HomeMy WebLinkAboutFMC 2016MONITORING SYSTEM CERTIFICATION For Use By All Jurisdictions Within the State of CaliforniaAuthority Cited: Chapter 6.7, Health and Safety Code; Chapter 16, Division 3, Title 23, California Code of Regulations This form must be used to document testing and servicing of monitoring equipment. A separate certification or report must be prepared for each monitoring system control panel by the technician who performs the work. A copy of this form must be provided to the tank system owner/operator. The owner/operator must submit a copy of this form to the local agency regulating UST systems within 30 days of test date. A.General Information Facility Name:Bldg. No.: Site Address:City:Zip: Facility Contact Person: Contact Phone No.: Make/Model of Monitoring System:Date of Testing/Servicing: B.Inventory of Equipment Tested/Certified Check the appropriate boxes to indicate specific equipment inspected/serviced: Tank ID:Tank ID: In-Tank Gauging Probe.Model:In-Tank Gauging Probe.Model: Annular Space or Vault Sensor.Model:Annular Space or Vault Sensor.Model: Piping Sump / Trench Sensor(s).Model:Piping Sump / Trench Sensor(s).Model: Fill Sump Sensor(s).Model:Fill Sump Sensor(s).Model: Mechanical Line Leak Detector.Model:Mechanical Line Leak Detector.Model: Electronic Line Leak Detector.Model:Electronic LineLeak Detector.Model: Tank Overfill / High-Level Sensor.Model:Tank Overfill / High-Level Sensor.Model: Other (specify equipment type and model in Section E on Page 2).Other (specify equipment type and model in Section E on Page 2). Tank ID:Tank ID: In-Tank Gauging Probe.Model:In-Tank Gauging Probe.Model: Annular Space or Vault Sensor.Model:Annular Space or Vault Sensor.Model: Piping Sump / TrenchSensor(s).Model:Piping Sump / Trench Sensor(s).Model: Fill Sump Sensor(s).Model:Fill Sump Sensor(s).Model: Mechanical Line Leak Detector.Model:Mechanical Line Leak Detector.Model: Electronic Line Leak Detector.Model:Electronic Line Leak Detector.Model: Tank Overfill / High-Level Sensor.Model:Tank Overfill / High-Level Sensor.Model: Other (specify equipment type and model in Section E on Page 2).Other (specify equipment type and model in Section E on Page 2). Dispenser ID:Dispenser ID: Dispenser Containment Sensor(s).Model:Dispenser Containment Sensor(s).Model: Shear Valve(s).Shear Valve(s). Dispenser Containment Float(s) and Chain(s).Dispenser Containment Float(s) and Chain(s). Dispenser ID:Dispenser ID: Dispenser Containment Sensor(s).Model:Dispenser Containment Sensor(s).Model: Shear Valve(s).Shear Valve(s). Dispenser Containment Float(s) and Chain(s).Dispenser Containment Float(s) and Chain(s). Dispenser ID:Dispenser ID: Dispenser Containment Sensor(s).Model:Dispenser Containment Sensor(s).Model: Shear Valve(s).Shear Valve(s). Dispenser Containment Float(s) and Chain(s).Dispenser Containment Float(s) and Chain(s). *If the facility contains more tanks or dispensers, copy this form. Include information for every tank and dispenser at the facility. C.Certification -I certify that the equipment identified in this document was inspected/serviced in accordance with the manufacturers’ guidelines. Attached to this Certification is information (e.g. manufacturers' checklists)necessary to verify that this information is correct and a Plot Plan showing the layout of monitoring equipment. For any equipment capable of generating such reports, I have also attached a copy of the report;(check all that apply):System set-up Alarm history report Technician Name (print):Signature: Certification No.:License. No.:804904 Testing Company Name:Confidence UST Services, Inc.Phone No.:(800)339-9930 Site Address:Date of Testing/Servicing: Page 1 of 3 #3362/Fastrip#633 6401SouthHStreetBakersfield93304 OmeroGarcia (661)393-7000 Veeder-RootTLS-350 07/28/2016 12,000gal.Regular 847390-107 794380-303 794380-208 794380-208 FX1V 847390-107 12,000gal.Super 847390-107 794380-303 794380-208 794380-208 FX1V 847390-107 102000gal.Diesel 847390-107 794380-303 794380-208 794380-208 FX1DV 847390-107 1-2 794380-208 3-4 794380-208 5-6 794380-208 794380-208 7-8 BryanSelf B37501 6401SouthHStreet Bakersfield,CA93304 07/28/2016 794380-208 794380-208 Monitoring System Certification D.Results of Testing/Servicing Software Version Installed: Complete the following checklist: Yes No*Isthe audible alarm operational? Yes No*Is the visual alarm operational? Yes No*Were all sensors visually inspected, functionally tested, and confirmed operational? Yes No*Were all sensors installed at lowest point of secondary containment and positioned so that other equipment will not interfere with their proper operation? Yes No* N/A If alarms are relayed to a remote monitoring station, is all communications equipment (e.g., modem) operational? Yes No* N/A For pressurized piping systems, does the turbine automatically shut down if the piping secondary containment monitoring system detects a leak, fails to operate, or is electrically disconnected? If yes: which sensors initiate positive shut-down? (Check all that apply) Sump/Trench Sensors; Dispenser Containment Sensors. Did you confirm positive shut-down due to leaks and sensor failure/disconnection? Yes; No. Yes No* N/A For tank systems that utilize the monitoring system as the primary tank overfill warning device (i.e., no mechanical overfill prevention valve is installed), is the overfill warning alarm visible and audible at the tank fill point(s) and operating properly? If so, at what percent oftank capacity does the alarm trigger? % Yes*NoWas any monitoring equipment replaced? If yes, identify specific sensors, probes, or other equipment replaced and list the manufacturer name and model for all replacement parts in Section E, below. Yes*NoWas liquid found inside any secondary containment systems designed as dry systems? (Check all that apply) Product; Water. If yes, describe causes in Section E, below. Yes No*Was monitoring system set-up reviewed to ensure proper settings? Attach set up reports, if applicable Yes No*Is all monitoring equipment operational per manufacturer’s specifications? * In Section E below, describe how and when these deficiencies were or will be corrected. E.Comments: Page 2 of 3 327.04 90 208 veeder-root liquid sensor was replaced in the 91 fill sump due to faulty sensor. Monitoring System Certification F.In-Tank Gauging / SIR Equipment: Check this box if tank gauging is used only for inventory control. Check this box if no tank gauging or SIR equipment is installed. This section must be completed if in-tank gauging equipment is used to perform leak detection monitoring. Complete the following checklist: Yes No*Has all input wiring been inspected for proper entry and termination, including testing for ground faults? Yes No*Were all tank gauging probes visually inspected for damage and residue buildup? Yes No*Was accuracy of system product level readings tested? Yes No*Was accuracy of system water level readings tested? Yes No*Were all probes reinstalled properly? Yes No*Were all items on the equipment manufacturer’s maintenance checklist completed? * In the Section H, below, describe how and when these deficiencies were or will be corrected. G.Line Leak Detectors (LLD):Check this box if LLDs are not installed. Complete the following checklist: Yes No* N/A For equipment start-up or annual equipment certification, was a leak simulated to verify LLD performance? (Check all that apply)Simulated leak rate: 3 g.p.h.; 0.1 g.p.h ; 0.2 g.p.h. Yes No*Were all LLDs confirmed operational and accurate within regulatory requirements? Yes No*Was the testing apparatus properly calibrated? Yes No* N/A For mechanical LLDs, does the LLD restrict product flow if it detects a leak? Yes No* N/A For electronic LLDs, does the turbine automatically shut off if the LLD detects a leak? Yes No* N/A For electronic LLDs, does the turbine automatically shut off if any portion of the monitoring system is disabled or disconnected? Yes No* N/A For electronic LLDs, does the turbine automatically shut off if any portion of the monitoring system malfunctions or fails a test? Yes No* N/A For electronic LLDs, have all accessible wiring connections been visually inspected? Yes No*Were all items on the equipment manufacturer’s maintenance checklist completed? * In the Section H, below, describe how and when these deficiencies were or will be corrected. H.Comments: Page 3 of 3 Leak Detector Test Results Sheet Customer Address: Work Order: Site Address: Test Date: Site Contact: Phone: Technician: Phone: 800-339-9930 ICC No.: Product Type LLD Type Model Serial No. Check Valve Holding Pressure Bleed Off ML. Leak Rate Tested: Pass/Fail 3 gph @ 10 psi 3 gph @ 10 psi 3 gph @ 10 psi 3 gph @ 10 psi 3 gph @ 10 psi 3 gph @ 10 psi 3 gph @ 10 psi 3 gph @ 10 psi Technician Name: Technician No.: Signature: Date: JacoHill P.O.Box82515 Bakersfield,CA93380-2515 36824 07/28/2016 8022804-UT Regular Mechanical FX1V BryanSelf (661)393-7000OmeroGarcia Bakersfield,CA93304 6401SouthHStreet #3362/Fastrip#633 39 psi225 Pass FX1VMechanicalPremium 42 psi 191 Pass FX1DVMechanicalDiesel 52 psi 80 Pass BryanSelf 8022804-UT 07/28/2016 Jaco 3362 on South H Setup and alarm history Set up 200 FASTRIP 3362 6401 S H ST BAKERSFIELD,CA93304 661-831-4709 JUL 28, 2016 8:44 AM TANK PRODUCT GALLONS INCHES WATER DEG F ULLAGE 1 UNLEADED 4604 39.18 1.2 90.8 7396 2 PREMIUM 9803 73.09 0.0 87.6 2197 3 DIESEL 6267 49.68 0.0 88.7 5733 I90500 JUL 28, 2016 8:44 AM SOFTWARE REVISION LEVEL VERSION 327.04 SOFTWARE# 346327-100-E CREATED - 07.02.06.10.28 S-MODULE# 330160-004-a SYSTEM FEATURES: PERIODIC IN-TANK TESTS ANNUAL IN-TANK TESTS ISD PMC I50500 JUL 28, 2016 8:44 AM SYSTEM TYPE AND LANGUAGE FLAG SYSTEM UNITS U.S. SYSTEM LANGUAGE ENGLISH SYSTEM DATE/TIME FORMAT MON DD YYYY HH:MM:SS xM I50201 JUL 28, 2016 8:44 AM SHIFT TIME 1 : 6:00 AM I50202 JUL 28, 2016 8:44 AM SHIFT TIME 2 : DISABLED I50203 JUL 28, 2016 8:44 AM SHIFT TIME 3 : DISABLED I50204 JUL 28, 2016 8:44 AM SHIFT TIME 4 : DISABLED I54600 JUL 28, 2016 8:44 AM TANK PER TST NEEDED WRN: DISABLED I54900 JUL 28, 2016 8:44 AM TANK ANN TST NEEDED WRN: DISABLED I55300 JUL 28, 2016 8:44 AM LINE RE-ENABLE METHOD PASS LINE TEST I55600 JUL 28, 2016 8:44 AM LINE PER TST NEEDED WRN: DISABLED I55900 JUL 28, 2016 8:44 AM LINE ANN TST NEEDED WRN: DISABLED I50D00 JUL 28, 2016 8:44 AM PRINT TC VOLUMES ENABLED I50E00 JUL 28, 2016 8:44 AM TEMP COMPENSATION VALUE (DEG F ): 60.0 I60B00 JUL 28, 2016 8:44 AM STICK HEIGHT OFFSET ENABLE STATUS DISABLED I51400 JUL 28, 2016 8:44 AM H-PROTOCOL DATA FORMAT HEIGHT I51A01 JUL 28, 2016 8:44 AM DAYLIGHT SAVING TIME ENABLED ON I51B00 JUL 28, 2016 8:44 AM DAYLIGHT SAVING TIME START DATE MAR WEEK 1 SUN 2:00 AM END DATE NOV WEEK 1 SUN 2:00 AM I51600 JUL 28, 2016 8:44 AM RE-DIRECT LOCAL PRINTOUT DISABLED I50400 JUL 28, 2016 8:44 AM 232 SECURITY CODE PORT SECURITY CODE STATUS 1 000000 DISABLED 2 000000 DISABLED 3 000000 DISABLED 4 000000 DISABLED 5 000000 DISABLED 6 000000 DISABLED I21900 JUL 28, 2016 8:44 AM TANK CHART SECURITY DISABLED I5BD00 JUL 28, 2016 8:44 AM CUSTOM ALARM LABELS DISABLED I56000 JUL 28, 2016 8:44 AM MASS/DENSITY DISABLED I88101 JUL 28, 2016 8:44 AM PORT SETTINGS: COMM BOARD : 1 (RS-232) BAUD RATE : 9600 PARITY : NONE STOP BIT : 1 STOP DATA LENGTH: 8 DATA RS-232 SECURITY CODE : DISABLED I88102 JUL 28, 2016 8:44 AM PORT SETTINGS: COMM BOARD : 2 (RS-232) BAUD RATE : 9600 PARITY : NONE STOP BIT : 1 STOP DATA LENGTH: 8 DATA RS-232 SECURITY CODE : DISABLED I88103 JUL 28, 2016 8:44 AM PORT SETTINGS: COMM BOARD : 3 (EDIM ) RS-232 SECURITY CODE : DISABLED I88104 JUL 28, 2016 8:44 AM I88105 JUL 28, 2016 8:44 AM I88106 JUL 28, 2016 8:44 AM I52000 JUL 28, 2016 8:44 AM RECEIVER AUTO DIAL TYPE & START TIME RCVR LOCATION LABEL DIAL TYPE START TIME 1 ON DATE ??? 28, 2016 DISABLED 2 ON DATE ??? 28, 2016 DISABLED 3 ON DATE ??? 28, 2016 DISABLED 4 ON DATE ??? 28, 2016 DISABLED 5 ON DATE ??? 28, 2016 DISABLED 6 ON DATE ??? 28, 2016 DISABLED 7 ON DATE ??? 28, 2016 DISABLED 8 ON DATE ??? 