Loading...
HomeMy WebLinkAbout250 COFFEE RD ELD 11-29-17Exclusive Providers for MDleak® and PHDleak® Testing Technologies Page 1 of 2 Test Type: Facility Name: Job #: 3672 Prepared For: PO #: Site Address: City: Primary Test Leak Rate: 0.005 gph State and Zip: CA 93309 Secondary Test Leak Rate: 0.1 gph Start Date: End Date: SYSTEM Tk-1 87 TK-2 91 TK-3 DSL Product Primary:PASS PASS PASS Product Secondary:PASS PASS PASS Vent Primary:PASS PASS PASS Vent Secondary:PASS PASS PASS VR Primary:PASS PASS NA VR Secondary:PASS PASS NA Tank:PASS PASS PASS Turbine Sump:PASS PASS PASS Turbine Sump Elect:PASS PASS PASS Turbine Head:PASS PASS PASS Fill/Vapor Sump:PASS PASS PASS Fill Sump Elect:PASS PASS PASS Fill & Vapor Poppet:PASS PASS NA UDC's:PASS PASS PASS Fill Spill Bucket:PASS PASS PASS Vapor Spill Bucket:PASS PASS NA Vent Box:PASS PASS PASS Certifying Field Technician: Ricardo Gonzalez State Lic. # : Certification Leak Rate: 0.005 gph Certifying Technician Signature: Date: Statement Confirmed by: Date: 1889 N Oracle Road Tucson, AZ 85705 Phone 855-255-5325 FAX: 1-520.509-3720 Sunset Mechanical Facility Certification CONFIDENTIAL California ELD New Construction Test Final Non-GC Detector Test Sully's 250 Coffee Road Bakersfield This is a statement to confirm that the components listed above, at the time of testing, have been tested to a leak sensitivity listed above using the MDleak®and PHDleak®Method. The MDleak ®and PHDleak ®Method is one of the most versatile and comprehensive testing procedure offered to the petroleum industry. All petroleum owners and contractors which utilize the MDleak ®and PHDleak ®Method can be assured that their facility has passed the Nation's highest standard in preventative leak detection. 11/29/2017 11/29/201711/28/2017 11/29/2017 Office use only I declare under penalty of perjury that I am a licensed tank tester in the MDleak ®and PHDleak ®method, a method listed by the NWGLDE organization and that the information contained in this report is true and correct to the best of my knowledge. If you have any questions on the testing please do not hesitate to call. @ 520-207-4878. 04-1695 Exclusive Providers for MDleak® and PHDleak® Testing Technologies Page 2 of 2 250 Coffee Road Log of Repaired Leak/s CONFIDENTIAL Tk-1 87 TK-2 91 TK-3 DSL Tank Volume: 20000 12000 8000 Manufacture: Modern Modern Modern Interstice: Vacuum Vacuum Vacuum Depth To Tank: 47" 49" 49" Tank Dia: 10 ft 10 ft 10 ft Depth to Fuel: Tank Sump Boots Turbine Bravo Smith Red Jacket 8 Gilbarco OPW Smith Smith Smith Fire-Flex OPW EVR: Healy Reference #Date Time Status System Component Manufacture None Reference #Date Time Status System Component Manufacture None 1889 N Oracle Road Tucson, AZ 85705 Phone 855-255-5325 FAX: 1-520.509-3720 Vapor Return / Vent: UDC/Dispensers Information Depth to Ground Water: Manufacture: NA Log of Repaired Leaks Log of Unrepaired Leaks Tank Information Containment Boots: Piping Information Manufacture Spill Buckets: Number of Dispensers: Manufacture: Shear Valve Manufacture: Flex: Product Lines: