Loading...
HomeMy WebLinkAboutCP TEST 2017 AES PLT – 100R Advanced Compliance 3704 Littlefalls Ct. Bakersfield, CA 93312 Ph#661-706-4321 Fax#661-589-9329 I declare under penalty of perjury that I am a licensed tank tester in the State of California and that the information in this report is true and correct to the best of my knowledge. X NAME: Circle Deli LINE #1: 87 UL TECHNICIAN: Bruce W. Hinsley ADDRESS: 1416 Golden State LINE #2: 91 UL LICENSE #: 90-1069 CITY/ ST.: Bakersfield, Ca. LINE #3: TEST DATE: 6/12/2017 THE CONVERSION CONSTANT IS FOUND BY: (60 MIN/HR) / (3790/MIL/GAL) = 0.0158311 (MIN/HOUR (GAL/MIN) Divide the volume differential by the test time (15 minutes) and multiply by 0.0158311, which will convert the volume differential from milliliters per minute to gallons per hour. The conversion constant causes the millimeters and minutes to cancel out PRODUCT TIME PSI START VOL (ml) END VOL (ml) TEST VOL DIFF. (ml) GPH GAIN/LOSS (ml) PASS FAIL 87 UL 11:00 50 212 208 4 -0.002 X “ 11:30 50 208 206 2 -0.002 X COMMENTS: PRODUCT TIME PSI START VOL (ml) END VOL (ml) TEST VOL DIFF. (ml) GPH GAIN/LOSS (ml) PASS FAIL 91 UL 11:45 50 198 190 8 -0.008 X “ 12:15 50 190 184 6 -0.006 X COMMENTS: PRODUCT TIME PSI START VOL (ml) END VOL (ml) TEST VOL DIFF. (ml) GPH GAIN/LOSS (ml) PASS FAIL COMMENTS: