HomeMy WebLinkAbout2017 FMCMONITORING SYSTEM CERTIFICATION
For Use By All Jurisdictions Within the State of CaliforniaAuthority Cited: Chapter 6.7, Health and Safety Code; Chapter 16, Division 3, Title 23, California Code of Regulations
This form must be used to document testing and servicing of monitoring equipment. A separate certification or report must be prepared for each
monitoring system control panel by the technician who performs the work. A copy of this form must be provided to the tank system owner/operator.
The owner/operator must submit a copy of this form to the local agency regulating UST systems within 30 days of test date.
A.General Information
Facility Name:Bldg. No.:
Site Address:City:Zip:
Facility Contact Person: Contact Phone No.:
Make/Model of Monitoring System:Date of Testing/Servicing:
B.Inventory of Equipment Tested/Certified
Check the appropriate boxes to indicate specific equipment inspected/serviced:
Tank ID:Tank ID:
In-Tank Gauging Probe.Model:In-Tank Gauging Probe.Model:
Annular Space or Vault Sensor.Model:Annular Space or Vault Sensor.Model:
Piping Sump / Trench Sensor(s).Model:Piping Sump / Trench Sensor(s).Model:
Fill Sump Sensor(s).Model:Fill Sump Sensor(s).Model:
Mechanical Line Leak Detector.Model:Mechanical Line Leak Detector.Model:
Electronic Line Leak Detector.Model:Electronic LineLeak Detector.Model:
Tank Overfill / High-Level Sensor.Model:Tank Overfill / High-Level Sensor.Model:
Other (specify equipment type and model in Section E on Page 2).Other (specify equipment type and model in Section E on Page 2).
Tank ID:Tank ID:
In-Tank Gauging Probe.Model:In-Tank Gauging Probe.Model:
Annular Space or Vault Sensor.Model:Annular Space or Vault Sensor.Model:
Piping Sump / TrenchSensor(s).Model:Piping Sump / Trench Sensor(s).Model:
Fill Sump Sensor(s).Model:Fill Sump Sensor(s).Model:
Mechanical Line Leak Detector.Model:Mechanical Line Leak Detector.Model:
Electronic Line Leak Detector.Model:Electronic Line Leak Detector.Model:
Tank Overfill / High-Level Sensor.Model:Tank Overfill / High-Level Sensor.Model:
Other (specify equipment type and model in Section E on Page 2).Other (specify equipment type and model in Section E on Page 2).
Dispenser ID:Dispenser ID:
Dispenser Containment Sensor(s).Model:Dispenser Containment Sensor(s).Model:
Shear Valve(s).Shear Valve(s).
Dispenser Containment Float(s) and Chain(s).Dispenser Containment Float(s) and Chain(s).
Dispenser ID:Dispenser ID:
Dispenser Containment Sensor(s).Model:Dispenser Containment Sensor(s).Model:
Shear Valve(s).Shear Valve(s).
Dispenser Containment Float(s) and Chain(s).Dispenser Containment Float(s) and Chain(s).
Dispenser ID:Dispenser ID:
Dispenser Containment Sensor(s).Model:Dispenser Containment Sensor(s).Model:
Shear Valve(s).Shear Valve(s).
Dispenser Containment Float(s) and Chain(s).Dispenser Containment Float(s) and Chain(s).
*If the facility contains more tanks or dispensers, copy this form. Include information for every tank and dispenser at the facility.
C.Certification -I certify that the equipment identified in this document was inspected/serviced in accordance with the manufacturers’
guidelines. Attached to this Certification is information (e.g. manufacturers' checklists)necessary to verify that this information is
correct and a Plot Plan showing the layout of monitoring equipment. For any equipment capable of generating such reports, I have also
attached a copy of the report;(check all that apply):System set-up Alarm history report
Technician Name (print):Signature:
Certification No.:License. No.:804904
Testing Company Name:Confidence UST Services, Inc.Phone No.:(800)339-9930
Site Address:Date of Testing/Servicing:
Page 1 of 3
#5562Fastrip#6
1640SouthChesterAvenueBakersfield93304
OmeroGarcia (661)393-7000
Veeder-RootTLS-350 09/07/2017
12,000gal.Regular1
847390-107
794390-420
794380-208
FX1V
847390-107
12,000gal.Regular2
847390-107
794390-420
794380-208
FX1V
847390-107
12,000gal.Super
847390-107
794390-420
794380-208
FX1V
847390-107
12,000gal.Diesel
847390-107
794390-420
794380-208
FX1DV
847390-107
1-2
794380-208
3-4
794380-208
5-6
794380-208 794380-208
7-8
TransitionSump(North)
794380-208
TransitionSump(South)
794380-208
AaronPerrrigo
B47853
1640SouthChesterAvenue Bakersfield,CA93304 09/07/2017
794380-208
794380-208
794380-208 794380-208
Monitoring System Certification
D.Results of Testing/Servicing
Software Version Installed:
Complete the following checklist:
Yes No*Isthe audible alarm operational?
Yes No*Is the visual alarm operational?
Yes No*Were all sensors visually inspected, functionally tested, and confirmed operational?
Yes No*Were all sensors installed at lowest point of secondary containment and positioned so that other equipment will
not interfere with their proper operation?
Yes No*
N/A
If alarms are relayed to a remote monitoring station, is all communications equipment (e.g., modem)
operational?
Yes No*
N/A
For pressurized piping systems, does the turbine automatically shut down if the piping secondary containment
monitoring system detects a leak, fails to operate, or is electrically disconnected? If yes: which sensors initiate
positive shut-down? (Check all that apply) Sump/Trench Sensors; Dispenser Containment Sensors.
Did you confirm positive shut-down due to leaks and sensor failure/disconnection? Yes; No.
Yes No*
N/A
For tank systems that utilize the monitoring system as the primary tank overfill warning device (i.e., no
mechanical overfill prevention valve is installed), is the overfill warning alarm visible and audible at the tank
fill point(s) and operating properly? If so, at what percent oftank capacity does the alarm trigger? %
Yes*NoWas any monitoring equipment replaced? If yes, identify specific sensors, probes, or other equipment replaced
and list the manufacturer name and model for all replacement parts in Section E, below.
Yes*NoWas liquid found inside any secondary containment systems designed as dry systems? (Check all that apply)
Product; Water. If yes, describe causes in Section E, below.
Yes No*Was monitoring system set-up reviewed to ensure proper settings? Attach set up reports, if applicable
Yes No*Is all monitoring equipment operational per manufacturer’s specifications?
* In Section E below, describe how and when these deficiencies were or will be corrected.
E.Comments:
Page 2 of 3
329.01
90
Monitoring System Certification
F.In-Tank Gauging / SIR Equipment: Check this box if tank gauging is used only for inventory control.
Check this box if no tank gauging or SIR equipment is installed.
This section must be completed if in-tank gauging equipment is used to perform leak detection monitoring.
Complete the following checklist:
Yes No*Has all input wiring been inspected for proper entry and termination, including testing for ground faults?
Yes No*Were all tank gauging probes visually inspected for damage and residue buildup?
Yes No*Was accuracy of system product level readings tested?
Yes No*Was accuracy of system water level readings tested?
Yes No*Were all probes reinstalled properly?
Yes No*Were all items on the equipment manufacturer’s maintenance checklist completed?
* In the Section H, below, describe how and when these deficiencies were or will be corrected.
G.Line Leak Detectors (LLD):Check this box if LLDs are not installed.
Complete the following checklist:
Yes No*
N/A
For equipment start-up or annual equipment certification, was a leak simulated to verify LLD performance?
(Check all that apply)Simulated leak rate: 3 g.p.h.; 0.1 g.p.h ; 0.2 g.p.h.
Yes No*Were all LLDs confirmed operational and accurate within regulatory requirements?
Yes No*Was the testing apparatus properly calibrated?
Yes No*
N/A
For mechanical LLDs, does the LLD restrict product flow if it detects a leak?
Yes No*
N/A
For electronic LLDs, does the turbine automatically shut off if the LLD detects a leak?
Yes No*
N/A
For electronic LLDs, does the turbine automatically shut off if any portion of the monitoring system is disabled
or disconnected?
Yes No*
N/A
For electronic LLDs, does the turbine automatically shut off if any portion of the monitoring system malfunctions
or fails a test?
Yes No*
N/A
For electronic LLDs, have all accessible wiring connections been visually inspected?
Yes No*Were all items on the equipment manufacturer’s maintenance checklist completed?
* In the Section H, below, describe how and when these deficiencies were or will be corrected.
H.Comments:
Page 3 of 3
Leak Detector Test Results Sheet
Customer Address: Work Order: Site Address:
Test Date:
Site Contact: Phone:
Technician: Phone: 800-339-9930 ICC No.:
Product Type LLD Type Model Serial No. Check
Valve
Holding
Pressure
Bleed
Off ML.
Leak
Rate
Tested:
Pass/Fail
3 gph @
10 psi
3 gph @
10 psi
3 gph @
10 psi
3 gph @
10 psi
3 gph @
10 psi
3 gph @
10 psi
3 gph @
10 psi
3 gph @
10 psi
Technician Name: Technician No.:
Signature: Date:
JacoHill
P.O.Box82515
Bakersfield,CA93380-2515
39907
09/07/2017
8485827-UT
Regular1
AaronPerrrigo
(661)393-7000OmeroGarcia
Bakersfield,CA93304
1640SouthChesterAvenue
#5562Fastrip#6
FX1VMechanicalRegular2 1060 Pass
FX1VMechanicalPremium 1250 Pass
FX1DVMechanicalDiesel 140 Pass
AaronPerrrigo 8485827-UT
09/07/2017
Jaco 5562 Fastrip Setup
Responses Received: 200 FASTRIP 562 MING-CHESTER BAKERSFIELD CA 661-397-8606 09-07-17 9:19 AM TANK PRODUCT GALLONS INCHES WATER DEG F ULLAGE 1 UNL 5063 48.70 0.0 91.1 6999 2 DIESEL 1607 21.29 0.0 90.3 10455 3 PNL 3709 38.62 0.8 91.4 8353 4 UNL 2 SIPON 5017 48.36 0.8 90.1 7045 I90500 09-07-17 9:19 AM SOFTWARE REVISION LEVEL VERSION 329.01 SOFTWARE# 346329-100-B CREATED - 09.01.29.15.44 S-MODULE# 330160-004-a SYSTEM FEATURES: PERIODIC IN-TANK TESTS ANNUAL IN-TANK TESTS ISD I50500 09-07-17 9:19 AM SYSTEM TYPE AND LANGUAGE FLAG SYSTEM UNITS U.S. SYSTEM LANGUAGE ENGLISH SYSTEM DATE/TIME FORMAT MM-DD-YY HH:MM:SS xM I50201 09-07-17 9:19 AM SHIFT TIME 1 : DISABLED I50202 09-07-17 9:19 AM SHIFT TIME 2 : DISABLED
I50203 09-07-17 9:19 AM SHIFT TIME 3 : DISABLED I50204 09-07-17 9:19 AM SHIFT TIME 4 : DISABLED I54600 09-07-17 9:19 AM TANK PER TST NEEDED WRN: DISABLED I54900 09-07-17 9:19 AM TANK ANN TST NEEDED WRN: DISABLED I55300 09-07-17 9:19 AM LINE RE-ENABLE METHOD PASS LINE TEST I55600 09-07-17 9:19 AM LINE PER TST NEEDED WRN: DISABLED I55900 09-07-17 9:19 AM LINE ANN TST NEEDED WRN: DISABLED I50D00 09-07-17 9:19 AM PRINT TC VOLUMES ENABLED I50E00 09-07-17 9:19 AM TEMP COMPENSATION
VALUE (DEG F ): 60.0 I60B00 09-07-17 9:19 AM STICK HEIGHT OFFSET ENABLE STATUS DISABLED I51400 09-07-17 9:19 AM H-PROTOCOL DATA FORMAT HEIGHT I51A01 09-07-17 9:19 AM DAYLIGHT SAVING TIME ENABLED ON I51B00 09-07-17 9:19 AM DAYLIGHT SAVING TIME START DATE APR WEEK 1 SUN 2:00 AM END DATE NOV WEEK 1 SUN 2:00 AM I51600 09-07-17 9:20 AM RE-DIRECT LOCAL PRINTOUT DISABLED I50400 09-07-17 9:20 AM 232 SECURITY CODE PORT SECURITY CODE STATUS 1 000000 DISABLED 2 000000 DISABLED 3 000000 DISABLED 4 000000 DISABLED 5 000000 DISABLED 6 000000 DISABLED
I21900 09-07-17 9:20 AM TANK CHART SECURITY DISABLED I5BD00 09-07-17 9:20 AM CUSTOM ALARM LABELS DISABLED I56000 09-07-17 9:20 AM MASS/DENSITY DISABLED I88101 09-07-17 9:20 AM PORT SETTINGS: COMM BOARD : 1 (RS-232) BAUD RATE : 9600 PARITY : NONE STOP BIT : 2 STOP DATA LENGTH: 8 DATA RS-232 SECURITY CODE : DISABLED I88102 09-07-17 9:20 AM PORT SETTINGS: COMM BOARD : 2 (RS-232) BAUD RATE : 9600 PARITY : NONE STOP BIT : 1 STOP DATA LENGTH: 8 DATA RS-232 SECURITY CODE : DISABLED I88103 09-07-17 9:20 AM PORT SETTINGS: COMM BOARD : 3 (EDIM ) RS-232 SECURITY CODE : DISABLED
I88104 09-07-17 9:20 AM I88105 09-07-17 9:20 AM I88106 09-07-17 9:20 AM I52000 09-07-17 9:20 AM RECEIVER AUTO DIAL TYPE & START TIME RCVR LOCATION LABEL DIAL TYPE START TIME 1 ON DATE JUN 25, 2015 DISABLED 2 ON DATE JUN 25, 2015 DISABLED 3 ON DATE JUN 25, 2015 DISABLED 4 ON DATE JUN 25, 2015 DISABLED 5 ON DATE JUN 25, 2015 DISABLED 6 ON DATE JUN 25, 2015 DISABLED 7 ON DATE JUN 25, 2015 DISABLED 8 ON DATE JUN 25, 2015 DISABLED I60100 09-07-17 9:20 AM TANK CONFIGURATION DEVICE LABEL CONFIGURED 1 UNL ON 2 DIESEL ON 3 PNL ON 4 UNL 2 SIPON ON I60200 09-07-17 9:20 AM TANK PRODUCT LABEL TANK PRODUCT LABEL 1 UNL 2 DIESEL 3 PNL 4 UNL 2 SIPON I60300 09-07-17 9:20 AM TANK PRODUCT CODE
TANK PRODUCT LABEL 1 UNL 1 2 DIESEL 2 3 PNL 3 4 UNL 2 SIPON 4 I60900 09-07-17 9:20 AM TANK THERMAL COEFFICIENT TANK PRODUCT LABEL 1 UNL 0.000700 2 DIESEL 0.000450 3 PNL 0.000700 4 UNL 2 SIPON 0.000700 I60700 09-07-17 9:20 AM TANK DIAMETER TANK PRODUCT LABEL INCHES 1 UNL 111.50 2 DIESEL 111.50 3 PNL 111.50 4 UNL 2 SIPON 111.50 I60A00 09-07-17 9:20 AM TANK FULL VOLUME TANK PRODUCT LABEL TANK PROFILE GALLONS 1 UNL 1 PT 12062 2 DIESEL 1 PT 12062 3 PNL 1 PT 12062 4 UNL 2 SIPON 1 PT 12062 I60400 09-07-17 9:20 AM TANK FULL VOLUME TANK PRODUCT LABEL GALLONS 1 UNL 12062 2 DIESEL 12062 3 PNL 12062 4 UNL 2 SIPON 12062 I60500 09-07-17 9:20 AM TANK 4 POINT VOLUMES TANK PRODUCT LABEL GALLONS 1 UNL 12062 0 0 0 2 DIESEL 12062 0 0 0 3 PNL 12062 0 0 0
4 UNL 2 SIPON 12062 0 0 0 I60600 09-07-17 9:20 AM TANK 20 POINT VOLUMES TANK PRODUCT LABEL GALLONS 1 UNL 12062 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 2 DIESEL 12062 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 3 PNL 12062 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 4 UNL 2 SIPON 12062 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 I61500 09-07-17 9:20 AM TANK PRODUCT LABEL METER DATA 1 UNL NO 2 DIESEL NO 3 PNL NO 4 UNL 2 SIPON NO I62F00 09-07-17 9:20 AM MAG PROBE FLOAT SIZE TANK PRODUCT LABEL FLOAT SIZE: 1 UNL 4.0 INCHES 2 DIESEL 3.0 INCHES 3 PNL 4.0 INCHES 4 UNL 2 SIPON 4.0 INCHES I62700 09-07-17 9:20 AM TANK HIGH WATER WARNING LIMIT TANK PRODUCT LABEL INCHES
1 UNL 2.0 2 DIESEL 0.0 3 PNL 2.0 4 UNL 2 SIPON 2.0 9999FF1B I62400 09-07-17 9:20 AM TANK HIGH WATER LEVEL LIMIT TANK PRODUCT LABEL INCHES 1 UNL 3.0 2 DIESEL 3.0 3 PNL 3.0 4 UNL 2 SIPON 3.0 I62800 09-07-17 9:20 AM TANK MAXIMUM VOLUME LIMIT TANK PRODUCT LABEL GALLONS 1 UNL 12062 2 DIESEL 12062 3 PNL 12062 4 UNL 2 SIPON 12062 I62300 09-07-17 9:20 AM TANK OVERFILL LEVEL LIMIT TANK PRODUCT LABEL GALLONS 1 UNL 10855 2 DIESEL 10855 3 PNL 10855 4 UNL 2 SIPON 10855 I62200 09-07-17 9:20 AM TANK HIGH PRODUCT LIMIT TANK PRODUCT LABEL GALLONS 1 UNL 11459 2 DIESEL 11459 3 PNL 11459 4 UNL 2 SIPON 11459 I62900 09-07-17 9:20 AM TANK DELIVERY REQUIRED LIMIT TANK PRODUCT LABEL GALLONS 1 UNL 1809 2 DIESEL 1809
3 PNL 1809 4 UNL 2 SIPON 1809 I62100 09-07-17 9:20 AM TANK LOW PRODUCT LIMIT TANK PRODUCT LABEL GALLONS 1 UNL 500 2 DIESEL 500 3 PNL 500 4 UNL 2 SIPON 500 I62600 09-07-17 9:20 AM TANK LEAK ALARM LIMIT TANK PRODUCT LABEL GALLONS 1 UNL 99 2 DIESEL 99 3 PNL 99 4 UNL 2 SIPON 99 I62500 09-07-17 9:20 AM TANK SUDDEN LOSS LIMIT TANK PRODUCT LABEL GALLONS 1 UNL 99 2 DIESEL 99 3 PNL 99 4 UNL 2 SIPON 99 I60800 09-07-17 9:20 AM TANK TILT TANK PRODUCT LABEL INCHES 1 UNL 4.50 2 DIESEL 2.50 3 PNL 4.30 4 UNL 2 SIPON 3.50 I60B00 09-07-17 9:20 AM STICK HEIGHT OFFSET ENABLE STATUS DISABLED I60C00 09-07-17 9:20 AM
