Loading...
HomeMy WebLinkAboutUST-DW REPORT 7/29/2015Underground Storage Tank Program DW Inspection Report Permission to Inspect: BAKERSFIELD FIRE DEPARTMENT Prevention Services Division 2101 H Street Bakersfield, CA 93301 Phone: 661-326-3979 Fax- 661-852-2171 Business Name: Fastrip #7785 (15-021-003025) Date:7/29/15 Address Name: 3701 Ming Avenue Inspector Name: Kris Karns (8292402) Inspection Type: Routine Report: Final NVO = No Violation Observed OUT = Out of Compliance NA = Not Applicable UD = Undetermined COS = Corrected On Site RPT = Repeat Violation Violation Program Requirement 00 4) SOC Comments No 0 0. I'm co"a z 0 z M ' 0 W L 6 > File Review Facility Tank Information 2030021 Facility has a valid Permit Tank 1-12000-REG -DW to Operate from the Tank 2-12000-SUP -DW CUPA - 23 CCR 16 2712(i); n ❑ ❑ None Tank 3-12000-DIES -DW HSC 6.7 25284 1 2010010 UST Operating Permit Application for Facility information and Tank information F-1 ❑ ❑ ❑ ❑ None submitted/maintained - 23 CCR 16 2711; HSC 6.7 25286(a) 2010001 Current BOE number submitted to the CUPA None and/or CERS - HSC 6.7 25286(c) 2030011 UST compliance statement and/or Designated Operator ❑ ❑ F-1 ❑ None current certification submitted - 23 CCR 16 2715(a), 2715(b) 2030046 A complete and accurate response plan has been submitted, approved and None maintained - 23 CCR 16 2632, 2634(e), 2641(h), 2712(i) 2030041 A complete and accurate plot plan has been submitted, approved and ❑ ❑ ❑ ❑ ❑ None maintained - 23 CCR 16 2632(d)(1 (C), 2711(a)(8) 2010006 Owner/Operator has not made false statements or representation on any ❑ ❑ ❑ ❑ ❑ None required document - HSC 6.725299 2010003 Owner/Operator has a DO and/or informed the CUPA of any change (s) [--j ❑ None within 30 days - 23 CCR 16 2715(a) Violation Program Requirement 4- 0 0.0 SOC Comments No M C) 0 20 00 1 z 0 z M 0 05 0 Testing 2030002 Owner/Operator has tested and certified leak None detection equipment annually - 23 CCR 16 2638 2030048 Secondary containment testing conducted every 36 months in accordance None with requirements m 23 CCR 16 2637 2030055 Spill buckets have been tested annually as None required - HSC 6.7 25284.2 2010009 Secondary containment test results submitted to the CUPA within 30 days None after the test - 23 CCR 16 2637(e) 2030064 CU PA was poperly notified within the prescribed number of None hours prior to testing - 23 CCR 16 26370, 2638(e), 2643(8), 2644.1(a)(4) 1 1 Install/Repair 2060009 Permits obtained to install, replace, repair, or ❑ ❑ ❑ ❑ ❑ None modify part of the UST system - 23 CCR 16 2712 UST System Observation General Monitoring 2030003 Leak detection system maintains continuous RD monitoring that activates ❑ ❑ ❑ None ❑ an audible and visual Yes alarm m 23 CCR 16 2632, 2634, 2636, 2666 2030016 The annular space of the tank, piping and sumps RD are continuously monitored and activates ❑ ❑ ❑ ❑ None ❑ the alarm - 23 CCR 16 Yes 2631(g), 2632(c)(2)(A)&(8), 2633(c ),2636(o 2030017 Product piping outside the UDC is fail-safe and shuts down the pump or E ❑ ❑ ❑ ❑ ❑ None restricts flow - 23 CCR 16 2636(0(5) 2030018 Turbine sump monitor RD activates an audible and visual alarm or stops the ❑ ❑ ❑ ❑ F-1 None ❑ flow of at the dispenser - Yes 23 CCR 16 26360(1) 1 1 1 Underground Storage Tank Program - DW Inspection Report v 2.0 Violation Program Requirement m .0 SOC Comments No a 0) 0 0. 4) 0 "W 1- cc 0 z 0 z 2030019 Monitoring system in the UDCs activates an audible and visual alarm E El ❑ ❑ ❑ ❑ None or stops the flow at the UDC -23 CCR 16 2636 (1 2030043 Leak detection equipment Dispenser #15-16 liquid sensor properly programmed or RD was not programmed for positive properly operated - 23 None Z shut down on Diesel. Technician CCR 16 2632, 2634, 2636, Yes changed programming and sensor 2666 was re-tested and positive shut down was confirmed on Diesel. 