HomeMy WebLinkAbout2017 FMCMONITORING SYSTEM CERTIFICATION For Use By All Jurisdictions Within the State of CaliforniaAuthority Cited: Chapter 6.7, Health and Safety Code; Chapter 16, Division 3, Title 23, California Code of Regulations This form must be used to document testing and servicing of monitoring equipment. A separate certification or report must be prepared for each monitoring system control panel by the technician who performs the work. A copy of this form must be provided to the tank system owner/operator. The owner/operator must submit a copy of this form to the local agency regulating UST systems within 30 days of test date. A.General Information Facility Name:Bldg. No.: Site Address:City:Zip: Facility Contact Person: Contact Phone No.: Make/Model of Monitoring System:Date of Testing/Servicing: B.Inventory of Equipment Tested/Certified Check the appropriate boxes to indicate specific equipment inspected/serviced: Tank ID:Tank ID: In-Tank Gauging Probe.Model:In-Tank Gauging Probe.Model: Annular Space or Vault Sensor.Model:Annular Space or Vault Sensor.Model: Piping Sump / Trench Sensor(s).Model:Piping Sump / Trench Sensor(s).Model: Fill Sump Sensor(s).Model:Fill Sump Sensor(s).Model: Mechanical Line Leak Detector.Model:Mechanical Line Leak Detector.Model: Electronic Line Leak Detector.Model:Electronic LineLeak Detector.Model: Tank Overfill / High-Level Sensor.Model:Tank Overfill / High-Level Sensor.Model: Other (specify equipment type and model in Section E on Page 2).Other (specify equipment type and model in Section E on Page 2). Tank ID:Tank ID: In-Tank Gauging Probe.Model:In-Tank Gauging Probe.Model: Annular Space or Vault Sensor.Model:Annular Space or Vault Sensor.Model: Piping Sump / TrenchSensor(s).Model:Piping Sump / Trench Sensor(s).Model: Fill Sump Sensor(s).Model:Fill Sump Sensor(s).Model: Mechanical Line Leak Detector.Model:Mechanical Line Leak Detector.Model: Electronic Line Leak Detector.Model:Electronic Line Leak Detector.Model: Tank Overfill / High-Level Sensor.Model:Tank Overfill / High-Level Sensor.Model: Other (specify equipment type and model in Section E on Page 2).Other (specify equipment type and model in Section E on Page 2). Dispenser ID:Dispenser ID: Dispenser Containment Sensor(s).Model:Dispenser Containment Sensor(s).Model: Shear Valve(s).Shear Valve(s). Dispenser Containment Float(s) and Chain(s).Dispenser Containment Float(s) and Chain(s). Dispenser ID:Dispenser ID: Dispenser Containment Sensor(s).Model:Dispenser Containment Sensor(s).Model: Shear Valve(s).Shear Valve(s). Dispenser Containment Float(s) and Chain(s).Dispenser Containment Float(s) and Chain(s). Dispenser ID:Dispenser ID: Dispenser Containment Sensor(s).Model:Dispenser Containment Sensor(s).Model: Shear Valve(s).Shear Valve(s). Dispenser Containment Float(s) and Chain(s).Dispenser Containment Float(s) and Chain(s). *If the facility contains more tanks or dispensers, copy this form. Include information for every tank and dispenser at the facility. C.Certification -I certify that the equipment identified in this document was inspected/serviced in accordance with the manufacturers’ guidelines. Attached to this Certification is information (e.g. manufacturers' checklists)necessary to verify that this information is correct and a Plot Plan showing the layout of monitoring equipment. For any equipment capable of generating such reports, I have also attached a copy of the report;(check all that apply):System set-up Alarm history report Technician Name (print):Signature: Certification No.:License. No.:804904 Testing Company Name:Confidence UST Services, Inc.Phone No.:(800)339-9930 Site Address:Date of Testing/Servicing: Page 1 of 3 #7785/Fastrip#32 3701MingAvenueBakersfield93309 OmeroGarcia (661)393-7000 Veeder-RootTLS-350 07/24/2017 12,000gal.Regular 847390-107 794380-303 794380-208 794380-208 FX1V 847390-107 12,000gal.Super 847390-107 794380-303 794380-208 794380-208 FX1V 847390-107 12,000gal.Diesel 847390-107 794380-303 794380-208 794380-208 FX1DV 847390-107 1-2 794380-208 3-4 794380-208 5-6 794380-208 794380-208 7-8 AaronPerrigo B47853 3701MingAvenue Bakersfield,CA93309 07/24/2017 794380-208 794380-208 Monitoring System Certification D.Results of Testing/Servicing Software Version Installed: Complete the following checklist: Yes No*Isthe audible alarm operational? Yes No*Is the visual alarm operational? Yes No*Were all sensors visually inspected, functionally tested, and confirmed operational? Yes No*Were all sensors installed at lowest point of secondary containment and positioned so that other equipment will not interfere with their proper operation? Yes No* N/A If alarms are relayed to a remote monitoring station, is all communications equipment (e.g., modem) operational? Yes No* N/A For pressurized piping systems, does the turbine automatically shut down if the piping secondary containment monitoring system detects a leak, fails to operate, or is electrically disconnected? If yes: which sensors initiate positive shut-down? (Check all that apply) Sump/Trench Sensors; Dispenser Containment Sensors. Did you confirm positive shut-down due to leaks and sensor failure/disconnection? Yes; No. Yes No* N/A For tank systems that utilize the monitoring system as the primary tank overfill warning device (i.e., no mechanical overfill prevention valve is installed), is the overfill warning alarm visible and audible at the tank fill point(s) and operating properly? If so, at what percent oftank capacity does the alarm trigger? % Yes*NoWas any monitoring equipment replaced? If yes, identify specific sensors, probes, or other equipment replaced and list the manufacturer name and model for all replacement parts in Section E, below. Yes*NoWas liquid found inside any secondary containment systems designed as dry systems? (Check all that apply) Product; Water. If yes, describe causes in Section E, below. Yes No*Was monitoring system set-up reviewed to ensure proper settings? Attach set up reports, if applicable Yes No*Is all monitoring equipment operational per manufacturer’s specifications? * In Section E below, describe how and when these deficiencies were or will be corrected. E.Comments: Page 2 of 3 329.02 90 Monitoring System Certification F.In-Tank Gauging / SIR Equipment: Check this box if tank gauging is used only for inventory control. Check this box if no tank gauging or SIR equipment is installed. This section must be completed if in-tank gauging equipment is used to perform leak detection monitoring. Complete the following checklist: Yes No*Has all input wiring been inspected for proper entry and termination, including testing for ground faults? Yes