Phone No.:(800)339-9930 Site Address:Date of Testing/Servicing: Page 1 of 3 Sully'sDowntown(South) 2317LStreetBakersfield93301 FrankSullivan (661)327-5008 Veeder-RootTLS-350 11/07/2016 12,000gal.Regular 847390-107 794390-420 794390-420 794380-208 794380-208 FX1V 847390-107 8,000gal.Plus 847390-107 FX1V 847390-107 10,000gal.Super 847390-107 794390-420 794380-208 847390-107 FX1V 794380-208 1-2 794380-208 794380-208 794380-208 794380-208 3-4 5-6 7-8 9-10 794380-208 11-12 Austin Sterling B47853 2317LStreet Bakersfield,CA93301 11/07/2016 Monitoring System Certification D.Results of Testing/Servicing Software Version Installed: Complete the following checklist: Yes No*Isthe audible alarm operational? Yes No*Is the visual alarm operational? Yes No*Were all sensors visually inspected, functionally tested, and confirmed operational? Yes No*Were all sensors installed at lowest point of secondary containment and positioned so that other equipment will not interfere with their proper operation? Yes No* N/A If alarms are relayed to a remote monitoring station, is all communications equipment (e.g., modem) operational? Yes No* N/A For pressurized piping systems, does the turbine automatically shut down if the piping secondary containment monitoring system detects a leak, fails to operate, or is electrically disconnected? If yes: which sensors initiate positive shut-down? (Check all that apply) Sump/Trench Sensors; Dispenser Containment Sensors. Did you confirm positive shut-down due to leaks and sensor failure/disconnection? Yes; No. Yes No* N/A For tank systems that utilize the monitoring system as the primary tank overfill warning device (i.e., no mechanical overfill prevention valve is installed), is the overfill warning alarm visible and audible at the tank fill point(s) and operating properly? If so, at what percent oftank capacity does the alarm trigger? % Yes*NoWas any monitoring equipment replaced? If yes, identify specific sensors, probes, or other equipment replaced and list the manufacturer name and model for all replacement parts in Section E, below. Yes*NoWas liquid found inside any secondary containment systems designed as dry systems? (Check all that apply) Product; Water. If yes, describe causes in Section E, below. Yes No*Was monitoring system set-up reviewed to ensure proper settings? Attach set up reports, if applicable Yes No*Is all monitoring equipment operational per manufacturer’s specifications? * In Section E below, describe how and when these deficiencies were or will be corrected. E.Comments: Page 2 of 3 329.00 90 Monitoring System Certification F.In-Tank Gauging / SIR Equipment: Check this box if tank gauging is used only for inventory control. Check this box if no tank gauging or SIR equipment is installed. This section must be completed if in-tank gauging equipment is used to perform leak detection monitoring. Complete the following checklist: Yes No*Has all input wiring been inspected for proper entry and termination, including testing for ground faults? Yes No*Were all tank gauging probes visually inspected for damage and residue buildup? Yes No*Was accuracy of system product level readings tested? Yes No*Was accuracy of system water level readings tested? Yes No*Were all probes reinstalled properly? Yes No*Were all items on the equipment manufacturer’s maintenance checklist completed? * In the Section H, below, describe how and when these deficiencies were or will be corrected. G.Line Leak Detectors (LLD):Check this box if LLDs are not installed. Complete the following checklist: Yes No* N/A For equipment start-up or annual equipment certification, was a leak simulated to verify LLD performance? (Check all that apply)Simulated leak rate: 3 g.p.h.; 0.1 g.p.h ; 0.2 g.p.h. Yes No*Were all LLDs confirmed operational and accurate within regulatory requirements? Yes No*Was the testing apparatus properly calibrated? Yes No* N/A For mechanical LLDs, does the LLD restrict product flow if it detects a leak? Yes No* N/A For electronic LLDs, does the turbine automatically shut off if the LLD detects a leak? Yes No* N/A For electronic LLDs, does the turbine automatically shut off if any portion of the monitoring system is disabled or disconnected? Yes No* N/A For electronic LLDs, does the turbine automatically shut off if any portion of the monitoring system malfunctions or fails a test? Yes No* N/A For electronic LLDs, have all accessible wiring connections been visually inspected? Yes No*Were all items on the equipment manufacturer’s maintenance checklist completed? * In the Section H, below, describe how and when these deficiencies were or will be corrected. H.Comments: Page 3 of 3 Leak Detector Test Results Sheet Customer Address: Work Order: Site Address: Test Date: Site Contact: Phone: Technician: Phone: 800-339-9930 ICC No.: Product Type LLD Type Model Serial No. Check Valve Holding Pressure Bleed Off ML. Leak Rate Tested: Pass/Fail 3 gph @ 10 psi 3 gph @ 10 psi 3 gph @ 10 psi 3 gph @ 10 psi 3 gph @ 10 psi 3 gph @ 10 psi 3 gph @ 10 psi 3 gph @ 10 psi Technician Name: Technician No.: Signature: Date: SullivanPetroleum,LLC 1000TruxtunAvenue Bakersfield,CA93301 37708 11/07/2016 8339953 Regular Mechanical FX1V Austin Sterling (661)327-5008FrankSullivan Bakersfield,CA93301 2317LStreet Sully'sDowntown(South) 30 psi80 ml Pass FX1VMechanicalPlus 35 psi70 ml Pass FX1VMechanicalPremium 30 psi75 ml Pass Austin Sterling 8339953 11/07/2016 Sullys down town south system setup Responses Received: 200 DOWNTOWN CHEV SOUTH 2317 L STREET BAKERSFIELD CA 93301 NOV 7, 2016 11:58 AM TANK PRODUCT GALLONS INCHES WATER DEG F ULLAGE 1 SUPREME 3997 63.06 0.0 75.2 4107 2 PLUS 3643 36.90 0.0 79.7 6502 3 UNLEADED 8788 87.31 0.0 74.8 3253 I90500 NOV 7, 2016 11:58 AM SOFTWARE REVISION LEVEL VERSION 329.00 SOFTWARE# 346329-100-A CREATED - 08.10.09.17.08 S-MODULE# 330160-004-a SYSTEM FEATURES: PERIODIC IN-TANK TESTS ANNUAL IN-TANK TESTS ISD I50500 NOV 7, 2016 11:58 AM SYSTEM TYPE AND LANGUAGE FLAG SYSTEM UNITS U.S. SYSTEM LANGUAGE ENGLISH SYSTEM DATE/TIME FORMAT MON DD YYYY HH:MM:SS xM I50201 NOV 7, 2016 