2060005 System constructed with a monitoring system capable of detecting entry ❑ E-1 ❑ ❑ ❑ None into secondary containment - HSC 6.7 25291(b) 2060014 Correct leak detection equipment installed for RD the type of system E-1 ❑ ❑ ❑ ❑ None ❑ present - 23 CCR 16 2638, Yes HSC 6.7 25290.1, 25290.2, 25291 2060015 Sensor located in the RD proper position/location - Z E-1 ❑ ❑ ❑ ❑ None ❑ 23 CCR 16 2630(d), 2641(a) Yes 2030062 Facility is in compliance RD with not tampering with or disabling leak detection Z None ❑ devices or alarms - HSC Yes 6.7 25299(a)(9) 2060022 System constructed with a monitoring system capable of detecting entry E ❑ E-1 ❑ r--j ❑ None into secondary containment - HSC 6.7 25290.2(d) 2030034 Tag/sticker on affixed monitoring equipment being certified, repaired, ❑ E-1 None or replaced - 23 CCR 16 2638(o VPH Monitoring VPH 2030065 Interstitial monitoring of RD the annular spaces of the UST is properly ❑ ❑ Z ❑ None ❑ maintained - HSC 6.7 Yes 25290.1(e 2060023 System constructed with a monitoring system capable of detecting entry into secondary F-1 [--j None containment - HSC 6.7 25290.1(d) Underground Storage Tank Program - DW Inspection Report v 2.0 Violation Program Requirement 0 0 SOC Comments No 0 0 CL CS) 0 Z 0 Z D 0 W Line Leak Detector 2060012 Line leak detector installed on pressurized RD piping system - HSC 6.7 None ❑ 25290.1(h), 25290.2(8), Yes 25291(1), 25292(e), 2636(0 (2) 2030026 Line leak detectors detect a 3 gph leak and/or RD audible and visual alarm ❑ ❑ ❑ None ❑ function properly - 23 Yes CCR 16 2636(0(6), 2666(c) 2030027 Turbine shuts down when a leak is detected or RD when line leak detector is None ❑ disconnected - 23 CCR 16 Yes 2666(g) 2030025 Pressurized piping able to detect a 3.0 gph leak RD within an hour, and None ❑ restricts the flow or Yes alarms - 23 CCR 16 2636(0(2) Secondary Containment 2060010 UST storing a hazardous RD substance has secondary Z ❑ ❑ None [:1 containment - HSC 6.7 Yes 125292 Underground Storage Tank Program - DW Inspection Report v 2.0 violation Program Requirement 0 0 W= sO C- Comments No D a 0 0. 120 M 00 Z 0 Z D of 2030008 UDC, sumps, and/or other secondary containment in good None condition and/or are free of debris/liquid - HSC 6.7 25290.1, 25290.2, 25291 2030040 Secondarily contained RD piping maintained to allow Z ❑ ❑ E] E:] E) None ❑ liquid to drain into sump - Yes 23 CCR 16 2630(d), 2641 (a) 2060006 Secondary containment piping slopes back to the None collection sump m 23 CCR 16 263(c) 2030047 Secondary containment maintained tight and has been confirmed by testing ❑ MEJ ❑ None - 23 CCR 16 2662, HSC 6.7 25290.1(c)(2), 25290.2(c)(2), 25291(a), 25292(e) 2030060 Entry fittings in secondary containment for UST system maintained ❑ ❑ F-1 ❑ ❑ None tight/sealed - 23 CCR 16 2630, 2635(d), 2636(c), 2666 2060020 Spill bucket is installed and has a functional drain RP valve or other means to ❑ ❑ ❑ ❑ None ❑ remove liquid - 23 CCR 16 Yes 2635(b),,2665 2030054 Spill bucket maintained in Rp Diesel Spill Bucket failed lake test, good condition and free of E] E ❑ ❑ n ❑ None Z technician replaced spill bucket debris and/or liquid - 23 Yes like for like. New spill bucket was CCR 16 2635(b), 2715(c)(2) re-tested and passed. 2060019 Spill bucket to has a minimum capacity of five Z ❑ ❑ None gallons - 23 CCR 16 2635(b), 2665 Overfill 2030035 UST system is operated RP to prevent unauthorized release, including spills 0 F-1 ❑ ❑ ❑ ❑ None F-1 and overfills - HSC 6.7 Yes 25292.1 (a) 2030036 Overfill prevention system RP has not been overridden and meets overfill ❑ ❑ ❑ ❑ ❑ None [:1 requirements - 23 CCR 16 Yes 2635(b)(2), 2665 Underground Storage Tank Program - DW Inspection Report v 2.0 Violation Program Requirement 4- 0 0 Q SOC Comments No 0 > �- :n < a (1) 0 �- M E Mo 1 z 0 z 1 M V Ix On Site Records Certifications 2030023 Required designated operators or contractors maintain a proper and 0 ❑ None current ICC certification - 23 CCR 16 2715 2030024 Service technician, installer, and/ or employee maintain a ❑ ❑ ❑ None proper license - 23 CCR 162715 2030031 Employee or contractor obtained and maintained proper manufacturer None certification - 23 CCR 16 2715 2010007 Submit/maintain current Certificate of Financial