No*Were all tank gauging probes visually inspected for damage and residue buildup? Yes No*Was accuracy of system product level readings tested? Yes No*Was accuracy of system water level readings tested? Yes No*Were all probes reinstalled properly? Yes No*Were all items on the equipment manufacturer’s maintenance checklist completed? * In the Section H, below, describe how and when these deficiencies were or will be corrected. G.Line Leak Detectors (LLD):Check this box if LLDs are not installed. Complete the following checklist: Yes No* N/A For equipment start-up or annual equipment certification, was a leak simulated to verify LLD performance? (Check all that apply)Simulated leak rate: 3 g.p.h.; 0.1 g.p.h ; 0.2 g.p.h. Yes No*Were all LLDs confirmed operational and accurate within regulatory requirements? Yes No*Was the testing apparatus properly calibrated? Yes No* N/A For mechanical LLDs, does the LLD restrict product flow if it detects a leak? Yes No* N/A For electronic LLDs, does the turbine automatically shut off if the LLD detects a leak? Yes No* N/A For electronic LLDs, does the turbine automatically shut off if any portion of the monitoring system is disabled or disconnected? Yes No* N/A For electronic LLDs, does the turbine automatically shut off if any portion of the monitoring system malfunctions or fails a test? Yes No* N/A For electronic LLDs, have all accessible wiring connections been visually inspected? Yes No*Were all items on the equipment manufacturer’s maintenance checklist completed? * In the Section H, below, describe how and when these deficiencies were or will be corrected. H.Comments: Page 3 of 3 Leak Detector Test Results Sheet Customer Address: Work Order: Site Address: Test Date: Site Contact: Phone: Technician: Phone: 800-339-9930 ICC No.: Product Type LLD Type Model Serial No. Check Valve Holding Pressure Bleed Off ML. Leak Rate Tested: Pass/Fail 3 gph @ 10 psi 3 gph @ 10 psi 3 gph @ 10 psi 3 gph @ 10 psi 3 gph @ 10 psi 3 gph @ 10 psi 3 gph @ 10 psi 3 gph @ 10 psi Technician Name: Technician No.: Signature: Date: JamiesonHill P.O.Box82515 Bakersfield,CA93380-2515 39363 07/24/2017 8485827-UT Regular Mechanical FX1V AaronPerrigo (661)393-7000OmeroGarcia Bakersfield,CA93309 3701MingAvenue #7785/Fastrip#32 13 psi Pass FX1VMechanicalPremium 10 psi Pass FX1DVMechanicalDiesel 12 psi Pass AaronPerrigo 8485827-UT 07/24/2017 Jaco 7785 Setup Responses Received: 200 FASTRIP 785 3701 MING AVE BAKERSFIELD 93309 661-397-3699 JUL 24, 2017 8:47 AM TANK PRODUCT GALLONS INCHES WATER DEG F ULLAGE 1 UNLEADED 7374 54.45 0.0 83.4 4626 2 PREMIUM 6385 48.19 0.8 89.2 5615 3 DIESEL 2794 26.06 0.0 87.6 9206 I90500 JUL 24, 2017 8:47 AM SOFTWARE REVISION LEVEL VERSION 329.02 SOFTWARE# 346329-100-C CREATED - 09.07.01.16.29 S-MODULE# 330160-004-a SYSTEM FEATURES: PERIODIC IN-TANK TESTS ANNUAL IN-TANK TESTS ISD I50500 JUL 24, 2017 8:47 AM SYSTEM TYPE AND LANGUAGE FLAG SYSTEM UNITS U.S. SYSTEM LANGUAGE ENGLISH SYSTEM DATE/TIME FORMAT MON DD YYYY HH:MM:SS xM I50201 JUL 24, 2017 8:47 AM SHIFT TIME 1 : 6:00 AM I50202 JUL 24, 2017 8:47 AM SHIFT TIME 2 : DISABLED I50203 JUL 24, 2017 8:47 AM SHIFT TIME 3 : DISABLED I50204 JUL 24, 2017 8:47 AM SHIFT TIME 4 : DISABLED I54600 JUL 24, 2017 8:47 AM TANK PER TST NEEDED WRN: DISABLED I54900 JUL 24, 2017 8:47 AM TANK ANN TST NEEDED WRN: DISABLED I55300 JUL 24, 2017 8:47 AM LINE RE-ENABLE METHOD PASS LINE TEST I55600 JUL 24, 2017 8:47 AM LINE PER TST NEEDED WRN: DISABLED I55900 JUL 24, 2017 8:47 AM LINE ANN TST NEEDED WRN: DISABLED I50D00 JUL 24, 2017 8:47 AM PRINT TC VOLUMES ENABLED I50E00 JUL 24, 2017 8:47 AM TEMP COMPENSATION VALUE (DEG F ): 60.0 I60B00 JUL 24, 2017 8:47 AM STICK HEIGHT OFFSET ENABLE STATUS DISABLED I51400 JUL 24, 2017 8:47 AM H-PROTOCOL DATA FORMAT HEIGHT I51A01 JUL 24, 2017 8:47 AM DAYLIGHT SAVING TIME ENABLED ON I51B00 JUL 24, 2017 8:47 AM DAYLIGHT SAVING TIME START DATE MAR WEEK 1 SUN 2:00 AM END DATE NOV WEEK 1 SUN 2:00 AM I51600 JUL 24, 2017 8:47 AM RE-DIRECT LOCAL PRINTOUT DISABLED I50400 JUL 24, 2017 8:47 AM 232 SECURITY CODE PORT SECURITY CODE STATUS 1 000000 DISABLED 2 000000 DISABLED 3 000000 DISABLED 4 000000 DISABLED 5 000000 DISABLED 6 000000 DISABLED I21900 JUL 24, 2017 8:47 AM TANK CHART SECURITY DISABLED I5BD00 JUL 24, 2017 8:47 AM CUSTOM ALARM LABELS DISABLED I56000 JUL 24, 2017 8:47 AM MASS/DENSITY DISABLED I88101 JUL 24, 2017 8:47 AM PORT SETTINGS: COMM BOARD : 1 (EDIM ) RS-232 SECURITY CODE : DISABLED I88102 JUL 24, 2017 8:47 AM PORT SETTINGS: COMM BOARD : 2 (RS-232) BAUD RATE : 9600 PARITY : NONE STOP BIT : 1 STOP DATA LENGTH: 8 DATA RS-232 SECURITY CODE : DISABLED I88103 JUL 24, 2017 8:47 AM PORT SETTINGS: COMM BOARD : 3 (RS-232) BAUD RATE : 9600 PARITY : NONE STOP BIT : 1 STOP DATA LENGTH: 8 DATA RS-232 SECURITY CODE : DISABLED I88104 JUL 24, 2017 8:47 AM I88105 JUL 24, 2017 8:47 AM I88106 JUL 24, 2017 8:47 AM I52000 JUL 24, 2017 8:47 AM RECEIVER AUTO DIAL TYPE & START TIME RCVR LOCATION LABEL DIAL TYPE START TIME 1 ON DATE MAR 9, 2011 DISABLED 2 ON DATE MAR 9, 2011 DISABLED 3 ON DATE MAR 9, 2011 DISABLED 4 ON DATE MAR 9, 2011 DISABLED 5 ON DATE MAR 9, 2011 DISABLED 6 ON DATE MAR 9, 2011 DISABLED 7 ON DATE MAR 9, 2011 DISABLED 8 ON DATE MAR 9, 2011 DISABLED I60100 JUL 24, 2017 8:47 AM TANK CONFIGURATION DEVICE LABEL CONFIGURED 1 UNLEADED ON 2 PREMIUM ON 3 DIESEL ON 4 OFF I60200 JUL 24, 2017 8:47 AM TANK PRODUCT LABEL TANK PRODUCT LABEL 1 UNLEADED 2 PREMIUM 3 DIESEL 4 I60300 JUL 24, 2017 8:47 AM TANK PRODUCT CODE TANK PRODUCT LABEL 1 UNLEADED 1 2 PREMIUM 2 3 DIESEL 3 4 4 I60900 JUL 24, 2017 8:47 AM TANK THERMAL COEFFICIENT TANK PRODUCT LABEL 1 UNLEADED 0.000700 2 PREMIUM 0.000700 3 DIESEL 0.000450 4 0.000000 I60700 JUL 24, 2017 8:47 AM TANK DIAMETER TANK PRODUCT LABEL INCHES 1 UNLEADED 96.00 2 PREMIUM 96.00 3 DIESEL 96.00 4 0.00 I60A00 JUL 24, 2017 8:47 AM TANK FULL VOLUME TANK PRODUCT LABEL TANK PROFILE GALLONS 1 UNLEADED 4 PTS 12000 2 PREMIUM 4 PTS 12000 3 DIESEL 4 PTS 12000 4 1 PT 0 I60400 JUL 24, 2017 8:47 AM TANK FULL VOLUME TANK PRODUCT LABEL GALLONS 1 UNLEADED 12000 2 PREMIUM 12000 3 DIESEL 12000 4 0 I60500 JUL 24, 2017 8:47 AM TANK 4 POINT VOLUMES TANK PRODUCT LABEL GALLONS 1 UNLEADED 12000 9999 6355 2505 2 PREMIUM 12000 9999 6355 2505 3 DIESEL 12000 9999 6355 2505 4 0 0 0 0 I60600 JUL 24, 2017 8:47 AM TANK 20 POINT VOLUMES TANK PRODUCT LABEL GALLONS 1 UNLEADED 12000 0 0 0 0 9999 0 0 0 0 6355 0 0 0 0 2505 0 0 0 0 2 PREMIUM 12000 0 0 0 0 9999 0 0 0 0 6355 0 0 0 0 2505 0 0 0 0 3 DIESEL 12000 0 0 0 0 9999 0 0 0 0 6355 0 0 0 0 2505 0 0 0 0 4 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 I61500 JUL 24, 2017 8:47 AM TANK PRODUCT LABEL METER DATA 1 UNLEADED NO 2 