11:58 AM SHIFT TIME 1 : 6:00 AM I50202 NOV 7, 2016 11:58 AM SHIFT TIME 2 : DISABLED I50203 NOV 7, 2016 11:58 AM SHIFT TIME 3 : DISABLED I50204 NOV 7, 2016 11:58 AM SHIFT TIME 4 : DISABLED I54600 NOV 7, 2016 11:58 AM TANK PER TST NEEDED WRN: DISABLED I54900 NOV 7, 2016 11:58 AM TANK ANN TST NEEDED WRN: DISABLED I55300 NOV 7, 2016 11:58 AM LINE RE-ENABLE METHOD PASS LINE TEST I55600 NOV 7, 2016 11:58 AM LINE PER TST NEEDED WRN: DISABLED I55900 NOV 7, 2016 11:58 AM LINE ANN TST NEEDED WRN: DISABLED I50D00 NOV 7, 2016 11:58 AM PRINT TC VOLUMES ENABLED I50E00 NOV 7, 2016 11:58 AM TEMP COMPENSATION VALUE (DEG F ): 60.0 I60B00 NOV 7, 2016 11:58 AM STICK HEIGHT OFFSET ENABLE STATUS DISABLED I51400 NOV 7, 2016 11:58 AM H-PROTOCOL DATA FORMAT HEIGHT I51A01 NOV 7, 2016 11:58 AM DAYLIGHT SAVING TIME ENABLED OFF I51B00 NOV 7, 2016 11:58 AM DAYLIGHT SAVING TIME START DATE MAR WEEK 2 SUN 2:00 AM END DATE NOV WEEK 1 SUN 2:00 AM I51600 NOV 7, 2016 11:58 AM RE-DIRECT LOCAL PRINTOUT DISABLED I50400 NOV 7, 2016 11:58 AM 232 SECURITY CODE PORT SECURITY CODE STATUS 1 231782 ENABLED 2 231782 ENABLED 3 000000 DISABLED 4 000000 DISABLED 5 231782 ENABLED 6 000000 DISABLED I21900 NOV 7, 2016 11:58 AM TANK CHART SECURITY DISABLED I5BD00 NOV 7, 2016 11:58 AM CUSTOM ALARM LABELS DISABLED I56000 NOV 7, 2016 11:58 AM MASS/DENSITY DISABLED I88101 NOV 7, 2016 11:58 AM PORT SETTINGS: COMM BOARD : 1 (EDIM ) RS-232 SECURITY CODE : 231782 I88102 NOV 7, 2016 11:58 AM PORT SETTINGS: COMM BOARD : 2 (RS-232) BAUD RATE : 9600 PARITY : NONE STOP BIT : 1 STOP DATA LENGTH: 8 DATA RS-232 SECURITY CODE : 231782 I88103 NOV 7, 2016 11:58 AM I88104 NOV 7, 2016 11:58 AM I88105 NOV 7, 2016 11:58 AM PORT SETTINGS: COMM BOARD : 5 (S-SAT ) BAUD RATE : 9600 PARITY : NONE STOP BIT : 1 STOP DATA LENGTH: 8 DATA RS-232 SECURITY CODE : 231782 DTR NORMAL STATE: HIGH I88106 NOV 7, 2016 11:58 AM I52000 NOV 7, 2016 11:58 AM RECEIVER AUTO DIAL TYPE & START TIME RCVR LOCATION LABEL DIAL TYPE START TIME 1 ON DATE JUL 9, 2015 2:15 PM 2 ON DATE JUL 9, 2015 2:15 PM 3 ON DATE JUL 9, 2015 2:15 PM 4 ON DATE JUL 9, 2015 2:15 PM 5 ON DATE JUL 9, 2015 2:15 PM 6 ON DATE JUL 9, 2015 2:15 PM 7 ON DATE JUL 9, 2015 2:15 PM 8 VEEDER ROOT (FMS) ON DATE JUL 9, 2015 2:15 PM I60100 NOV 7, 2016 11:59 AM TANK CONFIGURATION DEVICE LABEL CONFIGURED 1 SUPREME ON 2 PLUS ON 3 UNLEADED ON 4 OFF I60200 NOV 7, 2016 11:59 AM TANK PRODUCT LABEL TANK PRODUCT LABEL 1 SUPREME 2 PLUS 3 UNLEADED 4 I60300 NOV 7, 2016 11:59 AM TANK PRODUCT CODE TANK PRODUCT LABEL 1 SUPREME 1 2 PLUS 2 3 UNLEADED 3 4 4 I60900 NOV 7, 2016 11:59 AM TANK THERMAL COEFFICIENT TANK PRODUCT LABEL 1 SUPREME 0.000700 2 PLUS 0.000700 3 UNLEADED 0.000700 4 0.000000 I60700 NOV 7, 2016 11:59 AM TANK DIAMETER TANK PRODUCT LABEL INCHES 1 SUPREME 127.50 2 PLUS 95.00 3 UNLEADED 127.50 4 0.00 I60A00 NOV 7, 2016 11:59 AM TANK FULL VOLUME TANK PRODUCT LABEL TANK PROFILE GALLONS 1 SUPREME 1 PT 8104 2 PLUS 1 PT 10145 3 UNLEADED 1 PT 12041 4 50 PTS 0 I60400 NOV 7, 2016 11:59 AM TANK FULL VOLUME TANK PRODUCT LABEL GALLONS 1 SUPREME 8104 2 PLUS 10145 3 UNLEADED 12041 4 0 I60500 NOV 7, 2016 11:59 AM TANK 4 POINT VOLUMES TANK PRODUCT LABEL GALLONS 1 SUPREME 8104 0 0 0 2 PLUS 10145 0 0 0 3 UNLEADED 12041 0 0 0 4 0 0 0 0 I60600 NOV 7, 2016 11:59 AM TANK 20 POINT VOLUMES TANK PRODUCT LABEL GALLONS 1 SUPREME 8104 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 2 PLUS 10145 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 3 UNLEADED 12041 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 4 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 I61500 NOV 7, 2016 11:59 AM TANK PRODUCT LABEL METER DATA 1 SUPREME NO 2 PLUS NO 3 UNLEADED NO 4 NO I62F00 NOV 7, 2016 11:59 AM MAG PROBE FLOAT SIZE TANK PRODUCT LABEL FLOAT SIZE: 1 SUPREME 4.0 INCHES 2 PLUS 4.0 INCHES 3 UNLEADED 4.0 INCHES I62700 NOV 7, 2016 11:59 AM TANK HIGH WATER WARNING LIMIT TANK PRODUCT LABEL INCHES 1 SUPREME 2.0 2 PLUS 2.0 3 UNLEADED 2.0 9999FF1B I62400 NOV 7, 2016 11:59 AM TANK HIGH WATER LEVEL LIMIT TANK PRODUCT LABEL INCHES 1 SUPREME 3.0 2 PLUS 3.0 3 UNLEADED 3.0 I62800 NOV 7, 2016 11:59 AM TANK MAXIMUM VOLUME LIMIT TANK PRODUCT LABEL GALLONS 1 SUPREME 8104 2 PLUS 10145 3 UNLEADED 12041 4 0 I62300 NOV 7, 2016 11:59 AM TANK OVERFILL LEVEL LIMIT TANK PRODUCT LABEL GALLONS 1 SUPREME 7293 2 PLUS 9130 3 UNLEADED 10837 4 0 I62200 NOV 7, 2016 11:59 AM TANK HIGH PRODUCT LIMIT TANK PRODUCT LABEL GALLONS 1 SUPREME 7698 2 PLUS 9637 3 UNLEADED 11439 4 0 I62900 NOV 7, 2016 11:59 AM TANK DELIVERY REQUIRED LIMIT TANK PRODUCT LABEL GALLONS 1 SUPREME 810 2 PLUS 1014 3 UNLEADED 1204 4 0 I62100 NOV 7, 2016 11:59 AM TANK LOW PRODUCT LIMIT TANK PRODUCT LABEL GALLONS 1 SUPREME 800 2 PLUS 1000 3 UNLEADED 1200 4 0 I62600 NOV 7, 2016 11:59 AM TANK LEAK ALARM LIMIT TANK PRODUCT LABEL GALLONS 1 SUPREME 99 2 PLUS 99 3 UNLEADED 99 4 99 I62500 NOV 7, 2016 11:59 AM TANK SUDDEN LOSS LIMIT TANK PRODUCT LABEL GALLONS 1 SUPREME 99 2 PLUS 99 3 UNLEADED 99 4 99 I60800 NOV 7, 2016 11:59 AM TANK TILT TANK PRODUCT LABEL INCHES 1 SUPREME 2.86 2 PLUS 0.73 3 UNLEADED 1.10 4 0.00 I60B00 NOV 7, 2016 11:59 AM STICK HEIGHT OFFSET ENABLE STATUS DISABLED I60C00 NOV 7, 2016 11:59 AM TANK STICK HEIGHT OFFSET TANK PRODUCT LABEL INCHES 1 SUPREME 0.00 2 PLUS 0.00 3 UNLEADED 0.00 4 0.00 I61200 NOV 7, 2016 11:59 AM TANK MANIFOLDED PARTNERS TANK PRODUCT LABEL SIPHON MANIFOLDED TANKS LINE MANIFOLDED TANKS 1 SUPREME NONE NONE 2 PLUS NONE NONE 3 UNLEADED NONE NONE 4 NONE NONE I63600 NOV 7, 2016 11:59 AM PERIODIC LEAK TEST MIN VOLUME TANK PRODUCT LABEL GALLONS 1 SUPREME 810 2 PLUS 1014 3 UNLEADED 1204 4 0 I62A00 NOV 7, 2016 11:59 AM ANNUAL LEAK TEST MIN VOLUME TANK PRODUCT LABEL GALLONS 1 SUPREME 810 2 PLUS 1014 3 UNLEADED 1204 4 0 I62C00 NOV 7, 2016 11:59 AM TANK PERIODIC TEST TYPE TANK PRODUCT LABEL PERIODIC TEST TYPE 1 SUPREME STANDARD 2 PLUS STANDARD 3 UNLEADED STANDARD 4 STANDARD I62D00 NOV 7, 2016 11:59 AM TANK LEAK TEST FAIL ALARMS TANK PRODUCT LABEL 1 SUPREME GROSS TEST FAIL ALARM DISABLED PERIODIC TEST FAIL ALARM DISABLED ANNUAL TEST FAIL ALARM DISABLED 2 PLUS GROSS TEST FAIL ALARM DISABLED PERIODIC TEST FAIL ALARM DISABLED ANNUAL TEST FAIL ALARM DISABLED 3 UNLEADED GROSS TEST FAIL ALARM DISABLED PERIODIC TEST FAIL ALARM DISABLED ANNUAL TEST FAIL ALARM DISABLED 4 GROSS TEST FAIL ALARM DISABLED PERIODIC TEST FAIL ALARM DISABLED ANNUAL TEST FAIL ALARM DISABLED I63100 NOV 7, 2016 11:59 AM TANK LEAK TEST AVERAGING TANK PRODUCT LABEL ANNUAL PERIODIC 1 SUPREME OFF OFF 2 PLUS OFF OFF 3 UNLEADED OFF OFF 4 OFF OFF I63000 NOV 7, 2016 11:59 AM IN-TANK LEAK TEST NOTIFY TANK PRODUCT LABEL TANK TEST NOTIFY: 1 SUPREME OFF 2 PLUS OFF 3 UNLEADED OFF 4 OFF I63200 NOV 7, 2016 11:59 AM TANK TEST SIPHON BREAK TANK PRODUCT LABEL SIPHON BREAK 1 SUPREME OFF 2 PLUS OFF 3 UNLEADED OFF 4 OFF I61000 NOV 7, 2016 11:59 AM TANK DELIVERY DELAY TANK PRODUCT LABEL 1 SUPREME 1 2 PLUS 1 3 UNLEADED 1 4 1 I63A00 NOV 7, 2016 11:59 AM LOW LEVEL PUMP THRESHOLD FOR SEQUENTIAL LINE MANIFOLD TANK PRODUCT LABEL PUMP THRESHOLD 1 SUPREME 10.00% 2 PLUS 10.00% 3 UNLEADED 10.00% 4 10.00% I61100 NOV 7, 2016 11:59 AM LEAK TEST METHOD - - - - - - - - - - - - TEST ON DATE : ALL TANK JAN 2, 2016 START TIME : 2:00 AM TEST RATE :0.20 GAL/HR DURATION : 2 HOURS TST EARLY STOP:DISABLED I61300 NOV 7, 2016 11:59 AM CSLD PROBABLITY OF DETECTION I61400 NOV 7, 2016 11:59 AM CSLD CLIMATE FACTOR I61600 NOV 7, 2016 11:59 AM TANK PRODUCT LABEL CAL UPDATE 1 SUPREME IMMEDIATE 2 PLUS IMMEDIATE 3 UNLEADED IMMEDIATE 4 IMMEDIATE I61A00 NOV 7, 2016 11:59 AM IN-TANK LEAK TEST EARLY STOP TANK PRODUCT LABEL TST EARLY STOP: 1 SUPREME DISABLED 2 PLUS DISABLED 3 UNLEADED DISABLED 4 DISABLED I61B00 NOV 7, 2016 11:59 AM IN-TANK LEAK GROSS TEST AUTO-CONFIRM I61C00 NOV 7, 2016 11:59 AM CSLD REPORT ONLY I62B00 NOV 7, 2016 11:59 AM TANK LAST ANNUAL TEST TANK PRODUCT LABEL DATE 1 SUPREME ??? 0, 0 2 PLUS ??? 0, 0 3 UNLEADED ??? 0, 0 4 ??? 0, 0 I63300 NOV 7, 2016 11:59 AM LEAK TEST REPORT FORMAT: NORMAL I63400 NOV 7, 2016 11:59 AM RECONCILIATION WARNING LIMIT TANK PRODUCT LABEL GALLONS 1 SUPREME 0 2 PLUS 0 3 UNLEADED 0 4 0 I63500 NOV 7, 2016 11:59 AM RECONCILIATION ALARM LIMIT TANK PRODUCT LABEL GALLONS 1 SUPREME 1 2 PLUS 1 3 UNLEADED 1 4 1 I63900 NOV 7, 2016 11:59 AM ACCU CHART END SHAPE FACTOR TANK PRODUCT LABEL 1 SUPREME END FACTOR: NONE 2 PLUS END FACTOR: NONE 3 UNLEADED END FACTOR: NONE 4 END FACTOR: NONE I78000 NOV 7, 2016 11:59 AM I77700 NOV 7, 2016 11:59 AM I77800 NOV 7, 2016 11:59 AM I78C00 NOV 7, 2016 11:59 AM I78300 NOV 7, 2016 11:59 AM I78F00 NOV 7, 2016 11:59 AM I78700 NOV 7, 2016 11:59 AM I70200 NOV 7, 2016 11:59 AM LIQUID LABEL DEVICE LABEL 1 89 STP 2 87 91 ANN 3 87 STP 4 91 STP 5 89 ANN 6 DISP 1-2 7 DISP 3-4 8 DISP 5-6 9 DISP 7-8 10 DISP 9-10 11 DISP 11-12 12 13 14 15 16 I70300 NOV 7, 2016 11:59 AM LIQUID TYPE SENSOR LOCATION TYPE 1 89 STP TRI-STATE (SINGLE FLOAT) 2 87 91 ANN TRI-STATE (SINGLE FLOAT) 3 87 STP TRI-STATE (SINGLE FLOAT) 4 91 STP TRI-STATE (SINGLE FLOAT) 5 89 ANN TRI-STATE (SINGLE FLOAT) 6 DISP 1-2 TRI-STATE (SINGLE FLOAT) 7 DISP 3-4 TRI-STATE (SINGLE FLOAT) 8 DISP 5-6 TRI-STATE (SINGLE FLOAT) 9 DISP 7-8 TRI-STATE (SINGLE FLOAT) 10 DISP 9-10 TRI-STATE (SINGLE FLOAT) 11 DISP 11-12 TRI-STATE (SINGLE FLOAT) 12 TRI-STATE (SINGLE FLOAT) 13 TRI-STATE (SINGLE FLOAT) 14 TRI-STATE (SINGLE FLOAT) 15 TRI-STATE (SINGLE FLOAT) 16 TRI-STATE (SINGLE FLOAT) I70400 NOV 7, 2016 11:59 AM LIQUID CATEGORY SENSOR LOCATION CATEGORY 1 89 STP STP SUMP 2 87 91 ANN ANNULAR SPACE 3 87 STP STP SUMP 4 91 STP STP SUMP 5 89 ANN ANNULAR SPACE 6 DISP 1-2 DISPENSER PAN 7 DISP 3-4 DISPENSER PAN 8 DISP 5-6 DISPENSER PAN 9 DISP 7-8 DISPENSER PAN 10 DISP 9-10 DISPENSER PAN 11 DISP 11-12 DISPENSER PAN 12 OTHER SENSORS 13 OTHER SENSORS 14 OTHER SENSORS 15 OTHER SENSORS 16 OTHER SENSORS I74200 NOV 7, 2016 11:59 AM I74300 NOV 7, 2016 11:59 AM I74400 NOV 7, 2016 11:59 AM I74700 NOV 7, 2016 11:59 AM I74800 NOV 7, 2016 11:59 AM I74900 NOV 7, 2016 11:59 AM I7BC00 NOV 7, 2016 11:59 AM I80200 NOV 7, 2016 11:59 AM I80300 NOV 7, 2016 11:59 AM I80400 NOV 7, 2016 11:59 AM I80700 NOV 7, 2016 11:59 AM RELAY LABEL DEVICE LABEL 1 UNLEADED 2 PLUS 3 SUPREME 4 OVERFILL ALARM I80900 NOV 7, 2016 11:59 AM RELAY ORIENTATION RELAY DESIGNATION ORIENTATION 1 UNLEADED NORMALLY CLOSED 2 PLUS NORMALLY CLOSED 3 SUPREME NORMALLY CLOSED 4 OVERFILL ALARM NORMALLY OPEN I80B00 NOV 7, 2016 11:59 AM RELAY TANK ASSIGNMENT RELAY DESIGNATION TANK 1 UNLEADED 3 2 PLUS 2 3 SUPREME 1 4 OVERFILL ALARM NONE I80A00 NOV 7, 2016 11:59 AM RELAY TYPE RELAY DESIGNATION TYPE 1 UNLEADED STANDARD 2 PLUS STANDARD 3 SUPREME STANDARD 4 OVERFILL ALARM STANDARD I80C00 NOV 7, 2016 11:59 AM I80800 NOV 7, 2016 11:59 AM RELAY SETUP REPORT R 1:UNLEADED TYPE: STANDARD NORMALLY CLOSED TANK #: 3 LIQUID SENSOR ALMS L 3:FUEL ALARM L 6:FUEL ALARM L 7:FUEL ALARM L 8:FUEL ALARM L 9:FUEL ALARM L10:FUEL ALARM L11:FUEL ALARM L 3:SENSOR OUT ALARM L 6:SENSOR OUT ALARM L 7:SENSOR OUT ALARM L 8:SENSOR OUT ALARM L 9:SENSOR OUT ALARM L10:SENSOR OUT ALARM L11:SENSOR OUT ALARM L 3:SHORT ALARM L 6:SHORT ALARM L 7:SHORT ALARM L 8:SHORT ALARM L 9:SHORT ALARM L10:SHORT ALARM L11:SHORT ALARM ISD SITE ALARMS ISD GROSS PRES FAIL ISD DEGRD PRES FAIL ISD VAPOR LEAK FAIL ISD VP PRES FAIL ISD VP STATUS FAIL ISD HOSE ALARMS h 1:GROSS COLLECT FAIL h 2:GROSS COLLECT FAIL h 3:GROSS COLLECT FAIL h 4:GROSS COLLECT FAIL h 5:GROSS COLLECT FAIL h 6:GROSS COLLECT FAIL h 7:GROSS COLLECT FAIL h 8:GROSS COLLECT FAIL h 9:GROSS COLLECT FAIL h10:GROSS COLLECT FAIL h11:GROSS COLLECT FAIL h12:GROSS COLLECT FAIL h 1:DEGRD COLLECT FAIL h 2:DEGRD COLLECT FAIL h 3:DEGRD COLLECT FAIL h 4:DEGRD COLLECT FAIL h 5:DEGRD COLLECT FAIL h 6:DEGRD COLLECT FAIL h 7:DEGRD COLLECT FAIL h 8:DEGRD COLLECT FAIL h 9:DEGRD COLLECT FAIL h10:DEGRD COLLECT FAIL h11:DEGRD COLLECT FAIL h12:DEGRD COLLECT FAIL R 2:PLUS TYPE: STANDARD NORMALLY CLOSED TANK #: 2 LIQUID SENSOR ALMS L 1:FUEL ALARM L 5:FUEL ALARM L 6:FUEL ALARM L 7:FUEL ALARM L 8:FUEL ALARM L 9:FUEL ALARM L10:FUEL ALARM L11:FUEL ALARM L 1:SENSOR OUT ALARM L 5:SENSOR OUT ALARM L 6:SENSOR OUT ALARM L 7:SENSOR OUT ALARM L 8:SENSOR OUT ALARM L 9:SENSOR OUT ALARM L10:SENSOR OUT ALARM L11:SENSOR OUT ALARM L 1:SHORT ALARM L 5:SHORT ALARM L 6:SHORT ALARM L 7:SHORT ALARM L 8:SHORT ALARM L 9:SHORT ALARM L10:SHORT ALARM L11:SHORT ALARM ISD SITE ALARMS ISD GROSS PRES FAIL ISD DEGRD PRES FAIL ISD VAPOR LEAK FAIL ISD VP PRES FAIL ISD VP STATUS FAIL ISD HOSE ALARMS h 1:GROSS COLLECT FAIL h 2:GROSS COLLECT FAIL h 3:GROSS COLLECT FAIL h 4:GROSS COLLECT FAIL h 5:GROSS COLLECT FAIL h 6:GROSS COLLECT FAIL h 7:GROSS COLLECT FAIL h 8:GROSS COLLECT FAIL h 9:GROSS COLLECT FAIL h10:GROSS COLLECT FAIL h11:GROSS COLLECT FAIL h12:GROSS COLLECT FAIL h 1:DEGRD COLLECT FAIL h 2:DEGRD COLLECT FAIL h 3:DEGRD COLLECT FAIL h 4:DEGRD COLLECT FAIL h 5:DEGRD COLLECT FAIL h 6:DEGRD COLLECT FAIL h 7:DEGRD COLLECT FAIL h 8:DEGRD COLLECT FAIL h 9:DEGRD COLLECT FAIL h10:DEGRD COLLECT FAIL h11:DEGRD COLLECT FAIL h12:DEGRD COLLECT FAIL R 3:SUPREME TYPE: STANDARD NORMALLY CLOSED TANK #: 1 LIQUID SENSOR ALMS L 4:FUEL ALARM L 6:FUEL ALARM L 7:FUEL ALARM L 8:FUEL ALARM L 9:FUEL ALARM L10:FUEL ALARM L11:FUEL ALARM L 4:SENSOR OUT ALARM L 6:SENSOR OUT ALARM L 7:SENSOR OUT ALARM L 8:SENSOR OUT ALARM L 9:SENSOR OUT ALARM L10:SENSOR OUT ALARM L11:SENSOR OUT ALARM L 4:SHORT ALARM L 6:SHORT ALARM L 7:SHORT ALARM L 8:SHORT ALARM L 9:SHORT ALARM L10:SHORT ALARM L11:SHORT ALARM ISD SITE ALARMS ISD GROSS PRES FAIL ISD DEGRD PRES FAIL ISD VAPOR LEAK FAIL ISD VP PRES FAIL ISD VP STATUS FAIL ISD HOSE ALARMS h 1:GROSS COLLECT FAIL h 2:GROSS COLLECT FAIL h 3:GROSS COLLECT FAIL h 4:GROSS COLLECT FAIL h 5:GROSS COLLECT FAIL h 6:GROSS COLLECT FAIL h 7:GROSS COLLECT FAIL h 8:GROSS COLLECT FAIL h 9:GROSS COLLECT FAIL h10:GROSS COLLECT FAIL h11:GROSS COLLECT FAIL h12:GROSS COLLECT FAIL h 1:DEGRD COLLECT FAIL h 2:DEGRD COLLECT FAIL h 3:DEGRD COLLECT FAIL h 4:DEGRD COLLECT FAIL h 5:DEGRD COLLECT FAIL h 6:DEGRD COLLECT FAIL h 7:DEGRD COLLECT FAIL h 8:DEGRD COLLECT FAIL h 9:DEGRD COLLECT FAIL h10:DEGRD COLLECT FAIL h11:DEGRD COLLECT FAIL h12:DEGRD COLLECT FAIL R 4:OVERFILL ALARM TYPE: STANDARD NORMALLY OPEN TANK #: NONE IN-TANK ALARMS ALL:OVERFILL ALARM ALL:HIGH PRODUCT ALARM ALL:MAX PRODUCT ALARM I79000 NOV 7, 2016 12:00 PM EDIM:1 VR:349634-003-C TD:06.05.11.11.15 I79100 NOV 7, 2016 12:00 PM I72300 NOV 7, 2016 12:00 PM DOWNTOWN CHEV SOUTH 2317 L STREET BAKERSFIELD CA 93301 SMARTSENSOR ASSIGNMENT DEVICE LABEL CATEGORY 01 FM 1-2 AIR FLOW METER 02 FM 3-4 AIR FLOW METER 03 FM 5-6 AIR FLOW METER 04 FM 7-8 AIR FLOW METER 05 FM 9-10 AIR FLOW METER 06 FM 11-12 AIR FLOW METER 07 UNKNOWN 08 PS 1-2 VAPOR PRESSURE 09 UNKNOWN 10 UNKNOWN 11 UNKNOWN 12 UNKNOWN 13 UNKNOWN 14 UNKNOWN 15 UNKNOWN 16 UNKNOWN 17 UNKNOWN 18 UNKNOWN 19 UNKNOWN 20 UNKNOWN 21 UNKNOWN 22 UNKNOWN 23 UNKNOWN 24 UNKNOWN 25 UNKNOWN 26 UNKNOWN 27 UNKNOWN 28 UNKNOWN 29 UNKNOWN 30 UNKNOWN 31 UNKNOWN 32 UNKNOWN 33 UNKNOWN 34 UNKNOWN 35 UNKNOWN 36 UNKNOWN 37 UNKNOWN 38 UNKNOWN 39 UNKNOWN 40 UNKNOWN I72A00 NOV 7, 2016 12:00 PM VACUUM SENSOR VOLUME DEVICE LABEL VOLUME IV4E00 NOV 7, 2016 12:00 PM DOWNTOWN CHEV SOUTH 2317 L STREET BAKERSFIELD CA 93301 EVR/ISD SETUP TYPE: VACUUM ASSIST VACUUM ASSIST TYPE: HEALY VAC IV4F00 NOV 7, 2016 12:00 PM DOWNTOWN CHEV SOUTH 2317 L STREET BAKERSFIELD CA 93301 NOZZLE A/L RANGE A/L RATIO: 0.95 - 1.15 IV4000 NOV 7, 2016 12:00 PM DOWNTOWN CHEV SOUTH 2317 L STREET BAKERSFIELD CA 93301 VAPOR PROCESSOR TYPE NONE IV4700 NOV 7, 2016 12:00 PM DOWNTOWN CHEV SOUTH 2317 L STREET BAKERSFIELD CA 93301 ASSESSMENT TIME START TIME: 10:00 AM TIME DELAY MINUTES: 1 IV5200 NOV 7, 2016 12:00 PM DOWNTOWN CHEV SOUTH 2317 L STREET BAKERSFIELD CA 93301 ACCEPT HIGH ORVR: NO IV4A00 NOV 7, 2016 12:00 PM DOWNTOWN CHEV SOUTH 2317 L STREET BAKERSFIELD CA 93301 ISD HOSE TABLE HOSE FP FP AFM HOSE ID ID LABEL ID LABEL 01 33 01 01 BLEND3 02 34 02 01 BLEND3 03 35 03 02 BLEND3 04 03 04 02 BLEND3 05 04 05 03 BLEND3 06 05 06 03 BLEND3 07 06 07 04 BLEND3 08 07 08 04 BLEND3 09 08 09 05 BLEND3 10 09 10 05 BLEND3 11 02 11 06 BLEND3 12 10 12 06 BLEND3 IV4B00 NOV 7, 2016 12:00 PM DOWNTOWN CHEV SOUTH 2317 L STREET BAKERSFIELD CA 93301 PRODUCT/HOSE MAP TABLE FP AFID M1/H1 M2/H2 M3/H3 M4/H4 02 06 02/11 01/11 xx/xx xx/xx 03 02 02/04 00/04 01/04 xx/xx 04 03 02/05 00/05 01/05 xx/xx 05 03 02/06 00/06 01/06 xx/xx 06 04 02/07 00/07 01/07 xx/xx 07 04 02/08 00/08 01/08 xx/xx 08 05 02/09 00/09 01/09 xx/xx 09 05 02/10 00/10 01/10 xx/xx 10 06 02/12 00/12 01/12 xx/xx 33 01 02/01 00/01 01/01 xx/xx 34 01 02/02 00/02 01/02 xx/xx 35 02 02/03 00/03 01/03 xx/xx IV4900 NOV 7, 2016 12:00 PM DOWNTOWN CHEV SOUTH 2317 L STREET BAKERSFIELD CA 93301 LABEL TABLE ID LABEL 01 UNASSIGNED 02 BLEND3 03 REGULAR 04 MID GRADE 05 PREMIUM 06 GOLD 07 BRONZE 08 SILVER 09 BLEND2 10 BLEND4 IV1000 NOV 7, 2016 12:00 PM ISD VERSION: 01.02 Sullys down town south alarm history before Responses Received: I10200 NOV 7, 2016 11:56 AM DOWNTOWN CHEV SOUTH 2317 L STREET BAKERSFIELD CA 93301 SYSTEM CONFIGURATION SLOT BOARD TYPE POWER ON RESET CURRENT 1 8SMARTSENSOR BD 39614 39891 2 4 PROBE / G.T. 162032 163077 3 INTERSTITIAL BD 200676 201666 4 INTERSTITIAL BD 200288 201378 5 UNUSED 8582861 9532202 6 UNUSED 8576936 9522587 7 UNUSED 8572884 9508653 8 UNUSED 8575912 9497782 9 RELAY BOARD 14962 15000 10 UNUSED 8576912 9495507 11 UNUSED 8569441 9507973 12 UNUSED 8582293 9490337 13 UNUSED 8581073 9493614 14 UNUSED 8577958 9503165 15 UNUSED 8571597 9487742 16 UNUSED 8575279 9502570 COMM 1 ELEC DISP INT. 100734 100959 COMM 2 RS232 SERIAL BD 14962 14978 COMM 3 UNUSED 8581117 9490720 COMM 4 UNUSED 8589133 9498719 COMM 5 SERIAL SAT BD 485401 486760 COMM 6 UNUSED 8584820 9506569 I90200 NOV 7, 2016 11:56 AM SOFTWARE REVISION LEVEL VERSION 329.00 SOFTWARE# 346329-100-A CREATED - 08.10.09.17.08 S-MODULE# 330160-004-a SYSTEM FEATURES: PERIODIC IN-TANK TESTS ANNUAL IN-TANK TESTS ISD I11100 NOV 7, 2016 11:56 AM DOWNTOWN CHEV SOUTH 2317 L STREET BAKERSFIELD CA 93301 PRIORITY ALARM HISTORY ID CATEGORY DESCRIPTION ALARM TYPE STATE DATE TIME D 8 OTHER VEEDER ROOT (FMS) AUTODIAL FAILURE CLEAR 11-03-16 12:25PM D 8 OTHER VEEDER ROOT (FMS) AUTODIAL FAILURE ALARM 11-03-16 12:20AM D 8 OTHER VEEDER ROOT (FMS) AUTODIAL FAILURE CLEAR 11-03-16 12:20AM T 3 TANK UNLEADED OVERFILL ALARM CLEAR 11-03-16 12:02AM T 3 TANK UNLEADED OVERFILL ALARM ALARM 11-02-16 11:55PM D 8 OTHER VEEDER ROOT (FMS) AUTODIAL FAILURE ALARM 11-02-16 10:36PM L 2 ANNULAR 87 91 ANN SENSOR OUT ALARM CLEAR 11-02-16 10:13PM L 2 ANNULAR 87 91 ANN SENSOR OUT ALARM ALARM 11-02-16 10:11PM L 2 ANNULAR 87 91 ANN SENSOR OUT ALARM CLEAR 10-28-16 5:17PM L 2 ANNULAR 87 91 ANN SENSOR OUT ALARM ALARM 10-28-16 4:54PM L 2 ANNULAR 87 91 ANN SENSOR OUT ALARM CLEAR 10-28-16 4:36PM L 2 ANNULAR 87 91 ANN SENSOR OUT ALARM ALARM 10-28-16 4:19PM L 2 ANNULAR 87 91 ANN SENSOR OUT ALARM CLEAR 10-28-16 4:18PM L 2 ANNULAR 87 91 ANN SENSOR OUT ALARM ALARM 10-28-16 4:16PM L 2 ANNULAR 87 91 ANN SENSOR OUT ALARM CLEAR 10-08-16 1:19AM L 2 ANNULAR 87 91 ANN SENSOR OUT ALARM ALARM 10-08-16 1:19AM OTHER MISSING HOSE SETUP CLEAR 7-30-16 10:00AM OTHER MISS VAPOR FLOW MTR CLEAR 7-30-16 8:37AM OTHER MISS VAPOR FLOW MTR ALARM 7-30-16 8:28AM OTHER MISSING HOSE SETUP ALARM 7-30-16 8:28AM L 3 STP SUMP 87 STP FUEL ALARM CLEAR 7-29-16 4:27PM L 3 STP SUMP 87 STP FUEL ALARM ALARM 7-29-16 3:45PM h 9 OTHER FP9: BLEND3 GROSS COLLECT FAIL CLEAR 7-29-16 1:45PM h 8 OTHER FP8: BLEND3 GROSS COLLECT FAIL CLEAR 7-29-16 1:45PM h 9 OTHER FP9: BLEND3 GROSS COLLECT FAIL ALARM 7-29-16 10:05AM h 8 OTHER FP8: BLEND3 GROSS COLLECT FAIL ALARM 7-29-16 10:05AM L 3 STP SUMP 87 STP FUEL ALARM CLEAR 7-09-16 9:28PM L 3 STP SUMP 87 STP FUEL ALARM ALARM 7-09-16 7:10PM L 3 STP SUMP 87 STP FUEL ALARM CLEAR 6-12-16 8:08AM L 3 STP SUMP 87 STP FUEL ALARM ALARM 6-12-16 7:03AM E 1 OTHER COMMUNICATION ALARM CLEAR 6-02-16 3:24PM E 1 OTHER COMMUNICATION ALARM ALARM 6-02-16 3:23PM E 1 OTHER COMMUNICATION ALARM CLEAR 6-02-16 1:35PM E 1 OTHER COMMUNICATION ALARM ALARM 6-02-16 8:06AM L 3 STP SUMP 87 STP FUEL ALARM CLEAR 5-17-16 8:34PM L 3 STP SUMP 87 STP FUEL ALARM ALARM 5-17-16 8:34PM T 3 TANK UNLEADED OVERFILL ALARM CLEAR 4-29-16 10:02PM T 3 TANK UNLEADED OVERFILL ALARM ALARM 4-29-16 9:59PM h11 OTHER FP11: BLEND3 DEGRD COLLECT FAIL CLEAR 12-30-15 10:18AM h11 OTHER FP11: BLEND3 DEGRD COLLECT FAIL ALARM 12-30-15 10:01AM OTHER ISD GROSS PRES FAIL CLEAR 11-25-15 10:19AM OTHER ISD GROSS PRES FAIL ALARM 11-25-15 10:01AM L10 DISP PAN DISP 9-10 FUEL ALARM CLEAR 11-10-15 11:04AM L10 DISP PAN DISP 9-10 FUEL ALARM ALARM 11-10-15 11:03AM L 4 STP SUMP 91 STP SENSOR OUT ALARM CLEAR 11-10-15 10:33AM L 8 DISP PAN DISP 5-6 SENSOR OUT ALARM CLEAR 11-10-15 10:33AM L 7 DISP PAN DISP 3-4 SENSOR OUT ALARM CLEAR 11-10-15 10:33AM L 6 DISP PAN DISP 1-2 SENSOR OUT ALARM CLEAR 11-10-15 10:33AM L 3 STP SUMP 87 STP SENSOR OUT ALARM CLEAR 11-10-15 10:33AM L 2 ANNULAR 87 91 ANN SENSOR OUT ALARM CLEAR 11-10-15 10:33AM I11200 NOV 7, 2016 11:56 AM DOWNTOWN CHEV SOUTH 2317 L STREET BAKERSFIELD CA 93301 NON-PRIORITY ALARM HISTORY ID CATEGORY DESCRIPTION ALARM TYPE STATE DATE TIME h 7 OTHER FP7: BLEND3 DEGRD COLLECT WARN ALARM 11-07-16 10:01AM h11 OTHER FP11: BLEND3 DEGRD COLLECT WARN CLEAR 11-06-16 10:00AM h12 OTHER FP12: BLEND3 DEGRD COLLECT WARN ALARM 11-05-16 10:01AM OTHER ISD GROSS PRES WARN ALARM 11-04-16 10:01AM h11 OTHER FP11: BLEND3 DEGRD COLLECT WARN ALARM 11-04-16 10:01AM h11 OTHER FP11: BLEND3 DEGRD COLLECT WARN CLEAR 11-03-16 10:00AM SYSTEM PRINTER ERROR CLEAR 11-02-16 10:12PM SYSTEM PAPER OUT CLEAR 11-02-16 10:12PM SYSTEM PAPER OUT ALARM 11-02-16 10:12PM SYSTEM PRINTER ERROR ALARM 11-02-16 10:12PM SYSTEM PRINTER ERROR CLEAR 11-02-16 10:12PM SYSTEM PAPER OUT CLEAR 11-02-16 10:12PM SYSTEM PRINTER ERROR ALARM 11-02-16 8:13PM SYSTEM PAPER OUT ALARM 11-02-16 8:13PM h11 OTHER FP11: BLEND3 DEGRD COLLECT WARN ALARM 11-02-16 10:01AM h10 OTHER FP10: BLEND3 DEGRD COLLECT WARN CLEAR 10-31-16 8:40AM h 8 OTHER FP8: BLEND3 DEGRD COLLECT WARN CLEAR 10-28-16 10:00AM h10 OTHER FP10: BLEND3 DEGRD COLLECT WARN ALARM 10-27-16 10:01AM h 8 OTHER FP8: BLEND3 DEGRD COLLECT WARN ALARM 10-27-16 10:01AM h 1 OTHER FP1: BLEND3 DEGRD COLLECT WARN CLEAR 10-21-16 10:00AM h 1 OTHER FP1: BLEND3 DEGRD COLLECT WARN ALARM 10-20-16 10:01AM h 4 OTHER FP4: BLEND3 DEGRD COLLECT WARN CLEAR 10-20-16 10:00AM h 4 OTHER FP4: BLEND3 DEGRD COLLECT WARN ALARM 10-18-16 10:02AM SYSTEM PRINTER ERROR CLEAR 10-16-16 1:17AM SYSTEM PAPER OUT CLEAR 10-16-16 1:17AM SYSTEM PRINTER ERROR ALARM 10-16-16 1:10AM SYSTEM PAPER OUT ALARM 10-16-16 1:10AM h 9 OTHER FP9: BLEND3 DEGRD COLLECT WARN CLEAR 10-06-16 10:00AM h 9 OTHER FP9: BLEND3 DEGRD COLLECT WARN ALARM 10-04-16 10:03AM OTHER ISD GROSS PRES WARN CLEAR 9-30-16 2:15PM h 7 OTHER FP7: BLEND3 DEGRD COLLECT WARN CLEAR 9-26-16 10:00AM SYSTEM PRINTER ERROR CLEAR 9-26-16 3:23AM SYSTEM PAPER OUT CLEAR 9-26-16 3:23AM SYSTEM PRINTER ERROR ALARM 9-26-16 3:22AM SYSTEM PAPER OUT ALARM 9-26-16 3:22AM SYSTEM PRINTER ERROR CLEAR 9-26-16 3:22AM SYSTEM PAPER OUT CLEAR 9-26-16 3:22AM SYSTEM PRINTER ERROR ALARM 9-26-16 3:22AM SYSTEM PAPER OUT ALARM 9-26-16 3:22AM SYSTEM PRINTER ERROR CLEAR 9-26-16 3:22AM SYSTEM PAPER OUT CLEAR 9-26-16 3:22AM SYSTEM PRINTER ERROR ALARM 9-26-16 3:19AM SYSTEM PAPER OUT ALARM 9-26-16 3:19AM SYSTEM PRINTER ERROR CLEAR 9-26-16 3:19AM SYSTEM PAPER OUT CLEAR 9-26-16 3:19AM SYSTEM PRINTER ERROR ALARM 9-26-16 3:16AM SYSTEM PAPER OUT ALARM 9-26-16 3:16AM SYSTEM PRINTER ERROR CLEAR 9-26-16 3:15AM SYSTEM PAPER OUT CLEAR 9-26-16 3:15AM SYSTEM PRINTER ERROR ALARM 9-26-16 3:13AM I20600 NOV 7, 2016 11:56 AM DOWNTOWN CHEV SOUTH 2317 L STREET BAKERSFIELD CA 93301 TANK ALARM HISTORY TANK 1 SUPREME OVERFILL ALARM NOV 10, 2015 10:20 AM PROBE OUT NOV 10, 2015 10:20 AM NOV 10, 2015 9:27 AM JUL 9, 2015 1:30 PM LOW TEMP WARNING NOV 10, 2015 10:21 AM TANK 2 PLUS OVERFILL ALARM NOV 10, 2015 10:23 AM PROBE OUT NOV 10, 2015 10:24 AM NOV 10, 2015 9:26 AM TANK 3 UNLEADED OVERFILL ALARM NOV 2, 2016 11:55 PM APR 29, 2016 9:59 PM NOV 10, 2015 10:18 AM PROBE OUT NOV 10, 2015 10:18 AM NOV 10, 2015 9:27 AM JUL 9, 2015 1:22 PM LOW TEMP WARNING NOV 10, 2015 10:19 AM I38200 NOV 7, 2016 11:56 AM I30200 NOV 7, 2016 11:56 AM DOWNTOWN CHEV SOUTH 2317 L STREET BAKERSFIELD CA 93301 LIQUID ALARM HISTORY REPORT SENSOR LOCATION 1 89 STP NOV 10, 2015 10:32 AM SENSOR OUT ALARM NOV 10, 2015 9:58 AM FUEL ALARM NOV 10, 2015 9:55 AM FUEL ALARM 2 87 91 ANN NOV 2, 2016 10:11 PM SENSOR OUT ALARM OCT 28, 2016 4:54 PM SENSOR OUT ALARM