TANK STICK HEIGHT OFFSET TANK PRODUCT LABEL INCHES 1 UNL 0.00 2 DIESEL 0.00 3 PNL 0.00 4 UNL 2 SIPON 0.00 I61200 09-07-17 9:20 AM TANK MANIFOLDED PARTNERS TANK PRODUCT LABEL SIPHON MANIFOLDED TANKS LINE MANIFOLDED TANKS 1 UNL NONE NONE 2 DIESEL NONE NONE 3 PNL NONE NONE 4 UNL 2 SIPON NONE NONE I63600 09-07-17 9:20 AM PERIODIC LEAK TEST MIN VOLUME TANK PRODUCT LABEL GALLONS 1 UNL 1206 2 DIESEL 120 3 PNL 120 4 UNL 2 SIPON 120 I62A00 09-07-17 9:20 AM ANNUAL LEAK TEST MIN VOLUME TANK PRODUCT LABEL GALLONS 1 UNL 0 2 DIESEL 0 3 PNL 0 4 UNL 2 SIPON 120 I62C00 09-07-17 9:20 AM TANK PERIODIC TEST TYPE TANK PRODUCT LABEL PERIODIC TEST TYPE 1 UNL STANDARD 2 DIESEL STANDARD 3 PNL STANDARD 4 UNL 2 SIPON STANDARD I62D00 09-07-17 9:20 AM TANK LEAK TEST FAIL ALARMS TANK PRODUCT LABEL
1 UNL GROSS TEST FAIL ALARM DISABLED PERIODIC TEST FAIL ALARM DISABLED 2 DIESEL GROSS TEST FAIL ALARM DISABLED PERIODIC TEST FAIL ALARM DISABLED ANNUAL TEST FAIL ALARM DISABLED 3 PNL GROSS TEST FAIL ALARM DISABLED PERIODIC TEST FAIL ALARM DISABLED 4 UNL 2 SIPON GROSS TEST FAIL ALARM DISABLED PERIODIC TEST FAIL ALARM DISABLED ANNUAL TEST FAIL ALARM DISABLED I63100 09-07-17 9:20 AM TANK LEAK TEST AVERAGING TANK PRODUCT LABEL ANNUAL PERIODIC 1 UNL OFF OFF 2 DIESEL OFF OFF 3 PNL OFF OFF 4 UNL 2 SIPON OFF OFF I63000 09-07-17 9:20 AM IN-TANK LEAK TEST NOTIFY TANK PRODUCT LABEL TANK TEST NOTIFY: 1 UNL OFF 2 DIESEL OFF 3 PNL OFF 4 UNL 2 SIPON OFF I63200 09-07-17 9:20 AM TANK TEST SIPHON BREAK TANK PRODUCT LABEL SIPHON BREAK 1 UNL OFF 2 DIESEL OFF 3 PNL OFF 4 UNL 2 SIPON OFF I61000 09-07-17 9:20 AM TANK DELIVERY DELAY TANK PRODUCT LABEL 1 UNL 1
2 DIESEL 1 3 PNL 1 4 UNL 2 SIPON 1 I63A00 09-07-17 9:20 AM LOW LEVEL PUMP THRESHOLD FOR SEQUENTIAL LINE MANIFOLD TANK PRODUCT LABEL PUMP THRESHOLD 1 UNL 10.00% 2 DIESEL 10.00% 3 PNL 10.00% 4 UNL 2 SIPON 10.00% I61100 09-07-17 9:20 AM LEAK TEST METHOD - - - - - - - - - - - - TEST ON DATE : TANK 1 MAR 19, 2009 START TIME : DISABLED TEST RATE :0.20 GAL/HR DURATION : 2 HOURS TST EARLY STOP:DISABLED TEST ON DATE : TANK 2 JAN 29, 2009 START TIME : DISABLED TEST RATE :0.20 GAL/HR DURATION : 2 HOURS TST EARLY STOP:DISABLED TEST ON DATE : TANK 3 JAN 29, 2009 START TIME : DISABLED TEST RATE :0.20 GAL/HR DURATION : 2 HOURS TST EARLY STOP:DISABLED TEST ON DATE : TANK 4 JAN 29, 2009 START TIME : DISABLED TEST RATE :0.20 GAL/HR DURATION : 2 HOURS TST EARLY STOP:DISABLED I61300 09-07-17 9:20 AM CSLD PROBABLITY OF DETECTION
I61400 09-07-17 9:20 AM CSLD CLIMATE FACTOR I61600 09-07-17 9:20 AM TANK PRODUCT LABEL CAL UPDATE 1 UNL IMMEDIATE 2 DIESEL IMMEDIATE 3 PNL IMMEDIATE 4 UNL 2 SIPON IMMEDIATE I61A00 09-07-17 9:20 AM IN-TANK LEAK TEST EARLY STOP TANK PRODUCT LABEL TST EARLY STOP: 1 UNL DISABLED 2 DIESEL DISABLED 3 PNL DISABLED 4 UNL 2 SIPON DISABLED I61B00 09-07-17 9:20 AM IN-TANK LEAK GROSS TEST AUTO-CONFIRM I61C00 09-07-17 9:20 AM CSLD REPORT ONLY I62B00 09-07-17 9:20 AM TANK LAST ANNUAL TEST TANK PRODUCT LABEL DATE 1 UNL 00-00-00 2 DIESEL 00-00-00 3 PNL 00-00-00 4 UNL 2 SIPON 00-00-00 I63300 09-07-17 9:20 AM
LEAK TEST REPORT FORMAT: NORMAL I63400 09-07-17 9:20 AM RECONCILIATION WARNING LIMIT TANK PRODUCT LABEL GALLONS 1 UNL 0 2 DIESEL 0 3 PNL 0 4 UNL 2 SIPON 0 I63500 09-07-17 9:20 AM RECONCILIATION ALARM LIMIT TANK PRODUCT LABEL GALLONS 1 UNL 1 2 DIESEL 1 3 PNL 1 4 UNL 2 SIPON 1 I63900 09-07-17 9:20 AM ACCU CHART END SHAPE FACTOR TANK PRODUCT LABEL 1 UNL END FACTOR: NONE 2 DIESEL END FACTOR: NONE 3 PNL END FACTOR: NONE 4 UNL 2 SIPON END FACTOR: NONE I78000 09-07-17 9:20 AM I77700 09-07-17 9:20 AM
I77800 09-07-17 9:20 AM I78C00 09-07-17 9:20 AM I78300 09-07-17 9:20 AM I78F00 09-07-17 9:20 AM I78700 09-07-17 9:20 AM I70200 09-07-17 9:20 AM LIQUID LABEL DEVICE LABEL 1 UNL 1 STP 2 UNL1 ANN 3 DIESEL 4 DIESEL ANN 5 PNL STP 6 PNL ANN 7 UNL2 SIPON 8 UNL2 ANN 9 DISP 1-2 10 DISP 3-4 11 DISP 5-6 12 DISP 7-8 13 TRANS NO. 14 TRANS SO. 15 16 I70300 09-07-17 9:20 AM LIQUID TYPE SENSOR LOCATION TYPE 1 UNL 1 STP TRI-STATE (SINGLE FLOAT) 2 UNL1 ANN TRI-STATE (SINGLE FLOAT) 3 DIESEL TRI-STATE (SINGLE FLOAT) 4 DIESEL ANN TRI-STATE (SINGLE FLOAT) 5 PNL STP TRI-STATE (SINGLE FLOAT) 6 PNL ANN TRI-STATE (SINGLE FLOAT) 7 UNL2 SIPON TRI-STATE (SINGLE FLOAT)
8 UNL2 ANN TRI-STATE (SINGLE FLOAT) 9 DISP 1-2 TRI-STATE (SINGLE FLOAT) 10 DISP 3-4 TRI-STATE (SINGLE FLOAT) 11 DISP 5-6 TRI-STATE (SINGLE FLOAT) 12 DISP 7-8 TRI-STATE (SINGLE FLOAT) 13 TRANS NO. TRI-STATE (SINGLE FLOAT) 14 TRANS SO. TRI-STATE (SINGLE FLOAT) 15 TRI-STATE (SINGLE FLOAT) 16 TRI-STATE (SINGLE FLOAT) I70400 09-07-17 9:20 AM LIQUID CATEGORY SENSOR LOCATION CATEGORY 1 UNL 1 STP STP SUMP 2 UNL1 ANN ANNULAR SPACE 3 DIESEL STP SUMP 4 DIESEL ANN ANNULAR SPACE 5 PNL STP STP SUMP 6 PNL ANN ANNULAR SPACE 7 UNL2 SIPON STP SUMP 8 UNL2 ANN ANNULAR SPACE 9 DISP 1-2 DISPENSER PAN 10 DISP 3-4 DISPENSER PAN 11 DISP 5-6 DISPENSER PAN 12 DISP 7-8 DISPENSER PAN 13 TRANS NO. PIPING SUMP 14 TRANS SO. PIPING SUMP 15 OTHER SENSORS 16 OTHER SENSORS I74200 09-07-17 9:20 AM I74300 09-07-17 9:20 AM I74400 09-07-17 9:20 AM I74700 09-07-17 9:20 AM I74800 09-07-17 9:20 AM I74900
09-07-17 9:20 AM I7BC00 09-07-17 9:20 AM I80200 09-07-17 9:20 AM I80300 09-07-17 9:20 AM I80400 09-07-17 9:20 AM I80700 09-07-17 9:20 AM RELAY LABEL DEVICE LABEL 1 UNL 1 2 DIESEL 3 PNL 4 5 OVERFILL ALARM 6 7 8 I80900 09-07-17 9:20 AM RELAY ORIENTATION RELAY DESIGNATION ORIENTATION 1 UNL 1 NORMALLY OPEN 2 DIESEL NORMALLY CLOSED 3 PNL NORMALLY OPEN 4 NORMALLY OPEN 5 OVERFILL ALARM NORMALLY OPEN 6 NORMALLY OPEN 7 NORMALLY OPEN 8 NORMALLY OPEN I80B00 09-07-17 9:20 AM RELAY TANK ASSIGNMENT
RELAY DESIGNATION TANK 1 UNL 1 1 2 DIESEL 2 3 PNL 3 4 NONE 5 OVERFILL ALARM NONE 6 NONE 7 NONE 8 NONE I80A00 09-07-17 9:20 AM RELAY TYPE RELAY DESIGNATION TYPE 1 UNL 1 PUMP CONTROL OUTPUT 2 DIESEL STANDARD 3 PNL PUMP CONTROL OUTPUT 4 STANDARD 5 OVERFILL ALARM STANDARD 6 STANDARD 7 STANDARD 8 STANDARD I80C00 09-07-17 9:20 AM I80800 09-07-17 9:20 AM RELAY SETUP REPORT R 1:UNL 1 TYPE: PUMP CONTROL OUTPUT TANK #: 1 LIQUID SENSOR ALMS L 1:FUEL ALARM L 7:FUEL ALARM L 9:FUEL ALARM L10:FUEL ALARM L11:FUEL ALARM L12:FUEL ALARM L 1:SENSOR OUT ALARM L 7:SENSOR OUT ALARM L 9:SENSOR OUT ALARM L10:SENSOR OUT ALARM L11:SENSOR OUT ALARM L12:SENSOR OUT ALARM L 1:SHORT ALARM L 7:SHORT ALARM L 9:SHORT ALARM L10:SHORT ALARM L11:SHORT ALARM