28, 2016 DISABLED I60100 JUL 28, 2016 8:44 AM TANK CONFIGURATION DEVICE LABEL CONFIGURED 1 UNLEADED ON 2 PREMIUM ON 3 DIESEL ON 4 OFF I60200 JUL 28, 2016 8:44 AM TANK PRODUCT LABEL TANK PRODUCT LABEL 1 UNLEADED 2 PREMIUM 3 DIESEL 4 I60300 JUL 28, 2016 8:44 AM TANK PRODUCT CODE TANK PRODUCT LABEL 1 UNLEADED 1 2 PREMIUM 2 3 DIESEL 3 4 4 I60900 JUL 28, 2016 8:44 AM TANK THERMAL COEFFICIENT TANK PRODUCT LABEL 1 UNLEADED 0.000700 2 PREMIUM 0.000700 3 DIESEL 0.000450 4 0.000000 I60700 JUL 28, 2016 8:44 AM TANK DIAMETER TANK PRODUCT LABEL INCHES 1 UNLEADED 96.00 2 PREMIUM 96.00 3 DIESEL 96.00 4 0.00 I60A00 JUL 28, 2016 8:44 AM TANK FULL VOLUME TANK PRODUCT LABEL TANK PROFILE GALLONS 1 UNLEADED 1 PT 12000 2 PREMIUM 1 PT 12000 3 DIESEL 1 PT 12000 4 1 PT 0 I60400 JUL 28, 2016 8:44 AM TANK FULL VOLUME TANK PRODUCT LABEL GALLONS 1 UNLEADED 12000 2 PREMIUM 12000 3 DIESEL 12000 4 0 I60500 JUL 28, 2016 8:44 AM TANK 4 POINT VOLUMES TANK PRODUCT LABEL GALLONS 1 UNLEADED 12000 0 0 0 2 PREMIUM 12000 0 0 0 3 DIESEL 12000 0 0 0 4 0 0 0 0 I60600 JUL 28, 2016 8:44 AM TANK 20 POINT VOLUMES TANK PRODUCT LABEL GALLONS 1 UNLEADED 12000 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 2 PREMIUM 12000 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 3 DIESEL 12000 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 4 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 I61500 JUL 28, 2016 8:44 AM TANK PRODUCT LABEL METER DATA 1 UNLEADED NO 2 PREMIUM NO 3 DIESEL NO 4 NO I62F00 JUL 28, 2016 8:44 AM MAG PROBE FLOAT SIZE TANK PRODUCT LABEL FLOAT SIZE: 1 UNLEADED 4.0 INCHES 2 PREMIUM 4.0 INCHES 3 DIESEL 4.0 INCHES I62700 JUL 28, 2016 8:44 AM TANK HIGH WATER WARNING LIMIT TANK PRODUCT LABEL INCHES 1 UNLEADED 2.0 2 PREMIUM 2.0 3 DIESEL 2.0 9999FF1B I62400 JUL 28, 2016 8:44 AM TANK HIGH WATER LEVEL LIMIT TANK PRODUCT LABEL INCHES 1 UNLEADED 3.0 2 PREMIUM 3.0 3 DIESEL 3.0 I62800 JUL 28, 2016 8:44 AM TANK MAXIMUM VOLUME LIMIT TANK PRODUCT LABEL GALLONS 1 UNLEADED 12000 2 PREMIUM 12000 3 DIESEL 12000 4 0 I62300 JUL 28, 2016 8:44 AM TANK OVERFILL LEVEL LIMIT TANK PRODUCT LABEL GALLONS 1 UNLEADED 10800 2 PREMIUM 10800 3 DIESEL 10800 4 0 I62200 JUL 28, 2016 8:44 AM TANK HIGH PRODUCT LIMIT TANK PRODUCT LABEL GALLONS 1 UNLEADED 11400 2 PREMIUM 11400 3 DIESEL 11400 4 0 I62900 JUL 28, 2016 8:44 AM TANK DELIVERY REQUIRED LIMIT TANK PRODUCT LABEL GALLONS 1 UNLEADED 1200 2 PREMIUM 1200 3 DIESEL 1200 4 0 I62100 JUL 28, 2016 8:44 AM TANK LOW PRODUCT LIMIT TANK PRODUCT LABEL GALLONS 1 UNLEADED 1200 2 PREMIUM 1200 3 DIESEL 1200 4 0 I62600 JUL 28, 2016 8:44 AM TANK LEAK ALARM LIMIT TANK PRODUCT LABEL GALLONS 1 UNLEADED 99 2 PREMIUM 99 3 DIESEL 99 4 99 I62500 JUL 28, 2016 8:44 AM TANK SUDDEN LOSS LIMIT TANK PRODUCT LABEL GALLONS 1 UNLEADED 99 2 PREMIUM 99 3 DIESEL 99 4 99 I60800 JUL 28, 2016 8:44 AM TANK TILT TANK PRODUCT LABEL INCHES 1 UNLEADED 9.00 2 PREMIUM 8.00 3 DIESEL 0.00 4 0.00 I60B00 JUL 28, 2016 8:44 AM STICK HEIGHT OFFSET ENABLE STATUS DISABLED I60C00 JUL 28, 2016 8:44 AM TANK STICK HEIGHT OFFSET TANK PRODUCT LABEL INCHES 1 UNLEADED 0.00 2 PREMIUM 0.00 3 DIESEL 0.00 4 0.00 I61200 JUL 28, 2016 8:44 AM TANK MANIFOLDED PARTNERS TANK PRODUCT LABEL SIPHON MANIFOLDED TANKS LINE MANIFOLDED TANKS 1 UNLEADED NONE NONE 2 PREMIUM NONE NONE 3 DIESEL NONE NONE 4 NONE NONE I63600 JUL 28, 2016 8:44 AM PERIODIC LEAK TEST MIN VOLUME TANK PRODUCT LABEL GALLONS 1 UNLEADED 120 2 PREMIUM 120 3 DIESEL 120 4 0 I62A00 JUL 28, 2016 8:44 AM ANNUAL LEAK TEST MIN VOLUME TANK PRODUCT LABEL GALLONS 1 UNLEADED 120 2 PREMIUM 120 3 DIESEL 120 4 0 I62C00 JUL 28, 2016 8:44 AM TANK PERIODIC TEST TYPE TANK PRODUCT LABEL PERIODIC TEST TYPE 1 UNLEADED STANDARD 2 PREMIUM STANDARD 3 DIESEL STANDARD 4 STANDARD I62D00 JUL 28, 2016 8:44 AM TANK LEAK TEST FAIL ALARMS TANK PRODUCT LABEL 1 UNLEADED GROSS TEST FAIL ALARM DISABLED PERIODIC TEST FAIL ALARM DISABLED ANNUAL TEST FAIL ALARM DISABLED 2 PREMIUM GROSS TEST FAIL ALARM DISABLED PERIODIC TEST FAIL ALARM DISABLED ANNUAL TEST FAIL ALARM DISABLED 3 DIESEL GROSS TEST FAIL ALARM DISABLED PERIODIC TEST FAIL ALARM DISABLED ANNUAL TEST FAIL ALARM DISABLED 4 GROSS TEST FAIL ALARM DISABLED PERIODIC TEST FAIL ALARM DISABLED ANNUAL TEST FAIL ALARM DISABLED I63100 JUL 28, 2016 8:44 AM TANK LEAK TEST AVERAGING TANK PRODUCT LABEL ANNUAL PERIODIC 1 UNLEADED OFF OFF 2 PREMIUM OFF OFF 3 DIESEL OFF OFF 4 OFF OFF I63000 JUL 28, 2016 8:44 AM IN-TANK LEAK TEST NOTIFY TANK PRODUCT LABEL TANK TEST NOTIFY: 1 UNLEADED OFF 2 PREMIUM OFF 3 DIESEL OFF 4 OFF I63200 JUL 28, 2016 8:44 AM TANK TEST SIPHON BREAK TANK PRODUCT LABEL SIPHON BREAK 1 UNLEADED OFF 2 PREMIUM OFF 3 DIESEL OFF 4 OFF I61000 JUL 28, 2016 8:44 AM TANK DELIVERY DELAY TANK PRODUCT LABEL 1 UNLEADED 1 2 PREMIUM 1 3 DIESEL 1 4 1 I63A00 JUL 28, 2016 8:44 AM LOW LEVEL PUMP THRESHOLD FOR SEQUENTIAL LINE MANIFOLD TANK PRODUCT LABEL PUMP THRESHOLD 1 UNLEADED 10.00% 2 PREMIUM 10.00% 3 DIESEL 10.00% 4 10.00% I61100 JUL 28, 2016 8:44 AM LEAK TEST METHOD - - - - - - - - - - - - TEST ON DATE : ALL TANK FEB 6, 2007 START TIME : DISABLED TEST RATE :0.20 GAL/HR DURATION : 2 HOURS TST EARLY STOP:DISABLED I61300 JUL 28, 2016 8:44 AM CSLD PROBABLITY OF DETECTION I61400 JUL 28, 2016 8:44 AM CSLD CLIMATE FACTOR I61600 JUL 28, 2016 8:44 AM TANK PRODUCT LABEL CAL UPDATE 1 UNLEADED IMMEDIATE 2 PREMIUM IMMEDIATE 3 DIESEL IMMEDIATE 4 IMMEDIATE I61A00 JUL 28, 2016 8:44 AM IN-TANK LEAK TEST EARLY STOP TANK PRODUCT LABEL TST EARLY STOP: 1 UNLEADED DISABLED 2 PREMIUM DISABLED 3 DIESEL DISABLED 4 DISABLED I61B00 JUL 28, 2016 8:44 AM IN-TANK LEAK GROSS TEST AUTO-CONFIRM I61C00 JUL 28, 2016 8:44 AM CSLD REPORT ONLY I62B00 JUL 28, 2016 8:44 AM TANK LAST ANNUAL TEST TANK PRODUCT LABEL DATE 1 UNLEADED ??? 0, 0 2 PREMIUM ??? 0, 0 3 DIESEL ??? 0, 0 4 ??? 0, 0 I63300 JUL 28, 2016 8:44 AM LEAK TEST REPORT FORMAT: NORMAL I63400 JUL 28, 2016 8:44 AM RECONCILIATION WARNING LIMIT TANK PRODUCT LABEL GALLONS 1 UNLEADED 0 2 PREMIUM 0 3 DIESEL 0 4 0 I63500 JUL 28, 2016 8:44 AM RECONCILIATION ALARM LIMIT TANK PRODUCT LABEL GALLONS 1 UNLEADED 1 2 PREMIUM 1 3 DIESEL 1 4 1 I63900 JUL 28, 2016 8:44 AM ACCU CHART END SHAPE FACTOR TANK PRODUCT LABEL 1 UNLEADED END FACTOR: NONE 2 PREMIUM END FACTOR: NONE 3 DIESEL END FACTOR: NONE 4 END FACTOR: NONE I78000 JUL 28, 2016 8:44 AM I77700 JUL 28, 2016 8:44 AM I77800 JUL 28, 2016 8:44 AM I78C00 JUL 28, 2016 8:44 AM I78300 JUL 28, 2016 8:44 AM I78F00 JUL 28, 2016 8:44 AM I78700 JUL 28, 2016 8:44 AM I70200 JUL 28, 2016 8:44 AM LIQUID LABEL DEVICE LABEL 1 UNL STP 2 UNL FILL 3 UNL ANN 4 PNL STP 5 PNL FILL 6 PNL ANN 7 DSL STP 8 DSL FILL 9 DSL ANN 10 DISP 1-2 11 DISP 3-4 12 DISP 5-6 13 DISP 7-8 14 15 16 I70300 JUL 28, 2016 8:44 AM LIQUID TYPE SENSOR LOCATION TYPE 1 UNL STP TRI-STATE (SINGLE FLOAT) 2 UNL FILL TRI-STATE (SINGLE FLOAT) 3 UNL ANN DUAL POINT HYDROSTATIC 4 PNL STP TRI-STATE (SINGLE FLOAT) 5 PNL FILL TRI-STATE (SINGLE FLOAT) 6 PNL ANN DUAL POINT HYDROSTATIC 7 DSL STP TRI-STATE (SINGLE FLOAT) 8 DSL FILL TRI-STATE (SINGLE FLOAT) 9 DSL ANN DUAL POINT HYDROSTATIC 10 DISP 1-2 TRI-STATE (SINGLE FLOAT) 11 DISP 3-4 TRI-STATE (SINGLE FLOAT) 12 DISP 5-6 TRI-STATE (SINGLE FLOAT) 13 DISP 7-8 TRI-STATE (SINGLE FLOAT) 14 