Responsibility /mechanism of financial assurance - ❑ ❑ ❑ ❑ None 23 CCR 16 2711; 23 CCR 18 2808.1, 2809-2809.2; HSC 6.7 25292.2; HSC 6.75 25299.30-25299.34 Designated Operator 2010004 Copies of DO inspections for last 12 months and list of trained employees E ❑ ❑ ❑ ❑ ❑ None maintained - 23 CCR 16 2715 2030013 Designated operator properly conducted the monthly inspection and ❑ ❑ ❑ ❑ ❑ None the reports are complete - 23 CCR 16 2715 2030010 DO notified operator of any condition observed during the monthly ❑ ❑ None inspection that may require action - 23 CCR 16 2715(d) 2030012 DO employee training performed, current for at least one employee on None site, and a log kept - 23 CCR 16 2715(c)(6), 27150 Underground Storage Tank Program - DW Inspection Report v 2.0 Violation Program Requirement 4- C 0 0 SOC Comments No Oa M, C( 0 (0 CL 120 Z 0 Z > Logs 2030001 Leak detection alarm logs, maintenance and RD records of appropriate ❑ ❑ ❑ ❑ ❑ None ❑ follow-up actions Yes maintained - 23 CCR 16 2632, 2634, 2712(b) Maintenance/Tests 2010008 Monitoring, maintenance, repairs, linings, and RD upgrade records 1:1 El 1:1 1:1 E] None ❑ maintained for the proper Yes time period - 23 CCR 16 2712(b) Documentation 2030033 Failure to maintain on site an approved monitoring None plan - 23 CCR 16 2632, 2634, 2711, 2712(1) 2030037 Written agreement between the tank owner and tank operator to monitor the tank system None is maintained - 23 CCR 16 2620(b); HSC 6.7 25284(a)(3) 2030061 Suspected or actual unauthorized release RD reported in appropriate ❑ ❑ ❑ None ❑ time frame - HSC 6.7 Yes 29295 _29294, General Operating Requirements Permit Condition/Approval 2030039 Compliance with all operating permit ❑ ❑ ❑ ❑ ❑ None conditions - 23 CCR 16 2712; HSC 6.7 25299 2030059 UST system maintained in accordance with exclusion/exemption ❑ ❑ ❑ None status - HSC 6.7 25281.6, 25283.5 2030014 Owner/Operator received approval and has implemented a training None program at an unstaffed facility - 23 CCR 16 2715( 0(2) 2030015 Facility exhibited that the method used to monitor the tank meets the monitoring methods in 0 ❑ None 2643(f) - 23 CCR 16 2643 Underground Storage Tank Program - DW Inspection Report v 2.0 Violation Program Requirement 4- 0 0 4) = SOC Comments No M 4C 0 0 0. 42 (a Im"a - z 0 z D 0 W 4) > Red Tag 2030045 Red Tag information is legible and has not been ❑ El 0 ❑ ❑ ❑ None tampered with - 23 CCR 16 2717.1( ) 2030044 Facility did not allow for deposit of petroleum into a UST that has a red tag None affixed to the fill - 23 CCR 162717.1(0 Install/Repair 2060024 UST system is made of or lined with materials that are compatible with the None substance stored - 23 CCR 16 2631.1 2060021 Striker plate installed and positioned correctly - 23 ❑ ❑ ❑ E ❑ ❑ None CCR 16 2631(c), 2662(d) I I I I ❑ There were no violations noted for this inspection. ZThis report shall serve as a "NOTICE TO COMPLY" for Minor Violations, and a "NOTICE OF VIOLATION" for Major violations. You are, hereby, ordered to correct the above noted violations within 30 days, or according to correction summaries provided. Formal enforcement and/or penalty assessment may be initiated for any violations noted, and for those not corrected in a timely manner. (NOTE: If this is a preliminary report, a final report will follow.) Inspectors Signature: Date: -4 t ) ek I ( -(: 73 Inspector: Enter # of Violations: RD: I RP: ' Check one box for facility Significant Operational`Status (SOC) to be reported to SWRCB and US EPA: ❑ SOC with both Release Detection and Release Detection (Facility has no Release Prevention and no Release Prevention Violations) ❑ Not in SOC (Facility has both Release Prevention and Release Detection Violations) ESOC with Release Detection only (Facility has no Release Detection violations but one or more Release Prevention violations) ❑ SOC with Release Prevention only (Facility has no Release Prevention violations but one or more Release Detection violations) Underground Storage Tank Program - DW Inspection Report v 2.0