L12:SHORT ALARM ISD SITE ALARMS ISD GROSS PRES FAIL ISD DEGRD PRES FAIL ISD VAPOR LEAK FAIL ISD VP PRES FAIL ISD VP STATUS FAIL ISD HOSE ALARMS ALL:GROSS COLLECT FAIL ALL:DEGRD COLLECT FAIL ALL:FLOW COLLECT FAIL R 2:DIESEL TYPE: STANDARD NORMALLY CLOSED TANK #: 2 LIQUID SENSOR ALMS L 3:FUEL ALARM L 9:FUEL ALARM L11:FUEL ALARM L 3:SENSOR OUT ALARM L 9:SENSOR OUT ALARM L11:SENSOR OUT ALARM L 3:SHORT ALARM L 9:SHORT ALARM L11:SHORT ALARM R 3:PNL TYPE: PUMP CONTROL OUTPUT TANK #: 3 LIQUID SENSOR ALMS L 5:FUEL ALARM L 9:FUEL ALARM L10:FUEL ALARM L11:FUEL ALARM L12:FUEL ALARM L 5:SENSOR OUT ALARM L 9:SENSOR OUT ALARM L10:SENSOR OUT ALARM L11:SENSOR OUT ALARM L12:SENSOR OUT ALARM L 5:SHORT ALARM L 9:SHORT ALARM L10:SHORT ALARM L11:SHORT ALARM L12:SHORT ALARM ISD SITE ALARMS ISD GROSS PRES FAIL ISD DEGRD PRES FAIL ISD VAPOR LEAK FAIL ISD VP PRES FAIL
ISD VP STATUS FAIL ISD HOSE ALARMS ALL:GROSS COLLECT FAIL ALL:DEGRD COLLECT FAIL ALL:FLOW COLLECT FAIL R 4: TYPE: STANDARD NORMALLY OPEN TANK #: NONE - NO ALARM ASSIGNMENTS - R 5:OVERFILL ALARM TYPE: STANDARD NORMALLY OPEN TANK #: NONE IN-TANK ALARMS ALL:OVERFILL ALARM ALL:HIGH PRODUCT ALARM ALL:MAX PRODUCT ALARM R 6: TYPE: STANDARD NORMALLY OPEN TANK #: NONE - NO ALARM ASSIGNMENTS - R 7: TYPE: STANDARD NORMALLY OPEN TANK #: NONE - NO ALARM ASSIGNMENTS - R 8: TYPE: STANDARD NORMALLY OPEN TANK #: NONE - NO ALARM ASSIGNMENTS - I79000 09-07-17 9:21 AM
EDIM:1 VR:349634-003-C TD:06.05.11.11.15 I79100 09-07-17 9:21 AM I72300 09-07-17 9:21 AM FASTRIP 562 MING-CHESTER BAKERSFIELD CA 661-397-8606 SMARTSENSOR ASSIGNMENT DEVICE LABEL CATEGORY 01 V.P. SENSOR 3-4 VAPOR PRESSURE 02 F.M. 1-2 AIR FLOW METER 03 F.M. 3-4 AIR FLOW METER 04 F.M. 5-6 AIR FLOW METER 05 F.M. 7-8 AIR FLOW METER 06 UNKNOWN 07 UNKNOWN 08 UNKNOWN 09 UNKNOWN 10 UNKNOWN 11 UNKNOWN 12 UNKNOWN 13 UNKNOWN 14 UNKNOWN 15 UNKNOWN 16 UNKNOWN 17 UNKNOWN 18 UNKNOWN 19 UNKNOWN 20 UNKNOWN 21 UNKNOWN 22 UNKNOWN 23 UNKNOWN 24 UNKNOWN 25 UNKNOWN 26 UNKNOWN 27 UNKNOWN 28 UNKNOWN 29 UNKNOWN 30 UNKNOWN 31 UNKNOWN 32 UNKNOWN 33 UNKNOWN 34 UNKNOWN 35 UNKNOWN 36 UNKNOWN 37 UNKNOWN 38 UNKNOWN 39 UNKNOWN 40 UNKNOWN
IV4E00 09-07-17 9:21 AM FASTRIP 562 MING-CHESTER BAKERSFIELD CA 661-397-8606 EVR/ISD SETUP TYPE: VACUUM ASSIST VACUUM ASSIST TYPE: HEALY VAC IV4F00 09-07-17 9:21 AM FASTRIP 562 MING-CHESTER BAKERSFIELD CA 661-397-8606 NOZZLE A/L RANGE A/L RATIO: 0.95 - 1.15 IV4000 09-07-17 9:21 AM FASTRIP 562 MING-CHESTER BAKERSFIELD CA 661-397-8606 VAPOR PROCESSOR TYPE NONE IV4700 09-07-17 9:21 AM FASTRIP 562 MING-CHESTER BAKERSFIELD CA 661-397-8606 ASSESSMENT TIME START TIME: 10:00 AM TIME DELAY MINUTES: 1 IV5200 09-07-17 9:21 AM FASTRIP 562 MING-CHESTER BAKERSFIELD CA 661-397-8606
ACCEPT HIGH ORVR: NO IV4A00 09-07-17 9:21 AM FASTRIP 562 MING-CHESTER BAKERSFIELD CA 661-397-8606 ISD HOSE TABLE HOSE FP FP AFM HOSE ID ID LABEL ID LABEL 01 01 01 01 BLEND3 02 02 02 01 BLEND3 03 03 03 02 BLEND3 04 04 04 02 BLEND3 05 05 05 03 BLEND3 06 06 06 03 BLEND3 07 07 07 04 BLEND3 08 08 08 04 BLEND3 IV4B00 09-07-17 9:21 AM FASTRIP 562 MING-CHESTER BAKERSFIELD CA 661-397-8606 PRODUCT/HOSE MAP TABLE FP AFID M1/H1 M2/H2 M3/H3 M4/H4 01 01 02/01 03/01 09/01 xx/xx 02 01 02/02 03/02 09/02 xx/xx 03 02 02/03 03/03 09/03 xx/xx 04 02 02/04 03/04 09/04 xx/xx 05 03 02/05 03/05 09/05 xx/xx 06 03 02/06 03/06 09/06 xx/xx 07 04 02/07 03/07 09/07 xx/xx 08 04 09/08 02/08 03/08 xx/xx IV4900 09-07-17 9:21 AM FASTRIP 562 MING-CHESTER BAKERSFIELD CA 661-397-8606 LABEL TABLE ID LABEL 01 UNASSIGNED 02 BLEND3 03 REGULAR 04 MID GRADE
05 PREMIUM 06 GOLD 07 BRONZE 08 SILVER 09 BLEND2 10 BLEND4 IV1000 09-07-17 9:21 AM ISD VERSION: 01.02
Jaco 5562 Fastrip Alarm History
Responses Received: I10200 09-07-17 9:23 AM FASTRIP 562 MING-CHESTER BAKERSFIELD CA 661-397-8606 SYSTEM CONFIGURATION SLOT BOARD TYPE POWER ON RESET CURRENT 1 7SMARTSENSOR BD 507665 508526 2 4 PROBE / G.T. 161197 161672 3 INTERSTITIAL BD 202022 202466 4 INTERSTITIAL BD 202285 202681 5 UNUSED 4771731 4786578 6 UNUSED 4769349 4782046 7 UNUSED 4768731 4784400 8 UNUSED 4767364 4785720 9 STP SENSE BOARD 33179 33260 10 RELAY BOARD 14910 14903 11 RELAY BOARD 14977 15014 12 UNUSED 4771496 4787380 13 UNUSED 4768694 4779349 14 UNUSED 4767239 4788524 15 UNUSED 4767856 4782980 16 UNUSED 4767724 4786126 COMM 1 RS232 SERIAL BD 14932 14970 COMM 2 RS232 SERIAL BD 14999 14992 COMM 3 ELEC DISP INT. 101084 101337 COMM 4 UNUSED 4770481 4789602 COMM 5 UNUSED 4765783 4785136 COMM 6 UNUSED 4767217 4784894 I90200 09-07-17 9:23 AM SOFTWARE REVISION LEVEL VERSION 329.01 SOFTWARE# 346329-100-B CREATED - 09.01.29.15.44 S-MODULE# 330160-004-a SYSTEM FEATURES: PERIODIC IN-TANK TESTS ANNUAL IN-TANK TESTS ISD I11100 09-07-17 9:23 AM FASTRIP 562 MING-CHESTER BAKERSFIELD CA 661-397-8606
PRIORITY ALARM HISTORY ID CATEGORY DESCRIPTION ALARM TYPE STATE DATE TIME L 4 ANNULAR DIESEL ANN FUEL ALARM CLEAR 09-07-17 9:18 AM T 1 TANK UNL OVERFILL ALARM CLEAR 09-05-17 4:40 AM T 1 TANK UNL OVERFILL ALARM ALARM 09-05-17 4:38 AM L 4 ANNULAR DIESEL ANN FUEL ALARM ALARM 09-03-17 5:31 PM L 8 ANNULAR UNL2 ANN SENSOR OUT ALARM CLEAR 08-31-17 12:26 PM L 1 STP SUMP UNL 1 STP SENSOR OUT ALARM CLEAR 08-31-17 12:26 PM L 4 ANNULAR DIESEL ANN SENSOR OUT ALARM CLEAR 08-31-17 12:26 PM L 7 STP SUMP UNL2 SIPON SENSOR OUT ALARM CLEAR 08-31-17 12:26 PM L 3 STP SUMP DIESEL SENSOR OUT ALARM CLEAR 08-31-17 12:26 PM L14 PIPE TRANS SO. SENSOR OUT ALARM CLEAR 08-31-17 12:26 PM L13 PIPE TRANS NO. SENSOR OUT ALARM CLEAR 08-31-17 12:26 PM L12 DISP PAN DISP 7-8 SENSOR OUT ALARM CLEAR 08-31-17 12:26 PM L 2 ANNULAR UNL1 ANN SENSOR OUT ALARM CLEAR 08-31-17 12:26 PM L 6 ANNULAR PNL ANN SENSOR OUT ALARM CLEAR 08-31-17 12:26 PM L 9 DISP PAN DISP 1-2 SENSOR OUT ALARM CLEAR 08-31-17 12:26 PM L11 DISP PAN DISP 5-6 SENSOR OUT ALARM CLEAR 08-31-17 12:26 PM L 5 STP SUMP PNL STP SENSOR OUT ALARM CLEAR 08-31-17 12:26 PM L10 DISP PAN DISP 3-4 SENSOR OUT ALARM CLEAR 08-31-17 12:26 PM L 8 ANNULAR UNL2 ANN SENSOR OUT ALARM ALARM 08-31-17 12:26 PM L 7 STP SUMP UNL2 SIPON SENSOR OUT ALARM ALARM 08-31-17 12:26 PM L 6 ANNULAR