TRI-STATE (SINGLE FLOAT) 15 TRI-STATE (SINGLE FLOAT) 16 TRI-STATE (SINGLE FLOAT) I70400 JUL 28, 2016 8:44 AM LIQUID CATEGORY SENSOR LOCATION CATEGORY 1 UNL STP STP SUMP 2 UNL FILL PIPING SUMP 3 UNL ANN ANNULAR SPACE 4 PNL STP STP SUMP 5 PNL FILL PIPING SUMP 6 PNL ANN ANNULAR SPACE 7 DSL STP STP SUMP 8 DSL FILL PIPING SUMP 9 DSL ANN ANNULAR SPACE 10 DISP 1-2 DISPENSER PAN 11 DISP 3-4 DISPENSER PAN 12 DISP 5-6 DISPENSER PAN 13 DISP 7-8 DISPENSER PAN 14 OTHER SENSORS 15 OTHER SENSORS 16 OTHER SENSORS I74200 JUL 28, 2016 8:45 AM I74300 JUL 28, 2016 8:45 AM I74400 JUL 28, 2016 8:45 AM I74700 JUL 28, 2016 8:45 AM I74800 JUL 28, 2016 8:45 AM I74900 JUL 28, 2016 8:45 AM I7BC00 JUL 28, 2016 8:45 AM I80200 JUL 28, 2016 8:45 AM I80300 JUL 28, 2016 8:45 AM I80400 JUL 28, 2016 8:45 AM I80700 JUL 28, 2016 8:45 AM RELAY LABEL DEVICE LABEL 1 POS SHUT DOWN 2 OVERFILL ALARM 3 4 I80900 JUL 28, 2016 8:45 AM RELAY ORIENTATION RELAY DESIGNATION ORIENTATION 1 POS SHUT DOWN NORMALLY CLOSED 2 OVERFILL ALARM NORMALLY OPEN 3 NORMALLY OPEN 4 NORMALLY OPEN I80B00 JUL 28, 2016 8:45 AM RELAY TANK ASSIGNMENT RELAY DESIGNATION TANK 1 POS SHUT DOWN 1 2 OVERFILL ALARM NONE 3 NONE 4 NONE I80A00 JUL 28, 2016 8:45 AM RELAY TYPE RELAY DESIGNATION TYPE 1 POS SHUT DOWN STANDARD 2 OVERFILL ALARM STANDARD 3 STANDARD 4 STANDARD I80C00 JUL 28, 2016 8:45 AM I80800 JUL 28, 2016 8:45 AM RELAY SETUP REPORT R 1:POS SHUT DOWN TYPE: STANDARD NORMALLY CLOSED TANK #: 1 LIQUID SENSOR ALMS L 1:FUEL ALARM L 4:FUEL ALARM L 7:FUEL ALARM L10:FUEL ALARM L11:FUEL ALARM L12:FUEL ALARM L13:FUEL ALARM L 1:SENSOR OUT ALARM L 4:SENSOR OUT ALARM L 7:SENSOR OUT ALARM L10:SENSOR OUT ALARM L11:SENSOR OUT ALARM L12:SENSOR OUT ALARM L13:SENSOR OUT ALARM L 1:SHORT ALARM L 4:SHORT ALARM L 7:SHORT ALARM L10:SHORT ALARM L11:SHORT ALARM L12:SHORT ALARM L13:SHORT ALARM ISD SITE ALARMS ISD GROSS PRES FAIL ISD DEGRD PRES FAIL ISD VAPOR LEAK FAIL ISD HOSE ALARMS ALL:GROSS COLLECT FAIL ALL:DEGRD COLLECT FAIL ALL:FLOW COLLECT FAIL R 2:OVERFILL ALARM TYPE: STANDARD NORMALLY OPEN TANK #: NONE IN-TANK ALARMS ALL:OVERFILL ALARM ALL:HIGH PRODUCT ALARM ALL:MAX PRODUCT ALARM R 3: TYPE: STANDARD NORMALLY OPEN TANK #: NONE - NO ALARM ASSIGNMENTS - R 4: TYPE: STANDARD NORMALLY OPEN TANK #: NONE - NO ALARM ASSIGNMENTS - I79000 JUL 28, 2016 8:45 AM EDIM:1 VR:349634-003-C TD:06.05.11.11.15 I79100 JUL 28, 2016 8:45 AM I72300 JUL 28, 2016 8:45 AM FASTRIP 3362 6401 S H ST BAKERSFIELD,CA93304 661-831-4709 SMARTSENSOR ASSIGNMENT DEVICE LABEL CATEGORY 01 PS 1-2 VAPOR PRESSURE 02 FM 1-2 AIR FLOW METER 03 FM 3-4 AIR FLOW METER 04 F-M 5-6 AIR FLOW METER 05 FM 7-8 AIR FLOW METER 06 UNKNOWN 07 UNKNOWN 08 UNKNOWN 09 UNKNOWN 10 UNKNOWN 11 UNKNOWN 12 UNKNOWN 13 UNKNOWN 14 UNKNOWN 15 UNKNOWN 16 UNKNOWN 17 UNKNOWN 18 UNKNOWN 19 UNKNOWN 20 UNKNOWN 21 UNKNOWN 22 UNKNOWN 23 UNKNOWN 24 UNKNOWN 25 UNKNOWN 26 UNKNOWN 27 UNKNOWN 28 UNKNOWN 29 UNKNOWN 30 UNKNOWN 31 UNKNOWN 32 UNKNOWN 33 UNKNOWN 34 UNKNOWN 35 UNKNOWN 36 UNKNOWN 37 UNKNOWN 38 UNKNOWN 39 UNKNOWN 40 UNKNOWN IV4E00 JUL 28, 2016 8:45 AM FASTRIP 3362 6401 S H ST BAKERSFIELD,CA93304 661-831-4709 EVR/ISD SETUP TYPE: VACUUM ASSIST VACUUM ASSIST TYPE: HEALY VAC IV4F00 JUL 28, 2016 8:45 AM FASTRIP 3362 6401 S H ST BAKERSFIELD,CA93304 661-831-4709 NOZZLE A/L RANGE A/L RATIO: 0.95 - 1.15 IV4000 JUL 28, 2016 8:45 AM FASTRIP 3362 6401 S H ST BAKERSFIELD,CA93304 661-831-4709 VAPOR PROCESSOR TYPE NO VAPOR PROCESSOR IV4700 JUL 28, 2016 8:45 AM FASTRIP 3362 6401 S H ST BAKERSFIELD,CA93304 661-831-4709 ASSESSMENT TIME START TIME: 10:00 AM TIME DELAY MINUTES: 1 IV5200 JUL 28, 2016 8:45 AM FASTRIP 3362 6401 S H ST BAKERSFIELD,CA93304 661-831-4709 ACCEPT HIGH ORVR: NO IV4A00 JUL 28, 2016 8:45 AM FASTRIP 3362 6401 S H ST BAKERSFIELD,CA93304 661-831-4709 ISD HOSE TABLE HOSE FP FP AFM HOSE ID ID LABEL ID LABEL 01 33 01 01 BLEND3 02 34 02 01 BLEND3 03 35 03 02 BLEND3 04 00 04 02 BLEND3 05 01 05 03 BLEND3 06 02 06 03 BLEND3 07 03 07 04 BLEND3 08 04 08 04 BLEND3 IV4B00 JUL 28, 2016 8:45 AM FASTRIP 3362 6401 S H ST BAKERSFIELD,CA93304 661-831-4709 PRODUCT/HOSE MAP TABLE FP AFID M1/H1 M2/H2 M3/H3 M4/H4 00 02 02/04 03/04 09/04 xx/xx 01 03 02/05 03/05 09/05 xx/xx 02 03 02/06 03/06 09/06 xx/xx 03 04 02/07 03/07 09/07 xx/xx 04 04 02/08 03/08 09/08 xx/xx 33 01 02/01 03/01 09/01 xx/xx 34 01 02/02 03/02 09/02 xx/xx 35 02 02/03 03/03 09/03 xx/xx IV4900 JUL 28, 2016 8:45 AM FASTRIP 3362 6401 S H ST BAKERSFIELD,CA93304 661-831-4709 LABEL TABLE ID LABEL 01 UNASSIGNED 02 BLEND3 03 REGULAR 04 MID GRADE 05 PREMIUM 06 GOLD 07 BRONZE 08 SILVER 09 BLEND2 10 BLEND4 IV1000 JUL 28, 2016 8:45 AM ISD VERSION: 01.01 Alarm History I10200 JUL 28, 2016 8:47 AM FASTRIP 3362 6401 S H ST BAKERSFIELD,CA93304 661-831-4709 SYSTEM CONFIGURATION SLOT BOARD TYPE POWER ON RESET CURRENT 1 8SMARTSENSOR BD 39555 39558 2 4 PROBE / G.T. 164633 164577 3 INTERSTITIAL BD 202423 202456 4 INTERSTITIAL BD 202561 202640 5 UNUSED 9906997 9932656 6 UNUSED 9897468 9924186 7 UNUSED 9890938 9919808 8 UNUSED 9896475 9922351 9 UNUSED 9892269 9919016 10 RELAY BOARD 14977 14985 11 UNUSED 9897276 9924722 12 UNUSED 9891872 9920498 13 UNUSED 9892489 9919746 14 UNUSED 9889997 9916960 15 UNUSED 9889004 9922930 16 UNUSED 9892887 9920631 COMM 1 RS232 SERIAL BD 14999 15007 COMM 2 RS232 SERIAL BD 15110 15096 COMM 3 ELEC DISP INT. 101667 101752 COMM 4 UNUSED 9900938 9928194 COMM 5 UNUSED 9895026 9922333 COMM 6 UNUSED 9888364 9918353 I90200 JUL 28, 2016 8:47 AM SOFTWARE REVISION LEVEL VERSION 327.04 SOFTWARE# 346327-100-E CREATED - 07.02.06.10.28 S-MODULE# 330160-004-a SYSTEM FEATURES: PERIODIC IN-TANK TESTS ANNUAL IN-TANK TESTS ISD PMC I11100 JUL 28, 2016 8:47 AM FASTRIP 3362 6401 S H ST BAKERSFIELD,CA93304 661-831-4709 PRIORITY ALARM HISTORY ID CATEGORY DESCRIPTION ALARM TYPE STATE DATE TIME L 6 ANNULAR PNL ANN HIGH LIQUID ALARM ALARM 7-28-16 1:36AM L 6 ANNULAR PNL ANN HIGH LIQUID ALARM CLEAR 7-27-16 7:11PM L 6 ANNULAR PNL ANN HIGH LIQUID ALARM ALARM 7-27-16 5:00PM T 3 TANK DIESEL PROBE OUT CLEAR 7-22-16 10:42AM T 3 TANK DIESEL PROBE OUT ALARM 7-22-16 10:42AM T 2 TANK PREMIUM PROBE OUT CLEAR 7-22-16 10:42AM T 2 TANK PREMIUM PROBE OUT ALARM 7-22-16 10:41AM T 1 TANK UNLEADED PROBE OUT CLEAR 7-22-16 10:41AM T 1 TANK UNLEADED PROBE OUT ALARM 7-22-16 10:41AM L 2 PIPE UNL FILL SENSOR OUT ALARM CLEAR 7-22-16 9:53AM L 8 PIPE DSL FILL SENSOR OUT ALARM CLEAR 7-22-16 9:53AM L 7 STP SUMP DSL STP SENSOR OUT ALARM CLEAR 7-22-16 