PREMIUM NO 3 DIESEL NO 4 NO I62F00 JUL 24, 2017 8:47 AM MAG PROBE FLOAT SIZE TANK PRODUCT LABEL FLOAT SIZE: 1 UNLEADED 4.0 INCHES 2 PREMIUM 4.0 INCHES 3 DIESEL 4.0 INCHES I62700 JUL 24, 2017 8:47 AM TANK HIGH WATER WARNING LIMIT TANK PRODUCT LABEL INCHES 1 UNLEADED 2.0 2 PREMIUM 2.0 3 DIESEL 2.0 9999FF1B I62400 JUL 24, 2017 8:47 AM TANK HIGH WATER LEVEL LIMIT TANK PRODUCT LABEL INCHES 1 UNLEADED 3.0 2 PREMIUM 3.0 3 DIESEL 3.0 I62800 JUL 24, 2017 8:47 AM TANK MAXIMUM VOLUME LIMIT TANK PRODUCT LABEL GALLONS 1 UNLEADED 12000 2 PREMIUM 12000 3 DIESEL 12000 4 0 I62300 JUL 24, 2017 8:47 AM TANK OVERFILL LEVEL LIMIT TANK PRODUCT LABEL GALLONS 1 UNLEADED 10800 2 PREMIUM 10800 3 DIESEL 10800 4 0 I62200 JUL 24, 2017 8:47 AM TANK HIGH PRODUCT LIMIT TANK PRODUCT LABEL GALLONS 1 UNLEADED 11400 2 PREMIUM 11400 3 DIESEL 11400 4 0 I62900 JUL 24, 2017 8:47 AM TANK DELIVERY REQUIRED LIMIT TANK PRODUCT LABEL GALLONS 1 UNLEADED 1800 2 PREMIUM 1800 3 DIESEL 1800 4 0 I62100 JUL 24, 2017 8:47 AM TANK LOW PRODUCT LIMIT TANK PRODUCT LABEL GALLONS 1 UNLEADED 1200 2 PREMIUM 1200 3 DIESEL 1200 4 0 I62600 JUL 24, 2017 8:47 AM TANK LEAK ALARM LIMIT TANK PRODUCT LABEL GALLONS 1 UNLEADED 99 2 PREMIUM 99 3 DIESEL 99 4 99 I62500 JUL 24, 2017 8:47 AM TANK SUDDEN LOSS LIMIT TANK PRODUCT LABEL GALLONS 1 UNLEADED 99 2 PREMIUM 99 3 DIESEL 99 4 99 I60800 JUL 24, 2017 8:47 AM TANK TILT TANK PRODUCT LABEL INCHES 1 UNLEADED 0.00 2 PREMIUM 3.00 3 DIESEL 3.00 4 0.00 I60B00 JUL 24, 2017 8:47 AM STICK HEIGHT OFFSET ENABLE STATUS DISABLED I60C00 JUL 24, 2017 8:47 AM TANK STICK HEIGHT OFFSET TANK PRODUCT LABEL INCHES 1 UNLEADED 0.00 2 PREMIUM 0.00 3 DIESEL 0.00 4 0.00 I61200 JUL 24, 2017 8:47 AM TANK MANIFOLDED PARTNERS TANK PRODUCT LABEL SIPHON MANIFOLDED TANKS LINE MANIFOLDED TANKS 1 UNLEADED NONE NONE 2 PREMIUM NONE NONE 3 DIESEL NONE NONE 4 NONE NONE I63600 JUL 24, 2017 8:47 AM PERIODIC LEAK TEST MIN VOLUME TANK PRODUCT LABEL GALLONS 1 UNLEADED 120 2 PREMIUM 120 3 DIESEL 120 4 0 I62A00 JUL 24, 2017 8:47 AM ANNUAL LEAK TEST MIN VOLUME TANK PRODUCT LABEL GALLONS 1 UNLEADED 120 2 PREMIUM 120 3 DIESEL 120 4 0 I62C00 JUL 24, 2017 8:47 AM TANK PERIODIC TEST TYPE TANK PRODUCT LABEL PERIODIC TEST TYPE 1 UNLEADED STANDARD 2 PREMIUM STANDARD 3 DIESEL STANDARD 4 STANDARD I62D00 JUL 24, 2017 8:47 AM TANK LEAK TEST FAIL ALARMS TANK PRODUCT LABEL 1 UNLEADED GROSS TEST FAIL ALARM DISABLED PERIODIC TEST FAIL ALARM DISABLED ANNUAL TEST FAIL ALARM DISABLED 2 PREMIUM GROSS TEST FAIL ALARM DISABLED PERIODIC TEST FAIL ALARM DISABLED ANNUAL TEST FAIL ALARM DISABLED 3 DIESEL GROSS TEST FAIL ALARM DISABLED PERIODIC TEST FAIL ALARM DISABLED ANNUAL TEST FAIL ALARM DISABLED 4 GROSS TEST FAIL ALARM DISABLED PERIODIC TEST FAIL ALARM DISABLED ANNUAL TEST FAIL ALARM DISABLED I63100 JUL 24, 2017 8:47 AM TANK LEAK TEST AVERAGING TANK PRODUCT LABEL ANNUAL PERIODIC 1 UNLEADED OFF OFF 2 PREMIUM OFF OFF 3 DIESEL OFF OFF 4 OFF OFF I63000 JUL 24, 2017 8:48 AM IN-TANK LEAK TEST NOTIFY TANK PRODUCT LABEL TANK TEST NOTIFY: 1 UNLEADED OFF 2 PREMIUM OFF 3 DIESEL OFF 4 OFF I63200 JUL 24, 2017 8:48 AM TANK TEST SIPHON BREAK TANK PRODUCT LABEL SIPHON BREAK 1 UNLEADED OFF 2 PREMIUM OFF 3 DIESEL OFF 4 OFF I61000 JUL 24, 2017 8:48 AM TANK DELIVERY DELAY TANK PRODUCT LABEL 1 UNLEADED 1 2 PREMIUM 1 3 DIESEL 1 4 1 I63A00 JUL 24, 2017 8:48 AM LOW LEVEL PUMP THRESHOLD FOR SEQUENTIAL LINE MANIFOLD TANK PRODUCT LABEL PUMP THRESHOLD 1 UNLEADED 10.00% 2 PREMIUM 10.00% 3 DIESEL 10.00% 4 10.00% I61100 JUL 24, 2017 8:48 AM LEAK TEST METHOD - - - - - - - - - - - - TEST ON DATE : ALL TANK JUL 1, 2009 START TIME : DISABLED TEST RATE :0.20 GAL/HR DURATION : 2 HOURS TST EARLY STOP:DISABLED I61300 JUL 24, 2017 8:48 AM CSLD PROBABLITY OF DETECTION I61400 JUL 24, 2017 8:48 AM CSLD CLIMATE FACTOR I61600 JUL 24, 2017 8:48 AM TANK PRODUCT LABEL CAL UPDATE 1 UNLEADED IMMEDIATE 2 PREMIUM IMMEDIATE 3 DIESEL IMMEDIATE 4 IMMEDIATE I61A00 JUL 24, 2017 8:48 AM IN-TANK LEAK TEST EARLY STOP TANK PRODUCT LABEL TST EARLY STOP: 1 UNLEADED DISABLED 2 PREMIUM DISABLED 3 DIESEL DISABLED 4 DISABLED I61B00 JUL 24, 2017 8:48 AM IN-TANK LEAK GROSS TEST AUTO-CONFIRM I61C00 JUL 24, 2017 8:48 AM CSLD REPORT ONLY I62B00 JUL 24, 2017 8:48 AM TANK LAST ANNUAL TEST TANK PRODUCT LABEL DATE 1 UNLEADED ??? 0, 0 2 PREMIUM ??? 0, 0 3 DIESEL ??? 0, 0 4 ??? 0, 0 I63300 JUL 24, 2017 8:48 AM LEAK TEST REPORT FORMAT: NORMAL I63400 JUL 24, 2017 8:48 AM RECONCILIATION WARNING LIMIT TANK PRODUCT LABEL GALLONS 1 UNLEADED 0 2 PREMIUM 0 3 DIESEL 0 4 0 I63500 JUL 24, 2017 8:48 AM RECONCILIATION ALARM LIMIT TANK PRODUCT LABEL GALLONS 1 UNLEADED 1 2 PREMIUM 1 3 DIESEL 1 4 1 I63900 JUL 24, 2017 8:48 AM ACCU CHART END SHAPE FACTOR TANK PRODUCT LABEL 1 UNLEADED END FACTOR: NONE 2 PREMIUM END FACTOR: NONE 3 DIESEL END FACTOR: NONE 4 END FACTOR: NONE I78000 JUL 24, 2017 8:48 AM I77700 JUL 24, 2017 8:48 AM I77800 JUL 24, 2017 8:48 AM I78C00 JUL 24, 2017 8:48 AM I78300 JUL 24, 2017 8:48 AM I78F00 JUL 24, 2017 8:48 AM I78700 JUL 24, 2017 8:48 AM I70200 JUL 24, 2017 8:48 AM LIQUID LABEL DEVICE LABEL 1 UNL STP 2 UNL FILL 3 UNL ANN 4 PNL STP 5 PNL FILL 6 PNL ANN 7 DSL STP 8 DSL FILL 9 DSL ANN 10 VENT BOX 11 DISP 1-2 12 DISP 3-4 13 DISP 5-6 14 DISP 7-8 15 16 I70300 JUL 24, 2017 8:48 AM LIQUID TYPE SENSOR LOCATION TYPE 1 UNL STP TRI-STATE (SINGLE FLOAT) 2 UNL FILL TRI-STATE (SINGLE FLOAT) 3 UNL ANN DUAL POINT HYDROSTATIC 4 PNL STP TRI-STATE (SINGLE FLOAT) 5 PNL FILL TRI-STATE (SINGLE FLOAT) 6 PNL ANN DUAL POINT HYDROSTATIC 7 DSL STP TRI-STATE (SINGLE FLOAT) 8 DSL FILL TRI-STATE (SINGLE FLOAT) 9 DSL ANN DUAL POINT HYDROSTATIC 10 VENT BOX TRI-STATE (SINGLE FLOAT) 11 DISP 1-2 TRI-STATE (SINGLE FLOAT) 12 DISP 3-4 TRI-STATE (SINGLE FLOAT) 13 DISP 5-6 TRI-STATE (SINGLE FLOAT) 14 DISP 7-8 TRI-STATE (SINGLE FLOAT) 15 TRI-STATE (SINGLE FLOAT) 16 TRI-STATE (SINGLE FLOAT) I70400 JUL 24, 2017 8:48 AM LIQUID CATEGORY SENSOR LOCATION CATEGORY 1 UNL STP STP SUMP 2 UNL FILL PIPING SUMP 3 UNL ANN ANNULAR SPACE 4 PNL STP STP SUMP 5 PNL FILL PIPING SUMP 6 PNL ANN ANNULAR SPACE 7 DSL STP STP SUMP 8 DSL FILL PIPING SUMP 9 DSL ANN ANNULAR SPACE 10 VENT BOX PIPING SUMP 11 DISP 1-2 DISPENSER PAN 12 DISP 3-4 DISPENSER PAN 13 DISP 5-6 DISPENSER PAN 14 DISP 7-8 DISPENSER PAN 15 OTHER SENSORS 16 OTHER SENSORS I74200 JUL 24, 2017 8:48 AM I74300 JUL 24, 2017 8:48 AM I74400 JUL 24, 2017 8:48 AM I74700 JUL 24, 2017 8:48 AM I74800 JUL 24, 2017 8:48 AM I74900 JUL 24, 2017 8:48 AM I7BC00 JUL 24, 2017 8:48 AM I80200 JUL 24, 2017 8:48 AM I80300 JUL 24, 2017 8:48 AM I80400 JUL 24, 2017 8:48 AM I80700 JUL 24, 2017 8:48 AM RELAY LABEL DEVICE LABEL 1 UNLEADED 2 PREMIUM 3 DIESEL 4 OVERFILL I80900 JUL 24, 2017 8:48 AM RELAY ORIENTATION RELAY DESIGNATION ORIENTATION 