HomeMy WebLinkAboutUST-DW REPORT 5/20/2015BAKERSFIELD FIRE DEPARTMENT
Prevention Services Division
Underground Storage Tank Pro ram 2101 H Street
DW Inspection Report tAAM')
Bakersfield, CA 93301
Permission to Inspect: Phone: 661-326-3979
Fax: 661-852-2171
Business Name: MINIT STOP-15-021-003150
Date:05/20/2015
Address Name: 2900 UNION AVE-JUNGLE COLOR INTERNATIONAL
Inspector Name: Shane Gardner #8248557
Inspection Type: Routine
Report: Final
NVO = No Violation Observed OUT = Out of Compliance NA = Not Applicable UD = Undetermined
COS = Corrected On Site RPT = Repeat Violation
Violation
Program Requirement
0
0 =
SOC
Comments
No
a
0
0.
z
0
z
M
(.)
File Review
Facility Tank Information
2030021
Facility has a valid Permit
Tank 1-15000-REG-DW
to Operate from the
Tank 2-5000-PRM-DW
CUPA - 23 CCR 16 2712(1);
El
El
0
Ej
None
None
Tank 3-
HSC 6.7 25284
Tank 4-
2010010
UST Operating Permit
Application for Facility
information and Tank
information
F]
F]
None
submitted/maintained - 23
CCR 16 2711; HSC 6.7
25286(a)
2010001
Current BOE number
submitted to the CUPA
F-1
❑
❑
❑
None
and/or CERS - HSC 6.7
25286(c)
2030011
UST compliance
current certs in cers are expired
statement and/or
for tech conducting the testing
Designated Operator
El
❑
❑
❑
None
current certification
submitted - 23 CCR 16
2715(a), 2715(b)
2030046
A complete and accurate
response plan has been
submitted, approved and
❑
❑
-0
F-1
�
None
maintained - 23 CCR 16
2632, 2634(e), 2641(h),
2712 /)
2030041
A complete and accurate
plot plan has been
submitted, approved and
Z
❑
❑
❑
❑
F-1
None
maintained - 23 CCR 16
2632(dj(1)(C), 2711
2010006
Owner/Operator has not
made false statements or
representation on any
❑
❑
❑
❑
❑
None
required document - HSC
6.725299
2010003
Owner/Operator has a
DO and/or informed the
CUPA of any change (s)
❑
❑
❑
❑
None
within 30 days - 23 CCR
16 2715(a)
Violation
Program Requirement
0 00
0
SOC
Comments
No
0
>
1—
M
<
a
0
0.
C a
12 =
CD"a
z
0
z
>
Testing
2030002
Owner/Operator has
tested and certified leak
91
❑
❑
❑
❑
❑
None
detection equipment
annually - 23 CCR 16 2638
2030048
Secondary containment
—
testing conducted every
36 months in accordance
❑
❑
❑
❑
❑
None
with requirements - 23
CCR 16 2637
2030055
Spill buckets have been
tested annually as
None
required - HSC 6.7 25284.2
2010009
Secondary containment
test results submitted to
the CUPA within 30 days
_PU
❑
❑
❑
None
after the test - 23 CCR 16
2637(e)
2030064
CUPA was poperly
notified within the
prescribed number of
None
hours prior to testing - 23
CCR 16 2637(1), 2638(e),
2643(8), 2644.1(a)(4)
Install/Repair
2060009
Permits obtained to
install, replace, repair, or
❑
❑
❑
❑
❑
None
modify part of the UST
system - 23 CCR 16 2712
UST System Observation
General Monitoring
2030003
Leak detection system
maintains continuous
RD
monitoring that activates
M
❑
❑
❑
None
[:1
an audible and visual
Yes
alarm - 23 CCR 16 2632,
2634, 2636, 2666
2030016
The annular space of the
tank, piping and sumps
RD
are continuously
monitored and activates
❑
F1
❑
None
❑
the alarm - 23 CCR 16
Yes
2631(8), 2632(c)(2)(A)&(B),
2633(c), 2636(o
2030017
Product piping outside the
UDC is fail-safe and shuts
down the pump or
None
restricts flow - 23 CCR 16
2636(1) (5)
2030018
Turbine sump monitor
RD
activates an audible and
visual alarm or stops the
None
❑
flow of at the dispenser -
Yes
23 CCR 16 26360(1)
Underground Storage Tank Program - DW Inspection Report v 2.0
Violation
Program Requirement
0 0
SOC
Comments
No
O
a
N
0
(L
�,c
Z
0
z
>
2030019
Monitoring system in the
UDCs activates an
audible and visual alarm
93
❑
❑
❑
❑
❑
None
or stops the flow at the
UDC -23 CCR 16
2030043
2636( 0(1)
Leak detection equipment
RD
L T
properly programmed or
properly operated - 23
❑
❑
❑
1:1
❑
None
CCR 16 2632, 2634, 2636,
Yes
2666
2060005
System constructed with
a monitoring system
capable of detecting entry
❑
❑
None
into secondary
containment - HSC 6.7
25291(b)
2060014
Correct leak detection
equipment installed for
RD
the type of system
❑
❑
❑
❑
❑
None
❑
present - 23 CCR 16 2638;
Yes
HSC 6.7 25290.1, 25290.2,
2060015
25291
Sensor located in the
-
RD
Ed
'""LLC6
proper position/location
F-1
❑
0
❑
❑
None
23 CCR 162630(d), 2641(a)
Yes
2030062
Facility is in compliance
RD
with not tampering with or
disabling leak detection
❑
❑
❑
❑
❑
None
❑
devices or alarms - HSC
Yes
6.7 25299(a)(9)
2060022
System constructed with
a monitoring system
capable of detecting entry
r-1
F-1
❑
❑
E:]
None
into secondary
containment - HSC 6.7
25290.2(d)
2030034
Tag/sticker on affixed
monitoring equipment
being certified, repaired,
F-1
0
El
El
n
❑
None
or replaced - 23 CCR 16
2638(o
VPH Monitoring VPH
2030065
Interstitial monitoring of
RD
the annular spaces of the
UST is properly
El
0
❑
❑
❑
None
❑
maintained - HSC 6.7
Yes
25290.1(e
2060023
System constructed with
a monitoring system
capable of detecting entry
into secondary
❑
E-1
❑
❑
None
containment - HSC 6.7
25290.1(d)
Underground Storage Tank Program - DW Inspection Report v 2.0
ST
Violation
Program Requirement
4-
0
0
SOC
Comments
No
0
>
a
a
0
0.
