HomeMy WebLinkAbout6501 Panama ELD Day 2Exclusive Providers for MDleak® MSleak® DPleak® and
PHDleak® Testing Technologies
Page 1 of 2
Test Type:
Facility Name: Job #: 3722
Prepared For: PO #:
Site Address:
City: Primary Test Leak Rate: .005gph
State and Zip: CA 93312 Secondary Test Leak Rate: .1gph
Start Date:End Date:
SYSTEM TK-1 87 TK-2 91 TK-3 DSL
Product Primary:PASS PASS PASS
Product Secondary:PASS PASS PASS
Vent Primary:PASS PASS PASS
Vent Secondary:PASS PASS PASS
VR Primary:PASS PASS NA
VR Secondary:PASS PASS NA
Tank:PASS PASS PASS
Turbine Sump:PASS PASS PASS
Turbine Sump Elect:PASS PASS PASS
Turbine Head:PASS PASS PASS
Fill/Vapor Sump:PASS PASS PASS
Fill Sump Elect:PASS PASS PASS
Vapor Return Poppet:PASS PASS NA
UDC's:PASS PASS PASS
Fill Spill Bucket:PASS PASS PASS
Vapor Spill Bucket:PASS PASS NA
Vent Box:PASS PASS PASS
Certifying Field Technician: Ricardo Gonzalez State Lic. # :
Certification Leak Rate: .005gph
Certifying Technician Signature: Date:
Statement Confirmed by: Date:
Sunset Mechanical
Facility Certification CONFIDENTIAL
California ELD New Construction Test MSLeak Detector
6501 Panama Lane
6501 Panama Lane
Bakersfield
This is a statement to confirm that the components listed above,at the time of testing,have been tested to a leak
sensitivity listed above using the DPleak®,MDleak®and PHDleak®Method.The DPleak®,MDleak®and PHDleak®
Method is one of the most versatile and comprehensive testing procedure offered to the petroleum industry.All petroleum
owners and contractors which utilize the DPleak®,MDleak®and PHDleak®Method can be assured that their facility has
passed the Nation's highest standard in preventative leak detection.
2/23/2018
2/23/20182/22/2018
2/26/2018
Office use only
I declare under penalty of perjury that I am a licensed tank tester in the DPleak®,MDleak®and PHDleak®method,a
method listed by the NWGLDE organization and that the information contained in this report is true and correct to the best
of my knowledge.
If you have any questions on the testing please do not hesitate to call. @ 855-255-5325.
04-1695
Exclusive Providers for MDleak® MSleak® DPleak® and
PHDleak® Testing Technologies
Page 2 of 2
6501 Panama Lane Log of Repaired Leak/s
CONFIDENTIAL
TK-1 87 TK-2 91 TK-3 DSL
Tank Volume: 20000 12000 8000
Manufacture: Modern Modern Modern
Interstice: Vacuum Vacuum Vacuum
Depth To Tank: 54"53"55"
Tank Dia: 10 ft 10 ft 10 ft
Depth to Fuel:
Tank Sump Boots Turbine
Containment SolutionsBravo Red Jacket
8
Gilbarco
OPW
Bravo
Smith
Smith
Fire-Flex
OPW
EVR: Healy
Reference #Date Time Status System Component Manufacture
126 2/22/18 13:15 Leak Final TK-1 87 Sump Fill bucket to face sheild adapter leaking OPW
127 2/22/18 13:17 Leak Final TK-2 91 Sump Fill bucket to face sheild adapter leaking OPW
Reference #Date Time Status System Component Manufacture
None
Vapor Return / Vent:
UDC/Dispensers Information
Depth to Ground Water:
Manufacture:
Log of Repaired Leaks
Log of Unrepaired Leaks
Tank Information
Containment Boots:
Piping Information
Manufacture
Spill Buckets:
Number of Dispensers:
Manufacture:
Shear Valve Manufacture:
Flex:
Product Lines: