Loading...
HomeMy WebLinkAboutFMC RESULTS 2018IMPACT VALVE LEAK DETECTOR LINE TEST MONITOR CERTIFICATION SPILL BUCKET TEST 11000 N. MoPac Expressway, Suite 500 Austin, Texas 78759 Phone: (512) 451-6334 Fax: (512) 459-1459 Date Printed and Mailed: 1/22/2018 BAKERSFIELD FIRE DEPARTMENT OFFICE OF ENVIRONMENTAL SERVICES INSPECTOR KRIS KARNS 1501 TRUXTUN AVE. BAKERSFIELD, CA 93301 Test Date: 1/16/2018 Order Number: 3437610 Dear Regulator, Enclosed are the results of recent testing performed at the following facility: CARMAX #7281 (CMX7281) 6801 Colony St Bakersfield, CA 93307 In an effort to keep all our record keeping and reporting requirements as current as possible, Tanknology kindly requests you notify Dawn Kohlmeyer in writing at dkohlmeyer@tanknology.com when your CUPA requires all records to be submitted electronically via the CERS database. Your assistance in this endeavor is greatly appreciated. Testing performed: Sincerely, Dawn Kohlmeyer Manager, Field Reporting Product Line Tightness Test Page 1 of 1 Work Order: 3437610 Date: 1/16/2018 Site Name/ID: CARMAX #7281 / CMX7281 Address: 6801 Colony St City: Bakersfield State: CA Zip: 93307 Tank Information Test Method Customer Tank ID Product Name Delivery Type Test Pressure Test Start Time Test End Time Final Leak Rate Test Result(P/F/I) Test was performed per 3rd party certifications as specified in 40 CFR parts 280 and 281 Tank # 1 Line # 1 TLD-1 1 UNLEADED UNLEADED Pressure 50 10:26 10:56 -0.01 Pass Yes Tank # Line # Tank # Line # Tank # Line # Tank # Line # Tank # Line # Technician Comments: Technician Name:Patrick Pfrang Certification #:44642 exp: 4/9/2019 Technician Signature: Environmental Compliance for Petroleum Systems ©2018 Tanknology Inc., Austin, TX.    All rights reserved.    tanknology.com LDT 5000 Field Test Apparatus Line Leak Detector Test Page 1 of 1 Work Order:3437610 Date:1/16/2018 Site Name / ID:CARMAX #7281 / CMX7281 Address:6801 Colony St City:Bakersfield State:CA Zip:93307 Tank ID Product Product Line Tested From Existing/New Mechanical/Electronic Manufacturer/Model Serial No. Pump Operating Pressure (psi) Calibrated Leak (ml/min) Calibrated Leak (gph) Holding PSI *N/A for Electronic LD's Resiliency (ml) *N/A for Electronic LD's Metering PSI *N/A for Electronic LD's Opening Time (sec) *N/A for Electronic LD's Test Results 1 UNLEADED UNLEADED 1 1 Existing Electronic Veeder Root PLLD 312121 29.00 189.0 3.00 Pass Technician Comments: Technician Name:Patrick Pfrang Certification #:44637 Technician Signature:Expire Date:4/10/2019 Environmental Compliance for Petroleum Systems © 2018 Tanknology Inc., Austin, TX.    All rights reserved.    