PNL ANN SENSOR OUT ALARM ALARM 08-31-17 12:26 PM L 5 STP SUMP PNL STP SENSOR OUT ALARM ALARM 08-31-17 12:26 PM L 4 ANNULAR DIESEL ANN SENSOR OUT ALARM ALARM 08-31-17 12:26 PM L 1 STP SUMP UNL 1 STP SENSOR OUT ALARM ALARM 08-31-17 12:26 PM L 3 STP SUMP DIESEL SENSOR OUT ALARM ALARM 08-31-17 12:26 PM L10 DISP PAN DISP 3-4 SENSOR OUT ALARM ALARM 08-31-17 12:26 PM L14 PIPE TRANS SO. SENSOR OUT ALARM ALARM 08-31-17 12:26 PM L 2 ANNULAR UNL1 ANN SENSOR OUT ALARM ALARM 08-31-17 12:26 PM L 9 DISP PAN DISP 1-2 SENSOR OUT ALARM ALARM 08-31-17 12:26 PM L13 PIPE TRANS NO. SENSOR OUT ALARM ALARM 08-31-17 12:26 PM L12 DISP PAN DISP 7-8 SENSOR OUT ALARM ALARM 08-31-17 12:26 PM L11 DISP PAN DISP 5-6 SENSOR OUT ALARM ALARM 08-31-17 12:26 PM T 3 TANK PNL PROBE OUT CLEAR 08-31-17 11:02 AM T 3 TANK PNL PROBE OUT ALARM 08-31-17 11:02 AM T 3 TANK PNL OVERFILL ALARM CLEAR 08-31-17 11:02 AM T 3 TANK PNL OVERFILL ALARM ALARM 08-31-17 11:00 AM T 2 TANK DIESEL PROBE OUT CLEAR 08-31-17 10:48 AM T 2 TANK DIESEL OVERFILL ALARM CLEAR 08-31-17 10:47 AM T 2 TANK DIESEL PROBE OUT ALARM 08-31-17 10:47 AM T 2 TANK DIESEL OVERFILL ALARM ALARM 08-31-17 10:47 AM T 1 TANK UNL PROBE OUT CLEAR 08-31-17 10:43 AM T 1 TANK UNL OVERFILL ALARM CLEAR 08-31-17 10:42 AM T 1 TANK UNL PROBE OUT ALARM 08-31-17 10:42 AM T 1 TANK UNL OVERFILL ALARM ALARM 08-31-17 10:42 AM T 4 TANK UNL 2 SIPON PROBE OUT CLEAR 08-31-17 10:41 AM T 4 TANK UNL 2 SIPON OVERFILL ALARM CLEAR 08-31-17 10:40 AM T 4 TANK UNL 2 SIPON PROBE OUT ALARM 08-31-17 10:40 AM T 4 TANK UNL 2 SIPON OVERFILL ALARM ALARM 08-31-17 10:39 AM L 1 STP SUMP UNL 1 STP FUEL ALARM CLEAR 08-31-17 10:37 AM L 1 STP SUMP UNL 1 STP FUEL ALARM ALARM 08-31-17 10:36 AM I11200 09-07-17 9:23 AM FASTRIP 562 MING-CHESTER BAKERSFIELD CA 661-397-8606
NON-PRIORITY ALARM HISTORY ID CATEGORY DESCRIPTION ALARM TYPE STATE DATE TIME SYSTEM PRINTER ERROR CLEAR 09-06-17 9:15 AM SYSTEM PRINTER ERROR ALARM 09-06-17 9:15 AM T 2 TANK DIESEL DELIVERY NEEDED ALARM 09-06-17 12:53 AM T 3 TANK PNL DELIVERY NEEDED CLEAR 08-31-17 11:03 AM T 3 TANK PNL DELIVERY NEEDED ALARM 08-31-17 11:03 AM T 3 TANK PNL INVALID FUEL LEVEL CLEAR 08-31-17 11:03 AM T 3 TANK PNL INVALID FUEL LEVEL ALARM 08-31-17 11:02 AM T 2 TANK DIESEL LOW TEMP WARNING CLEAR 08-31-17 10:48 AM T 2 TANK DIESEL DELIVERY NEEDED CLEAR 08-31-17 10:48 AM T 2 TANK DIESEL LOW TEMP WARNING ALARM 08-31-17 10:48 AM T 2 TANK DIESEL DELIVERY NEEDED ALARM 08-31-17 10:48 AM T 2 TANK DIESEL DELIVERY NEEDED CLEAR 08-31-17 9:28 AM T 2 TANK DIESEL DELIVERY NEEDED ALARM 08-31-17 9:26 AM h 4 OTHER FP4: BLEND3 DEGRD COLLECT WARN CLEAR 08-10-17 4:47 PM h 4 OTHER FP4: BLEND3 DEGRD COLLECT WARN ALARM 08-10-17 10:02 AM h 4 OTHER FP4: BLEND3 DEGRD COLLECT WARN CLEAR 08-09-17 10:00 AM h 4 OTHER FP4: BLEND3 DEGRD COLLECT WARN ALARM 08-06-17 10:02 AM T 2 TANK DIESEL DELIVERY NEEDED CLEAR 07-27-17 3:34 AM T 2 TANK DIESEL DELIVERY NEEDED ALARM 07-25-17 2:54 PM T 2 TANK DIESEL DELIVERY NEEDED CLEAR 07-18-17 5:04 AM T 2 TANK DIESEL DELIVERY NEEDED ALARM 07-17-17 11:52 PM SYSTEM PRINTER ERROR CLEAR 07-10-17 8:13 AM SYSTEM PAPER OUT CLEAR 07-10-17 8:13 AM SYSTEM PAPER OUT ALARM 07-10-17 8:13 AM SYSTEM PAPER OUT CLEAR 07-10-17 8:13 AM SYSTEM PAPER OUT ALARM 07-10-17 8:13 AM SYSTEM PAPER OUT CLEAR 07-10-17 8:13 AM SYSTEM PAPER OUT ALARM 07-10-17 8:13 AM SYSTEM PAPER OUT CLEAR 07-10-17 8:13 AM SYSTEM PAPER OUT ALARM 07-10-17 8:13 AM SYSTEM PAPER OUT CLEAR 07-10-17 8:13 AM SYSTEM PAPER OUT ALARM 07-10-17 8:13 AM SYSTEM PAPER OUT CLEAR 07-10-17 8:13 AM SYSTEM PRINTER ERROR ALARM 07-10-17 8:13 AM SYSTEM PRINTER ERROR CLEAR 07-10-17 8:13 AM SYSTEM PRINTER ERROR ALARM 07-10-17 8:12 AM SYSTEM PRINTER ERROR CLEAR 07-09-17 7:12 PM SYSTEM PRINTER ERROR ALARM 07-09-17 7:12 PM SYSTEM PRINTER ERROR CLEAR 07-09-17 7:12 PM SYSTEM PRINTER ERROR ALARM 07-09-17 7:11 PM SYSTEM PRINTER ERROR CLEAR 07-09-17 7:11 PM SYSTEM PAPER OUT ALARM 07-09-17 7:07 PM SYSTEM PAPER OUT CLEAR 07-09-17 7:07 PM SYSTEM PRINTER ERROR ALARM 07-09-17 7:07 PM SYSTEM PAPER OUT ALARM 07-09-17 7:07 PM SYSTEM PRINTER ERROR CLEAR 07-09-17 7:06 PM SYSTEM PAPER OUT CLEAR 07-09-17 7:06 PM SYSTEM PAPER OUT ALARM 07-09-17 7:06 PM SYSTEM PAPER OUT CLEAR 07-09-17 7:06 PM SYSTEM PRINTER ERROR ALARM 07-09-17 7:06 PM I20600 09-07-17 9:23 AM FASTRIP 562 MING-CHESTER BAKERSFIELD CA 661-397-8606
TANK ALARM HISTORY TANK 1 UNL OVERFILL ALARM 09-05-17 4:38 AM 08-31-17 10:42 AM 07-24-17 11:07 AM SUDDEN LOSS ALARM 08-31-17 9:28 AM 08-07-17 2:58 AM 08-06-17 2:33 AM PROBE OUT 08-31-17 10:42 AM 08-31-17 9:28 AM 09-09-16 9:42 AM DELIVERY NEEDED 02-12-16 9:14 AM 10-24-15 2:23 PM LOW TEMP WARNING 05-20-16 5:37 PM TANK 2 DIESEL OVERFILL ALARM 08-31-17 10:47 AM 09-09-16 9:45 AM 08-29-16 11:07 AM PROBE OUT 08-31-17 10:47 AM 08-31-17 9:27 AM 09-09-16 9:45 AM DELIVERY NEEDED 09-06-17 12:53 AM 08-31-17 10:48 AM 08-31-17 9:26 AM LOW TEMP WARNING 08-31-17 10:48 AM 09-09-16 9:46 AM 08-29-16 11:08 AM TANK 3 PNL OVERFILL ALARM 08-31-17 11:00 AM 09-09-16 9:48 AM 08-29-16 10:59 AM SUDDEN LOSS ALARM 08-31-17 9:25 AM 09-09-16 9:32 AM 09-08-15 10:17 AM INVALID FUEL LEVEL 08-31-17 11:02 AM 02-14-16 6:26 AM 01-04-16 7:25 PM PROBE OUT 08-31-17 11:02 AM 08-31-17 9:25 AM 09-12-16 8:25 AM DELIVERY NEEDED 08-31-17 11:03 AM 09-09-16 9:32 AM 08-29-16 11:01 AM LOW TEMP WARNING 09-09-16 9:34 AM
TANK 4 UNL 2 SIPON OVERFILL ALARM 08-31-17 10:39 AM 05-29-17 3:13 PM 05-29-17 3:01 PM SUDDEN LOSS ALARM 09-09-16 9:34 AM 08-29-16 11:17 AM 09-08-15 10:38 AM PROBE OUT 08-31-17 10:40 AM 08-31-17 9:29 AM 09-09-16 9:40 AM DELIVERY NEEDED 02-12-16 10:19 AM 10-24-15 3:41 PM I38200 09-07-17 9:23 AM I30200 09-07-17 9:23 AM FASTRIP 562 MING-CHESTER BAKERSFIELD CA 661-397-8606 LIQUID ALARM HISTORY REPORT SENSOR LOCATION 1 UNL 1 STP 08-31-17 12:26 PM SENSOR OUT ALARM 08-31-17 10:36 AM FUEL ALARM 08-31-17 10:34 AM SENSOR OUT ALARM 2 UNL1 ANN 08-31-17 12:26 PM SENSOR OUT ALARM 08-31-17 10:26 AM FUEL ALARM 09-09-16 9:52 AM SENSOR OUT ALARM 3 DIESEL 08-31-17 12:26 PM SENSOR OUT ALARM 08-31-17 10:16 AM FUEL ALARM 08-31-17 9:30 AM FUEL ALARM 4 DIESEL ANN 09-03-17 5:31 PM FUEL ALARM 08-31-17 12:26 PM SENSOR OUT ALARM 08-31-17 10:25 AM FUEL ALARM 5 PNL STP 08-31-17 12:26 PM SENSOR OUT ALARM 08-31-17 10:19 AM FUEL ALARM 09-09-16 9:52 AM SENSOR OUT ALARM 6 PNL ANN 08-31-17 12:26 PM SENSOR OUT ALARM 08-31-17 10:25 AM FUEL ALARM 09-09-16 9:52 AM SENSOR OUT ALARM 7 UNL2 SIPON 08-31-17 12:26 PM SENSOR OUT ALARM