9:53AM L12 DISP PAN DISP 5-6 SENSOR OUT ALARM CLEAR 7-22-16 9:53AM L11 DISP PAN DISP 3-4 SENSOR OUT ALARM CLEAR 7-22-16 9:53AM L 6 ANNULAR PNL ANN SENSOR OUT ALARM CLEAR 7-22-16 9:53AM L 4 STP SUMP PNL STP SENSOR OUT ALARM CLEAR 7-22-16 9:53AM L 3 ANNULAR UNL ANN SENSOR OUT ALARM CLEAR 7-22-16 9:53AM L10 DISP PAN DISP 1-2 SENSOR OUT ALARM CLEAR 7-22-16 9:53AM L 1 STP SUMP UNL STP SENSOR OUT ALARM CLEAR 7-22-16 9:53AM L 5 PIPE PNL FILL SENSOR OUT ALARM CLEAR 7-22-16 9:53AM L 9 ANNULAR DSL ANN SENSOR OUT ALARM CLEAR 7-22-16 9:53AM L13 DISP PAN DISP 7-8 SENSOR OUT ALARM CLEAR 7-22-16 9:53AM L 4 STP SUMP PNL STP SENSOR OUT ALARM ALARM 7-22-16 9:52AM L 3 ANNULAR UNL ANN SENSOR OUT ALARM ALARM 7-22-16 9:52AM L12 DISP PAN DISP 5-6 SENSOR OUT ALARM ALARM 7-22-16 9:52AM L11 DISP PAN DISP 3-4 SENSOR OUT ALARM ALARM 7-22-16 9:52AM L10 DISP PAN DISP 1-2 SENSOR OUT ALARM ALARM 7-22-16 9:52AM L 2 PIPE UNL FILL SENSOR OUT ALARM ALARM 7-22-16 9:52AM L 8 PIPE DSL FILL SENSOR OUT ALARM ALARM 7-22-16 9:52AM L 7 STP SUMP DSL STP SENSOR OUT ALARM ALARM 7-22-16 9:52AM L13 DISP PAN DISP 7-8 SENSOR OUT ALARM ALARM 7-22-16 9:52AM L 6 ANNULAR PNL ANN SENSOR OUT ALARM ALARM 7-22-16 9:52AM L 9 ANNULAR DSL ANN SENSOR OUT ALARM ALARM 7-22-16 9:52AM L 1 STP SUMP UNL STP SENSOR OUT ALARM ALARM 7-22-16 9:52AM L 5 PIPE PNL FILL SENSOR OUT ALARM ALARM 7-22-16 9:52AM T 1 TANK UNLEADED PROBE OUT CLEAR 7-22-16 9:48AM T 2 TANK PREMIUM OVERFILL ALARM CLEAR 7-22-16 9:48AM T 1 TANK UNLEADED PROBE OUT ALARM 7-22-16 9:48AM T 2 TANK PREMIUM OVERFILL ALARM ALARM 7-22-16 9:47AM T 2 TANK PREMIUM PROBE OUT CLEAR 7-22-16 9:47AM T 2 TANK PREMIUM OVERFILL ALARM CLEAR 7-22-16 9:47AM T 2 TANK PREMIUM PROBE OUT ALARM 7-22-16 9:47AM T 3 TANK DIESEL OVERFILL ALARM CLEAR 7-22-16 9:46AM T 2 TANK PREMIUM OVERFILL ALARM ALARM 7-22-16 9:46AM T 3 TANK DIESEL OVERFILL ALARM ALARM 7-22-16 9:44AM T 3 TANK DIESEL PROBE OUT CLEAR 7-22-16 9:38AM T 1 TANK UNLEADED PROBE OUT CLEAR 7-22-16 9:35AM T 1 TANK UNLEADED PROBE OUT ALARM 7-22-16 9:34AM T 2 TANK PREMIUM PROBE OUT CLEAR 7-22-16 9:34AM T 2 TANK PREMIUM PROBE OUT ALARM 7-22-16 9:34AM I11200 JUL 28, 2016 8:47 AM FASTRIP 3362 6401 S H ST BAKERSFIELD,CA93304 661-831-4709 NON-PRIORITY ALARM HISTORY ID CATEGORY DESCRIPTION ALARM TYPE STATE DATE TIME T 1 TANK UNLEADED HIGH PRODUCT ALARM CLEAR 7-22-16 9:49AM T 1 TANK UNLEADED HIGH PRODUCT ALARM ALARM 7-22-16 9:49AM T 2 TANK PREMIUM HIGH PRODUCT ALARM CLEAR 7-22-16 9:48AM T 2 TANK PREMIUM HIGH PRODUCT ALARM ALARM 7-22-16 9:48AM T 2 TANK PREMIUM HIGH PRODUCT ALARM CLEAR 7-22-16 9:47AM T 2 TANK PREMIUM HIGH PRODUCT ALARM ALARM 7-22-16 9:46AM T 1 TANK UNLEADED INVALID FUEL LEVEL CLEAR 7-13-16 9:57AM T 1 TANK UNLEADED INVALID FUEL LEVEL ALARM 7-13-16 6:37AM SYSTEM PRINTER ERROR CLEAR 6-29-16 6:02AM SYSTEM PAPER OUT CLEAR 6-29-16 6:02AM SYSTEM PRINTER ERROR ALARM 6-29-16 6:00AM SYSTEM PAPER OUT ALARM 6-29-16 6:00AM T 1 TANK UNLEADED INVALID FUEL LEVEL CLEAR 6-28-16 7:31AM T 1 TANK UNLEADED INVALID FUEL LEVEL ALARM 6-28-16 7:29AM OTHER ISD VAPOR LEAK WARN CLEAR 6-07-16 3:38PM OTHER ISD VAPOR LEAK WARN ALARM 6-07-16 10:01AM T 3 TANK DIESEL DELIVERY NEEDED CLEAR 6-05-16 12:37AM T 3 TANK DIESEL DELIVERY NEEDED ALARM 6-04-16 9:40PM T 1 TANK UNLEADED INVALID FUEL LEVEL CLEAR 6-04-16 8:50AM T 1 TANK UNLEADED INVALID FUEL LEVEL ALARM 6-04-16 5:34AM SYSTEM PRINTER ERROR CLEAR 6-01-16 6:06AM SYSTEM PAPER OUT CLEAR 6-01-16 6:06AM SYSTEM PRINTER ERROR ALARM 6-01-16 6:06AM SYSTEM PAPER OUT ALARM 6-01-16 6:06AM SYSTEM PRINTER ERROR CLEAR 6-01-16 6:06AM SYSTEM PAPER OUT CLEAR 6-01-16 6:06AM SYSTEM PRINTER ERROR ALARM 6-01-16 6:00AM SYSTEM PAPER OUT ALARM 6-01-16 6:00AM T 1 TANK UNLEADED INVALID FUEL LEVEL CLEAR 5-22-16 5:08PM T 1 TANK UNLEADED INVALID FUEL LEVEL ALARM 5-22-16 3:54PM T 1 TANK UNLEADED INVALID FUEL LEVEL CLEAR 5-15-16 3:05AM T 1 TANK UNLEADED INVALID FUEL LEVEL ALARM 5-14-16 11:18PM T 1 TANK UNLEADED INVALID FUEL LEVEL CLEAR 5-10-16 7:32PM T 1 TANK UNLEADED INVALID FUEL LEVEL ALARM 5-10-16 4:27PM T 1 TANK UNLEADED INVALID FUEL LEVEL CLEAR 5-09-16 12:08PM T 1 TANK UNLEADED INVALID FUEL LEVEL ALARM 5-09-16 9:53AM OTHER ISD VAPOR LEAK WARN CLEAR 5-06-16 7:17PM T 1 TANK UNLEADED INVALID FUEL LEVEL CLEAR 5-05-16 3:25AM T 1 TANK UNLEADED INVALID FUEL LEVEL ALARM 5-04-16 10:49PM T 1 TANK UNLEADED INVALID FUEL LEVEL CLEAR 5-04-16 1:11PM T 2 TANK PREMIUM INVALID FUEL LEVEL CLEAR 5-04-16 1:05PM T 2 TANK PREMIUM INVALID FUEL LEVEL ALARM 5-04-16 11:35AM T 1 TANK UNLEADED INVALID FUEL LEVEL ALARM 5-04-16 4:37AM OTHER ISD VAPOR LEAK WARN ALARM 5-03-16 10:01AM T 2 TANK PREMIUM INVALID FUEL LEVEL CLEAR 4-27-16 3:46PM T 1 TANK UNLEADED INVALID FUEL LEVEL CLEAR 4-27-16 3:44PM T 1 TANK UNLEADED INVALID FUEL LEVEL ALARM 4-27-16 1:44PM T 2 TANK PREMIUM INVALID FUEL LEVEL ALARM 4-27-16 12:28PM T 1 TANK UNLEADED INVALID FUEL LEVEL CLEAR 4-18-16 7:17PM T 1 TANK UNLEADED INVALID FUEL LEVEL ALARM 4-18-16 3:53PM I20600 JUL 28, 2016 8:47 AM FASTRIP 3362 6401 S H ST BAKERSFIELD,CA93304 661-831-4709 TANK ALARM HISTORY TANK 1 UNLEADED OVERFILL ALARM JUN 18, 2016 3:30 PM MAY 1, 2016 12:16 PM APR 22, 2016 2:45 AM LOW PRODUCT ALARM FEB 13, 2015 4:15 PM FEB 2, 2015 5:21 PM JAN 26, 2015 12:59 PM HIGH PRODUCT ALARM JUL 22, 2016 9:49 AM AUG 3, 2015 9:39 AM JUL 30, 2015 10:35 AM INVALID FUEL LEVEL JUL 13, 2016 6:37 AM JUN 28, 2016 7:29 AM JUN 4, 2016 5:34 AM PROBE OUT JUL 22, 2016 10:41 AM JUL 22, 2016 9:48 AM JUL 22, 2016 9:34 AM HIGH WATER WARNING AUG 3, 2015 10:56 AM AUG 3, 2015 9:51 AM DELIVERY NEEDED FEB 13, 2015 4:15 PM FEB 2, 2015 5:21 PM JAN 26, 2015 12:58 PM MAX PRODUCT ALARM JUL 30, 2015 10:35 AM FEB 27, 2015 9:42 PM JAN 28, 2015 7:43 PM TANK 2 PREMIUM OVERFILL ALARM JUL 22, 2016 9:47 AM JUL 22, 2016 9:46 AM JUL 7, 2016 11:59 PM HIGH PRODUCT ALARM JUL 22, 2016 9:48 AM JUL 22, 2016 9:46 AM MAR 11, 2016 1:38 AM INVALID FUEL LEVEL MAY 4, 2016 11:35 AM APR 27, 2016 12:28 PM FEB 29, 2016 1:33 PM PROBE OUT JUL 22, 2016 10:41 AM JUL 22, 2016 9:47 AM JUL 22, 2016 9:34 AM MAX PRODUCT ALARM JUL 30, 2015 10:40 AM TANK 3 DIESEL OVERFILL ALARM JUL 22, 2016 9:44 AM AUG 3, 2015 9:35 AM JUL 30, 2015 10:44 AM LOW PRODUCT ALARM JUN 4, 2016 9:40 PM AUG 3, 2015 9:36 AM AUG 3, 2015 9:32 AM INVALID FUEL LEVEL AUG 3, 2015 9:31 AM PROBE OUT JUL 22, 2016 10:42 AM JUL 22, 2016 9:33 AM AUG 3, 2015 9:36 AM DELIVERY NEEDED JUN 4, 2016 9:40 PM AUG 3, 2015 9:36 AM AUG 3, 2015 9:32 AM I38200 JUL 28, 2016 