1 UNLEADED NORMALLY OPEN 2 PREMIUM NORMALLY OPEN 3 DIESEL NORMALLY CLOSED 4 OVERFILL NORMALLY OPEN I80B00 JUL 24, 2017 8:48 AM RELAY TANK ASSIGNMENT RELAY DESIGNATION TANK 1 UNLEADED 1 2 PREMIUM 2 3 DIESEL NONE 4 OVERFILL NONE I80A00 JUL 24, 2017 8:48 AM RELAY TYPE RELAY DESIGNATION TYPE 1 UNLEADED PUMP CONTROL OUTPUT 2 PREMIUM PUMP CONTROL OUTPUT 3 DIESEL STANDARD 4 OVERFILL STANDARD I80C00 JUL 24, 2017 8:48 AM I80800 JUL 24, 2017 8:48 AM RELAY SETUP REPORT R 1:UNLEADED TYPE: PUMP CONTROL OUTPUT TANK #: 1 LIQUID SENSOR ALMS L 1:FUEL ALARM L11:FUEL ALARM L12:FUEL ALARM L13:FUEL ALARM L14:FUEL ALARM L 1:SENSOR OUT ALARM L11:SENSOR OUT ALARM L12:SENSOR OUT ALARM L13:SENSOR OUT ALARM L14:SENSOR OUT ALARM L 1:SHORT ALARM L11:SHORT ALARM L12:SHORT ALARM L13:SHORT ALARM L14:SHORT ALARM ISD SITE ALARMS ISD GROSS PRES FAIL ISD DEGRD PRES FAIL ISD VAPOR LEAK FAIL ISD VP PRES FAIL ISD VP STATUS FAIL ISD HOSE ALARMS ALL:GROSS COLLECT FAIL ALL:DEGRD COLLECT FAIL ALL:FLOW COLLECT FAIL R 2:PREMIUM TYPE: PUMP CONTROL OUTPUT TANK #: 2 LIQUID SENSOR ALMS L 4:FUEL ALARM L11:FUEL ALARM L12:FUEL ALARM L13:FUEL ALARM L14:FUEL ALARM L 4:SENSOR OUT ALARM L11:SENSOR OUT ALARM L12:SENSOR OUT ALARM L13:SENSOR OUT ALARM L14:SENSOR OUT ALARM L 4:SHORT ALARM L11:SHORT ALARM L12:SHORT ALARM L13:SHORT ALARM L14:SHORT ALARM ISD SITE ALARMS ISD GROSS PRES FAIL ISD DEGRD PRES FAIL ISD VAPOR LEAK FAIL ISD VP PRES FAIL ISD VP STATUS FAIL ISD HOSE ALARMS ALL:GROSS COLLECT FAIL ALL:DEGRD COLLECT FAIL ALL:FLOW COLLECT FAIL R 3:DIESEL TYPE: STANDARD NORMALLY CLOSED TANK #: NONE LIQUID SENSOR ALMS L 7:FUEL ALARM L11:FUEL ALARM L12:FUEL ALARM L13:FUEL ALARM L14:FUEL ALARM L 7:SENSOR OUT ALARM L11:SENSOR OUT ALARM L12:SENSOR OUT ALARM L13:SENSOR OUT ALARM L14:SENSOR OUT ALARM L11:SHORT ALARM L12:SHORT ALARM L13:SHORT ALARM L14:SHORT ALARM R 4:OVERFILL TYPE: STANDARD NORMALLY OPEN TANK #: NONE IN-TANK ALARMS ALL:OVERFILL ALARM ALL:HIGH PRODUCT ALARM I79000 JUL 24, 2017 8:48 AM EDIM:1 VR:349634-003-C TD:06.05.11.11.15 I79100 JUL 24, 2017 8:48 AM I72300 JUL 24, 2017 8:48 AM FASTRIP 785 3701 MING AVE BAKERSFIELD 93309 661-397-3699 SMARTSENSOR ASSIGNMENT DEVICE LABEL CATEGORY 01 VP 1-2 VAPOR PRESSURE 02 FM 1-2 AIR FLOW METER 03 FM 3-4 AIR FLOW METER 04 FM 5-6 AIR FLOW METER 05 FM 7-8 AIR FLOW METER 06 UNKNOWN 07 UNKNOWN 08 UNKNOWN 09 UNKNOWN 10 UNKNOWN 11 UNKNOWN 12 UNKNOWN 13 UNKNOWN 14 UNKNOWN 15 UNKNOWN 16 UNKNOWN 17 UNKNOWN 18 UNKNOWN 19 UNKNOWN 20 UNKNOWN 21 UNKNOWN 22 UNKNOWN 23 UNKNOWN 24 UNKNOWN 25 UNKNOWN 26 UNKNOWN 27 UNKNOWN 28 UNKNOWN 29 UNKNOWN 30 UNKNOWN 31 UNKNOWN 32 UNKNOWN 33 UNKNOWN 34 UNKNOWN 35 UNKNOWN 36 UNKNOWN 37 UNKNOWN 38 UNKNOWN 39 UNKNOWN 40 UNKNOWN IV4E00 JUL 24, 2017 8:48 AM FASTRIP 785 3701 MING AVE BAKERSFIELD 93309 661-397-3699 EVR/ISD SETUP TYPE: VACUUM ASSIST VACUUM ASSIST TYPE: HEALY VAC IV4F00 JUL 24, 2017 8:49 AM FASTRIP 785 3701 MING AVE BAKERSFIELD 93309 661-397-3699 NOZZLE A/L RANGE A/L RATIO: 0.95 - 1.15 IV4000 JUL 24, 2017 8:49 AM FASTRIP 785 3701 MING AVE BAKERSFIELD 93309 661-397-3699 VAPOR PROCESSOR TYPE NONE IV4700 JUL 24, 2017 8:49 AM FASTRIP 785 3701 MING AVE BAKERSFIELD 93309 661-397-3699 ASSESSMENT TIME START TIME: 10:00 AM TIME DELAY MINUTES: 1 IV5200 JUL 24, 2017 8:49 AM FASTRIP 785 3701 MING AVE BAKERSFIELD 93309 661-397-3699 ACCEPT HIGH ORVR: YES IV4A00 JUL 24, 2017 8:49 AM FASTRIP 785 3701 MING AVE BAKERSFIELD 93309 661-397-3699 ISD HOSE TABLE HOSE FP FP AFM HOSE ID ID LABEL ID LABEL 01 01 01 01 BLEND3 02 02 02 01 BLEND3 03 03 03 02 BLEND3 04 04 04 02 BLEND3 05 05 05 03 BLEND3 06 06 06 03 BLEND3 07 07 07 04 BLEND3 08 08 08 04 BLEND3 IV4B00 JUL 24, 2017 8:49 AM FASTRIP 785 3701 MING AVE BAKERSFIELD 93309 661-397-3699 PRODUCT/HOSE MAP TABLE FP AFID M1/H1 M2/H2 M3/H3 M4/H4 01 01 02/01 03/01 09/01 xx/xx 02 01 02/02 03/02 09/02 xx/xx 03 02 02/03 03/03 09/03 xx/xx 04 02 02/04 03/04 09/04 xx/xx 05 03 02/05 03/05 09/05 xx/xx 06 03 02/06 03/06 09/06 xx/xx 07 04 02/07 03/07 09/07 xx/xx 08 04 02/08 03/08 09/08 xx/xx IV4900 JUL 24, 2017 8:49 AM FASTRIP 785 3701 MING AVE BAKERSFIELD 93309 661-397-3699 LABEL TABLE ID LABEL 01 UNASSIGNED 02 BLEND3 03 REGULAR 04 MID GRADE 05 PREMIUM 06 GOLD 07 BRONZE 08 SILVER 09 BLEND2 10 BLEND4 IV1000 JUL 24, 2017 8:49 AM ISD VERSION: 01.02 Jaco 7785 Alarm History Responses Received: I10200 JUL 24, 2017 8:50 AM FASTRIP 785 3701 MING AVE BAKERSFIELD 93309 661-397-3699 SYSTEM CONFIGURATION SLOT BOARD TYPE POWER ON RESET CURRENT 1 7SMARTSENSOR BD 508342 503955 2 4 PROBE / G.T. 163473 163179 3 INTERSTITIAL BD 201165 201039 4 INTERSTITIAL BD 202252 201876 5 UNUSED 9852520 9796511 6 UNUSED 9818980 9791816 7 UNUSED 9810432 9790653 8 UNUSED 9806239 9791901 9 STP SENSE BOARD 32990 33037 10 RELAY BOARD 14864 14887 11 UNUSED 9809143 9803096 12 UNUSED 9805114 9793198 13 UNUSED 9800513 9792732 14 UNUSED 9800451 9786959 15 UNUSED 9800615 9790639 16 UNUSED 9794766 9793578 COMM 1 ELEC DISP INT. 100821 100893 COMM 2 RS232 SERIAL BD 14966 14972 COMM 3 RS232 SERIAL BD 14864 14887 COMM 4 UNUSED 9808713 9796899 COMM 5 UNUSED 9804828 9796053 COMM 6 UNUSED 9800206 9792711 I90200 JUL 24, 2017 8:50 AM SOFTWARE REVISION LEVEL VERSION 329.02 SOFTWARE# 346329-100-C CREATED - 09.07.01.16.29 S-MODULE# 330160-004-a SYSTEM FEATURES: PERIODIC IN-TANK TESTS ANNUAL IN-TANK TESTS ISD I11100 JUL 24, 2017 8:50 AM FASTRIP 785 3701 MING AVE BAKERSFIELD 93309 661-397-3699 PRIORITY ALARM HISTORY ID CATEGORY DESCRIPTION ALARM TYPE STATE DATE TIME L 9 ANNULAR DSL ANN HIGH LIQUID ALARM CLEAR 7-20-17 12:04AM L 9 ANNULAR DSL ANN HIGH LIQUID ALARM ALARM 7-19-17 11:48PM L 3 ANNULAR UNL ANN HIGH LIQUID ALARM CLEAR 7-17-17 2:22PM T 1 TANK UNLEADED OVERFILL ALARM CLEAR 7-17-17 2:18PM T 1 TANK UNLEADED OVERFILL ALARM ALARM 7-17-17 2:16PM L 3 ANNULAR UNL ANN HIGH LIQUID ALARM ALARM 7-17-17 2:16PM L 3 ANNULAR UNL ANN SENSOR OUT ALARM CLEAR 7-17-17 10:32AM L 2 PIPE UNL FILL SENSOR OUT ALARM CLEAR 7-17-17 10:32AM L 8 PIPE DSL FILL SENSOR OUT ALARM CLEAR 7-17-17 10:32AM L 7 STP SUMP DSL STP SENSOR OUT ALARM CLEAR 7-17-17 10:32AM L 6 ANNULAR PNL ANN SENSOR OUT ALARM CLEAR 7-17-17 10:32AM L 4 STP SUMP PNL STP SENSOR OUT ALARM CLEAR 7-17-17 10:32AM L 1 STP SUMP UNL STP SENSOR OUT ALARM CLEAR 7-17-17 10:32AM L10 PIPE VENT BOX SENSOR OUT ALARM CLEAR 7-17-17 10:32AM L 5 PIPE PNL FILL SENSOR OUT ALARM CLEAR 7-17-17 10:32AM L14 DISP PAN DISP 7-8 SENSOR OUT ALARM CLEAR 7-17-17 10:32AM L12 DISP PAN DISP 3-4 SENSOR OUT ALARM CLEAR 7-17-17 10:32AM L11 DISP PAN DISP 1-2 SENSOR OUT ALARM CLEAR 7-17-17 10:32AM L 9 ANNULAR DSL ANN SENSOR OUT ALARM CLEAR 7-17-17 10:32AM L13 DISP PAN DISP 5-6 SENSOR OUT ALARM CLEAR 7-17-17 10:32AM L14 DISP PAN DISP 7-8 SENSOR OUT ALARM ALARM 7-17-17 10:32AM