tanknology.com Impact Valve Inspection Impact Valve Operational Inspection Work Order:3437610 Date:1/16/2018 Site Name/ID:CARMAX #7281 Address:6801 Colony St City:Bakersfield State:CA Zip:93307 Dispenser Number Grade Secure Mount? Valve Lock?Pass/ Fail Comments 1/ 87 Pass Fail Not Tested Technician Comments: Technician Name:Patrick Pfrang Signature: Environmental Compliance for Petroleum Systems ©2018 Tanknology Inc., Austin, TX. All rights reserved. tanknology.com Appendix VI (Copies of Monitoring System Certification form and UST Monitoring Plot Plan available at http://www.swrcb.ca.gov.) MONITORING SYSTEM CERTIFICATION For Use By All Jurisdictions Within the State of California Authority Cited: Chapter 6.7, Health and Safety Code; Chapter 16, Division 3, Title 23, California Code of Regulations This form must be used to document testing and servicing of monitoring equipment. A separate certification or report must be prepared for each monitoring system control panel by the technician who performs the work. A copy of this form must be provided to the tank system owner/operator. The owner/operator must submit a copy of this form to the local agency regulating UST systems within 30 days of test date. A. General Information Facility Name:CARMAX #7281 Bldg. No.: Site Address:6801 Colony St City:Bakersfield Zip:93307 Facility Contact Person:Josh Martin - See e-mail Contact Phone No.:661-282-3016 Make/Model of Monitoring System:Veeder Root TLS-350 PLUS Date of Testing/Servicing:1/16/2018 B. Inventory of Equipment Tested/Certified Check the appropriate boxes to indicate specific equipment inspected/serviced: Tank ID:1 UNLEADED - UNLEADED In-Tank Gauging Probe.Model:846390-107 Annular Space or Vault Sensor.Model:794380-303 Piping Sump / Trench Sensor(s).Model:794380-323/304 Fill Sump Sensor(s).Model:794380-323/304 Mechanical Line Leak Detector.Model: Electronic Line Leak Detector.Model:Veeder Root PLLD - Tank Overfill / High-Level Sensor.Model:External Overfill Other (specify equipment type and model in Section E on Page 2). Tank ID: In-Tank Gauging Probe.Model: Annular Space or Vault Sensor.Model: Piping Sump / Trench Sensor(s).Model: Fill Sump Sensor(s).Model: Mechanical Line Leak Detector.Model: Electronic Line Leak Detector.Model: Tank Overfill / High-Level Sensor.Model: Other (specify equipment type and model in Section E on Page 2). Tank ID: In-Tank Gauging Probe.Model: Annular Space or Vault Sensor.Model: Piping Sump / Trench Sensor(s).Model: Fill Sump Sensor(s).Model: Mechanical Line Leak Detector.Model: Electronic Line Leak Detector.Model: Tank Overfill / High-Level Sensor.Model: Other (specify equipment type and model in Section E on Page 2). Tank ID: In-Tank Gauging Probe.Model: Annular Space or Vault Sensor.Model: Piping Sump / Trench Sensor(s).Model: Fill Sump Sensor(s).Model: Mechanical Line Leak Detector.Model: Electronic Line Leak Detector.Model: Tank Overfill / High-Level Sensor.Model: Other (specify equipment type and model in Section E on Page 2). Dispenser ID:1 Dispenser Containment Sensor(s).Model:794380-323/304 Shear Valve(s). Dispenser Containment Float(s) and Chain(s). Dispenser ID: Dispenser Containment Sensor(s).Model: Shear Valve(s). Dispenser Containment Float(s) and Chain(s). Dispenser ID: Dispenser Containment Sensor(s).Model: Shear Valve(s). Dispenser Containment Float(s) and Chain(s). Dispenser ID: Dispenser Containment Sensor(s).Model: Shear Valve(s). Dispenser Containment Float(s) and Chain(s). Dispenser ID: Dispenser Containment Sensor(s).Model: Shear Valve(s). Dispenser Containment Float(s) and Chain(s). Dispenser ID: Dispenser Containment Sensor(s).Model: Shear Valve(s). Dispenser Containment Float(s) and Chain(s). *If the facility contains more tanks or dispensers, copy this form. Include information for every tank and dispenser at the facility. C. Certification - I certify that the equipment identified in this document was inspected/serviced in accordance with the manufacturers’ guidelines. Attached to this Certification is information (e.g. manufacturers' checklists) necessary to verify that this information is correct and a Plot Plan showing the layout of monitoring equipment. For any equipment capable of generating such reports, I have also attached a copy of the report; (check all that apply): System set- up Alarm history report Technician Name (print):Patrick Pfrang Signature: Certification No.:A29052 License. No.:743160 Class 'A' Testing Company Name:Tanknology Phone No.:(800) 800-4633 Testing Company Address:11000 N. MoPac Expressway Suite 500 Date of Testing/Servicing:1/16/2018 Monitoring System Certification Page 1 of 4 12/07 D. Results of Testing/Servicing Software Version Installed:132.00 Complete the following checklist: Yes No*Is the audible alarm operational? Yes No*Is the visual alarm operational? Yes No*Were all sensors visually inspected, functionally tested, and confirmed operational? Yes No*Were all sensors installed at lowest point of secondary containment and positioned so that other equipment will not interfere with their proper operation? Yes No* N/A If alarms are relayed to a remote monitoring station, is all communications equipment (e.g. modem) operational? Yes No* N/A For pressurized piping systems, does the turbine automatically shut down if the piping secondary containment monitoring system detects a leak, fails to operate, or is electrically disconnected? If yes: which sensors initiate positive shut-down? (Check all that apply) Sump/Trench Sensors; Dispenser Containment Sensors. Did you confirm positive shut-down due to leaks and sensor failure/disconnection? Yes; No Yes No* N/A For tank systems that utilize the monitoring system as the primary tank overfill warning device (i.e. no mechanical overfill prevention valve is installed), is the overfill warning alarm visible and audible at the tank fill point(s) and operating properly? If so, at what percent of tank capacity does the alarm trigger? 90% Yes* No Was any monitoring equipment replaced? If yes, identify specific sensors, probes, or other equipment replaced and list the manufacturer name and model for all replacement parts in Section E, below. Yes* No Was liquid found inside any secondary containment systems designed as dry systems? (Check all that apply) Product; Water. If yes, describe causes in Section E, below. Yes No*Was monitoring system set-up reviewed to ensure proper settings? Attach set up reports, if applicable Yes No*Is all monitoring equipment operational per manufacturer's specifications? * In Section E below, describe how and when these deficiencies were or will be corrected. E. Comments: Replaced VR Mag Plus 4 in float kit. Vent sump has VR 794380-323/304 sensors. Monitoring System Certification Page 2 of 4 12/07 F. In-Tank Gauging / SIR Equipment: Check this box if tank gauging is used only for inventory control. Check this box if no tank gauging or SIR equipment is installed. This section must be completed if in-tank gauging equipment is used to perform leak detection monitoring. Complete the following checklist: Yes No*Has all input wiring been inspected for proper entry and termination, including testing for ground faults? Yes No*Were all tank gauging probes visually inspected for damage and residue buildup? Yes No*Was accuracy of system product level readings tested? Yes No*Was accuracy of system water level readings tested? Yes No*Were all probes reinstalled properly? Yes No*Were all items on the equipment manufacturer's maintenance checklist completed? * In the Section H, below, describe how and when these deficiencies were or will be corrected. G. Line Leak Detectors (LLD): Check this box if LLDs are not installed. Complete the following checklist: Yes No* N/A For equipment start-up or annual equipment certification, was a leak simulated to verify LLD performance? (Check all that apply) Simulated leak rate: 3 g.p.h.; 0.1 g.p.h; 0.2 g.p.h. Yes No*Were all LLDs confirmed operational and accurate within regulatory requirements? Yes No*Was the testing apparatus properly calibrated? Yes No* N/A For mechanical LLDs, does the LLD restrict product flow if it detects a leak? Yes No* N/A For electronic LLDs, does the turbine automatically shut off if the LLD detects a leak? Yes No* N/A For electronic LLDs that are programmed for positive shut down, does the turbine automatically shut off if any portion of the monitoring system is disabled or disconnected? Yes No* N/A For electronic LLDs that are programmed for positive shut down, does the turbine automatically shut off if any portion of the monitoring system malfunctions or fails a test? Yes No* N/A For electronic LLDs, have all accessible wiring connections been visually inspected? Yes No*Were all items on the equipment manufacturer's maintenance checklist completed? * In the Section H, below, describe how and when these deficiencies were or will be corrected. H.Comments: Page 3 of 4 12/07 Monitoring System Certification Form: Addendum for Vacuum/Pressure Interstitial Sensors LG 163-1, Enc. II I.Results of Vacuum/Pressure Monitoring Equipment Testing This page should be used to document testing and servicing of vacuum and pressure interstitial sensors. A copy of this form must be included with the Monitoring System Certification Form, which must be provided to the tank system owner/operator. The owner/operator must submit a copy of the Monitoring System Certification Form to the local agency regulating UST systems within 30 days of test date. Manufacturer: Veeder Root Model: 001 System Type: Pressure Vacuum Sensor ID s1 Component(s) Monitored by this Sensor:PRODUCT Sensor Functionality Test Result: Pass Fail Interstitial Communication Test Result: Pass Fail s2 Component(s) Monitored by this Sensor:VETN Sensor Functionality Test Result: Pass Fail Interstitial Communication Test Result: Pass Fail s3 Component(s) Monitored by this Sensor:VAPOR PIPE Sensor Functionality Test Result: Pass Fail Interstitial Communication Test Result: Pass Fail Component(s) Monitored by this Sensor: Sensor Functionality Test Result: Pass Fail Interstitial Communication Test Result: Pass Fail Component(s) Monitored by this Sensor: Sensor Functionality Test Result: Pass Fail Interstitial Communication Test Result: Pass Fail Component(s) Monitored by this Sensor: Sensor Functionality Test Result: Pass Fail Interstitial Communication Test Result: Pass Fail Component(s) Monitored by this Sensor: Sensor Functionality Test Result: Pass Fail Interstitial Communication Test Result: Pass Fail Component(s) Monitored by this Sensor: Sensor Functionality Test Result: Pass Fail Interstitial Communication Test Result: Pass Fail Component(s) Monitored by this Sensor: Sensor Functionality Test Result: Pass Fail Interstitial Communication Test Result: Pass Fail Component(s) Monitored by this Sensor: Sensor Functionality Test Result: Pass Fail Interstitial Communication Test Result: Pass Fail How was interstitial communication verified? Leak Introduced at Far End of Interstitial Space1 Gauge Visual Inspection Other (Describe in Sec. J, below) Vacuum was restored to operating levels in all interstitial spaces: Yes No (If no, describe in Sec. J, below) J. Comments (500 characters max. use additional sheets if needed): Page 4 of 4 1 If the sensor successfully detects a simulated vacuum/pressure leak introduced in the interstitial space at the furthest point from the sensor, vacuum/pressure has been demonstrated to be communicating throughout the interstice. WO: 3437610 SWRCB, January 2006 Spill Bucket Testing Report Form This form is intended for use by contractors performing annual testing of UST spill containment structures. The completed form and printouts from tests (if applicable), should be provided to the facility owner/operator for submittal to the local regulatory agency. 1. FACILITY INFORMATION Facility Name: CARMAX #7281 Date of Testing: 1/16/2018 Facility Address: 6801 Colony St , Bakersfield, CA 93307 Facility Contact: Josh Martin - See e-mail Phone: 661-282-3016 Date Local Agency Was Notified of Testing: 1/4/2018 Name of Local Agency Inspector (if present during testing): No inspector 2. TESTING CONTRACTOR INFORMATION Company Name: TANKNOLOGY INC. Technician Conducting Test: Patrick Pfrang Credentials1: CSLB Contractor ICC Service Tech. SWRCB Tank Tester Other (Specify) License Number(s): 8202676 3. SPILL BUCKET TESTING INFORMATION Test Method Used By: Hydrostatic Vacuum Other Test Equipment Used:Equipment Resolution: Identify Spill Bucket (By Tank Number, Stored Product, etc.) Bucket Installation Type: Bucket Diameter: Bucket Depth: Wait time between applying vacuum/water and start of test Test Start Time (TI): Initial Reading (RI): Test End Time(TF): Final Reading (RF): Test Duration(TF–TI): Change in Reading (RF–RI) : Pass/Fail Threshold or Criteria: Test Result: Spill Box # Tank 1 UNLEADED UNLEADED - Fill 1 - Direct - Below Grade in containment sump Direct Bury Contained in Sump 11.00 15.00 15 min 09:18:00 14.00 in. 10:18:00 14.00 in. 1 hr 0.00 in. +/- 0.00 Pass Spill Box # Direct Bury Contained in Sump min +/- Spill Box # Direct Bury Contained in Sump min +/- Spill Box # Direct Bury Contained in Sump min +/- Comments - (include information on repairs made prior to testing, and recommended follow-up for failed tests) CERTIFICATION OF TECHNICIAN RESPONSIBLE FOR CONDUCTING THIS TESTING I hereby certify that all the information contained in this report is true, accurate, and in full compliance with legal requirements. Technician's Signature:Date:1/16/2018 1State laws and regulations do not currently require testing to be performed by a qualified contractor. However, local requirements may be more stringent. WO: 3437610 Site Diagram (This site diagram is for reference only and is not drawn to scale) Work Order:3437610 Site ID / Name:CMX7281 / CARMAX #7281 Address:6801 Colony St City:Bakersfield State:CA Zip:93307 W.O.# SC1-3437610 Cust Ref#: CMX-171217-002/M102787 I50301 JAN 16, 2018 12:56 PM # 1:CARMAX I50302 JAN 16, 2018 12:56 PM # 2:6801 COLONY ST. I50303 JAN 16, 2018 12:56 PM # 3:BAKERSFIELD,CA 93307 I50304 JAN 16, 2018 12:56 PM # 4: I51700 JAN 16, 2018 12:56 PM SYSTEM TYPE AND LANGUAGE FLAG SYSTEM UNITS U.S. SYSTEM LANGUAGE ENGLISH SYSTEM DATE/TIME FORMAT MON DD YYYY HH:MM:SS xM I50F00 JAN 16, 2018 12:56 PM MON DD YYYY HH:MM:SS xM I10200 JAN 16, 2018 12:56 PM CARMAX 6801 COLONY ST. BAKERSFIELD,CA 93307 SYSTEM CONFIGURATION SLOT BOARD TYPE POWER ON RESET CURRENT 1 4 PROBE / G.T. 162334 162479 2 PLLD SENSOR BD 3893 3886 3 INTERSTITIAL BD 200197 200318 4 INTERSTITIAL BD 199838 199983 5 7SMARTSENSOR BD 505934 506078 6 UNUSED 9315975 9325976 7 UNUSED 9310880 9321327 8 UNUSED 9310751 9321391 9 PLLD POWER BD 100396 100503 10 RELAY BOARD 14999 14978 11 UNUSED 9311493 9324384 12 UNUSED 9315901 9321428 13 UNUSED 9308418 9310351 14 UNUSED 9315277 9322906 15 UNUSED 9307386 9316929 16 UNUSED 9307558 9318279 COMM 1 UNUSED 9315148 9326077 COMM 2 FAXMODEM BOARD 40240 40236 COMM 3 RS232 SERIAL BD 9316116 14849 COMM 4 UNUSED 9307601 9318214 COMM 5 UNUSED 9311493 9322242 COMM 6 UNUSED 9309902 9329633 I60100 JAN 16, 2018 12:57 PM TANK CONFIGURATION DEVICE LABEL CONFIGURED 1 UNLEADED ON 2 OFF 3 OFF 4 OFF I60200 JAN 16, 2018 12:57 PM TANK PRODUCT LABEL TANK PRODUCT LABEL 1 UNLEADED 2 3 4 I60300 JAN 16, 2018 12:57 PM TANK PRODUCT CODE TANK PRODUCT LABEL 1 UNLEADED 1 2 2 3 3 4 4 I60400 JAN 16, 2018 12:57 PM TANK FULL VOLUME TANK PRODUCT LABEL GALLONS 1 UNLEADED 11608 2 0 3 0 4 0 I60700 JAN 16, 2018 12:57 PM TANK DIAMETER TANK PRODUCT LABEL INCHES 1 UNLEADED 120.00 2 0.00 3 0.00 4 0.00 I60900 JAN 16, 2018 12:57 PM TANK THERMAL COEFFICIENT TANK PRODUCT LABEL 1 UNLEADED 0.000700 2 0.000000 3 0.000000 4 0.000000 I61200 JAN 16, 2018 12:57 PM TANK MANIFOLDED PARTNERS TANK PRODUCT LABEL SIPHON MANIFOLDED TANKS LINE MANIFOLDED TANKS 1 UNLEADED NONE NONE 2 NONE NONE 3 NONE NONE 4 NONE NONE I62100 JAN 16, 2018 12:57 PM TANK LOW PRODUCT LIMIT TANK PRODUCT LABEL GALLONS 1 UNLEADED 700 2 0 3 0 4 0 I62200 JAN 16, 2018 12:57 PM TANK HIGH PRODUCT LIMIT TANK PRODUCT LABEL GALLONS 1 UNLEADED 11027 2 0 3 0 4 0 I62300 JAN 16, 2018 12:57 PM TANK OVERFILL LEVEL LIMIT TANK PRODUCT LABEL GALLONS 1 UNLEADED 10447 2 0 3 0 4 0 I62400 JAN 16, 2018 12:57 PM TANK HIGH WATER LEVEL LIMIT TANK PRODUCT LABEL INCHES 1 UNLEADED 0.8 I62800 JAN 16, 2018 12:57 PM TANK MAXIMUM VOLUME LIMIT TANK PRODUCT LABEL GALLONS 1 UNLEADED 11608 2 0 3 0 4 0 I62900 JAN 16, 2018 12:57 PM TANK DELIVERY REQUIRED LIMIT TANK PRODUCT LABEL GALLONS 1 UNLEADED 1160 2 0 3 0 4 0 I70300 JAN 16, 2018 12:57 PM LIQUID TYPE SENSOR LOCATION TYPE 1 STP-SUMP SENSOR TRI-STATE (SINGLE FLOAT) 2 STP HYDRO SENSOR TRI-STATE (SINGLE FLOAT) 3 ANNULAR DUAL POINT HYDROSTATIC 4 FILL-SUMP SENSOR TRI-STATE (SINGLE FLOAT) 5 FILL HYDRO SENSOR TRI-STATE (SINGLE FLOAT) 6 VENT-BOX SENSOR TRI-STATE (SINGLE FLOAT) 7 VENT HYDRO SENSOR TRI-STATE (SINGLE FLOAT) 8 DISPENSOR-PAN SENSOR TRI-STATE (SINGLE FLOAT) 9 DISPENSOR HYDRO SENS TRI-STATE (SINGLE FLOAT) 10 TRI-STATE (SINGLE FLOAT) 11 TRI-STATE (SINGLE FLOAT) 12 TRI-STATE (SINGLE FLOAT) 13 TRI-STATE (SINGLE FLOAT) 14 TRI-STATE (SINGLE FLOAT) 15 TRI-STATE (SINGLE FLOAT) 16 TRI-STATE (SINGLE FLOAT) I72100 JAN 16, 2018 12:58 PM SMART SENSOR CONFIGURATION DEVICE LABEL CONFIGURED 1 PRODUCT ON 2 VENT ON 3 VAPOR PIPE ON 4 OFF 5 OFF 6 OFF 7 OFF 8 ATMP ON I72200 JAN 16, 2018 12:58 PM SMART SENSOR LABEL DEVICE LABEL 1 PRODUCT 2 VENT 3 VAPOR PIPE 4 5 6 7 8 ATMP I78500 JAN 16, 2018 12:58 PM PRESSURE LINE LEAK TANK NUMBER LINE TANK NUMBER Q 1:UNLEADED 1 Q 2:UNLEADED 1 Q 3: NONE I72900 JAN 16, 2018 12:58 PM VACUUM SENSOR PUMP NUMBER DEVICE LABEL PUMP NUMBER 1 PRODUCT Q 2:UNLEADED 2 VENT Q 2:UNLEADED 3 VAPOR PIPE Q 2:UNLEADED I72A00 JAN 16, 2018 12:58 PM VACUUM SENSOR VOLUME DEVICE LABEL VOLUME 1 PRODUCT 104.9 GALLONS 2 VENT 13.8 GALLONS 3 VAPOR PIPE 55.2 GALLONS I72B00 JAN 16, 2018 12:58 PM VACUUM SENSOR RELIEF VALVE PRESENT DEVICE LABEL RELIEF VALVE 1 PRODUCT NO 2 VENT NO 3 VAPOR PIPE NO I72C00 JAN 16, 2018 12:58 PM VACUUM SENSOR RELIEF VALVE PRESSURE DEVICE LABEL RELIEF VALVE PRESSURE 1 PRODUCT -9.0 PSI 2 VENT -9.0 PSI 3 VAPOR PIPE -9.0 PSI I90200 JAN 16, 2018 12:58 PM SOFTWARE REVISION LEVEL VERSION 132.00 SOFTWARE# 346132-100-A CREATED - 11.05.27.16.29 S-MODULE# 330160-060-A SYSTEM FEATURES: PERIODIC IN-TANK TESTS ANNUAL IN-TANK TESTS PLLD 0.10 AUTO 0.20 REPETITIV WPLLD 0.10 AUTO 0.20 REPETITIV I20600 JAN 16, 2018 12:58 PM CARMAX 6801 COLONY ST. BAKERSFIELD,CA 