8:47 AM I30200 JUL 28, 2016 8:47 AM FASTRIP 3362 6401 S H ST BAKERSFIELD,CA93304 661-831-4709 LIQUID ALARM HISTORY REPORT SENSOR LOCATION 1 UNL STP JUL 22, 2016 9:52 AM SENSOR OUT ALARM JUL 22, 2016 9:28 AM FUEL ALARM JUL 15, 2016 9:11 PM FUEL ALARM 2 UNL FILL JUL 22, 2016 9:52 AM SENSOR OUT ALARM JUL 22, 2016 9:26 AM FUEL ALARM MAY 6, 2016 1:11 PM FUEL ALARM 3 UNL ANN JUL 22, 2016 9:52 AM SENSOR OUT ALARM JUL 22, 2016 9:23 AM LOW LIQUID ALARM AUG 3, 2015 9:48 AM SENSOR OUT ALARM 4 PNL STP JUL 22, 2016 9:52 AM SENSOR OUT ALARM JUL 22, 2016 9:29 AM FUEL ALARM AUG 3, 2015 9:48 AM SENSOR OUT ALARM 5 PNL FILL JUL 22, 2016 9:52 AM SENSOR OUT ALARM AUG 3, 2015 9:48 AM SENSOR OUT ALARM AUG 3, 2015 9:19 AM FUEL ALARM 6 PNL ANN JUL 28, 2016 1:36 AM HIGH LIQUID ALARM JUL 27, 2016 5:00 PM HIGH LIQUID ALARM JUL 22, 2016 9:52 AM SENSOR OUT ALARM 7 DSL STP JUL 22, 2016 9:52 AM SENSOR OUT ALARM JUL 22, 2016 9:29 AM FUEL ALARM JUL 11, 2016 3:10 AM FUEL ALARM 8 DSL FILL JUL 22, 2016 9:52 AM SENSOR OUT ALARM JUL 22, 2016 9:27 AM FUEL ALARM MAY 10, 2016 11:31 AM FUEL ALARM 9 DSL ANN JUL 22, 2016 9:52 AM SENSOR OUT ALARM JUL 22, 2016 9:25 AM LOW LIQUID ALARM JUL 9, 2016 5:49 AM HIGH LIQUID ALARM 10 DISP 1-2 JUL 22, 2016 9:52 AM SENSOR OUT ALARM JUL 22, 2016 9:30 AM FUEL ALARM AUG 3, 2015 9:48 AM SENSOR OUT ALARM 11 DISP 3-4 JUL 22, 2016 9:52 AM SENSOR OUT ALARM JUL 22, 2016 9:30 AM FUEL ALARM AUG 3, 2015 9:48 AM SENSOR OUT ALARM 12 DISP 5-6 JUL 22, 2016 9:52 AM SENSOR OUT ALARM JUL 22, 2016 9:32 AM FUEL ALARM AUG 3, 2015 9:48 AM SENSOR OUT ALARM 13 DISP 7-8 JUL 22, 2016 9:52 AM SENSOR OUT ALARM JUL 22, 2016 9:31 AM FUEL ALARM AUG 3, 2015 9:48 AM SENSOR OUT ALARM I31600 JUL 28, 2016 8:47 AM FASTRIP 3362 6401 S H ST BAKERSFIELD,CA93304 661-831-4709 SMART SENSOR ALARM HISTORY REPORT SENSOR LOCATION 1 PS 1-2 APR 7, 2016 11:07 AM COMMUNICATION ALARM 2 FM 1-2 3 FM 3-4 4 F-M 5-6 5 FM 7-8 I40200 JUL 28, 2016 8:47 AM I40300 JUL 28, 2016 8:47 AM I34200 JUL 28, 2016 8:47 AM I34700 JUL 28, 2016 8:47 AM IV0100 JUL 28, 2016 8:47 AM FASTRIP 3362 6401 S H ST BAKERSFIELD,CA93304 661-831-4709 ISD ALARM STATUS REPORT EVR TYPE: VACUUM ASSIST ISD TYPE: 01.01 VAPOR PROCESSOR TYPE: NO VAPOR PROCESSOR OVERALL STATUS :PASS EVR VAPOR COLLECTION :PASS EVR VAPOR CONTAINMENT :PASS ISD MONITOR UP-TIME :100% STAGE I TRANSFERS: 0 of 0 NOTEST EVR/ISD PASS TIME :100% WARNING ALARMS DATE TIME DESCRIPTION READING VALUE 16-06-07 10:01:50 VAPOR CONTAINMENT LEAKAGE CFH@2 INCHES WC 9.95 16-05-06 10:01:30 VAPOR CONTAINMENT LEAKAGE CFH@2 INCHES WC 17.18 16-05-05 10:01:16 VAPOR CONTAINMENT LEAKAGE CFH@2 INCHES WC 17.46 16-05-04 10:01:09 VAPOR CONTAINMENT LEAKAGE CFH@2 INCHES WC 18.46 16-05-03 10:01:09 VAPOR CONTAINMENT LEAKAGE CFH@2 INCHES WC 17.93 16-03-23 10:01:48 A/L RATIO GROSS BLOCKAGE FP 3 BLEND3 BLKD 16-02-14 10:01:12 CONTAINMENT GROSS OVER PRESSURE WEEKLY 95% 3.88 16-02-01 10:01:48 CONTAINMENT GROSS OVER PRESSURE WEEKLY 95% 5.00 16-01-26 10:02:00 A/L RATIO GROSS BLOCKAGE FP 1 BLEND3 BLKD 16-01-21 10:01:56 CONTAINMENT GROSS OVER PRESSURE WEEKLY 95% 5.00 FAILURE ALARMS DATE TIME DESCRIPTION READING VALUE 14-09-14 17:30:16 A/L RATIO GROSS BLOCKAGE FP 6 BLEND3 BLKD 14-09-01 10:02:03 A/L RATIO GROSS BLOCKAGE FP 5 BLEND3 BLKD 12-06-25 10:02:07 A/L RATIO GROSS BLOCKAGE FP 8 BLEND3 BLKD 12-01-12 10:02:22 A/L RATIO GROSS BLOCKAGE FP 2 BLEND3 BLKD 12-01-12 10:02:22 A/L RATIO GROSS BLOCKAGE FP 1 BLEND3 BLKD 11-09-12 10:01:31 CONTAINMENT GROSS OVER PRESSURE WEEKLY 95% 3.42 11-03-21 10:02:14 VAPOR CONTAINMENT LEAKAGE CFH@2 INCHES WC 9.98 11-03-20 10:01:41 VAPOR CONTAINMENT LEAKAGE CFH@2 INCHES WC 10.16 11-03-09 10:02:12 A/L RATIO GROSS BLOCKAGE FP 8 BLEND3 BLKD 11-03-09 10:02:12 A/L RATIO GROSS BLOCKAGE FP 7 BLEND3 BLKD SHUTDOWN & MISCELLANEOUS EVENTS DATE TIME DESCRIPTION ACTION/NAME 16-07-22 10:01:11 READINESS ISD:PP EVR:PP ISD & EVR READY 16-07-22 09:51:50 READINESS ISD:PP EVR:NN EVR READINESS PENDING 16-07-22 09:51:50 ISD STARTUP 16-07-22 09:51:37 ISD SHUTDOWN 16-07-03 10:01:09 READINESS ISD:PP EVR:PP ISD & EVR READY 16-07-03 09:18:59 READINESS ISD:PP EVR:NN EVR READINESS PENDING 16-07-03 09:18:59 ISD STARTUP 16-07-03 09:18:53 ISD SHUTDOWN 16-07-03 01:26:05 READINESS ISD:PP EVR:NN EVR READINESS PENDING 16-07-03 01:26:05 ISD STARTUP Alarm history after testing I10200 JUL 28, 2016 10:50 AM FASTRIP 3362 6401 S H ST BAKERSFIELD,CA93304 661-831-4709 SYSTEM CONFIGURATION SLOT BOARD TYPE POWER ON RESET CURRENT 1 8SMARTSENSOR BD 39555 39494 2 4 PROBE / G.T. 164633 164448 3 INTERSTITIAL BD 202423 202287 4 INTERSTITIAL BD 202561 202402 5 UNUSED 9906997 9888730 6 UNUSED 9897468 9885851 7 UNUSED 9890938 9890014 8 UNUSED 9896475 9878877 9 UNUSED 9892269 9882002 10 RELAY BOARD 14977 14977 11 UNUSED 9897276 9888623 12 UNUSED 9891872 9885124 13 UNUSED 9892489 9881360 14 UNUSED 9889997 9882467 15 UNUSED 9889004 9877973 16 UNUSED 9892887 9878748 COMM 1 RS232 SERIAL BD 14999 14999 COMM 2 RS232 SERIAL BD 15110 15088 COMM 3 ELEC DISP INT. 101667 101630 COMM 4 UNUSED 9900938 9886165 COMM 5 UNUSED 9895026 9881670 COMM 6 UNUSED 9888364 9879611 I90200 JUL 28, 2016 10:50 AM SOFTWARE REVISION LEVEL VERSION 327.04 SOFTWARE# 346327-100-E CREATED - 07.02.06.10.28 S-MODULE# 330160-004-a SYSTEM FEATURES: PERIODIC IN-TANK TESTS ANNUAL IN-TANK TESTS ISD PMC I11100 JUL 28, 2016 10:50 AM FASTRIP 3362 6401 S H ST BAKERSFIELD,CA93304 661-831-4709 PRIORITY ALARM HISTORY ID CATEGORY DESCRIPTION ALARM TYPE STATE DATE TIME T 1 TANK UNLEADED PROBE OUT CLEAR 7-28-16 10:40AM T 1 TANK UNLEADED PROBE OUT ALARM 7-28-16 10:39AM L 5 PIPE PNL FILL FUEL ALARM CLEAR 7-28-16 10:19AM L 5 PIPE PNL FILL FUEL ALARM ALARM 7-28-16 10:15AM L 5 PIPE PNL FILL SENSOR OUT ALARM CLEAR 7-28-16 10:14AM L 5 PIPE PNL FILL SENSOR OUT ALARM ALARM 7-28-16 10:10AM L 5 PIPE PNL FILL FUEL ALARM CLEAR 7-28-16 10:10AM L 5 PIPE PNL FILL FUEL ALARM ALARM 7-28-16 10:10AM L 5 PIPE PNL FILL FUEL ALARM CLEAR 7-28-16 10:00AM L 5 PIPE PNL FILL FUEL ALARM ALARM 7-28-16 10:00AM L 8 PIPE DSL FILL FUEL ALARM CLEAR 7-28-16 9:55AM L 8 PIPE DSL FILL FUEL ALARM ALARM 7-28-16 9:54AM T 1 TANK UNLEADED MAX PRODUCT ALARM CLEAR 7-28-16 9:54AM L 2 PIPE UNL FILL FUEL ALARM CLEAR 7-28-16 9:53AM L 2 PIPE UNL FILL FUEL ALARM ALARM 7-28-16 9:53AM T 1 TANK UNLEADED OVERFILL ALARM CLEAR 7-28-16 9:38AM T 1 TANK UNLEADED MAX PRODUCT ALARM ALARM 7-28-16 9:37AM T 1 TANK UNLEADED OVERFILL ALARM ALARM 7-28-16 9:37AM T 3 TANK DIESEL PROBE