L12 DISP PAN DISP 3-4 SENSOR OUT ALARM ALARM 7-17-17 10:32AM L11 DISP PAN DISP 1-2 SENSOR OUT ALARM ALARM 7-17-17 10:32AM L 4 STP SUMP PNL STP SENSOR OUT ALARM ALARM 7-17-17 10:32AM L 3 ANNULAR UNL ANN SENSOR OUT ALARM ALARM 7-17-17 10:32AM L10 PIPE VENT BOX SENSOR OUT ALARM ALARM 7-17-17 10:32AM L 8 PIPE DSL FILL SENSOR OUT ALARM ALARM 7-17-17 10:32AM L 7 STP SUMP DSL STP SENSOR OUT ALARM ALARM 7-17-17 10:32AM L 2 PIPE UNL FILL SENSOR OUT ALARM ALARM 7-17-17 10:32AM L13 DISP PAN DISP 5-6 SENSOR OUT ALARM ALARM 7-17-17 10:32AM L 6 ANNULAR PNL ANN SENSOR OUT ALARM ALARM 7-17-17 10:32AM L 9 ANNULAR DSL ANN SENSOR OUT ALARM ALARM 7-17-17 10:32AM L 1 STP SUMP UNL STP SENSOR OUT ALARM ALARM 7-17-17 10:32AM L 5 PIPE PNL FILL SENSOR OUT ALARM ALARM 7-17-17 10:32AM L13 DISP PAN DISP 5-6 FUEL ALARM CLEAR 7-17-17 10:28AM L13 DISP PAN DISP 5-6 FUEL ALARM ALARM 7-17-17 10:28AM L14 DISP PAN DISP 7-8 FUEL ALARM CLEAR 7-17-17 10:27AM L14 DISP PAN DISP 7-8 FUEL ALARM ALARM 7-17-17 10:27AM L11 DISP PAN DISP 1-2 FUEL ALARM CLEAR 7-17-17 10:27AM L11 DISP PAN DISP 1-2 FUEL ALARM ALARM 7-17-17 10:27AM L12 DISP PAN DISP 3-4 FUEL ALARM CLEAR 7-17-17 10:24AM L12 DISP PAN DISP 3-4 FUEL ALARM ALARM 7-17-17 10:24AM L10 PIPE VENT BOX FUEL ALARM CLEAR 7-17-17 10:20AM L10 PIPE VENT BOX FUEL ALARM ALARM 7-17-17 10:19AM L 9 ANNULAR DSL ANN HIGH LIQUID ALARM CLEAR 7-17-17 10:09AM L 9 ANNULAR DSL ANN LOW LIQUID ALARM CLEAR 7-17-17 10:08AM L 9 ANNULAR DSL ANN HIGH LIQUID ALARM ALARM 7-17-17 10:08AM L 9 ANNULAR DSL ANN LOW LIQUID ALARM ALARM 7-17-17 10:08AM L 6 ANNULAR PNL ANN LOW LIQUID ALARM CLEAR 7-17-17 10:08AM L 6 ANNULAR PNL ANN LOW LIQUID ALARM ALARM 7-17-17 10:08AM I11200 JUL 24, 2017 8:50 AM FASTRIP 785 3701 MING AVE BAKERSFIELD 93309 661-397-3699 NON-PRIORITY ALARM HISTORY ID CATEGORY DESCRIPTION ALARM TYPE STATE DATE TIME T 1 TANK UNLEADED DELIVERY NEEDED CLEAR 7-23-17 1:39AM T 1 TANK UNLEADED DELIVERY NEEDED ALARM 7-22-17 11:22PM T 1 TANK UNLEADED DELIVERY NEEDED CLEAR 7-21-17 2:40PM T 1 TANK UNLEADED DELIVERY NEEDED ALARM 7-21-17 2:06PM h 5 OTHER FP5: BLEND3 GROSS COLLECT WARN CLEAR 7-18-17 12:31PM h 5 OTHER FP5: BLEND3 GROSS COLLECT WARN ALARM 7-18-17 10:01AM T 3 TANK DIESEL HIGH PRODUCT ALARM CLEAR 7-17-17 9:57AM T 3 TANK DIESEL HIGH PRODUCT ALARM ALARM 7-17-17 9:57AM T 2 TANK PREMIUM LOW TEMP WARNING CLEAR 7-17-17 9:57AM T 2 TANK PREMIUM LOW TEMP WARNING ALARM 7-17-17 9:56AM T 2 TANK PREMIUM HIGH PRODUCT ALARM CLEAR 7-17-17 9:55AM T 2 TANK PREMIUM HIGH PRODUCT ALARM ALARM 7-17-17 9:55AM T 1 TANK UNLEADED HIGH PRODUCT ALARM CLEAR 7-17-17 9:52AM T 1 TANK UNLEADED HIGH PRODUCT ALARM ALARM 7-17-17 9:52AM h 5 OTHER FP5: BLEND3 DEGRD COLLECT WARN CLEAR 7-17-17 8:46AM h 5 OTHER FP5: BLEND3 DEGRD COLLECT WARN ALARM 7-16-17 10:01AM T 1 TANK UNLEADED DELIVERY NEEDED CLEAR 7-12-17 11:31PM T 1 TANK UNLEADED DELIVERY NEEDED ALARM 7-12-17 10:04PM T 1 TANK UNLEADED DELIVERY NEEDED CLEAR 7-03-17 8:07PM T 1 TANK UNLEADED DELIVERY NEEDED ALARM 7-03-17 4:56PM h 5 OTHER FP5: BLEND3 DEGRD COLLECT WARN CLEAR 6-28-17 9:31AM T 1 TANK UNLEADED DELIVERY NEEDED CLEAR 6-27-17 6:53PM T 1 TANK UNLEADED DELIVERY NEEDED ALARM 6-27-17 4:14PM h 5 OTHER FP5: BLEND3 DEGRD COLLECT WARN ALARM 6-24-17 10:01AM T 1 TANK UNLEADED HIGH PRODUCT ALARM CLEAR 6-13-17 5:01AM T 1 TANK UNLEADED HIGH PRODUCT ALARM ALARM 6-13-17 3:29AM T 1 TANK UNLEADED DELIVERY NEEDED CLEAR 6-09-17 9:09PM T 1 TANK UNLEADED DELIVERY NEEDED ALARM 6-09-17 8:52PM T 1 TANK UNLEADED DELIVERY NEEDED CLEAR 6-08-17 6:43PM T 1 TANK UNLEADED DELIVERY NEEDED ALARM 6-08-17 5:58PM T 1 TANK UNLEADED HIGH PRODUCT ALARM CLEAR 6-07-17 7:00AM T 1 TANK UNLEADED HIGH PRODUCT ALARM ALARM 6-07-17 5:04AM T 1 TANK UNLEADED DELIVERY NEEDED CLEAR 6-02-17 2:35AM T 1 TANK UNLEADED DELIVERY NEEDED ALARM 6-01-17 7:57PM T 1 TANK UNLEADED DELIVERY NEEDED CLEAR 5-31-17 4:32PM T 1 TANK UNLEADED DELIVERY NEEDED ALARM 5-31-17 4:19PM SYSTEM PRINTER ERROR CLEAR 5-29-17 7:03PM SYSTEM PAPER OUT CLEAR 5-29-17 7:03PM SYSTEM PRINTER ERROR ALARM 5-29-17 6:59PM SYSTEM PAPER OUT ALARM 5-29-17 6:59PM T 1 TANK UNLEADED DELIVERY NEEDED CLEAR 5-20-17 2:34PM T 1 TANK UNLEADED DELIVERY NEEDED ALARM 5-20-17 2:32PM T 3 TANK DIESEL DELIVERY NEEDED CLEAR 5-19-17 3:27PM T 3 TANK DIESEL DELIVERY NEEDED ALARM 5-18-17 4:30PM T 1 TANK UNLEADED DELIVERY NEEDED CLEAR 5-17-17 7:57AM T 1 TANK UNLEADED DELIVERY NEEDED ALARM 5-17-17 5:48AM T 1 TANK UNLEADED DELIVERY NEEDED CLEAR 5-12-17 5:44PM T 1 TANK UNLEADED DELIVERY NEEDED ALARM 5-12-17 5:11PM T 3 TANK DIESEL DELIVERY NEEDED CLEAR 5-10-17 6:14PM T 1 TANK UNLEADED DELIVERY NEEDED CLEAR 5-10-17 6:13PM I20600 JUL 24, 2017 8:50 AM FASTRIP 785 3701 MING AVE BAKERSFIELD 93309 661-397-3699 TANK ALARM HISTORY TANK 1 UNLEADED OVERFILL ALARM JUL 17, 2017 2:16 PM JUL 16, 2017 3:18 AM JUL 1, 2017 4:43 AM LOW PRODUCT ALARM JUL 3, 2017 6:23 PM JUN 27, 2017 5:57 PM JUN 1, 2017 10:30 PM SUDDEN LOSS ALARM JUL 17, 2017 9:47 AM JUL 19, 2016 9:27 AM JUL 29, 2015 10:09 AM HIGH PRODUCT ALARM JUL 17, 2017 9:52 AM JUN 13, 2017 3:29 AM JUN 7, 2017 5:04 AM INVALID FUEL LEVEL MAY 4, 2017 4:33 PM DEC 7, 2016 6:46 PM DEC 4, 2016 9:49 PM PROBE OUT JUL 17, 2017 9:53 AM JUL 17, 2017 9:47 AM JUL 28, 2016 9:35 AM DELIVERY NEEDED JUL 22, 2017 11:22 PM JUL 21, 2017 2:06 PM JUL 12, 2017 10:04 PM MAX PRODUCT ALARM JUN 13, 2017 3:48 AM JUN 7, 2017 5:08 AM MAR 9, 2017 2:53 PM LOW TEMP WARNING JUL 28, 2016 9:36 AM JUL 29, 2015 10:12 AM JUL 31, 2014 9:52 AM TANK 2 PREMIUM OVERFILL ALARM DEC 27, 2016 2:44 PM OCT 28, 2016 10:22 AM SEP 23, 2016 3:26 PM LOW PRODUCT ALARM JAN 30, 2016 1:22 PM OCT 24, 2015 8:29 PM JUL 29, 2015 10:04 AM SUDDEN LOSS ALARM JUL 17, 2017 9:48 AM JUL 19, 2016 9:32 AM JUL 29, 2015 10:04 AM HIGH PRODUCT ALARM JUL 17, 2017 9:55 AM JUL 28, 2016 9:37 AM JUL 19, 2016 10:49 AM INVALID FUEL LEVEL JAN 30, 2016 4:42 PM OCT 24, 2015 8:59 PM JUL 22, 2015 10:24 AM PROBE OUT JUL 17, 2017 9:56 AM JUL 17, 2017 9:48 AM JUL 28, 2016 9:38 AM DELIVERY NEEDED MAY 5, 2016 3:23 PM APR 22, 2016 2:15 PM JAN 30, 2016 5:24 AM LOW TEMP WARNING JUL 17, 2017 9:56 AM JUL 28, 2016 9:39 AM JUL 28, 2016 8:34 AM TANK 3 DIESEL OVERFILL ALARM JUL 28, 2016 9:42 AM JUL 29, 2015 10:01 AM AUG 1, 2012 9:40 AM HIGH PRODUCT ALARM JUL 17, 2017 9:57 AM JUL 19, 2016 10:52 AM JUL 29, 2015 10:01 AM INVALID FUEL LEVEL JUL 31, 2014 9:46 AM JUL 22, 2014 10:34 AM AUG 1, 2013 1:33 PM PROBE OUT JUL 17, 2017 9:57 AM JUL 17, 2017 9:50 AM JUL 28, 2016 9:43 AM DELIVERY NEEDED MAY 18, 2017 4:30 PM MAY 10, 2017 4:37 PM APR 30, 2017 7:22 PM LOW TEMP WARNING JUL 19, 2016 10:54 AM JUL 29, 2015 10:02 AM JUL 22, 2015 10:28 AM I38200 JUL 24, 2017 8:50 AM I30200 JUL 24, 2017 8:50 AM FASTRIP 785 3701 MING AVE BAKERSFIELD 93309 661-397-3699 LIQUID ALARM HISTORY REPORT SENSOR LOCATION 1 UNL STP JUL 17, 2017 10:32 AM SENSOR OUT ALARM JUL 17, 2017 10:01 AM FUEL ALARM JUL 28, 2016 9:51 AM SENSOR OUT ALARM 2 UNL FILL JUL 17, 2017 10:32 AM SENSOR OUT ALARM JUL 17, 2017 10:05 AM FUEL ALARM FEB 16, 2017 3:31 PM FUEL ALARM 3 UNL ANN JUL 17, 2017 2:16 PM HIGH LIQUID ALARM JUL 17, 2017 10:32 AM SENSOR OUT ALARM JUL 17, 2017 10:07 AM HIGH LIQUID ALARM 4 PNL STP JUL 17, 2017 10:32 AM SENSOR OUT ALARM JUL 17, 2017 10:01 AM FUEL ALARM JUL 5, 2017 8:40 PM FUEL ALARM 5 PNL FILL JUL 17, 2017 10:32 AM SENSOR OUT ALARM JUL 17, 2017 10:04 AM FUEL ALARM JUL 17, 2017 9:38 AM FUEL ALARM 6 PNL ANN JUL 17, 2017 10:32 AM SENSOR OUT ALARM JUL 17, 2017 10:08 AM LOW LIQUID ALARM JUL 17, 2017 10:07 AM HIGH LIQUID ALARM 7 DSL STP JUL 17, 2017 10:32 AM SENSOR OUT ALARM JUL 17, 2017 10:02 AM FUEL ALARM JUN 13, 2017 12:57 AM FUEL ALARM 8 DSL FILL JUL 17, 2017 10:32 AM SENSOR OUT ALARM JUL 17, 2017 10:04 AM FUEL ALARM APR 18, 2017 1:28 PM FUEL ALARM 9 DSL ANN JUL 19, 2017 11:48 PM HIGH LIQUID ALARM JUL 17, 2017 10:32 AM SENSOR OUT ALARM JUL 17, 2017 10:08 AM HIGH LIQUID ALARM 10 VENT BOX JUL 17, 2017 10:32 AM SENSOR OUT ALARM JUL 17, 2017 10:19 AM FUEL ALARM JUL 28, 2016 9:51 AM SENSOR OUT ALARM 11 DISP 1-2 JUL 17, 2017 10:32 AM SENSOR OUT ALARM JUL 17, 2017 10:27 AM FUEL ALARM OCT 14, 2016 2:39 PM SENSOR OUT ALARM 12 DISP 3-4 JUL 17, 2017 10:32 AM SENSOR OUT ALARM JUL 17, 2017 10:24 AM FUEL ALARM JUL 28, 2016 9:51 AM SENSOR OUT ALARM 13 DISP 5-6 JUL 17, 2017 10:32 AM SENSOR OUT ALARM JUL 17, 2017 10:28 AM FUEL ALARM JUL 28, 2016 9:51 AM SENSOR OUT ALARM 14 DISP 7-8 JUL 17, 2017 10:32 AM SENSOR OUT ALARM JUL 17, 2017 10:27 AM FUEL ALARM JUL 28, 2016 9:51 AM SENSOR OUT ALARM I31600 JUL 24, 2017 8:51 AM FASTRIP 785 3701 MING AVE BAKERSFIELD 93309 661-397-3699 SMART SENSOR ALARM HISTORY REPORT SENSOR LOCATION 1 VP 1-2 OCT 14, 2016 2:33 PM COMMUNICATION ALARM 2 FM 1-2 3 FM 3-4 4 FM 5-6 5 FM 7-8 JUL 11, 2012 5:01 PM COMMUNICATION ALARM JAN 11, 2012 6:17 PM COMMUNICATION ALARM AUG 17, 2010 10:25 AM COMMUNICATION ALARM I40200 JUL 24, 2017 8:51 AM I40300 JUL 24, 2017 8:51 AM I34200 JUL 24, 2017 8:51 AM I34700 JUL 24, 2017 8:51 AM IV0100 JUL 24, 2017 8:51 AM FASTRIP 785 3701 MING AVE BAKERSFIELD 93309 661-397-3699 ISD ALARM STATUS REPORT EVR TYPE: VACUUM ASSIST ISD TYPE: 01.02 VAPOR PROCESSOR TYPE: NONE OVERALL STATUS :PASS EVR VAPOR COLLECTION :PASS EVR VAPOR CONTAINMENT :PASS ISD MONITOR UP-TIME :100% STAGE I TRANSFERS: 2 of 2 PASS EVR/ISD PASS TIME :100% WARNING ALARMS DATE TIME DESCRIPTION READING VALUE 17-07-18 10:01:09 A/L RATIO GROSS BLOCKAGE FP 5 BLEND3 BLKD 17-07-16 10:01:12 A/L RATIO DEGRADATION FP 5 BLEND3 0.00 17-06-27 10:01:09 A/L RATIO DEGRADATION FP 5 BLEND3 0.77 17-06-26 10:01:09 A/L RATIO DEGRADATION FP 5 BLEND3 0.77 17-06-25 10:01:09 A/L RATIO DEGRADATION FP 5 BLEND3 0.78 17-06-24 10:01:09 A/L RATIO DEGRADATION FP 5 BLEND3 0.80 17-04-19 10:01:09 SENSOR OUT SELFTEST CHECK VAPOR FLOW METER f 1:FM 1-2 17-03-08 10:01:41 SENSOR OUT SELFTEST CHECK VAPOR FLOW METER f 1:FM 1-2 17-03-08 10:01:41 A/L RATIO GROSS BLOCKAGE FP 2 BLEND3 BLKD 17-03-08 10:01:40 A/L RATIO GROSS BLOCKAGE FP 1 BLEND3 BLKD FAILURE ALARMS DATE TIME DESCRIPTION READING VALUE 13-08-20 10:01:35 A/L RATIO GROSS BLOCKAGE FP 3 BLEND3 BLKD 13-03-15 10:02:04 A/L RATIO GROSS BLOCKAGE FP 3 BLEND3 BLKD 11-09-08 10:02:27 VAPOR CONTAINMENT LEAKAGE GROSS FAIL 11-06-28 10:02:43 A/L RATIO GROSS BLOCKAGE FP 8 BLEND3 BLKD 11-06-28 10:02:43 A/L RATIO GROSS BLOCKAGE FP 7 BLEND3 BLKD 11-06-27 10:02:45 A/L RATIO GROSS BLOCKAGE FP 7 BLEND3 BLKD 10-11-01 10:01:09 A/L RATIO GROSS BLOCKAGE FP 2 BLEND3 BLKD 10-11-01 10:01:09 A/L RATIO GROSS BLOCKAGE FP 1 BLEND3 BLKD SHUTDOWN & MISCELLANEOUS EVENTS DATE TIME DESCRIPTION ACTION/NAME 17-07-19 10:01:10 READINESS ISD:PP EVR:PP ISD & EVR READY 17-07-18 12:31:55 COLLECTION TEST HH05 GRADE TEST MANUALLY CLEARED 17-07-18 10:01:09 READINESS ISD:PP EVR:FP CHECK EVR SYSTEM 17-07-17 10:31:44 READINESS ISD:PP EVR:NN EVR READINESS PENDING 17-07-17 10:31:44 ISD STARTUP 17-07-17 10:31:25 ISD SHUTDOWN 17-07-17 08:46:49 COLLECTION TEST HH05 GRADE TEST MANUALLY CLEARED 17-06-28 09:31:42 COLLECTION TEST HH05 GRADE TEST MANUALLY CLEARED 17-04-19 15:12:18 SENSOR OUT TEST MANUALLY CLEARED 17-03-13 09:17:00 TIME CHANGE DETECTED AT: 17-03-13 08:14:48 Jaco 7785 Alarm History After Responses Received: I10200 JUL 24, 2017 10:54 AM FASTRIP 785 3701 MING AVE BAKERSFIELD 93309 661-397-3699 SYSTEM CONFIGURATION SLOT BOARD TYPE POWER ON RESET CURRENT 1 7SMARTSENSOR BD 508342 503071 2 4 PROBE / G.T. 163473 163033 3 INTERSTITIAL BD 201165 200734 4 INTERSTITIAL BD 202252 201743 5 UNUSED 9852520 9814551 6 UNUSED 9818980 9808144 7 UNUSED 9810432 9808123 8 UNUSED 9806239 9810104 9 STP SENSE BOARD 32990 33016 10 RELAY BOARD 14864 14887 11 UNUSED 9809143 9812137 12 UNUSED 9805114 9806784 13 UNUSED 9800513 9807965 14 UNUSED 9800451 9809524 15 UNUSED 9800615 9807332 16 UNUSED 9794766 9806405 COMM 1 ELEC DISP INT. 100821 100758 COMM 2 RS232 SERIAL BD 14966 14972 COMM 3 RS232 SERIAL BD 14864 14887 COMM 4 UNUSED 9808713 9816057 COMM 5 UNUSED 9804828 9806616 COMM 6 UNUSED 9800206 9808660 I90200 JUL 24, 2017 10:54 AM SOFTWARE REVISION LEVEL VERSION 329.02 SOFTWARE# 346329-100-C CREATED - 09.07.01.16.29 S-MODULE# 330160-004-a SYSTEM FEATURES: PERIODIC IN-TANK TESTS ANNUAL IN-TANK TESTS ISD I11100 JUL 24, 2017 10:54 AM FASTRIP 785 3701 MING AVE BAKERSFIELD 93309 661-397-3699 PRIORITY ALARM HISTORY ID CATEGORY DESCRIPTION ALARM TYPE STATE DATE TIME L 8 PIPE DSL FILL SENSOR OUT ALARM CLEAR 7-24-17 10:49AM L 7 STP SUMP DSL STP SENSOR OUT ALARM CLEAR 7-24-17 10:49AM L 6 ANNULAR PNL ANN SENSOR OUT ALARM CLEAR 7-24-17 10:49AM L 4 STP SUMP PNL STP SENSOR OUT ALARM CLEAR 7-24-17 10:49AM L 3 ANNULAR UNL ANN SENSOR OUT ALARM CLEAR 7-24-17 10:49AM L 2 PIPE UNL FILL SENSOR OUT ALARM CLEAR 7-24-17 10:49AM L14 DISP PAN DISP 7-8 SENSOR OUT ALARM CLEAR 7-24-17 10:49AM L 5 PIPE PNL FILL SENSOR OUT ALARM CLEAR 7-24-17 10:49AM L12 DISP PAN DISP 3-4 SENSOR OUT ALARM CLEAR 7-24-17 10:49AM L11 DISP PAN DISP 1-2 SENSOR OUT ALARM CLEAR 7-24-17 10:49AM L10 PIPE VENT BOX SENSOR OUT ALARM CLEAR 7-24-17 10:49AM L 1 STP SUMP UNL STP SENSOR OUT ALARM CLEAR 7-24-17 10:49AM L13 DISP PAN DISP 5-6 SENSOR OUT ALARM CLEAR 7-24-17 10:49AM L 9 ANNULAR DSL ANN SENSOR OUT ALARM CLEAR 7-24-17 10:49AM L 2 PIPE UNL FILL SENSOR OUT ALARM ALARM 7-24-17 10:49AM L 8 PIPE DSL FILL SENSOR OUT ALARM ALARM 7-24-17 10:49AM L 7 STP SUMP DSL STP SENSOR OUT ALARM ALARM 7-24-17 10:49AM L 6 ANNULAR PNL ANN SENSOR OUT ALARM ALARM 7-24-17 10:49AM L14 DISP PAN DISP 7-8 SENSOR OUT ALARM ALARM 7-24-17 10:49AM L12 DISP PAN DISP 