93307 TANK ALARM HISTORY TANK 1 UNLEADED HIGH WATER ALARM JAN 16, 2018 10:48 AM AUG 8, 2017 7:40 AM JAN 17, 2017 9:26 AM OVERFILL ALARM JAN 16, 2018 11:18 AM AUG 28, 2017 3:19 PM JAN 17, 2017 9:34 AM LOW PRODUCT ALARM JAN 17, 2017 9:36 AM JAN 17, 2017 9:21 AM SUDDEN LOSS ALARM JAN 16, 2018 10:40 AM AUG 8, 2017 9:53 AM JAN 17, 2017 9:21 AM HIGH PRODUCT ALARM JAN 16, 2018 11:18 AM JAN 17, 2017 9:34 AM PROBE OUT JAN 16, 2018 10:43 AM HIGH WATER WARNING JAN 16, 2018 10:48 AM AUG 8, 2017 7:40 AM JAN 17, 2017 9:26 AM DELIVERY NEEDED JAN 16, 2018 11:21 AM JAN 16, 2018 10:45 AM JAN 16, 2018 10:41 AM MAX PRODUCT ALARM JAN 16, 2018 11:18 AM JAN 16, 2018 10:41 AM JAN 17, 2017 9:35 AM TANK 5 TANK 6 TANK 7 TANK 8 I30200 JAN 16, 2018 12:59 PM CARMAX 6801 COLONY ST. BAKERSFIELD,CA 93307 LIQUID ALARM HISTORY REPORT SENSOR LOCATION 1 STP-SUMP SENSOR JAN 16, 2018 9:23 AM FUEL ALARM JAN 16, 2018 9:23 AM SENSOR OUT ALARM AUG 8, 2017 9:39 AM SENSOR OUT ALARM 2 STP HYDRO SENSOR JAN 16, 2018 10:03 AM SENSOR OUT ALARM JAN 16, 2018 9:24 AM FUEL ALARM JAN 17, 2017 11:53 AM SETUP DATA WARNING 3 ANNULAR JAN 16, 2018 10:03 AM SENSOR OUT ALARM JAN 16, 2018 9:29 AM LOW LIQUID ALARM JAN 16, 2018 9:29 AM HIGH LIQUID ALARM 4 FILL-SUMP SENSOR JAN 16, 2018 9:26 AM SENSOR OUT ALARM JAN 16, 2018 9:26 AM FUEL ALARM JAN 16, 2018 9:25 AM SENSOR OUT ALARM 5 FILL HYDRO SENSOR JAN 16, 2018 10:03 AM SENSOR OUT ALARM JAN 16, 2018 9:56 AM FUEL ALARM JAN 17, 2017 9:46 AM SENSOR OUT ALARM 6 VENT-BOX SENSOR JAN 16, 2018 9:30 AM SENSOR OUT ALARM JAN 16, 2018 9:30 AM FUEL ALARM JAN 16, 2018 9:30 AM SENSOR OUT ALARM 7 VENT HYDRO SENSOR JAN 16, 2018 10:03 AM SENSOR OUT ALARM JAN 16, 2018 9:31 AM FUEL ALARM JAN 17, 2017 9:46 AM SENSOR OUT ALARM 8 DISPENSOR-PAN SENSOR JAN 16, 2018 9:38 AM SENSOR OUT ALARM JAN 16, 2018 9:38 AM FUEL ALARM JAN 16, 2018 9:38 AM SENSOR OUT ALARM 9 DISPENSOR HYDRO SENS JAN 16, 2018 10:03 AM SENSOR OUT ALARM JAN 16, 2018 9:39 AM FUEL ALARM JAN 17, 2017 9:46 AM SENSOR OUT ALARM I31600 JAN 16, 2018 12:59 PM CARMAX 6801 COLONY ST. BAKERSFIELD,CA 93307 SMART SENSOR ALARM HISTORY REPORT SENSOR LOCATION 1 PRODUCT JAN 16, 2018 9:34 AM NO VACUUM ALARM JAN 16, 2018 9:34 AM HIGH LIQUID ALARM JAN 17, 2017 8:38 AM NO VACUUM ALARM 2 VENT JAN 16, 2018 9:34 AM NO VACUUM ALARM JAN 16, 2018 9:34 AM HIGH LIQUID ALARM JAN 17, 2017 8:38 AM NO VACUUM ALARM 3 VAPOR PIPE JAN 16, 2018 9:34 AM NO VACUUM ALARM JAN 16, 2018 9:34 AM HIGH LIQUID ALARM JAN 17, 2017 8:38 AM NO VACUUM ALARM 8 ATMP I38200 JAN 16, 2018 12:59 PM CARMAX 6801 COLONY ST. BAKERSFIELD,CA 93307 PRESSURE LINE LEAK ALARM HISTORY REPORT Q 2:UNLEADED JAN 16, 2018 10:16 AM PLLD SHUTDOWN ALARM JAN 16, 2018 10:16 AM GROSS LINE FAIL JAN 16, 2018 10:03 AM PLLD SHUTDOWN ALARM JAN 16, 2018 9:56 AM PLLD SHUTDOWN ALARM JAN 16, 2018 9:38 AM PLLD SHUTDOWN ALARM JAN 16, 2018 9:38 AM PLLD SHUTDOWN ALARM JAN 16, 2018 9:23 AM PLLD SHUTDOWN ALARM AUG 8, 2017 9:39 AM PLLD SHUTDOWN ALARM AUG 8, 2017 9:37 AM PLLD SHUTDOWN ALARM AUG 8, 2017 7:37 AM PLLD SHUTDOWN ALARM