08-31-17 10:15 AM FUEL ALARM 02-22-17 7:42 AM FUEL ALARM 8 UNL2 ANN 08-31-17 12:26 PM SENSOR OUT ALARM 08-31-17 10:26 AM FUEL ALARM 09-09-16 9:52 AM SENSOR OUT ALARM 9 DISP 1-2 08-31-17 12:26 PM SENSOR OUT ALARM 08-31-17 10:21 AM FUEL ALARM 09-09-16 9:52 AM SENSOR OUT ALARM 10 DISP 3-4 08-31-17 12:26 PM SENSOR OUT ALARM 08-31-17 10:20 AM FUEL ALARM 09-09-16 9:52 AM SENSOR OUT ALARM 11 DISP 5-6 08-31-17 12:26 PM SENSOR OUT ALARM 08-31-17 10:22 AM FUEL ALARM 09-09-16 9:52 AM SENSOR OUT ALARM 12 DISP 7-8 08-31-17 12:26 PM SENSOR OUT ALARM 08-31-17 10:24 AM FUEL ALARM 09-09-16 9:52 AM SENSOR OUT ALARM 13 TRANS NO. 08-31-17 12:26 PM SENSOR OUT ALARM 08-31-17 10:21 AM FUEL ALARM 01-23-17 12:46 PM FUEL ALARM 14 TRANS SO. 08-31-17 12:26 PM SENSOR OUT ALARM 08-31-17 10:23 AM FUEL ALARM 06-23-17 10:26 PM FUEL ALARM I31600 09-07-17 9:23 AM FASTRIP 562 MING-CHESTER BAKERSFIELD CA 661-397-8606 SMART SENSOR ALARM HISTORY REPORT SENSOR LOCATION 1 V.P. SENSOR 3-4 2 F.M. 1-2 06-25-15 4:13 PM COMMUNICATION ALARM 3 F.M. 3-4 06-25-15 4:13 PM COMMUNICATION ALARM 4 F.M. 5-6 06-25-15 4:13 PM COMMUNICATION ALARM 5 F.M. 7-8 03-20-17 9:13 AM COMMUNICATION ALARM 06-25-15 4:13 PM COMMUNICATION ALARM I40200 09-07-17 9:23 AM I40300
09-07-17 9:23 AM I34200 09-07-17 9:23 AM I34700 09-07-17 9:23 AM IV0100 09-07-17 9:23 AM FASTRIP 562 MING-CHESTER BAKERSFIELD CA 661-397-8606 ISD ALARM STATUS REPORT EVR TYPE: VACUUM ASSIST ISD TYPE: 01.02 VAPOR PROCESSOR TYPE: NONE OVERALL STATUS :PASS EVR VAPOR COLLECTION :PASS EVR VAPOR CONTAINMENT :PASS ISD MONITOR UP-TIME :100% STAGE I TRANSFERS: 0 of 0 NOTEST EVR/ISD PASS TIME :100% WARNING ALARMS DATE TIME DESCRIPTION READING VALUE 17-08-10 10:02:09 A/L RATIO DEGRADATION FP 4 BLEND3 0.80 17-08-08 10:02:09 A/L RATIO DEGRADATION FP 4 BLEND3 0.79 17-08-07 10:02:04 A/L RATIO DEGRADATION FP 4 BLEND3 0.80 17-08-06 10:02:18 A/L RATIO DEGRADATION FP 4 BLEND3 0.81 17-06-30 10:01:43 A/L RATIO GROSS BLOCKAGE FP 3 BLEND3 BLKD 17-06-28 10:02:48 VAPOR CONTAINMENT LEAKAGE CFH@2 INCHES WC 9.16 17-06-27 10:02:33 VAPOR CONTAINMENT LEAKAGE CFH@2 INCHES WC 8.56 17-06-07 10:01:09 A/L RATIO DEGRADATION FP 4 BLEND3 0.80 17-06-06 10:01:09 VAPOR CONTAINMENT LEAKAGE CFH@2 INCHES WC 21.25 17-06-05 10:01:09 A/L RATIO DEGRADATION FP 4 BLEND3 0.80 FAILURE ALARMS DATE TIME DESCRIPTION READING VALUE 17-04-23 10:02:39 VAPOR CONTAINMENT LEAKAGE CFH@2 INCHES WC 18.01 17-04-09 10:01:09 A/L RATIO GROSS BLOCKAGE FP 7 BLEND3 BLKD 15-06-02 10:02:05 VAPOR CONTAINMENT LEAKAGE CFH@2 INCHES WC 9.17 13-08-14 10:02:10 CONTAINMENT GROSS OVER PRESSURE WEEKLY 95% 3.13 11-01-03 10:01:19 VAPOR CONTAINMENT LEAKAGE CFH@2 INCHES WC 88.77 11-01-02 10:01:22 VAPOR CONTAINMENT LEAKAGE CFH@2 INCHES WC 90.19 11-01-01 10:01:28 VAPOR CONTAINMENT LEAKAGE CFH@2 INCHES WC 89.64 10-12-31 10:01:34 VAPOR CONTAINMENT LEAKAGE CFH@2 INCHES WC 55.83 10-11-12 10:01:46 CONTAINMENT GROSS OVER PRESSURE WEEKLY 95% 3.07 09-04-08 10:01:23 A/L RATIO GROSS BLOCKAGE FP 2 BLEND3 BLKD SHUTDOWN & MISCELLANEOUS EVENTS DATE TIME DESCRIPTION ACTION/NAME 17-08-30 10:02:45 READINESS ISD:PP EVR:PP ISD & EVR READY 17-08-30 04:39:07 READINESS ISD:PP EVR:NN EVR READINESS PENDING
17-08-30 04:39:07 ISD STARTUP 17-08-30 04:38:56 ISD SHUTDOWN 17-08-10 16:47:37 COLLECTION TEST HH04 GRADE TEST MANUALLY CLEARED 17-06-30 12:29:44 COLLECTION TEST HH03 GRADE TEST MANUALLY CLEARED 17-06-30 12:20:56 COLLECTION TEST HH03 GRADE TEST MANUALLY CLEARED 17-06-28 10:20:15 CONTAINMENT VAPOR LEAKAGE TEST MANUALLY CLEARED 17-06-28 10:20:08 CONTAINMENT GROSS & DEGRD TEST MANUALLY CLEARED 17-06-07 10:46:07 COLLECTION TEST HH04 GRADE TEST MANUALLY CLEARED
Jaco 5562 Fastrip Alarm History After
Responses Received: I10200 09-07-17 11:07 AM FASTRIP 562 MING-CHESTER BAKERSFIELD CA 661-397-8606 SYSTEM CONFIGURATION SLOT BOARD TYPE POWER ON RESET CURRENT 1 7SMARTSENSOR BD 507665 507873 2 4 PROBE / G.T. 161197 161330 3 INTERSTITIAL BD 202022 202368 4 INTERSTITIAL BD 202285 202344 5 UNUSED 4771731 4779227 6 UNUSED 4769349 4775014 7 UNUSED 4768731 4775191 8 UNUSED 4767364 4774992 9 STP SENSE BOARD 33179 33246 10 RELAY BOARD 14910 14888 11 RELAY BOARD 14977 14999 12 UNUSED 4771496 4781330 13 UNUSED 4768694 4776014 14 UNUSED 4767239 4777845 15 UNUSED 4767856 4777580 16 UNUSED 4767724 4778705 COMM 1 RS232 SERIAL BD 14932 14932 COMM 2 RS232 SERIAL BD 14999 14977 COMM 3 ELEC DISP INT. 101084 101242 COMM 4 UNUSED 4770481 4778418 COMM 5 UNUSED 4765783 4774757 COMM 6 UNUSED 4767217 4782278 I90200 09-07-17 11:07 AM SOFTWARE REVISION LEVEL VERSION 329.01 SOFTWARE# 346329-100-B CREATED - 09.01.29.15.44 S-MODULE# 330160-004-a SYSTEM FEATURES: PERIODIC IN-TANK TESTS ANNUAL IN-TANK TESTS ISD I11100 09-07-17 11:07 AM FASTRIP 562 MING-CHESTER BAKERSFIELD CA 661-397-8606
PRIORITY ALARM HISTORY ID CATEGORY DESCRIPTION ALARM TYPE STATE DATE TIME L 6 ANNULAR PNL ANN SENSOR OUT ALARM CLEAR 09-07-17 11:05 AM L 3 STP SUMP DIESEL SENSOR OUT ALARM CLEAR 09-07-17 11:05 AM L 4 ANNULAR DIESEL ANN SENSOR OUT ALARM CLEAR 09-07-17 11:05 AM L 2 ANNULAR UNL1 ANN SENSOR OUT ALARM CLEAR 09-07-17 11:05 AM L 8 ANNULAR UNL2 ANN SENSOR OUT ALARM CLEAR 09-07-17 11:05 AM L 7 STP SUMP UNL2 SIPON SENSOR OUT ALARM CLEAR 09-07-17 11:05 AM L 5 STP SUMP PNL STP SENSOR OUT ALARM CLEAR 09-07-17 11:05 AM L 1 STP SUMP UNL 1 STP SENSOR OUT ALARM CLEAR 09-07-17 11:05 AM L10 DISP PAN DISP 3-4 SENSOR OUT ALARM CLEAR 09-07-17 11:05 AM L14 PIPE TRANS SO. SENSOR OUT ALARM CLEAR 09-07-17 11:05 AM L12 DISP PAN DISP 7-8 SENSOR OUT ALARM CLEAR 09-07-17 11:05 AM L11 DISP PAN DISP 5-6 SENSOR OUT ALARM CLEAR 09-07-17 11:05 AM L 9 DISP PAN DISP 1-2 SENSOR OUT ALARM CLEAR 09-07-17 11:05 AM L13 PIPE TRANS NO. SENSOR OUT ALARM CLEAR 09-07-17 11:05 AM L14 PIPE TRANS SO. SENSOR OUT ALARM ALARM 09-07-17 11:05 AM L12 DISP PAN DISP 7-8 SENSOR OUT ALARM ALARM 09-07-17 11:05 AM L11 DISP PAN DISP 5-6 SENSOR OUT ALARM ALARM 09-07-17 11:05 AM L 4 ANNULAR DIESEL ANN SENSOR OUT ALARM ALARM 09-07-17 11:05 AM L 3 STP SUMP DIESEL SENSOR OUT ALARM ALARM 09-07-17 11:05 AM L10 DISP PAN DISP 3-4 SENSOR OUT ALARM ALARM 09-07-17 11:05 AM L 2 ANNULAR UNL1 ANN SENSOR OUT ALARM ALARM 09-07-17 11:05 AM L13 PIPE TRANS NO. SENSOR OUT ALARM ALARM 09-07-17 11:05 AM L 8 ANNULAR UNL2 ANN SENSOR OUT ALARM ALARM 09-07-17 11:05 AM L 7 STP SUMP UNL2 SIPON SENSOR OUT ALARM ALARM 09-07-17 11:05 AM L 5 STP SUMP PNL STP SENSOR OUT ALARM ALARM 09-07-17 11:05 AM L 6 ANNULAR PNL ANN SENSOR OUT ALARM ALARM 09-07-17 11:04 AM L 9 DISP PAN DISP 1-2 SENSOR OUT ALARM ALARM 09-07-17 11:04 AM L 1 STP SUMP UNL 1 STP SENSOR OUT ALARM ALARM 09-07-17 11:04 AM T 4 TANK UNL 2 SIPON PROBE OUT CLEAR 09-07-17 9:59 AM T 4 TANK UNL 2 SIPON OVERFILL ALARM CLEAR 09-07-17 9:59 AM T 4 TANK UNL 2 SIPON PROBE OUT ALARM 09-07-17 9:59 AM T 4 TANK UNL 2 SIPON OVERFILL ALARM ALARM 09-07-17 9:58 AM T 1 TANK UNL PROBE OUT CLEAR 09-07-17 9:57 AM T 1 TANK UNL OVERFILL ALARM CLEAR 09-07-17 9:56 AM T 1 TANK UNL PROBE OUT ALARM 09-07-17 9:56 AM T 1 TANK UNL OVERFILL ALARM ALARM 09-07-17 9:56 AM T 2 TANK DIESEL PROBE OUT CLEAR 09-07-17 9:54 AM T 2 TANK DIESEL OVERFILL ALARM CLEAR 09-07-17 9:54 AM T 2 TANK DIESEL PROBE OUT ALARM 09-07-17 9:54 AM T 2 TANK DIESEL OVERFILL ALARM ALARM 09-07-17 9:53 AM T 3 TANK PNL PROBE OUT CLEAR 09-07-17 9:49 AM T 3 TANK PNL OVERFILL ALARM CLEAR 09-07-17 9:49 AM T 3 TANK PNL PROBE OUT ALARM 09-07-17 9:49 AM T 3 TANK PNL OVERFILL ALARM ALARM 09-07-17 9:48 AM T 3 TANK PNL SUDDEN LOSS ALARM CLEAR 09-07-17 9:46 AM T 3 TANK PNL PROBE OUT CLEAR 09-07-17 9:44 AM T 3 TANK PNL PROBE OUT ALARM 09-07-17 9:43 AM T 3 TANK PNL SUDDEN LOSS ALARM ALARM 09-07-17 9:43 AM T 2 TANK DIESEL PROBE OUT CLEAR 09-07-17 9:43 AM T 2 TANK DIESEL PROBE OUT ALARM 09-07-17 9:42 AM I11200 09-07-17 11:07 AM FASTRIP 562 MING-CHESTER BAKERSFIELD CA 661-397-8606
NON-PRIORITY ALARM HISTORY ID CATEGORY DESCRIPTION ALARM TYPE STATE DATE TIME T 2 TANK DIESEL DELIVERY NEEDED ALARM 09-07-17 9:54 AM T 3 TANK PNL LOW TEMP WARNING CLEAR 09-07-17 9:50 AM T 3 TANK PNL LOW TEMP WARNING ALARM 09-07-17 9:50 AM T 2 TANK DIESEL DELIVERY NEEDED CLEAR 09-07-17 9:43 AM SYSTEM PRINTER ERROR CLEAR 09-06-17 9:15 AM SYSTEM PRINTER ERROR ALARM 09-06-17 9:15 AM T 2 TANK DIESEL DELIVERY NEEDED ALARM 09-06-17 12:53 AM T 3 TANK PNL DELIVERY NEEDED CLEAR 08-31-17 11:03 AM T 3 TANK PNL DELIVERY NEEDED ALARM 08-31-17 11:03 AM T 3 TANK PNL INVALID FUEL LEVEL CLEAR 08-31-17 11:03 AM T 3 TANK PNL INVALID FUEL LEVEL ALARM 08-31-17 11:02 AM T 2 TANK DIESEL LOW TEMP WARNING CLEAR 08-31-17 10:48 AM T 2 TANK DIESEL DELIVERY NEEDED CLEAR 08-31-17 10:48 AM T 2 TANK DIESEL LOW TEMP WARNING ALARM 08-31-17 10:48 AM T 2 TANK DIESEL DELIVERY NEEDED ALARM 08-31-17 10:48 AM T 2 TANK DIESEL DELIVERY NEEDED CLEAR 08-31-17 9:28 AM T 2 TANK DIESEL DELIVERY NEEDED ALARM 08-31-17 9:26 AM h 4 OTHER FP4: BLEND3 DEGRD COLLECT WARN CLEAR 08-10-17 4:47 PM h 4 OTHER FP4: BLEND3 DEGRD COLLECT WARN ALARM 08-10-17 10:02 AM h 4 OTHER FP4: BLEND3 DEGRD COLLECT WARN CLEAR 08-09-17 10:00 AM h 4 OTHER FP4: BLEND3 DEGRD COLLECT WARN ALARM 08-06-17 10:02 AM T 2 TANK DIESEL DELIVERY NEEDED CLEAR 07-27-17 3:34 AM T 2 TANK DIESEL DELIVERY NEEDED ALARM 07-25-17 2:54 PM T 2 TANK DIESEL DELIVERY NEEDED CLEAR 07-18-17 5:04 AM T 2 TANK DIESEL DELIVERY NEEDED ALARM 07-17-17 11:52 PM SYSTEM PRINTER ERROR CLEAR 07-10-17 8:13 AM SYSTEM PAPER OUT CLEAR 07-10-17 8:13 AM SYSTEM PAPER OUT ALARM 07-10-17 8:13 AM SYSTEM PAPER OUT CLEAR 07-10-17 8:13 AM SYSTEM PAPER OUT ALARM 07-10-17 8:13 AM SYSTEM PAPER OUT CLEAR 07-10-17 8:13 AM SYSTEM PAPER OUT ALARM 07-10-17 8:13 AM SYSTEM PAPER OUT CLEAR 07-10-17 8:13 AM SYSTEM PAPER OUT ALARM 07-10-17 8:13 AM SYSTEM PAPER OUT CLEAR 07-10-17 8:13 AM SYSTEM PAPER OUT ALARM 07-10-17 8:13 AM SYSTEM PAPER OUT CLEAR 07-10-17 8:13 AM SYSTEM PRINTER ERROR ALARM 07-10-17 8:13 AM SYSTEM PRINTER ERROR CLEAR 07-10-17 8:13 AM SYSTEM PRINTER ERROR ALARM 07-10-17 8:12 AM SYSTEM PRINTER ERROR CLEAR 07-09-17 7:12 PM SYSTEM PRINTER ERROR ALARM 07-09-17 7:12 PM SYSTEM PRINTER ERROR CLEAR 07-09-17 7:12 PM SYSTEM PRINTER ERROR ALARM 07-09-17 7:11 PM SYSTEM PRINTER ERROR CLEAR 07-09-17 7:11 PM SYSTEM PAPER OUT ALARM 07-09-17 7:07 PM SYSTEM PAPER OUT CLEAR 07-09-17 7:07 PM SYSTEM PRINTER ERROR ALARM 07-09-17 7:07 PM SYSTEM PAPER OUT ALARM 07-09-17 7:07 PM SYSTEM PRINTER ERROR CLEAR 07-09-17 7:06 PM I20600 09-07-17 11:07 AM FASTRIP 562 MING-CHESTER BAKERSFIELD CA 661-397-8606
TANK ALARM HISTORY TANK 1 UNL OVERFILL ALARM 09-07-17 9:56 AM 09-05-17 4:38 AM 08-31-17 10:42 AM SUDDEN LOSS ALARM 08-31-17 9:28 AM 08-07-17 2:58 AM 08-06-17 2:33 AM PROBE OUT 09-07-17 9:56 AM 09-07-17 9:41 AM 08-31-17 10:42 AM DELIVERY NEEDED 02-12-16 9:14 AM 10-24-15 2:23 PM LOW TEMP WARNING 05-20-16 5:37 PM TANK 2 DIESEL OVERFILL ALARM 09-07-17 9:53 AM 08-31-17 10:47 AM 09-09-16 9:45 AM PROBE OUT 09-07-17 9:54 AM 09-07-17 9:42 AM 08-31-17 10:47 AM DELIVERY NEEDED 09-07-17 9:54 AM 09-06-17 12:53 AM 08-31-17 10:48 AM LOW TEMP WARNING 08-31-17 10:48 AM 09-09-16 9:46 AM 08-29-16 11:08 AM TANK 3 PNL OVERFILL ALARM 09-07-17 9:48 AM 08-31-17 11:00 AM 09-09-16 9:48 AM SUDDEN LOSS ALARM 09-07-17 9:43 AM 08-31-17 9:25 AM 09-09-16 9:32 AM INVALID FUEL LEVEL 08-31-17 11:02 AM 02-14-16 6:26 AM 01-04-16 7:25 PM PROBE OUT 09-07-17 9:49 AM 09-07-17 9:43 AM 08-31-17 11:02 AM DELIVERY NEEDED 08-31-17 11:03 AM 09-09-16 9:32 AM 08-29-16 11:01 AM LOW TEMP WARNING 09-07-17 9:50 AM
09-09-16 9:34 AM TANK 4 UNL 2 SIPON OVERFILL ALARM 09-07-17 9:58 AM 08-31-17 10:39 AM 05-29-17 3:13 PM SUDDEN LOSS ALARM 09-09-16 9:34 AM 08-29-16 11:17 AM 09-08-15 10:38 AM PROBE OUT 09-07-17 9:59 AM 09-07-17 9:40 AM 08-31-17 10:40 AM DELIVERY NEEDED 02-12-16 10:19 AM 10-24-15 3:41 PM I38200 09-07-17 11:07 AM I30200 09-07-17 11:07 AM FASTRIP 562 MING-CHESTER BAKERSFIELD CA 661-397-8606 LIQUID ALARM HISTORY REPORT SENSOR LOCATION 1 UNL 1 STP 09-07-17 11:04 AM SENSOR OUT ALARM 09-07-17 9:29 AM FUEL ALARM 08-31-17 12:26 PM SENSOR OUT ALARM 2 UNL1 ANN 09-07-17 11:05 AM SENSOR OUT ALARM 09-07-17 9:31 AM FUEL ALARM 08-31-17 12:26 PM SENSOR OUT ALARM 3 DIESEL 09-07-17 11:05 AM SENSOR OUT ALARM 09-07-17 9:30 AM FUEL ALARM 08-31-17 12:26 PM SENSOR OUT ALARM 4 DIESEL ANN 09-07-17 11:05 AM SENSOR OUT ALARM 09-07-17 9:32 AM FUEL ALARM 09-03-17 5:31 PM FUEL ALARM 5 PNL STP 09-07-17 11:05 AM SENSOR OUT ALARM 09-07-17 9:31 AM FUEL ALARM 08-31-17 12:26 PM SENSOR OUT ALARM 6 PNL ANN 09-07-17 11:04 AM SENSOR OUT ALARM 09-07-17 9:33 AM FUEL ALARM 08-31-17 12:26 PM SENSOR OUT ALARM 7 UNL2 SIPON