3-4 SENSOR OUT ALARM ALARM 7-24-17 10:49AM L11 DISP PAN DISP 1-2 SENSOR OUT ALARM ALARM 7-24-17 10:49AM L 4 STP SUMP PNL STP SENSOR OUT ALARM ALARM 7-24-17 10:49AM L 3 ANNULAR UNL ANN SENSOR OUT ALARM ALARM 7-24-17 10:49AM L10 PIPE VENT BOX SENSOR OUT ALARM ALARM 7-24-17 10:49AM L 1 STP SUMP UNL STP SENSOR OUT ALARM ALARM 7-24-17 10:49AM L 5 PIPE PNL FILL SENSOR OUT ALARM ALARM 7-24-17 10:49AM L 9 ANNULAR DSL ANN SENSOR OUT ALARM ALARM 7-24-17 10:49AM L13 DISP PAN DISP 5-6 SENSOR OUT ALARM ALARM 7-24-17 10:48AM T 1 TANK UNLEADED PROBE OUT CLEAR 7-24-17 10:20AM T 1 TANK UNLEADED PROBE OUT ALARM 7-24-17 10:19AM T 2 TANK PREMIUM PROBE OUT CLEAR 7-24-17 10:18AM T 2 TANK PREMIUM PROBE OUT ALARM 7-24-17 10:18AM T 3 TANK DIESEL PROBE OUT CLEAR 7-24-17 10:17AM T 3 TANK DIESEL PROBE OUT ALARM 7-24-17 10:16AM L10 PIPE VENT BOX FUEL ALARM CLEAR 7-24-17 9:39AM L10 PIPE VENT BOX FUEL ALARM ALARM 7-24-17 9:39AM L 9 ANNULAR DSL ANN LOW LIQUID ALARM CLEAR 7-24-17 9:34AM L 9 ANNULAR DSL ANN LOW LIQUID ALARM ALARM 7-24-17 9:34AM L 9 ANNULAR DSL ANN HIGH LIQUID ALARM CLEAR 7-24-17 9:34AM L 9 ANNULAR DSL ANN LOW LIQUID ALARM CLEAR 7-24-17 9:34AM L 9 ANNULAR DSL ANN HIGH LIQUID ALARM ALARM 7-24-17 9:34AM L 9 ANNULAR DSL ANN LOW LIQUID ALARM ALARM 7-24-17 9:34AM L 6 ANNULAR PNL ANN LOW LIQUID ALARM CLEAR 7-24-17 9:34AM L 6 ANNULAR PNL ANN LOW LIQUID ALARM ALARM 7-24-17 9:34AM L 6 ANNULAR PNL ANN HIGH LIQUID ALARM CLEAR 7-24-17 9:34AM L 6 ANNULAR PNL ANN LOW LIQUID ALARM CLEAR 7-24-17 9:33AM L 6 ANNULAR PNL ANN HIGH LIQUID ALARM ALARM 7-24-17 9:33AM L 6 ANNULAR PNL ANN LOW LIQUID ALARM ALARM 7-24-17 9:33AM L 3 ANNULAR UNL ANN LOW LIQUID ALARM CLEAR 7-24-17 9:33AM L 3 ANNULAR UNL ANN LOW LIQUID ALARM ALARM 7-24-17 9:33AM I11200 JUL 24, 2017 10:54 AM FASTRIP 785 3701 MING AVE BAKERSFIELD 93309 661-397-3699 NON-PRIORITY ALARM HISTORY ID CATEGORY DESCRIPTION ALARM TYPE STATE DATE TIME SYSTEM PRINTER ERROR CLEAR 7-24-17 10:53AM SYSTEM PAPER OUT CLEAR 7-24-17 10:53AM SYSTEM PRINTER ERROR ALARM 7-24-17 10:50AM SYSTEM PAPER OUT ALARM 7-24-17 10:50AM SYSTEM PRINTER ERROR CLEAR 7-24-17 10:50AM SYSTEM PAPER OUT CLEAR 7-24-17 10:50AM SYSTEM PRINTER ERROR ALARM 7-24-17 10:49AM SYSTEM PAPER OUT ALARM 7-24-17 10:49AM T 1 TANK UNLEADED LOW TEMP WARNING CLEAR 7-24-17 10:22AM T 1 TANK UNLEADED LOW TEMP WARNING ALARM 7-24-17 10:20AM T 1 TANK UNLEADED HIGH PRODUCT ALARM CLEAR 7-24-17 9:44AM T 1 TANK UNLEADED HIGH PRODUCT ALARM ALARM 7-24-17 9:44AM T 2 TANK PREMIUM HIGH PRODUCT ALARM CLEAR 7-24-17 9:43AM T 2 TANK PREMIUM HIGH PRODUCT ALARM ALARM 7-24-17 9:43AM T 3 TANK DIESEL HIGH PRODUCT ALARM CLEAR 7-24-17 9:42AM T 3 TANK DIESEL HIGH PRODUCT ALARM ALARM 7-24-17 9:42AM T 3 TANK DIESEL DELIVERY NEEDED CLEAR 7-24-17 9:09AM T 3 TANK DIESEL DELIVERY NEEDED ALARM 7-24-17 9:08AM T 1 TANK UNLEADED DELIVERY NEEDED CLEAR 7-23-17 1:39AM T 1 TANK UNLEADED DELIVERY NEEDED ALARM 7-22-17 11:22PM T 1 TANK UNLEADED DELIVERY NEEDED CLEAR 7-21-17 2:40PM T 1 TANK UNLEADED DELIVERY NEEDED ALARM 7-21-17 2:06PM h 5 OTHER FP5: BLEND3 GROSS COLLECT WARN CLEAR 7-18-17 12:31PM h 5 OTHER FP5: BLEND3 GROSS COLLECT WARN ALARM 7-18-17 10:01AM T 3 TANK DIESEL HIGH PRODUCT ALARM CLEAR 7-17-17 9:57AM T 3 TANK DIESEL HIGH PRODUCT ALARM ALARM 7-17-17 9:57AM T 2 TANK PREMIUM LOW TEMP WARNING CLEAR 7-17-17 9:57AM T 2 TANK PREMIUM LOW TEMP WARNING ALARM 7-17-17 9:56AM T 2 TANK PREMIUM HIGH PRODUCT ALARM CLEAR 7-17-17 9:55AM T 2 TANK PREMIUM HIGH PRODUCT ALARM ALARM 7-17-17 9:55AM T 1 TANK UNLEADED HIGH PRODUCT ALARM CLEAR 7-17-17 9:52AM T 1 TANK UNLEADED HIGH PRODUCT ALARM ALARM 7-17-17 9:52AM h 5 OTHER FP5: BLEND3 DEGRD COLLECT WARN CLEAR 7-17-17 8:46AM h 5 OTHER FP5: BLEND3 DEGRD COLLECT WARN ALARM 7-16-17 10:01AM T 1 TANK UNLEADED DELIVERY NEEDED CLEAR 7-12-17 11:31PM T 1 TANK UNLEADED DELIVERY NEEDED ALARM 7-12-17 10:04PM T 1 TANK UNLEADED DELIVERY NEEDED CLEAR 7-03-17 8:07PM T 1 TANK UNLEADED DELIVERY NEEDED ALARM 7-03-17 4:56PM h 5 OTHER FP5: BLEND3 DEGRD COLLECT WARN CLEAR 6-28-17 9:31AM T 1 TANK UNLEADED DELIVERY NEEDED CLEAR 6-27-17 6:53PM T 1 TANK UNLEADED DELIVERY NEEDED ALARM 6-27-17 4:14PM h 5 OTHER FP5: BLEND3 DEGRD COLLECT WARN ALARM 6-24-17 10:01AM T 1 TANK UNLEADED HIGH PRODUCT ALARM CLEAR 6-13-17 5:01AM T 1 TANK UNLEADED HIGH PRODUCT ALARM ALARM 6-13-17 3:29AM T 1 TANK UNLEADED DELIVERY NEEDED CLEAR 6-09-17 9:09PM T 1 TANK UNLEADED DELIVERY NEEDED ALARM 6-09-17 8:52PM T 1 TANK UNLEADED DELIVERY NEEDED CLEAR 6-08-17 6:43PM T 1 TANK UNLEADED DELIVERY NEEDED ALARM 6-08-17 5:58PM T 1 TANK UNLEADED HIGH PRODUCT ALARM CLEAR 6-07-17 7:00AM T 1 TANK UNLEADED HIGH PRODUCT ALARM ALARM 6-07-17 5:04AM I20600 JUL 24, 2017 10:54 AM FASTRIP 785 3701 MING AVE BAKERSFIELD 93309 661-397-3699 TANK ALARM HISTORY TANK 1 UNLEADED OVERFILL ALARM JUL 17, 2017 2:16 PM JUL 16, 2017 3:18 AM JUL 1, 2017 4:43 AM LOW PRODUCT ALARM JUL 3, 2017 6:23 PM JUN 27, 2017 5:57 PM JUN 1, 2017 10:30 PM SUDDEN LOSS ALARM JUL 24, 2017 9:05 AM JUL 17, 2017 9:47 AM JUL 19, 2016 9:27 AM HIGH PRODUCT ALARM JUL 24, 2017 9:44 AM JUL 17, 2017 9:52 AM JUN 13, 2017 3:29 AM INVALID FUEL LEVEL MAY 4, 2017 4:33 PM DEC 7, 2016 6:46 PM DEC 4, 2016 9:49 PM PROBE OUT JUL 24, 2017 10:19 AM JUL 24, 2017 9:06 AM JUL 17, 2017 9:53 AM DELIVERY NEEDED JUL 22, 2017 11:22 PM JUL 21, 2017 2:06 PM JUL 12, 2017 10:04 PM MAX PRODUCT ALARM JUN 13, 2017 3:48 AM JUN 7, 2017 5:08 AM MAR 9, 2017 2:53 PM LOW TEMP WARNING JUL 24, 2017 10:20 AM JUL 28, 2016 9:36 AM JUL 29, 2015 10:12 AM TANK 2 PREMIUM OVERFILL ALARM DEC 27, 2016 2:44 PM OCT 28, 2016 10:22 AM SEP 23, 2016 3:26 PM LOW PRODUCT ALARM JAN 30, 2016 1:22 PM OCT 24, 2015 8:29 PM JUL 29, 2015 10:04 AM SUDDEN LOSS ALARM JUL 24, 2017 9:07 AM JUL 17, 2017 9:48 AM JUL 19, 2016 9:32 AM HIGH PRODUCT ALARM JUL 24, 2017 9:43 AM JUL 17, 2017 9:55 AM JUL 28, 2016 9:37 AM INVALID FUEL LEVEL JAN 30, 2016 4:42 PM OCT 24, 2015 8:59 PM JUL 22, 2015 10:24 AM PROBE OUT JUL 24, 2017 10:18 AM JUL 24, 2017 9:07 AM JUL 17, 2017 9:56 AM DELIVERY NEEDED MAY 5, 2016 3:23 PM APR 22, 2016 2:15 PM JAN 30, 2016 5:24 AM LOW TEMP WARNING JUL 17, 2017 9:56 AM JUL 28, 2016 9:39 AM JUL 28, 2016 8:34 AM TANK 3 DIESEL OVERFILL ALARM JUL 28, 2016 9:42 AM JUL 29, 2015 10:01 AM AUG 1, 2012 9:40 AM HIGH PRODUCT ALARM JUL 24, 2017 9:42 AM JUL 17, 2017 9:57 AM JUL 19, 2016 10:52 AM INVALID FUEL LEVEL JUL 31, 2014 9:46 AM JUL 22, 2014 10:34 AM AUG 1, 2013 1:33 PM PROBE OUT JUL 24, 2017 10:16 AM JUL 24, 2017 9:09 AM JUL 17, 2017 9:57 AM DELIVERY NEEDED JUL 24, 2017 9:08 AM MAY 18, 2017 4:30 PM MAY 10, 2017 4:37 PM LOW TEMP WARNING JUL 19, 2016 10:54 AM JUL 29, 2015 10:02 AM JUL 22, 2015 10:28 AM I38200 JUL 24, 2017 10:54 AM I30200 JUL 24, 2017 10:54 AM FASTRIP 785 3701 