OUT CLEAR 7-28-16 9:35AM T 1 TANK UNLEADED OVERFILL ALARM CLEAR 7-28-16 9:34AM T 1 TANK UNLEADED OVERFILL ALARM ALARM 7-28-16 9:34AM T 1 TANK UNLEADED MAX PRODUCT ALARM CLEAR 7-28-16 9:34AM T 1 TANK UNLEADED MAX PRODUCT ALARM ALARM 7-28-16 9:32AM T 2 TANK PREMIUM PROBE OUT CLEAR 7-28-16 9:30AM T 2 TANK PREMIUM OVERFILL ALARM CLEAR 7-28-16 9:30AM T 2 TANK PREMIUM PROBE OUT ALARM 7-28-16 9:30AM T 2 TANK PREMIUM MAX PRODUCT ALARM CLEAR 7-28-16 9:30AM T 2 TANK PREMIUM MAX PRODUCT ALARM ALARM 7-28-16 9:29AM T 2 TANK PREMIUM OVERFILL ALARM ALARM 7-28-16 9:28AM T 2 TANK PREMIUM PROBE OUT CLEAR 7-28-16 9:27AM T 3 TANK DIESEL PROBE OUT ALARM 7-28-16 9:26AM T 2 TANK PREMIUM PROBE OUT ALARM 7-28-16 9:26AM T 2 TANK PREMIUM OVERFILL ALARM CLEAR 7-28-16 9:25AM T 3 TANK DIESEL OVERFILL ALARM CLEAR 7-28-16 9:24AM T 2 TANK PREMIUM OVERFILL ALARM ALARM 7-28-16 9:24AM T 3 TANK DIESEL MAX PRODUCT ALARM CLEAR 7-28-16 9:23AM T 3 TANK DIESEL MAX PRODUCT ALARM ALARM 7-28-16 9:22AM T 3 TANK DIESEL OVERFILL ALARM ALARM 7-28-16 9:22AM L 3 ANNULAR UNL ANN SENSOR OUT ALARM CLEAR 7-28-16 9:18AM L13 DISP PAN DISP 7-8 SENSOR OUT ALARM CLEAR 7-28-16 9:18AM L12 DISP PAN DISP 5-6 SENSOR OUT ALARM CLEAR 7-28-16 9:18AM L11 DISP PAN DISP 3-4 SENSOR OUT ALARM CLEAR 7-28-16 9:18AM L10 DISP PAN DISP 1-2 SENSOR OUT ALARM CLEAR 7-28-16 9:18AM L 5 PIPE PNL FILL SENSOR OUT ALARM CLEAR 7-28-16 9:18AM L 2 PIPE UNL FILL SENSOR OUT ALARM CLEAR 7-28-16 9:18AM L 9 ANNULAR DSL ANN SENSOR OUT ALARM CLEAR 7-28-16 9:18AM L 1 STP SUMP UNL STP SENSOR OUT ALARM CLEAR 7-28-16 9:18AM L 5 PIPE PNL FILL SENSOR OUT ALARM ALARM 7-28-16 9:18AM L 3 ANNULAR UNL ANN SENSOR OUT ALARM ALARM 7-28-16 9:18AM L10 DISP PAN DISP 1-2 SENSOR OUT ALARM ALARM 7-28-16 9:18AM I11200 JUL 28, 2016 10:50 AM FASTRIP 3362 6401 S H ST BAKERSFIELD,CA93304 661-831-4709 NON-PRIORITY ALARM HISTORY ID CATEGORY DESCRIPTION ALARM TYPE STATE DATE TIME L 5 PIPE PNL FILL SETUP DATA WARNING CLEAR 7-28-16 10:01AM L 5 PIPE PNL FILL SETUP DATA WARNING ALARM 7-28-16 10:01AM T 1 TANK UNLEADED HIGH PRODUCT ALARM CLEAR 7-28-16 9:54AM T 1 TANK UNLEADED HIGH PRODUCT ALARM ALARM 7-28-16 9:37AM T 1 TANK UNLEADED HIGH PRODUCT ALARM CLEAR 7-28-16 9:34AM T 1 TANK UNLEADED HIGH PRODUCT ALARM ALARM 7-28-16 9:32AM T 2 TANK PREMIUM LOW TEMP WARNING CLEAR 7-28-16 9:31AM T 2 TANK PREMIUM LOW TEMP WARNING ALARM 7-28-16 9:30AM T 2 TANK PREMIUM HIGH PRODUCT ALARM CLEAR 7-28-16 9:30AM T 2 TANK PREMIUM HIGH PRODUCT ALARM ALARM 7-28-16 9:28AM T 2 TANK PREMIUM HIGH PRODUCT ALARM CLEAR 7-28-16 9:26AM T 2 TANK PREMIUM HIGH PRODUCT ALARM ALARM 7-28-16 9:23AM T 3 TANK DIESEL HIGH PRODUCT ALARM CLEAR 7-28-16 9:23AM T 3 TANK DIESEL HIGH PRODUCT ALARM ALARM 7-28-16 9:22AM T 2 TANK PREMIUM INVALID FUEL LEVEL CLEAR 7-28-16 9:00AM T 1 TANK UNLEADED INVALID FUEL LEVEL CLEAR 7-28-16 9:00AM T 2 TANK PREMIUM INVALID FUEL LEVEL ALARM 7-28-16 8:59AM T 1 TANK UNLEADED INVALID FUEL LEVEL ALARM 7-28-16 8:59AM T 1 TANK UNLEADED HIGH PRODUCT ALARM CLEAR 7-22-16 9:49AM T 1 TANK UNLEADED HIGH PRODUCT ALARM ALARM 7-22-16 9:49AM T 2 TANK PREMIUM HIGH PRODUCT ALARM CLEAR 7-22-16 9:48AM T 2 TANK PREMIUM HIGH PRODUCT ALARM ALARM 7-22-16 9:48AM T 2 TANK PREMIUM HIGH PRODUCT ALARM CLEAR 7-22-16 9:47AM T 2 TANK PREMIUM HIGH PRODUCT ALARM ALARM 7-22-16 9:46AM T 1 TANK UNLEADED INVALID FUEL LEVEL CLEAR 7-13-16 9:57AM T 1 TANK UNLEADED INVALID FUEL LEVEL ALARM 7-13-16 6:37AM SYSTEM PRINTER ERROR CLEAR 6-29-16 6:02AM SYSTEM PAPER OUT CLEAR 6-29-16 6:02AM SYSTEM PRINTER ERROR ALARM 6-29-16 6:00AM SYSTEM PAPER OUT ALARM 6-29-16 6:00AM T 1 TANK UNLEADED INVALID FUEL LEVEL CLEAR 6-28-16 7:31AM T 1 TANK UNLEADED INVALID FUEL LEVEL ALARM 6-28-16 7:29AM OTHER ISD VAPOR LEAK WARN CLEAR 6-07-16 3:38PM OTHER ISD VAPOR LEAK WARN ALARM 6-07-16 10:01AM T 3 TANK DIESEL DELIVERY NEEDED CLEAR 6-05-16 12:37AM T 3 TANK DIESEL DELIVERY NEEDED ALARM 6-04-16 9:40PM T 1 TANK UNLEADED INVALID FUEL LEVEL CLEAR 6-04-16 8:50AM T 1 TANK UNLEADED INVALID FUEL LEVEL ALARM 6-04-16 5:34AM SYSTEM PRINTER ERROR CLEAR 6-01-16 6:06AM SYSTEM PAPER OUT CLEAR 6-01-16 6:06AM SYSTEM PRINTER ERROR ALARM 6-01-16 6:06AM SYSTEM PAPER OUT ALARM 6-01-16 6:06AM SYSTEM PRINTER ERROR CLEAR 6-01-16 6:06AM SYSTEM PAPER OUT CLEAR 6-01-16 6:06AM SYSTEM PRINTER ERROR ALARM 6-01-16 6:00AM SYSTEM PAPER OUT ALARM 6-01-16 6:00AM T 1 TANK UNLEADED INVALID FUEL LEVEL CLEAR 5-22-16 5:08PM T 1 TANK UNLEADED INVALID FUEL LEVEL ALARM 5-22-16 3:54PM T 1 TANK UNLEADED INVALID FUEL LEVEL CLEAR 5-15-16 3:05AM T 1 TANK UNLEADED INVALID FUEL LEVEL ALARM 5-14-16 11:18PM I20600 JUL 28, 2016 10:50 AM FASTRIP 3362 6401 S H ST BAKERSFIELD,CA93304 661-831-4709 TANK ALARM HISTORY TANK 1 UNLEADED OVERFILL ALARM JUL 28, 2016 9:37 AM JUL 28, 2016 9:34 AM JUN 18, 2016 3:30 PM LOW PRODUCT ALARM FEB 13, 2015 4:15 PM FEB 2, 2015 5:21 PM JAN 26, 2015 12:59 PM HIGH PRODUCT ALARM JUL 28, 2016 9:37 AM JUL 28, 2016 9:32 AM JUL 22, 2016 9:49 AM INVALID FUEL LEVEL JUL 28, 2016 8:59 AM JUL 13, 2016 6:37 AM JUN 28, 2016 7:29 AM PROBE OUT JUL 28, 2016 10:39 AM JUL 28, 2016 8:58 AM JUL 22, 2016 10:41 AM HIGH WATER WARNING AUG 3, 2015 10:56 AM AUG 3, 2015 9:51 AM DELIVERY NEEDED FEB 13, 2015 4:15 PM FEB 2, 2015 5:21 PM JAN 26, 2015 12:58 PM MAX PRODUCT ALARM JUL 28, 2016 9:37 AM JUL 28, 2016 9:32 AM JUL 30, 2015 10:35 AM TANK 2 PREMIUM OVERFILL ALARM JUL 28, 2016 9:28 AM JUL 28, 2016 9:24 AM JUL 22, 2016 9:47 AM HIGH PRODUCT ALARM JUL 28, 2016 9:28 AM JUL 28, 2016 9:23 AM JUL 22, 2016 9:48 AM INVALID FUEL LEVEL JUL 28, 2016 8:59 AM MAY 4, 2016 11:35 AM APR 27, 2016 12:28 PM PROBE OUT JUL 28, 2016 9:30 AM JUL 28, 2016 9:26 AM JUL 28, 2016 8:59 AM MAX PRODUCT ALARM JUL 28, 2016 9:29 AM JUL 30, 2015 10:40 AM LOW TEMP WARNING JUL 28, 2016 9:30 AM TANK 3 DIESEL OVERFILL ALARM JUL 28, 2016 9:22 AM JUL 22, 2016 9:44 AM AUG 3, 2015 9:35 AM LOW PRODUCT ALARM JUN 4, 2016 9:40 PM AUG 3, 2015 9:36 AM AUG 3, 2015 9:32 AM HIGH PRODUCT ALARM JUL 28, 2016 9:22 AM INVALID FUEL LEVEL AUG 3, 2015 9:31 AM PROBE OUT JUL 28, 2016 9:26 AM JUL 28, 2016 9:00 AM JUL 22, 2016 10:42 AM DELIVERY NEEDED JUN 4, 2016 9:40 PM AUG 3, 2015 9:36 AM AUG 3, 2015 9:32 AM MAX PRODUCT ALARM JUL 28, 2016 9:22 AM I38200 JUL 28, 2016 10:50 AM I30200 JUL 28, 2016 10:50 AM FASTRIP 3362 6401 S H ST BAKERSFIELD,CA93304 661-831-4709 LIQUID ALARM HISTORY REPORT SENSOR LOCATION 1 UNL STP JUL 28, 2016 9:18 AM SENSOR OUT ALARM JUL 28, 2016 9:11 AM FUEL ALARM JUL 22, 2016 