OCT 28, 2016 4:19 PM SENSOR OUT ALARM 3 87 STP JUL 29, 2016 3:45 PM FUEL ALARM JUL 9, 2016 7:10 PM FUEL ALARM JUN 12, 2016 7:03 AM FUEL ALARM 4 91 STP NOV 10, 2015 10:32 AM SENSOR OUT ALARM NOV 10, 2015 9:40 AM FUEL ALARM NOV 10, 2015 9:39 AM FUEL ALARM 5 89 ANN NOV 10, 2015 10:32 AM SENSOR OUT ALARM NOV 10, 2015 10:15 AM FUEL ALARM MAY 22, 2015 12:04 PM FUEL ALARM 6 DISP 1-2 NOV 10, 2015 10:32 AM SENSOR OUT ALARM NOV 10, 2015 10:01 AM FUEL ALARM MAY 22, 2015 10:07 AM FUEL ALARM 7 DISP 3-4 NOV 10, 2015 10:32 AM SENSOR OUT ALARM NOV 10, 2015 10:04 AM FUEL ALARM JUN 24, 2015 9:27 AM SENSOR OUT ALARM 8 DISP 5-6 NOV 10, 2015 10:32 AM SENSOR OUT ALARM NOV 10, 2015 10:05 AM FUEL ALARM MAY 22, 2015 5:03 PM FUEL ALARM 9 DISP 7-8 NOV 10, 2015 10:32 AM SENSOR OUT ALARM NOV 10, 2015 10:07 AM FUEL ALARM MAY 22, 2015 9:34 AM FUEL ALARM 10 DISP 9-10 NOV 10, 2015 11:03 AM FUEL ALARM NOV 10, 2015 10:32 AM SENSOR OUT ALARM NOV 10, 2015 10:13 AM FUEL ALARM 11 DISP 11-12 NOV 10, 2015 10:32 AM SENSOR OUT ALARM NOV 10, 2015 10:08 AM FUEL ALARM MAY 22, 2015 9:33 AM FUEL ALARM I31600 NOV 7, 2016 11:56 AM DOWNTOWN CHEV SOUTH 2317 L STREET BAKERSFIELD CA 93301 SMART SENSOR ALARM HISTORY REPORT SENSOR LOCATION 1 FM 1-2 2 FM 3-4 OCT 9, 2008 8:11 AM COMMUNICATION ALARM 3 FM 5-6 OCT 9, 2008 8:11 AM COMMUNICATION ALARM 4 FM 7-8 OCT 9, 2008 8:11 AM COMMUNICATION ALARM 5 FM 9-10 OCT 9, 2008 8:11 AM COMMUNICATION ALARM 6 FM 11-12 OCT 9, 2008 8:11 AM COMMUNICATION ALARM 8 PS 1-2 OCT 9, 2008 8:11 AM COMMUNICATION ALARM I40200 NOV 7, 2016 11:56 AM I40300 NOV 7, 2016 11:56 AM I34200 NOV 7, 2016 11:56 AM I34700 NOV 7, 2016 11:56 AM IV0100 NOV 7, 2016 11:56 AM DOWNTOWN CHEV SOUTH 2317 L STREET BAKERSFIELD CA 93301 ISD ALARM STATUS REPORT EVR TYPE: VACUUM ASSIST ISD TYPE: 01.02 VAPOR PROCESSOR TYPE: NONE OVERALL STATUS :WARN EVR VAPOR COLLECTION :WARN EVR VAPOR CONTAINMENT :WARN ISD MONITOR UP-TIME :100% STAGE I TRANSFERS: 0 of 0 NOTEST EVR/ISD PASS TIME : 0% WARNING ALARMS DATE TIME DESCRIPTION READING VALUE 16-11-07 10:01:09 CONTAINMENT GROSS OVER PRESSURE WEEKLY 95% 3.68 16-11-07 10:01:09 A/L RATIO DEGRADATION FP12 BLEND3 0.78 16-11-07 10:01:09 A/L RATIO DEGRADATION FP 7 BLEND3 0.80 16-11-06 10:01:09 CONTAINMENT GROSS OVER PRESSURE WEEKLY 95% 3.64 16-11-06 10:01:09 A/L RATIO DEGRADATION FP12 BLEND3 0.79 16-11-05 10:01:18 CONTAINMENT GROSS OVER PRESSURE WEEKLY 95% 3.57 16-11-05 10:01:18 A/L RATIO DEGRADATION FP12 BLEND3 0.81 16-11-05 10:01:17 A/L RATIO DEGRADATION FP11 BLEND3 0.81 16-11-04 10:01:09 CONTAINMENT GROSS OVER PRESSURE WEEKLY 95% 3.56 16-11-04 10:01:09 A/L RATIO DEGRADATION FP11 BLEND3 0.00 FAILURE ALARMS DATE TIME DESCRIPTION READING VALUE 16-07-29 10:05:57 A/L RATIO GROSS BLOCKAGE FP 9 BLEND3 BLKD 16-07-29 10:05:57 A/L RATIO GROSS BLOCKAGE FP 8 BLEND3 BLKD 15-12-30 10:01:45 A/L RATIO DEGRADATION FP11 BLEND3 0.75 15-11-25 10:01:10 CONTAINMENT GROSS OVER PRESSURE WEEKLY 95% 3.75 15-07-13 10:03:17 A/L RATIO GROSS BLOCKAGE FP 5 BLEND3 BLKD 15-07-12 10:03:57 A/L RATIO GROSS BLOCKAGE FP 5 BLEND3 BLKD 15-05-31 10:09:16 A/L RATIO GROSS BLOCKAGE FP 9 BLEND3 0.29 15-05-22 00:00:09 SENSOR OUT SELFTEST E 1 15-05-22 00:00:09 SETUP SELFTEST MISSING TANK(S) 15-05-22 00:00:09 SETUP SELFTEST MISSING HOSE(S) SHUTDOWN & MISCELLANEOUS EVENTS DATE TIME DESCRIPTION ACTION/NAME 16-11-06 01:00:00 TIME CHANGE DETECTED AT: 16-11-06 02:00:13 16-10-31 08:40:22 COLLECTION TEST HH10 GRADE TEST MANUALLY CLEARED 16-09-30 14:15:00 CONTAINMENT GROSS & DEGRD TEST MANUALLY CLEARED 16-09-19 18:36:18 COLLECTION TEST HH01 GRADE TEST MANUALLY CLEARED 16-08-30 16:26:02 COLLECTION TEST HH10 GRADE TEST MANUALLY CLEARED 16-08-30 16:25:57 COLLECTION TEST HH08 GRADE TEST MANUALLY CLEARED 16-08-23 13:18:58 COLLECTION TEST HH01 GRADE TEST MANUALLY CLEARED 16-08-19 10:02:49 READINESS ISD:PP EVR:PP ISD & EVR READY 16-08-19 01:08:02 READINESS ISD:PP EVR:NN EVR READINESS PENDING 16-08-19 01:08:02 ISD STARTUP Sullys down town south alarm history after Responses Received: I10200 NOV 7, 2016 4:29 PM DOWNTOWN CHEV SOUTH 2317 L STREET BAKERSFIELD CA 93301 SYSTEM CONFIGURATION SLOT BOARD TYPE POWER ON RESET CURRENT 1 8SMARTSENSOR BD 39614 39633 2 4 PROBE / G.T. 162032 162148 3 INTERSTITIAL BD 200676 201098 4 INTERSTITIAL BD 200288 200573 5 UNUSED 8582861 9102244 6 UNUSED 8576936 9100128 7 UNUSED 8572884 9098580 8 UNUSED 8575912 9096093 9 RELAY BOARD 14962 14977 10 UNUSED 8576912 9091661 11 UNUSED 8569441 9101739 12 UNUSED 8582293 9096613 13 UNUSED 8581073 9104575 14 UNUSED 8577958 9095828 15 UNUSED 8571597 9094977 16 UNUSED 8575279 9101238 COMM 1 ELEC DISP INT. 100734 100847 COMM 2 RS232 SERIAL BD 14962 14977 COMM 3 UNUSED 8581117 9107847 COMM 4 UNUSED 8589133 9097158 COMM 5 SERIAL SAT BD 485401 485569 COMM 6 UNUSED 8584820 9100670 I90200 NOV 7, 2016 4:29 PM SOFTWARE REVISION LEVEL VERSION 329.00 SOFTWARE# 346329-100-A CREATED - 08.10.09.17.08 S-MODULE# 330160-004-a SYSTEM FEATURES: PERIODIC IN-TANK TESTS ANNUAL IN-TANK TESTS ISD I11100 NOV 7, 2016 4:29 PM DOWNTOWN CHEV SOUTH 2317 L STREET BAKERSFIELD CA 93301 PRIORITY ALARM HISTORY ID CATEGORY DESCRIPTION ALARM TYPE STATE DATE TIME L 3 STP SUMP 87 STP SENSOR OUT ALARM CLEAR 11-07-16 3:28PM L 3 STP SUMP 87 STP SENSOR OUT ALARM ALARM 11-07-16 3:26PM L 3 STP SUMP 87 STP SENSOR OUT ALARM CLEAR 11-07-16 3:13PM L 3 STP SUMP 87 STP SENSOR OUT ALARM ALARM 11-07-16 2:45PM L 3 STP SUMP 87 STP SENSOR OUT ALARM CLEAR 11-07-16 2:44PM L 3 STP SUMP 87 STP SENSOR OUT ALARM ALARM 11-07-16 2:40PM L 3 STP SUMP 87 STP SENSOR OUT ALARM CLEAR 11-07-16 2:39PM L 3 STP SUMP 87 STP SENSOR OUT ALARM ALARM 11-07-16 2:39PM L 3 STP SUMP 87 STP SENSOR OUT ALARM CLEAR 11-07-16 2:38PM L 3 STP SUMP 87 STP SENSOR OUT ALARM ALARM 11-07-16 2:27PM L 3 STP SUMP 87 STP SENSOR OUT ALARM CLEAR 11-07-16 2:27PM L 3 STP SUMP 87 STP SENSOR OUT ALARM ALARM 11-07-16 2:04PM E 1 OTHER COMMUNICATION ALARM CLEAR 11-07-16 1:30PM E 1 OTHER COMMUNICATION ALARM ALARM 11-07-16 1:22PM L11 DISP PAN DISP 11-12 SENSOR OUT ALARM CLEAR 11-07-16 1:06PM L10 DISP PAN DISP 9-10 SENSOR OUT ALARM CLEAR 11-07-16 1:06PM L 9 DISP PAN DISP 7-8 SENSOR OUT ALARM CLEAR 11-07-16 1:06PM L 4 STP SUMP 91 STP SENSOR OUT ALARM CLEAR 11-07-16 1:06PM L 3 STP SUMP 87 STP SENSOR OUT ALARM CLEAR 11-07-16 1:06PM L 2 ANNULAR 87 91 ANN SENSOR OUT ALARM CLEAR 11-07-16 1:06PM L 8 DISP PAN DISP 5-6 SENSOR OUT ALARM CLEAR 11-07-16 1:06PM L 7 DISP PAN DISP 3-4 SENSOR OUT ALARM CLEAR 11-07-16 1:06PM L 6 DISP PAN DISP 1-2 SENSOR OUT ALARM CLEAR 11-07-16 1:06PM L 1 STP SUMP 89 STP SENSOR OUT ALARM CLEAR 11-07-16 1:06PM L 5 ANNULAR 89 ANN SENSOR OUT ALARM CLEAR 11-07-16 1:06PM L10 DISP PAN DISP 9-10 SENSOR OUT ALARM ALARM 11-07-16 1:06PM L 6 DISP PAN DISP 1-2 SENSOR OUT ALARM ALARM 11-07-16 1:06PM L11 DISP PAN DISP 11-12 SENSOR OUT ALARM ALARM 11-07-16 1:06PM L 9 DISP PAN DISP 7-8 SENSOR OUT ALARM ALARM 11-07-16 1:06PM L 4 STP SUMP 91 STP SENSOR OUT ALARM ALARM 11-07-16 1:06PM L 3 STP SUMP 87 STP SENSOR OUT ALARM ALARM 11-07-16 1:05PM L 2 ANNULAR 87 91 ANN SENSOR OUT ALARM ALARM 11-07-16 1:05PM L 8 DISP PAN DISP 5-6 SENSOR OUT ALARM ALARM 11-07-16 1:05PM L 7 DISP PAN DISP 3-4 SENSOR OUT ALARM ALARM 11-07-16 1:05PM L 5 ANNULAR 89 ANN SENSOR OUT ALARM ALARM 11-07-16 1:05PM L 1 STP SUMP 89 STP SENSOR OUT ALARM ALARM 11-07-16 1:05PM T 2 TANK PLUS PROBE OUT CLEAR 11-07-16 1:01PM T 2 TANK PLUS OVERFILL ALARM CLEAR 11-07-16 1:00PM T 2 TANK PLUS PROBE OUT ALARM 11-07-16 1:00PM T 2 TANK PLUS OVERFILL ALARM ALARM 11-07-16 1:00PM T 3 TANK UNLEADED PROBE OUT CLEAR 11-07-16 12:59PM T 3 TANK UNLEADED PROBE OUT ALARM 11-07-16 12:58PM T 1 TANK SUPREME PROBE OUT CLEAR 11-07-16 12:57PM T 1 TANK SUPREME OVERFILL ALARM CLEAR 11-07-16 12:56PM T 1 TANK SUPREME PROBE OUT ALARM 11-07-16 12:56PM T 1 TANK SUPREME OVERFILL ALARM ALARM 11-07-16 12:56PM L 2 ANNULAR 87 91 ANN FUEL ALARM CLEAR 11-07-16 12:54PM L 2 ANNULAR 87 91 ANN FUEL ALARM ALARM 11-07-16 12:54PM L 5 ANNULAR 89 ANN FUEL ALARM CLEAR 11-07-16 12:54PM L 5 ANNULAR 89 ANN FUEL ALARM ALARM 11-07-16 12:53PM I11200 NOV 7, 2016 4:30 PM DOWNTOWN CHEV SOUTH 2317 L STREET BAKERSFIELD CA 93301 NON-PRIORITY ALARM HISTORY ID CATEGORY DESCRIPTION ALARM TYPE STATE DATE TIME h12 OTHER FP12: BLEND3 DEGRD COLLECT WARN CLEAR 11-07-16 3:16PM h 7 OTHER FP7: BLEND3 DEGRD COLLECT WARN CLEAR 11-07-16 3:16PM OTHER ISD GROSS PRES WARN CLEAR 11-07-16 3:16PM T 2 TANK PLUS INVALID FUEL LEVEL CLEAR 11-07-16 1:01PM T 2 TANK PLUS INVALID FUEL LEVEL ALARM 11-07-16 1:01PM T 3 TANK UNLEADED LOW TEMP WARNING CLEAR 11-07-16 12:59PM T 3 TANK UNLEADED LOW TEMP WARNING ALARM 11-07-16 12:59PM T 3 TANK UNLEADED HIGH PRODUCT ALARM CLEAR 11-07-16 12:58PM T 3 TANK UNLEADED HIGH PRODUCT ALARM ALARM 11-07-16 12:58PM T 1 TANK SUPREME HIGH PRODUCT ALARM CLEAR 11-07-16 12:56PM T 1 TANK SUPREME HIGH PRODUCT ALARM ALARM 11-07-16 12:56PM T 2 TANK PLUS DELIVERY NEEDED CLEAR 11-07-16 12:25PM T 2 TANK PLUS DELIVERY NEEDED ALARM 11-07-16 12:24PM T 3 TANK UNLEADED LOW TEMP WARNING CLEAR 11-07-16 12:22PM T 3 TANK UNLEADED LOW TEMP WARNING ALARM 11-07-16 12:22PM h 7 OTHER FP7: BLEND3 DEGRD COLLECT WARN ALARM 11-07-16 10:01AM h11 OTHER FP11: BLEND3 DEGRD COLLECT WARN CLEAR 11-06-16 10:00AM h12 OTHER FP12: BLEND3 DEGRD COLLECT WARN ALARM 11-05-16 10:01AM OTHER ISD GROSS PRES WARN ALARM 11-04-16 10:01AM h11 OTHER FP11: BLEND3 DEGRD COLLECT WARN ALARM 11-04-16 10:01AM h11 OTHER FP11: BLEND3 DEGRD COLLECT WARN CLEAR 11-03-16 10:00AM SYSTEM PRINTER ERROR CLEAR 11-02-16 10:12PM SYSTEM PAPER OUT CLEAR 11-02-16 10:12PM SYSTEM PAPER OUT ALARM 11-02-16 10:12PM SYSTEM PRINTER ERROR ALARM 11-02-16 10:12PM SYSTEM PRINTER ERROR CLEAR 11-02-16 10:12PM SYSTEM PAPER OUT CLEAR 11-02-16 10:12PM SYSTEM PRINTER ERROR ALARM 11-02-16 8:13PM SYSTEM PAPER OUT ALARM 11-02-16 8:13PM h11 OTHER FP11: BLEND3 DEGRD COLLECT WARN ALARM 11-02-16 10:01AM h10 OTHER FP10: BLEND3 DEGRD COLLECT WARN CLEAR 10-31-16 8:40AM h 8 OTHER FP8: BLEND3 DEGRD COLLECT WARN CLEAR 10-28-16 10:00AM h10 OTHER FP10: BLEND3 DEGRD COLLECT WARN ALARM 10-27-16 10:01AM h 8 OTHER FP8: BLEND3 DEGRD COLLECT WARN ALARM 10-27-16 10:01AM h 1 OTHER FP1: BLEND3 DEGRD COLLECT WARN CLEAR 10-21-16 10:00AM h 1 OTHER FP1: BLEND3 DEGRD COLLECT WARN ALARM 10-20-16 10:01AM h 4 OTHER FP4: BLEND3 DEGRD COLLECT WARN CLEAR 10-20-16 10:00AM h 4 OTHER FP4: BLEND3 DEGRD COLLECT WARN ALARM 10-18-16 10:02AM SYSTEM PRINTER ERROR CLEAR 10-16-16 1:17AM SYSTEM PAPER OUT CLEAR 10-16-16 1:17AM SYSTEM PRINTER ERROR ALARM 10-16-16 1:10AM SYSTEM PAPER OUT ALARM 10-16-16 1:10AM h 9 OTHER FP9: BLEND3 DEGRD COLLECT WARN CLEAR 10-06-16 10:00AM h 9 OTHER FP9: BLEND3 DEGRD COLLECT WARN ALARM 10-04-16 10:03AM OTHER ISD GROSS PRES WARN CLEAR 9-30-16 2:15PM h 7 OTHER FP7: BLEND3 DEGRD COLLECT WARN CLEAR 9-26-16 10:00AM SYSTEM PRINTER ERROR CLEAR 9-26-16 3:23AM SYSTEM PAPER OUT CLEAR 9-26-16 3:23AM SYSTEM PRINTER ERROR ALARM 9-26-16 3:22AM SYSTEM PAPER OUT ALARM 9-26-16 3:22AM I20600 NOV 7, 2016 4:30 PM DOWNTOWN CHEV SOUTH 2317 L STREET BAKERSFIELD CA 93301 TANK ALARM HISTORY TANK 1 SUPREME OVERFILL ALARM NOV 7, 2016 12:56 PM NOV 10, 2015 10:20 AM HIGH PRODUCT ALARM NOV 7, 2016 12:56 PM PROBE OUT NOV 7, 2016 12:56 PM NOV 7, 2016 12:23 PM NOV 10, 2015 10:20 AM LOW TEMP WARNING NOV 10, 2015 10:21 AM TANK 2 PLUS OVERFILL ALARM NOV 7, 2016 1:00 PM NOV 10, 2015 10:23 AM LOW PRODUCT ALARM NOV 7, 2016 12:24 PM INVALID FUEL LEVEL NOV 7, 2016 1:01 PM PROBE OUT NOV 7, 2016 1:00 PM NOV 7, 2016 12:24 PM NOV 10, 2015 10:24 AM DELIVERY NEEDED NOV 7, 2016 12:24 PM TANK 3 UNLEADED OVERFILL ALARM NOV 2, 2016 11:55 PM APR 29, 2016 9:59 PM NOV 10, 2015 10:18 AM HIGH PRODUCT ALARM NOV 7, 2016 12:58 PM PROBE OUT NOV 7, 2016 12:58 PM NOV 7, 2016 12:21 PM NOV 10, 2015 10:18 AM LOW TEMP WARNING NOV 7, 2016 12:59 PM NOV 7, 2016 12:22 PM NOV 10, 2015 10:19 AM I38200 NOV 7, 2016 4:30 PM I30200 NOV 7, 2016 4:30 PM DOWNTOWN CHEV SOUTH 2317 L STREET BAKERSFIELD CA 93301 LIQUID ALARM HISTORY REPORT SENSOR LOCATION 1 89 STP NOV 7, 2016 1:05 PM SENSOR OUT ALARM NOV 7, 2016 12:49 PM FUEL ALARM NOV 10, 2015 10:32 AM SENSOR OUT ALARM 2 87 91 ANN NOV 7, 2016 1:05 PM SENSOR OUT ALARM NOV 7, 2016 12:54 PM FUEL ALARM NOV 2, 2016 10:11 PM SENSOR OUT ALARM 3 87 STP NOV 7, 2016 3:26 PM SENSOR OUT ALARM NOV 7, 2016 2:45 PM SENSOR OUT ALARM NOV 7, 2016 2:40 