09-07-17 11:05 AM SENSOR OUT ALARM 09-07-17 9:28 AM FUEL ALARM 08-31-17 12:26 PM SENSOR OUT ALARM 8 UNL2 ANN 09-07-17 11:05 AM SENSOR OUT ALARM 09-07-17 9:31 AM FUEL ALARM 08-31-17 12:26 PM SENSOR OUT ALARM 9 DISP 1-2 09-07-17 11:04 AM SENSOR OUT ALARM 09-07-17 9:36 AM FUEL ALARM 08-31-17 12:26 PM SENSOR OUT ALARM 10 DISP 3-4 09-07-17 11:05 AM SENSOR OUT ALARM 09-07-17 9:38 AM FUEL ALARM 08-31-17 12:26 PM SENSOR OUT ALARM 11 DISP 5-6 09-07-17 11:05 AM SENSOR OUT ALARM 09-07-17 9:35 AM FUEL ALARM 08-31-17 12:26 PM SENSOR OUT ALARM 12 DISP 7-8 09-07-17 11:05 AM SENSOR OUT ALARM 09-07-17 9:37 AM FUEL ALARM 08-31-17 12:26 PM SENSOR OUT ALARM 13 TRANS NO. 09-07-17 11:05 AM SENSOR OUT ALARM 09-07-17 9:33 AM FUEL ALARM 08-31-17 12:26 PM SENSOR OUT ALARM 14 TRANS SO. 09-07-17 11:05 AM SENSOR OUT ALARM 09-07-17 9:34 AM FUEL ALARM 08-31-17 12:26 PM SENSOR OUT ALARM I31600 09-07-17 11:07 AM FASTRIP 562 MING-CHESTER BAKERSFIELD CA 661-397-8606 SMART SENSOR ALARM HISTORY REPORT SENSOR LOCATION 1 V.P. SENSOR 3-4 2 F.M. 1-2 06-25-15 4:13 PM COMMUNICATION ALARM 3 F.M. 3-4 06-25-15 4:13 PM COMMUNICATION ALARM 4 F.M. 5-6 06-25-15 4:13 PM COMMUNICATION ALARM 5 F.M. 7-8 03-20-17 9:13 AM COMMUNICATION ALARM 06-25-15 4:13 PM COMMUNICATION ALARM I40200 09-07-17 11:07 AM
I40300 09-07-17 11:07 AM I34200 09-07-17 11:07 AM I34700 09-07-17 11:07 AM IV0100 09-07-17 11:07 AM FASTRIP 562 MING-CHESTER BAKERSFIELD CA 661-397-8606 ISD ALARM STATUS REPORT EVR TYPE: VACUUM ASSIST ISD TYPE: 01.02 VAPOR PROCESSOR TYPE: NONE OVERALL STATUS :PASS EVR VAPOR COLLECTION :PASS EVR VAPOR CONTAINMENT :PASS ISD MONITOR UP-TIME :100% STAGE I TRANSFERS: 5 of 5 PASS EVR/ISD PASS TIME :100% WARNING ALARMS DATE TIME DESCRIPTION READING VALUE 17-08-10 10:02:09 A/L RATIO DEGRADATION FP 4 BLEND3 0.80 17-08-08 10:02:09 A/L RATIO DEGRADATION FP 4 BLEND3 0.79 17-08-07 10:02:04 A/L RATIO DEGRADATION FP 4 BLEND3 0.80 17-08-06 10:02:18 A/L RATIO DEGRADATION FP 4 BLEND3 0.81 17-06-30 10:01:43 A/L RATIO GROSS BLOCKAGE FP 3 BLEND3 BLKD 17-06-28 10:02:48 VAPOR CONTAINMENT LEAKAGE CFH@2 INCHES WC 9.16 17-06-27 10:02:33 VAPOR CONTAINMENT LEAKAGE CFH@2 INCHES WC 8.56 17-06-07 10:01:09 A/L RATIO DEGRADATION FP 4 BLEND3 0.80 17-06-06 10:01:09 VAPOR CONTAINMENT LEAKAGE CFH@2 INCHES WC 21.25 17-06-05 10:01:09 A/L RATIO DEGRADATION FP 4 BLEND3 0.80 FAILURE ALARMS DATE TIME DESCRIPTION READING VALUE 17-04-23 10:02:39 VAPOR CONTAINMENT LEAKAGE CFH@2 INCHES WC 18.01 17-04-09 10:01:09 A/L RATIO GROSS BLOCKAGE FP 7 BLEND3 BLKD 15-06-02 10:02:05 VAPOR CONTAINMENT LEAKAGE CFH@2 INCHES WC 9.17 13-08-14 10:02:10 CONTAINMENT GROSS OVER PRESSURE WEEKLY 95% 3.13 11-01-03 10:01:19 VAPOR CONTAINMENT LEAKAGE CFH@2 INCHES WC 88.77 11-01-02 10:01:22 VAPOR CONTAINMENT LEAKAGE CFH@2 INCHES WC 90.19 11-01-01 10:01:28 VAPOR CONTAINMENT LEAKAGE CFH@2 INCHES WC 89.64 10-12-31 10:01:34 VAPOR CONTAINMENT LEAKAGE CFH@2 INCHES WC 55.83 10-11-12 10:01:46 CONTAINMENT GROSS OVER PRESSURE WEEKLY 95% 3.07 09-04-08 10:01:23 A/L RATIO GROSS BLOCKAGE FP 2 BLEND3 BLKD SHUTDOWN & MISCELLANEOUS EVENTS DATE TIME DESCRIPTION ACTION/NAME 17-09-07 11:04:40 READINESS ISD:PP EVR:NN EVR READINESS PENDING
17-09-07 11:04:40 ISD STARTUP 17-09-07 11:04:30 ISD SHUTDOWN 17-08-30 10:02:45 READINESS ISD:PP EVR:PP ISD & EVR READY 17-08-30 04:39:07 READINESS ISD:PP EVR:NN EVR READINESS PENDING 17-08-30 04:39:07 ISD STARTUP 17-08-30 04:38:56 ISD SHUTDOWN 17-08-10 16:47:37 COLLECTION TEST HH04 GRADE TEST MANUALLY CLEARED 17-06-30 12:29:44 COLLECTION TEST HH03 GRADE TEST MANUALLY CLEARED 17-06-30 12:20:56 COLLECTION TEST HH03 GRADE TEST MANUALLY CLEARED
SWRCB, January 2006
Spill Bucket Testing Report Form
This form is intended for use by contractors performing annual testing of UST spill containment structures. The completed form and
printouts from tests (if applicable), should be provided to the facility owner/operator forsubmittal to the local regulatory agency.
1.FACILITY INFORMATION
Facility Name:Date of Testing:
Facility Address:
Facility Contact:Phone:
Date Local Agency Was Notified of Testing :
Name of Local Agency Inspector (if present during testing):
2.TESTING CONTRACTOR INFORMATION
Company Name:Confidence UST Services, Inc.
Technician Conducting Test:
Credentials1:CSLB Contractor ICC Service Tech. SWRCB Tank Tester Other (Specify)
License Number(s):CSLB#804904 ICC#
3.SPILL BUCKET TESTING INFORMATION
Test Method Used:Hydrostatic Vacuum Other
Test Equipment Used:Lake TestEquipment Resolution:0.0625”
Identify Spill Bucket (By Tank
Number, Stored Product, etc.)
1234
Bucket Installation Type: Direct Bury
Contained in Sump
Direct Bury
Contained in Sump
Direct Bury
Contained in Sump
Direct Bury
Contained in Sump
Bucket Diameter:
Bucket Depth:
Wait time between applying
vacuum/water and start of test:
Test Start Time (TI):
Initial Reading (RI):
Test End Time (TF):
Final Reading (RF):
Test Duration (TF – TI):
Change in Reading (RF -RI):
Pass/Fail Threshold or
Criteria:
Test Result: Pass Fail Pass Fail Pass Fail Pass Fail
Comments –(include information on repairs made prior to testing, and recommended follow-up for failed tests)
CERTIFICATION OF TECHNICIAN RESPONSIBLE FOR CONDUCTING THIS TESTING
I hereby certify that all the information contained in this report is true, accurate, and in full compliance with legal requirements.
Technician’s Signature:________________________________________________ Date:_________
1 State laws and regulations do not currently require testing to be performed by a qualified contractor. However, local requirements
may be more stringent.
#5562Fastrip#6 09/07/2017
1640SouthChesterAvenue Bakersfield,CA93304
OmeroGarcia(661)393-7000
08/22/2017
None present
AaronPerrrigo
8485827-UT
Regular1
12.00"
13.50"
5min.
9:00 am
9.50"
10:00 am
9.50"
1hour
0.00"
0.0625"
Regular2
12.00"
13.00"
5min.
9:00 am
9.00"
10:00 am
9.00"
1hour
0.00"
0.0625"0.0625"
Super
12.00"
12.00"
5min.
9:00 am
9.50"
10:00 am
9.50"
1hour
0.00"
Diesel
12.00"
11.50"
5min.
9:00 am
9.75"
10:00 am
9.75"
1hour
0.00"
0.0625"
09/07/2017