9:52 AM SENSOR OUT ALARM 2 UNL FILL JUL 28, 2016 9:53 AM FUEL ALARM JUL 28, 2016 9:18 AM SENSOR OUT ALARM JUL 22, 2016 9:52 AM SENSOR OUT ALARM 3 UNL ANN JUL 28, 2016 9:18 AM SENSOR OUT ALARM JUL 28, 2016 9:15 AM LOW LIQUID ALARM JUL 28, 2016 9:15 AM HIGH LIQUID ALARM 4 PNL STP JUL 28, 2016 9:10 AM FUEL ALARM JUL 22, 2016 9:52 AM SENSOR OUT ALARM JUL 22, 2016 9:29 AM FUEL ALARM 5 PNL FILL JUL 28, 2016 10:15 AM FUEL ALARM JUL 28, 2016 10:10 AM SENSOR OUT ALARM JUL 28, 2016 10:10 AM FUEL ALARM 6 PNL ANN JUL 28, 2016 9:15 AM HIGH LIQUID ALARM JUL 28, 2016 9:15 AM LOW LIQUID ALARM JUL 28, 2016 1:36 AM HIGH LIQUID ALARM 7 DSL STP JUL 28, 2016 9:10 AM FUEL ALARM JUL 22, 2016 9:52 AM SENSOR OUT ALARM JUL 22, 2016 9:29 AM FUEL ALARM 8 DSL FILL JUL 28, 2016 9:54 AM FUEL ALARM JUL 22, 2016 9:52 AM SENSOR OUT ALARM JUL 22, 2016 9:27 AM FUEL ALARM 9 DSL ANN JUL 28, 2016 9:18 AM SENSOR OUT ALARM JUL 28, 2016 9:17 AM LOW LIQUID ALARM JUL 28, 2016 9:17 AM HIGH LIQUID ALARM 10 DISP 1-2 JUL 28, 2016 9:18 AM SENSOR OUT ALARM JUL 28, 2016 9:11 AM FUEL ALARM JUL 22, 2016 9:52 AM SENSOR OUT ALARM 11 DISP 3-4 JUL 28, 2016 9:18 AM SENSOR OUT ALARM JUL 28, 2016 9:11 AM FUEL ALARM JUL 22, 2016 9:52 AM SENSOR OUT ALARM 12 DISP 5-6 JUL 28, 2016 9:18 AM SENSOR OUT ALARM JUL 28, 2016 9:12 AM FUEL ALARM JUL 22, 2016 9:52 AM SENSOR OUT ALARM 13 DISP 7-8 JUL 28, 2016 9:18 AM SENSOR OUT ALARM JUL 28, 2016 9:12 AM FUEL ALARM JUL 22, 2016 9:52 AM SENSOR OUT ALARM I31600 JUL 28, 2016 10:50 AM FASTRIP 3362 6401 S H ST BAKERSFIELD,CA93304 661-831-4709 SMART SENSOR ALARM HISTORY REPORT SENSOR LOCATION 1 PS 1-2 APR 7, 2016 11:07 AM COMMUNICATION ALARM 2 FM 1-2 3 FM 3-4 4 F-M 5-6 5 FM 7-8 I40200 JUL 28, 2016 10:50 AM I40300 JUL 28, 2016 10:50 AM I34200 JUL 28, 2016 10:50 AM I34700 JUL 28, 2016 10:50 AM IV0100 JUL 28, 2016 10:50 AM FASTRIP 3362 6401 S H ST BAKERSFIELD,CA93304 661-831-4709 ISD ALARM STATUS REPORT EVR TYPE: VACUUM ASSIST ISD TYPE: 01.01 VAPOR PROCESSOR TYPE: NO VAPOR PROCESSOR OVERALL STATUS :PASS EVR VAPOR COLLECTION :PASS EVR VAPOR CONTAINMENT :PASS ISD MONITOR UP-TIME : 99% STAGE I TRANSFERS: 7 of 7 PASS EVR/ISD PASS TIME :100% WARNING ALARMS DATE TIME DESCRIPTION READING VALUE 16-06-07 10:01:50 VAPOR CONTAINMENT LEAKAGE CFH@2 INCHES WC 9.95 16-05-06 10:01:30 VAPOR CONTAINMENT LEAKAGE CFH@2 INCHES WC 17.18 16-05-05 10:01:16 VAPOR CONTAINMENT LEAKAGE CFH@2 INCHES WC 17.46 16-05-04 10:01:09 VAPOR CONTAINMENT LEAKAGE CFH@2 INCHES WC 18.46 16-05-03 10:01:09 VAPOR CONTAINMENT LEAKAGE CFH@2 INCHES WC 17.93 16-03-23 10:01:48 A/L RATIO GROSS BLOCKAGE FP 3 BLEND3 BLKD 16-02-14 10:01:12 CONTAINMENT GROSS OVER PRESSURE WEEKLY 95% 3.88 16-02-01 10:01:48 CONTAINMENT GROSS OVER PRESSURE WEEKLY 95% 5.00 16-01-26 10:02:00 A/L RATIO GROSS BLOCKAGE FP 1 BLEND3 BLKD 16-01-21 10:01:56 CONTAINMENT GROSS OVER PRESSURE WEEKLY 95% 5.00 FAILURE ALARMS DATE TIME DESCRIPTION READING VALUE 14-09-14 17:30:16 A/L RATIO GROSS BLOCKAGE FP 6 BLEND3 BLKD 14-09-01 10:02:03 A/L RATIO GROSS BLOCKAGE FP 5 BLEND3 BLKD 12-06-25 10:02:07 A/L RATIO GROSS BLOCKAGE FP 8 BLEND3 BLKD 12-01-12 10:02:22 A/L RATIO GROSS BLOCKAGE FP 2 BLEND3 BLKD 12-01-12 10:02:22 A/L RATIO GROSS BLOCKAGE FP 1 BLEND3 BLKD 11-09-12 10:01:31 CONTAINMENT GROSS OVER PRESSURE WEEKLY 95% 3.42 11-03-21 10:02:14 VAPOR CONTAINMENT LEAKAGE CFH@2 INCHES WC 9.98 11-03-20 10:01:41 VAPOR CONTAINMENT LEAKAGE CFH@2 INCHES WC 10.16 11-03-09 10:02:12 A/L RATIO GROSS BLOCKAGE FP 8 BLEND3 BLKD 11-03-09 10:02:12 A/L RATIO GROSS BLOCKAGE FP 7 BLEND3 BLKD SHUTDOWN & MISCELLANEOUS EVENTS DATE TIME DESCRIPTION ACTION/NAME 16-07-28 10:01:09 READINESS ISD:PP EVR:PP ISD & EVR READY 16-07-28 09:18:50 READINESS ISD:PP EVR:NN EVR READINESS PENDING 16-07-28 09:18:50 ISD STARTUP 16-07-28 09:18:45 ISD SHUTDOWN 16-07-22 10:01:11 READINESS ISD:PP EVR:PP ISD & EVR READY 16-07-22 09:51:50 READINESS ISD:PP EVR:NN EVR READINESS PENDING 16-07-22 09:51:50 ISD STARTUP 16-07-22 09:51:37 ISD SHUTDOWN 16-07-03 10:01:09 READINESS ISD:PP EVR:PP ISD & EVR READY 16-07-03 09:18:59 READINESS ISD:PP EVR:NN EVR READINESS PENDING SWRCB, January 2006 Spill Bucket Testing Report Form This form is intended for use by contractors performing annual testing of UST spill containment structures. The completed form and printouts from tests (if applicable), should be provided to the facility owner/operator forsubmittal to the local regulatory agency. 1.FACILITY INFORMATION Facility Name:Date of Testing: Facility Address: Facility Contact:Phone: Date Local Agency Was Notified of Testing : Name of Local Agency Inspector (if present during testing): 2.TESTING CONTRACTOR INFORMATION Company Name:Confidence UST Services, Inc. Technician Conducting Test: Credentials1:CSLB Contractor ICC Service Tech. SWRCB Tank Tester Other (Specify) License Number(s):CSLB#804904 ICC# 3.SPILL BUCKET TESTING INFORMATION Test Method Used:Hydrostatic Vacuum Other Test Equipment Used:Lake TestEquipment Resolution:0.0625” Identify Spill Bucket (By Tank Number, Stored Product, etc.) 1234 Bucket Installation Type: Direct Bury Contained in Sump Direct Bury Contained in Sump Direct Bury Contained in Sump Direct Bury Contained in Sump Bucket Diameter: Bucket Depth: Wait time between applying vacuum/water and start of test: Test Start Time (TI): Initial Reading (RI): Test End Time (TF): Final Reading (RF): Test Duration (TF – TI): Change in Reading (RF -RI): Pass/Fail Threshold or Criteria: Test Result: Pass Fail Pass Fail Pass Fail Pass Fail Comments –(include information on repairs made prior to testing, and recommended follow-up for failed tests) CERTIFICATION OF TECHNICIAN RESPONSIBLE FOR CONDUCTING THIS TESTING I hereby certify that all the information contained in this report is true, accurate, and in full compliance with legal requirements. Technician’s Signature:________________________________________________ Date:_________ 1 State laws and regulations do not currently require testing to be performed by a qualified contractor. However, local requirements may be more stringent. #3362/Fastrip#633 07/28/2016 6401SouthHStreet Bakersfield,CA93304 OmeroGarcia(661)393-7000 06/14/2016 ShaneGardner BryanSelf 8022804-UT Regular 12.00" 12.50" 5min. 9:05 am 9.00" 10:05 am 9.00" 1hour Pass 0.0625" Super 12.00" 12.50" 5min. 9:05 am 9.50" 10:05 am 9.50" 1hour Pass 0.0625"0.0625" Diesel 12.00" 12.75" 5min. 9:05 am 9.25" 10:05 am 9.25" 1hour Pass 07/28/2016