HomeMy WebLinkAbout3463_Pretest CERT_Arco_Bakersfield CA_CFS_160714Exclusive Providers for MDleak® and
PHDleak® Testing Technologies
Page 1 of 5
Test Type:
Facility Name: Job #: 3463
Prepared For:
Site Address:
City: Primary Test Leak Rate: 0.005 gph
State and Zip: CA 93307 Secondary Test Leak Rate: 0.1 gph
Start Date: End Date:
SYSTEM Tk-1 87 TK-2 91 TK-3 DSL
Product Primary:PASS PASS PASS
Product Secondary:PASS PASS PASS
Vent Primary:PASS PASS PASS
Vent Secondary:PASS PASS PASS
VR Primary:PASS PASS NA
VR Secondary:PASS PASS NA
Tank:Not Tested Not Tested Not Tested
Turbine Sump:PASS FAIL PASS
Turbine Sump Elect:Not Tested Not Tested Not Tested
Turbine Head:Not Tested Not Tested Not Tested
Fill/Vapor Sump:FAIL PASS PASS
Fill Sump Elect:Not Tested Not Tested Not Tested
Fill & Vapor Poppet:Not Tested Not Tested NA
UDC's:FAIL FAIL PASS
Fill Spill Bucket:Not Tested Not Tested Not Tested
Vapor Spill Bucket:Not Tested Not Tested NA
Vent Box: PASS PASS PASS
Certifying Field Technician: Ricardo Gonzalez State Lic. # :
Certification Leak Rate: 0.005 gph
Certifying Technician Signature: Date:
Statement Confirmed by: Date: 7/8/2016
Office use only
I declare under penalty of perjury that I am a licensed tank tester in the MDleak
®and PHDleak
®method, a method listed
by the NWGLDE organization and that the information contained in this report is true and correct to the best of my
knowledge.
If you have any questions on the testing please do not hesitate to call. @ 520-207-4878.
04-1695
This is a statement to confirm that the components listed above, at the time of testing, have been tested to a leak
sensitivity listed above using the MDleak®and PHDleak®Method. The MDleak
®and PHDleak
®Method is one of the
most versatile and comprehensive testing procedure offered to the petroleum industry. All petroleum owners and
contractors which utilize the MDleak
®and PHDleak
®Method can be assured that their facility has passed the Nation's
highest standard in preventative leak detection.
7/1/2016
7/1/20166/30/2016
1819 E Brundage Lane
Bakersfield
Complete Fueling Solutions
Facility Certification CONFIDENTIAL
California ELD New Construction Test Pretest Non-GC Detector Test
Arco AM/PM
1889 N Oracle Road Tucson, AZ 85705 Phone 855-255-5325 FAX: 1-520.509-3720
Exclusive Providers for MDleak® and
PHDleak® Testing Technologies
Page 2 of 5
1819 E Brundage Lane Log of Repaired Leak/s
CONFIDENTIAL
Tk-1 87 TK-2 91 TK-3 DSL
Tank Volume: 25 12000 8000
Manufacture: Xerxes Xerxes Xerxes
Interstice: Brine Brine Brine
Depth To Tank:
Tank Dia:
Depth to Fuel:
Tank Sump Boots Turbine
Smith FE Petro
8
OPW
Smith
Smith
Smith
Fire-Flex
EVR:
Reference #Date Time Status System Component Manufacture
20 6/30/16 9:31 Leak Pretest UDC UDC 1 Plug on VR Valve
22 6/30/16 9:34 Leak Pretest UDC UDC 3 Bolt on Shear Valve
23 6/30/16 9:35 Leak Pretest UDC UDC 4 Plug on 91 Shear Valve
24 6/30/16 9:36 Leak Pretest UDC UDC 5 3/8" Plug on 91 Shear Valve
25 6/30/16 9:37 Leak Pretest UDC UDC 6 Plug on Shear Valve
26 6/30/16 9:38 Leak Pretest UDC UDC 7 Casing on 91 Shear Valve
27 6/30/16 9:39 Leak Pretest UDC UDC 8 Plug on 87 & 91 Shear Valve
39 6/30/16 12:51 Leak Pretest Tk-1 87 Sump Turbine Cap on VR Line
41 6/30/16 12:53 Leak Pretest TK-2 91 Sump Turbine Union on Product Line
Reference #Date Time Status System Component Manufacture
Log of Unrepaired Leaks
Log of Repaired Leaks
Tank Information
Containment Boots:
Piping Information
Manufacture
Spill Buckets:
Number of Dispensers:
Manufacture:
Shear Valve Manufacture:
Flex:
Product Lines:
Vapor Return / Vent:
UDC/Dispensers Information
Depth to Ground Water:
Manufacture:
1889 N Oracle Road Tucson, AZ 85705 Phone 855-255-5325 FAX: 1-520.509-3720
Exclusive Providers for MDleak® and
PHDleak® Testing Technologies
Page 3 of 5
1819 E Brundage Lane Reference Addendum CONFIDENTIAL
Site Photo Site Photo
Site Photo Site Photo
Site Photo Site Photo
1889 N Oracle Road Tucson, AZ 85705 Phone 855-255-5325 FAX: 1-520.509-3720
Exclusive Providers for MDleak® and
PHDleak® Testing Technologies
Page 4 of 5
1819 E Brundage Lane Reference Addendum CONFIDENTIAL
Photo Reference 20 Photo Reference 22
Photo Reference 23 Photo Reference 24
Photo Reference 25 Photo Reference 26
1889 N Oracle Road Tucson, AZ 85705 Phone 855-255-5325 FAX: 1-520.509-3720
Exclusive Providers for MDleak® and
PHDleak® Testing Technologies
Page 5 of 5
1819 E Brundage Lane Reference Addendum CONFIDENTIAL
Photo Reference 27 Photo Reference 39
Photo Reference 41
1889 N Oracle Road Tucson, AZ 85705 Phone 855-255-5325 FAX: 1-520.509-3720