PM SENSOR OUT ALARM 4 91 STP NOV 7, 2016 1:06 PM SENSOR OUT ALARM NOV 7, 2016 12:48 PM FUEL ALARM NOV 10, 2015 10:32 AM SENSOR OUT ALARM 5 89 ANN NOV 7, 2016 1:05 PM SENSOR OUT ALARM NOV 7, 2016 12:53 PM FUEL ALARM NOV 10, 2015 10:32 AM SENSOR OUT ALARM 6 DISP 1-2 NOV 7, 2016 1:06 PM SENSOR OUT ALARM NOV 7, 2016 12:50 PM FUEL ALARM NOV 10, 2015 10:32 AM SENSOR OUT ALARM 7 DISP 3-4 NOV 7, 2016 1:05 PM SENSOR OUT ALARM NOV 7, 2016 12:49 PM FUEL ALARM NOV 10, 2015 10:32 AM SENSOR OUT ALARM 8 DISP 5-6 NOV 7, 2016 1:05 PM SENSOR OUT ALARM NOV 7, 2016 12:51 PM FUEL ALARM NOV 10, 2015 10:32 AM SENSOR OUT ALARM 9 DISP 7-8 NOV 7, 2016 1:06 PM SENSOR OUT ALARM NOV 7, 2016 12:51 PM FUEL ALARM NOV 10, 2015 10:32 AM SENSOR OUT ALARM 10 DISP 9-10 NOV 7, 2016 1:06 PM SENSOR OUT ALARM NOV 7, 2016 12:53 PM FUEL ALARM NOV 10, 2015 11:03 AM FUEL ALARM 11 DISP 11-12 NOV 7, 2016 1:06 PM SENSOR OUT ALARM NOV 7, 2016 12:52 PM FUEL ALARM NOV 10, 2015 10:32 AM SENSOR OUT ALARM I31600 NOV 7, 2016 4:30 PM DOWNTOWN CHEV SOUTH 2317 L STREET BAKERSFIELD CA 93301 SMART SENSOR ALARM HISTORY REPORT SENSOR LOCATION 1 FM 1-2 2 FM 3-4 OCT 9, 2008 8:11 AM COMMUNICATION ALARM 3 FM 5-6 OCT 9, 2008 8:11 AM COMMUNICATION ALARM 4 FM 7-8 OCT 9, 2008 8:11 AM COMMUNICATION ALARM 5 FM 9-10 OCT 9, 2008 8:11 AM COMMUNICATION ALARM 6 FM 11-12 OCT 9, 2008 8:11 AM COMMUNICATION ALARM 8 PS 1-2 OCT 9, 2008 8:11 AM COMMUNICATION ALARM I40200 NOV 7, 2016 4:30 PM I40300 NOV 7, 2016 4:30 PM I34200 NOV 7, 2016 4:30 PM I34700 NOV 7, 2016 4:30 PM IV0100 NOV 7, 2016 4:30 PM DOWNTOWN CHEV SOUTH 2317 L STREET BAKERSFIELD CA 93301 ISD ALARM STATUS REPORT EVR TYPE: VACUUM ASSIST ISD TYPE: 01.02 VAPOR PROCESSOR TYPE: NONE OVERALL STATUS :WARN EVR VAPOR COLLECTION :WARN EVR VAPOR CONTAINMENT :WARN ISD MONITOR UP-TIME :100% STAGE I TRANSFERS: 0 of 0 NOTEST EVR/ISD PASS TIME : 0% WARNING ALARMS DATE TIME DESCRIPTION READING VALUE 16-11-07 10:01:09 CONTAINMENT GROSS OVER PRESSURE WEEKLY 95% 3.68 16-11-07 10:01:09 A/L RATIO DEGRADATION FP12 BLEND3 0.78 16-11-07 10:01:09 A/L RATIO DEGRADATION FP 7 BLEND3 0.80 16-11-06 10:01:09 CONTAINMENT GROSS OVER PRESSURE WEEKLY 95% 3.64 16-11-06 10:01:09 A/L RATIO DEGRADATION FP12 BLEND3 0.79 16-11-05 10:01:18 CONTAINMENT GROSS OVER PRESSURE WEEKLY 95% 3.57 16-11-05 10:01:18 A/L RATIO DEGRADATION FP12 BLEND3 0.81 16-11-05 10:01:17 A/L RATIO DEGRADATION FP11 BLEND3 0.81 16-11-04 10:01:09 CONTAINMENT GROSS OVER PRESSURE WEEKLY 95% 3.56 16-11-04 10:01:09 A/L RATIO DEGRADATION FP11 BLEND3 0.00 FAILURE ALARMS DATE TIME DESCRIPTION READING VALUE 16-07-29 10:05:57 A/L RATIO GROSS BLOCKAGE FP 9 BLEND3 BLKD 16-07-29 10:05:57 A/L RATIO GROSS BLOCKAGE FP 8 BLEND3 BLKD 15-12-30 10:01:45 A/L RATIO DEGRADATION FP11 BLEND3 0.75 15-11-25 10:01:10 CONTAINMENT GROSS OVER PRESSURE WEEKLY 95% 3.75 15-07-13 10:03:17 A/L RATIO GROSS BLOCKAGE FP 5 BLEND3 BLKD 15-07-12 10:03:57 A/L RATIO GROSS BLOCKAGE FP 5 BLEND3 BLKD 15-05-31 10:09:16 A/L RATIO GROSS BLOCKAGE FP 9 BLEND3 0.29 15-05-22 00:00:09 SENSOR OUT SELFTEST E 1 15-05-22 00:00:09 SETUP SELFTEST MISSING TANK(S) 15-05-22 00:00:09 SETUP SELFTEST MISSING HOSE(S) SHUTDOWN & MISCELLANEOUS EVENTS DATE TIME DESCRIPTION ACTION/NAME 16-11-07 15:16:19 COLLECTION TEST HH12 GRADE TEST MANUALLY CLEARED 16-11-07 15:16:15 COLLECTION TEST HH07 GRADE TEST MANUALLY CLEARED 16-11-07 15:16:08 CONTAINMENT GROSS & DEGRD TEST MANUALLY CLEARED 16-11-07 13:05:09 READINESS ISD:PP EVR:NN EVR READINESS PENDING 16-11-07 13:05:09 ISD STARTUP 16-11-07 13:04:59 ISD SHUTDOWN 16-11-06 01:00:00 TIME CHANGE DETECTED AT: 16-11-06 02:00:13 16-10-31 08:40:22 COLLECTION TEST HH10 GRADE TEST MANUALLY CLEARED 16-09-30 14:15:00 CONTAINMENT GROSS & DEGRD TEST MANUALLY CLEARED 16-09-19 18:36:18 COLLECTION TEST HH01 GRADE TEST MANUALLY CLEARED SWRCB, January 2006 Spill Bucket Testing Report Form This form is intended for use by contractors performing annual testing of UST spill containment structures. The completed form and printouts from tests (if applicable), should be provided to the facility owner/operator forsubmittal to the local regulatory agency. 1.FACILITY INFORMATION Facility Name:Date of Testing: Facility Address: Facility Contact:Phone: Date Local Agency Was Notified of Testing : Name of Local Agency Inspector (if present during testing): 2.TESTING CONTRACTOR INFORMATION Company Name:Confidence UST Services, Inc. Technician Conducting Test: Credentials1:CSLB Contractor ICC Service Tech. SWRCB Tank Tester Other (Specify) License Number(s):CSLB#804904 ICC# 3.SPILL BUCKET TESTING INFORMATION Test Method Used:Hydrostatic Vacuum Other Test Equipment Used:Lake TestEquipment Resolution:0.0625” Identify Spill Bucket (By Tank Number, Stored Product, etc.) 1234 Bucket Installation Type: Direct Bury Contained in Sump Direct Bury Contained in Sump Direct Bury Contained in Sump Direct Bury Contained in Sump Bucket Diameter: Bucket Depth: Wait time between applying vacuum/water and start of test: Test Start Time (TI): Initial Reading (RI): Test End Time (TF): Final Reading (RF): Test Duration (TF – TI): Change in Reading (RF -RI): Pass/Fail Threshold or Criteria: Test Result: Pass Fail Pass Fail Pass Fail Pass Fail Comments –(include information on repairs made prior to testing, and recommended follow-up for failed tests) CERTIFICATION OF TECHNICIAN RESPONSIBLE FOR CONDUCTING THIS TESTING I hereby certify that all the information contained in this report is true, accurate, and in full compliance with legal requirements. Technician’s Signature:________________________________________________ Date:_________ 1 State laws and regulations do not currently require testing to be performed by a qualified contractor. However, local requirements may be more stringent. Sully'sDowntown(South)11/07/2016 2317LStreet Bakersfield,CA93301 FrankSullivan(661)327-5008 10/14/2016 Kris Karns Austin Sterling 8339953 Regular 12.00" 12.00" 5min. 11:55 am 9.50" 12:55 pm 9.50" 1hour 0.00" 0.0625" Plus 12.00" 12.00" 5min. 11:55 am 9.25" 12:55 pm 9.25" 1hour 0.00" 0.0625"0.0625" Super 12.00" 12.00" 5min. 11:55 am 9.00" 12:55 pm 9.00" 1hour 0.00" " 11/07/2016