00
I
Z
0
Z
U
)>
In
Line Leak
Detector
2060012
Line leak detector
installed on pressurized
RD
piping system - HSC 6.7
W1
❑
F-1
El
F-1
❑
None
❑
25290.1(h), 25290.2(8),
Yes
25291(1), 25292(e),
2636(1) (2)
2030026
Line leak detectors detect
a 3 gph leak and/or
RD
audible and visual alarm
21
❑
❑
❑
❑
❑
None
❑
function properly - 23
Yes
CCR 16 2636(0(6),
2666(c)
2030027
Turbine shuts down when
RD
a leak is detected or
when line leak detector is
❑
❑
0
❑
❑
❑
None
❑
disconnected - 23 CCR 16
Yes
2666
2030025
Pressurized piping able to
detect a 3.0 gph leak
RD
within an hour, and
FKJ
None
❑
restricts the flow or
Yes
alarms - 23 CCR 16
2636(0(2)
Secondary Containment
2060010
UST storing a hazardous
RD
substance has secondary
Z
None
❑
containment - HSC 6.7
Yes
25292
Underground Storage Tank Program - DW Inspection Report v 2.0
Violation
Program Requirement
4-
0 0
4)
SOC
Comments
No
n
<
a
0
t:
"
Z
0
Z
=1
UL
>
2030008
UDC, sumps, and/or
other secondary
containment in good
None
condition and/or are free
of debris/liquid - HSC 6.7
25290.1, 25290.2, 25291
2030040
Secondarily contained
RD
piping maintained to allow
rvi
F,-I
E]
Ej
F1
None
❑
liquid to drain into sump m
Yes
23 CCR 16 2630(d), 2641(a)
2060006
Secondary containment
piping slopes back to the
IM
❑
❑
❑
❑
❑
None
collection sump - 23 CCR
16 263(c)
2030047
Secondary containment
maintained tight and has
been confirmed by testing
M
FIEj
❑
❑
❑
None
- 23 CCR 16 2662, HSC 6.7
25290.1(c)(2), 25290.2(c)(2),
25291(a), 25292(e)
2030060
Entry fittings in secondary
containment for UST
system maintained
None
tight/sealed - 23 CCR 16
2630, 2635(d), 2636(c),
2666
2060020
Spill bucket is installed
RP
and has a functional drain
valve or other means to
None
❑
remove liquid - 23 CCR 16
Yes
2030054
2635(b), 2665
Spill bucket maintained in
RP
good condition and free of
M
r--j
F-1
❑
❑
None
[?I/
debris and/or liquid - 23
Yes
CCR 16 2635(b), 2715(c)(2)
2060019
Spill bucket to has a
minimum capacity of five
91
❑
On
❑
❑
None
gallons - 23 CCR 16
2635(b), 2665
Overfill
2030035
UST system is operated
RP
to prevent unauthorized
release, including spills
❑
❑
None
and overfills - HSC 6.7
Yes
25292.1 (a)
2030036
Overfill prevention system
RP
has not been overridden
and meets overfill
E)
None
❑
requirements - 23 CCR 16
Yes
2635(b)(2), 2665
Underground Storage Tank Program - DW Inspection Report v 2.0
Violation
Program Requirement
4-
0 (D.0
SOC
Comments
No
0
>
1�-
:3
a
0
(L
M 0
Z
0
z
M
On Site Records
Certifications
2030023
Required designated
operators or contractors
maintain a proper and
❑
❑
❑
❑
❑
None
current ICC certification -
23 CCR 16 2715
1
1
1
2030024
Service technician,
installer, and/ or
employee maintain a
❑
None
proper license - 23 CCR
162715
2030031
Employee or contractor
obtained and maintained
proper manufacturer
❑
❑
❑
None
certification - 23 CCR 16
2715
2010007
Submit/maintain current
Certificate of Financial
Responsibility/mechanism
of financial assurance -
❑
❑
❑
None
23 CCR 16 2711; 23 CCR
18 2808.1, 2809-2809.2;
HSC 6.7 25292.2; HSC
6.75 25299.30-25299.34
Designated Operator
2010004
Copies of DO inspections
for last 12 months and list
of trained employees
❑
❑
❑
❑
❑
None
maintained - 23 CCR 16
2715
2030013
Designated operator
properly conducted the
monthly inspection and
❑
❑
❑
❑
❑
None
the reports are complete -
23 CCR 16 2715
2030010
DO notified operator of
any condition observed
during the monthly
❑
None
inspection that may
require action - 23 CCR 16
2715(d)
2030012
DO employee training
L4s
performed, current for at
least one employee on
None
site, and a log kept - 23
CCR 16 2715(c)(6), 2715(1)
Underground Storage Tank Program - DW Inspection Report v 2.0
Violation
.Program Requirement
P
4-
0 0
SOC
Comments
No
0>
a
0
�_
a.
cc
0 0
Z
0
Z
:3
0
Logs
2030001
Leak detection alarm
NAWM
logs, maintenance and
RD
JP Ac—tr&%JS
records of appropriate
None
Ef
4Q`F "07 a-e-f PC-
follow-up actions
Yes
maintained - 23 CCR 16
2632, 2634, 2712(b)
Maintenance/Tests
2010008
Monitoring, maintenance,
repairs, linings, and
RD
upgrade records
None
[:1
maintained for the proper
Yes
time period - 23 CCR 16
2712(M
Documentation
2030033
Failure to maintain on site
an approved monitoring
❑
❑
❑
❑
❑
None
plan - 23 CCR 16 2632,
2634, 2711, 2712(i)
2030037
Written agreement
between the tank owner
and tank operator to
monitor the tank system
F-1
n
E:]
❑
F]
None
is maintained - 23 CCR 16
2620(b); HSC 6.7
25284(a)(3)
2030061
Suspected or actual
RD
unauthorized release
reported in appropriate
❑
❑
None
[:1
time frame - HSC 6.7
Yes
29294,29295
1 A
General Operating Requirements
Permit Condition/Approval
2030039
Compliance with all
operating permit
El
❑
❑
❑
❑
r-1
None
conditions - 23 CCR 16
2712, HSC 6.7 25299
2030059
UST system maintained
in accordance with
exclusion/exemption
❑
F1
R
❑
❑
None
status - HSC 6.7 25281.6,
25283.5
2030014
Owner/Operator received
approval and has
implemented a training
❑
❑
0
❑
❑
❑
None
program at an unstaffed
facility - 23 CCR 16
2715 2)
2030015
Facility exhibited that the
method used to monitor
the tank meets the
monitoring methods in
[4
❑
❑
❑
❑
❑
None
2643(f) - 23 CCR 16 2643
Underground Storage Tank Program - DW Inspection Report V /-.V
Violation
Program Requirement
m o
SOC
Comments
No
¢
o
co
a
L5
z
O
z
D
v
W
of
Red Tag
2030045
Red Tag information is
legible and has not been
❑
❑
❑
❑
❑
None
tampered with - 23 CCR
16 2717.1(8
2030044
Facility did not allow for
deposit of petroleum into
a UST that has a red tag
❑
❑
[21
❑
❑
❑
None
affixed to the fill - 23 CCR
16 2717.1(
Install /Repair
2060024
UST system is made of or
lined with materials that
are compatible with the
R
❑
❑
❑
❑
❑
None
substance stored - 23
CCR 16 2631.1
2060021
Striker plate installed and
positioned correctly - 23
❑
❑
❑
®
❑
❑
None
CCR 16 2631(c), 2662(d)
❑ There were no violations noted for this inspection.
Eflfhis report shall serve as a "NOTICE TO COMPLY" for Minor Violations, and a "NOTICE OF VIOLATION" for
Major violations. You are, hereby, ordered to correct the above noted violations within 30 days, or according to
correction summaries provided. Formal enforcement and /or penalty assessment may be initiated for any
violations noted, and for those not corrected in a timely manner. (NOTE: If this is a preliminary report, a final report
will follow.)
Inspectors Signature: Date: _�1 JO
Inspector: Enter # of Violations: RD: -3 RP:
Check one box for facility Significant Operational Status (SOC) to be reported to SWRCB and US EPA:
❑ SOC with both Release Detection and Release Detection (Facility has no Release Prevention and no Release
��Not tion Violations)
in SO C (Facility has both Release Prevention and Release Detection Violations)
❑SOC with Release Detection only (Facility has no Release Detection violations but one or more Release Prevention
violations)
❑ SOC with Release Prevention only (Facility has no Release Prevention violations but one or more Release Detection
violations)
Underground Storage Tank Program - DW Inspection Report v 2.0