MING AVE BAKERSFIELD 93309 661-397-3699 LIQUID ALARM HISTORY REPORT SENSOR LOCATION 1 UNL STP JUL 24, 2017 10:49 AM SENSOR OUT ALARM JUL 24, 2017 9:19 AM FUEL ALARM JUL 17, 2017 10:32 AM SENSOR OUT ALARM 2 UNL FILL JUL 24, 2017 10:49 AM SENSOR OUT ALARM JUL 24, 2017 9:31 AM FUEL ALARM JUL 17, 2017 10:32 AM SENSOR OUT ALARM 3 UNL ANN JUL 24, 2017 10:49 AM SENSOR OUT ALARM JUL 24, 2017 9:33 AM LOW LIQUID ALARM JUL 24, 2017 9:33 AM HIGH LIQUID ALARM 4 PNL STP JUL 24, 2017 10:49 AM SENSOR OUT ALARM JUL 24, 2017 9:20 AM FUEL ALARM JUL 17, 2017 10:32 AM SENSOR OUT ALARM 5 PNL FILL JUL 24, 2017 10:49 AM SENSOR OUT ALARM JUL 24, 2017 9:32 AM FUEL ALARM JUL 17, 2017 10:32 AM SENSOR OUT ALARM 6 PNL ANN JUL 24, 2017 10:49 AM SENSOR OUT ALARM JUL 24, 2017 9:34 AM LOW LIQUID ALARM JUL 24, 2017 9:33 AM HIGH LIQUID ALARM 7 DSL STP JUL 24, 2017 10:49 AM SENSOR OUT ALARM JUL 24, 2017 9:24 AM FUEL ALARM JUL 17, 2017 10:32 AM SENSOR OUT ALARM 8 DSL FILL JUL 24, 2017 10:49 AM SENSOR OUT ALARM JUL 24, 2017 9:32 AM FUEL ALARM JUL 17, 2017 10:32 AM SENSOR OUT ALARM 9 DSL ANN JUL 24, 2017 10:49 AM SENSOR OUT ALARM JUL 24, 2017 9:34 AM LOW LIQUID ALARM JUL 24, 2017 9:34 AM HIGH LIQUID ALARM 10 VENT BOX JUL 24, 2017 10:49 AM SENSOR OUT ALARM JUL 24, 2017 9:39 AM FUEL ALARM JUL 17, 2017 10:32 AM SENSOR OUT ALARM 11 DISP 1-2 JUL 24, 2017 10:49 AM SENSOR OUT ALARM JUL 24, 2017 9:30 AM FUEL ALARM JUL 17, 2017 10:32 AM SENSOR OUT ALARM 12 DISP 3-4 JUL 24, 2017 10:49 AM SENSOR OUT ALARM JUL 24, 2017 9:24 AM FUEL ALARM JUL 17, 2017 10:32 AM SENSOR OUT ALARM 13 DISP 5-6 JUL 24, 2017 10:48 AM SENSOR OUT ALARM JUL 24, 2017 9:29 AM FUEL ALARM JUL 17, 2017 10:32 AM SENSOR OUT ALARM 14 DISP 7-8 JUL 24, 2017 10:49 AM SENSOR OUT ALARM JUL 24, 2017 9:27 AM FUEL ALARM JUL 17, 2017 10:32 AM SENSOR OUT ALARM I31600 JUL 24, 2017 10:54 AM FASTRIP 785 3701 MING AVE BAKERSFIELD 93309 661-397-3699 SMART SENSOR ALARM HISTORY REPORT SENSOR LOCATION 1 VP 1-2 OCT 14, 2016 2:33 PM COMMUNICATION ALARM 2 FM 1-2 3 FM 3-4 4 FM 5-6 5 FM 7-8 JUL 11, 2012 5:01 PM COMMUNICATION ALARM JAN 11, 2012 6:17 PM COMMUNICATION ALARM AUG 17, 2010 10:25 AM COMMUNICATION ALARM I40200 JUL 24, 2017 10:54 AM I40300 JUL 24, 2017 10:54 AM I34200 JUL 24, 2017 10:54 AM I34700 JUL 24, 2017 10:54 AM IV0100 JUL 24, 2017 10:54 AM FASTRIP 785 3701 MING AVE BAKERSFIELD 93309 661-397-3699 ISD ALARM STATUS REPORT EVR TYPE: VACUUM ASSIST ISD TYPE: 01.02 VAPOR PROCESSOR TYPE: NONE OVERALL STATUS :PASS EVR VAPOR COLLECTION :PASS EVR VAPOR CONTAINMENT :PASS ISD MONITOR UP-TIME :100% STAGE I TRANSFERS: 2 of 2 PASS EVR/ISD PASS TIME :100% WARNING ALARMS DATE TIME DESCRIPTION READING VALUE 17-07-18 10:01:09 A/L RATIO GROSS BLOCKAGE FP 5 BLEND3 BLKD 17-07-16 10:01:12 A/L RATIO DEGRADATION FP 5 BLEND3 0.00 17-06-27 10:01:09 A/L RATIO DEGRADATION FP 5 BLEND3 0.77 17-06-26 10:01:09 A/L RATIO DEGRADATION FP 5 BLEND3 0.77 17-06-25 10:01:09 A/L RATIO DEGRADATION FP 5 BLEND3 0.78 17-06-24 10:01:09 A/L RATIO DEGRADATION FP 5 BLEND3 0.80 17-04-19 10:01:09 SENSOR OUT SELFTEST CHECK VAPOR FLOW METER f 1:FM 1-2 17-03-08 10:01:41 SENSOR OUT SELFTEST CHECK VAPOR FLOW METER f 1:FM 1-2 17-03-08 10:01:41 A/L RATIO GROSS BLOCKAGE FP 2 BLEND3 BLKD 17-03-08 10:01:40 A/L RATIO GROSS BLOCKAGE FP 1 BLEND3 BLKD FAILURE ALARMS DATE TIME DESCRIPTION READING VALUE 13-08-20 10:01:35 A/L RATIO GROSS BLOCKAGE FP 3 BLEND3 BLKD 13-03-15 10:02:04 A/L RATIO GROSS BLOCKAGE FP 3 BLEND3 BLKD 11-09-08 10:02:27 VAPOR CONTAINMENT LEAKAGE GROSS FAIL 11-06-28 10:02:43 A/L RATIO GROSS BLOCKAGE FP 8 BLEND3 BLKD 11-06-28 10:02:43 A/L RATIO GROSS BLOCKAGE FP 7 BLEND3 BLKD 11-06-27 10:02:45 A/L RATIO GROSS BLOCKAGE FP 7 BLEND3 BLKD 10-11-01 10:01:09 A/L RATIO GROSS BLOCKAGE FP 2 BLEND3 BLKD 10-11-01 10:01:09 A/L RATIO GROSS BLOCKAGE FP 1 BLEND3 BLKD SHUTDOWN & MISCELLANEOUS EVENTS DATE TIME DESCRIPTION ACTION/NAME 17-07-24 10:48:39 READINESS ISD:PP EVR:NN EVR READINESS PENDING 17-07-24 10:48:39 ISD STARTUP 17-07-24 10:48:29 ISD SHUTDOWN 17-07-19 10:01:10 READINESS ISD:PP EVR:PP ISD & EVR READY 17-07-18 12:31:55 COLLECTION TEST HH05 GRADE TEST MANUALLY CLEARED 17-07-18 10:01:09 READINESS ISD:PP EVR:FP CHECK EVR SYSTEM 17-07-17 10:31:44 READINESS ISD:PP EVR:NN EVR READINESS PENDING 17-07-17 10:31:44 ISD STARTUP 17-07-17 10:31:25 ISD SHUTDOWN 17-07-17 08:46:49 COLLECTION TEST HH05 GRADE TEST MANUALLY CLEARED SWRCB, January 2006 Spill Bucket Testing Report Form This form is intended for use by contractors performing annual testing of UST spill containment structures. The completed form and printouts from tests (if applicable), should be provided to the facility owner/operator forsubmittal to the local regulatory agency. 1.FACILITY INFORMATION Facility Name:Date of Testing: Facility Address: Facility Contact:Phone: Date Local Agency Was Notified of Testing : Name of Local Agency Inspector (if present during testing): 2.TESTING CONTRACTOR INFORMATION Company Name:Confidence UST Services, Inc. Technician Conducting Test: Credentials1:CSLB Contractor ICC Service Tech. SWRCB Tank Tester Other (Specify) License Number(s):CSLB#804904 ICC# 3.SPILL BUCKET TESTING INFORMATION Test Method Used:Hydrostatic Vacuum Other Test Equipment Used:Lake TestEquipment Resolution:0.0625” Identify Spill Bucket (By Tank Number, Stored Product, etc.) 1234 Bucket Installation Type: Direct Bury Contained in Sump Direct Bury Contained in Sump Direct Bury Contained in Sump Direct Bury Contained in Sump Bucket Diameter: Bucket Depth: Wait time between applying vacuum/water and start of test: Test Start Time (TI): Initial Reading (RI): Test End Time (TF): Final Reading (RF): Test Duration (TF – TI): Change in Reading (RF -RI): Pass/Fail Threshold or Criteria: Test Result: Pass Fail Pass Fail Pass Fail Pass Fail Comments –(include information on repairs made prior to testing, and recommended follow-up for failed tests) CERTIFICATION OF TECHNICIAN RESPONSIBLE FOR CONDUCTING THIS TESTING I hereby certify that all the information contained in this report is true, accurate, and in full compliance with legal requirements. Technician’s Signature:________________________________________________ Date:_________ 1 State laws and regulations do not currently require testing to be performed by a qualified contractor. However, local requirements may be more stringent. #7785/Fastrip#32 07/24/2017 3701MingAvenue Bakersfield,CA93309 OmeroGarcia(661)393-7000 06/08/2017 Shane Gardner AaronPerrigo 8485827-UT Regular 12.00" 12.75" 5min. 9:15 am 9.50" 10:15 am 9.50" 1hour 0.00" 0.0625" Super 12.00" 13.00" 5 min. 9:15 am 9.50" 10:15 am 9.50" 1hour 0.00" 0.0625"0.0625" Diesel 12.00" 12.50" 5min. 9:15 am 10.25" 10:15 am 10.25" 1 hour 0.00" 07/24/2017