SPECIAL INSPECTION REPORT
Inspection Date: September 22, 2017
Site Name: 2233 D&G Liquors
Address: 2732 Brundage Lane, Bakersfield, CA
The following results for the above location represent the conclusions of the Special Inspection performed
on the Underground Storage Tank Lining, which are to be presented to the regulatory agency.
Tank No. 1
Capacity 12,000 gallons
Dimensions 8’ x 33’
Product Fuel
CCR Title 23-2663 (h) Pass Fail
(1) Tank has been cleaned so that no residue remains on the tank walls X
(2) Determine that tank has been vacuum tested at a vacuum of
5.3 inches of Hg for not less tank one minute X
(3) If the tank is constructed of fiberglass, taking interior diameter measurements
to verify whether the cross-section has compressed by more than 1%
of the original diameter NOT APPLICABLE
(4) Visually checked the internal lining for discontinuity, compression,
tension cracking and corrosion X
(5) Witness ultrasound test – average of 75% or greater of original thickness X
(6) Test for thickness and hardness of the lining in accordance with nationally
recognized industry codes. X
(7) Test the lining using an electrical resistance Holiday Detector in accordance
with nationally recognized industry codes; holidays located, repaired and
re-tested X
Determination:
Tank is suitable for continued use for a minimum of five (5) years ✓
Tank is suitable for continued use for a minimum of five (5) years ONLY if it is
relined or other improvements are made
The tank lining is no longer suitable for continued use and shall be closed in
accordance with Article 7.
Stamp:
_____________________________________
Thomas M. Allen III, Coating Inspector
_____________________________________
Anthony A. Hazelwood II
NACE Corrosion Specialist #4385
To: Sessions
P.O. Box 308
Oceano, CA 93475-0308
SPECIAL INSPECTION REPORT
Inspection Date: September 22, 2017
Site Name: 2233 D&G Liquors
Address: 2732 Brundage Lane, Bakersfield, CA
The following results for the above location represent the conclusions of the Special Inspection performed
on the Underground Storage Tank Lining, which are to be presented to the regulatory agency.
Tank No. 2
Capacity 12,000 gallons
Dimensions 8’ x 33’
Product Fuel
CCR Title 23-2663 (h) Pass Fail
(1) Tank has been cleaned so that no residue remains on the tank walls X
(2) Determine that tank has been vacuum tested at a vacuum of
5.3 inches of Hg for not less tank one minute X
(3) If the tank is constructed of fiberglass, taking interior diameter measurements
to verify whether the cross-section has compressed by more than 1%
of the original diameter NOT APPLICABLE
(4) Visually checked the internal lining for discontinuity, compression,
tension cracking and corrosion X
(5) Witness ultrasound test – average of 75% or greater of original thickness X
(6) Test for thickness and hardness of the lining in accordance with nationally
recognized industry codes. X
(7) Test the lining using an electrical resistance Holiday Detector in accordance
with nationally recognized industry codes; holidays located, repaired and
re-tested X
Determination:
Tank is suitable for continued use for a minimum of five (5) years ✓
Tank is suitable for continued use for a minimum of five (5) years ONLY if it is
relined or other improvements are made
The tank lining is no longer suitable for continued use and shall be closed in
accordance with Article 7.
Stamp:
_____________________________________
Thomas M. Allen III, Coating Inspector
_____________________________________
Anthony A. Hazelwood II
NACE Corrosion Specialist #4385
To: Sessions
P.O. Box 308
Oceano, CA 93475-0308
SPECIAL INSPECTION REPORT
Inspection Date: September 22, 2017
Site Name: 2233 D&G Liquors
Address: 2732 Brundage Lane, Bakersfield, CA
The following results for the above location represent the conclusions of the Special Inspection performed
on the Underground Storage Tank Lining, which are to be presented to the regulatory agency.
Tank No. 3
Capacity 12,000 gallons
Dimensions 8’ x 33’
Product Fuel
CCR Title 23-2663 (h) Pass Fail
(1) Tank has been cleaned so that no residue remains on the tank walls X
(2) Determine that tank has been vacuum tested at a vacuum of
5.3 inches of Hg for not less tank one minute X
(3) If the tank is constructed of fiberglass, taking interior diameter measurements
to verify whether the cross-section has compressed by more than 1%
of the original diameter NOT APPLICABLE
(4) Visually checked the internal lining for discontinuity, compression,
tension cracking and corrosion X
(5) Witness ultrasound test – average of 75% or greater of original thickness X
(6) Test for thickness and hardness of the lining in accordance with nationally
recognized industry codes. X
(7) Test the lining using an electrical resistance Holiday Detector in accordance
with nationally recognized industry codes; holidays located, repaired and
re-tested X
Determination:
Tank is suitable for continued use for a minimum of five (5) years ✓
Tank is suitable for continued use for a minimum of five (5) years ONLY if it is
relined or other improvements are made
The tank lining is no longer suitable for continued use and shall be closed in
accordance with Article 7.
Stamp:
_____________________________________
Thomas M. Allen III, Coating Inspector
_____________________________________
Anthony A. Hazelwood II
NACE Corrosion Specialist #4385