HomeMy WebLinkAbout1.2-7291 Record Drawinglu Know what's below. Call before you dig. CITY OF BAKERSFIELD COUNTY OF KERN CALIFORNIA FOR TENTATIVE TRACT N0. 7291 COORDINATION NOTE: CONTRACTOR TO COORDINATE CONSTRUCTION OF THIS PROJECT WITH THE STREET PLANS FOR BOTH TRACT 7291 AND FOR THE MINI STORAGE FACILITY AT 15000 STOCKDALE HIGHWAY INDEX OF SHEETS 1. COVER SHEET 2. NOTES 3. STOCKDALE HIGHWAY PLAN AND PROFILE SHEET 4. CLAUDIA AUTUMN PLAN & PROFILE SHEET 1 5. CLAUDIA AUTUMN PLAN & PROFILE SHEET 2 6. DETAIL SHEET BENCHMARK BENCHMARK: TOP OF BRASS DISC LOCATED AT THE SOUTHEAST CORNER OF PROJECT SITE, AND THE 10' OFFSET LINE (WEST) FROM THE CENTERLINE OF CLAUDIA AUTUM DRIVE (40' WEST OF THE EAST RIM AT THE INTERSECTION WITH STOCKDALE HIGHWAY. ELEVATION IS 356.69' (NAVD88) THE BENCHMARK DERIVED FOR THIS PROJECT LOCATION WAS DERIVED USING NGS' ONLINE POSITIONING USERS SERVICE (OPUS). THE ELEVATIONS PROVIDED ARE BASED ON THE NAVD88 DATUM AND ARE DERIVED FROM POST PROCESSED GPS SOLUTIONS. THE BASE STATIONS USED FOR THIS DERIVATION WERE PID-DM7566, PID-DM6180, PID-DM6177 (EPOCH 2002.0000, GEOID09). BASIS OF BEARING A BEARING OF S 89° 29'34'E SHOWN FOR THE SOUTH LINE OF THE SOUTHEAST QUARTER OF SECTION 34, T29S., R.26E., M.D.BAM., ON THE MAP FILED IN BOOK 10 OF RECORDS OF SURVEYS AT PAGES 197 AND 198, IN THE OFFICE OF THE KERN COUNTY RECORDER WAS USED AS THE BASIS OF BEARINGS ON THIS MAP. MATERIALS LIST ITEM DESCRIPTION QUANTITY UNIT 1 Install Catch Basin 1.0 E.A. 2 Install 18" RCP SD Pipe 28.0 LF. 3 6"PVC Sanitary Sewer Pipe 583.0 L.F. 4 48" Sanitary Sewer Manhole 2.0 E.A 5 Connect to Existing Sewer 1.0 E.A 6 Install 4" PVC Sewer Lateral 735.0 L.F. 7 Install City Standard SS Cleanout 1.0 E.A LIST OF CITY OF BAKERSFIELD STANDARD DETAILS SIN -1 SW -2 SW -3 SW -5 SW -6 SW -7 0-14 D-16 NOTE: 1. PRIOR TO THE START OF ANY PHASE OF CONSTRUCTION, THE CITY CONSTRUCTION INSPECTION DEPARTMENT SHALL BE GIVEN 24 HOURS NOTICE. TELEPHONE 326-3049 2. ALL MATERIALS SUPPLIED FOR THIS PROJECT REQUIRE A CERTIFICATE OF COMPLIANCE STATING THAT THE REQUIREMENTS AND STANDARDS SET FORTH BY THE CITY OF BAKERSFIELD HAVE BEEN MET. JOHNSON RD PROJECTITE WESTSME PKWY TRACT 7 91 SHEET5 TML�AVE `,Lil LLL CD SHEET4 SHF03 STOCKDALE HWY fflH jai rTITf.'^ (�RT/v z KERN RIVER VICINITY MAP N.T.S. > i z w t N 0 H N N � �n LLJ N m <O cD y QX m ti Y QCr- m U ZD = m LOT 18 L0716 LOT 14 LOT 12 LOT 10 LOT 8 m LOT 6 H F— LOT 1 LOT 15 LOT 13 LOT 11 ZD LISH d LOT 7 LOT', O Z ---t 7¢ g'r 'Q CO LTJ z U IY 3zC Q a LLI 0 MLLE U U o -_ AUTUMN RD — _ _ _ _CLAUDIA _ z 0 NORTH ENGINEERS STATEMENT THESE PLANS AND SPECIFICATIONS WERE PREPARED BY ME OR LINER MY DIRECTION AND TO THE BEST OF MY KNOWLEGE AND BELIEF COMPLY WITH THE CITY OF BAKERSFIELD ORDINANCES, STANDARDS, AND DESIGN CRITERIA AND INCLUDE ALL IMPROVEMENT REQUIREMENTS OF THE ADVISORY AGENCY OR OTHER REVIEW BOARD. I AM RESPONSIBLE FOR ALL CALCULATIONS AND DRAWINGS ON THESE PLANS AND ANY ERRORS, OMMISSIONS OR VIOLATIONS OF THOSE ORDINANCES, STANDARDS AND DESIGN CRITERIA SHALL BE CORRECTED DURING APPROVED BY: STEVEN d. MACIAS RC.E. 83360 DATE KEY MAP N.T.S. LOT4 I LOT 3 I LOT 2 ILOT1 APPROVED BY: NICOLAS FIDLER PUBLIC WORKS DIRECTOR DATE R.C.E. 6169 EXP 12/31716 REVIEWED BY: ASSISTANT PUBLIC WORKS DIRECTOR DATE RECORDS NO. PLOT DATE: Sep 15, 2016 JOB No: 14292 FILE NAME: 142K -0 -0 -SS CV SCALE: NONE SHEET NO.: 1 OF 6 i z w t N 0 H N N � �n LLJ N m <O cD y QX m ti Y QCr- m U ZD m o w o m w H F— z PLOT DATE: Sep 15, 2016 JOB No: 14292 FILE NAME: 142K -0 -0 -SS CV SCALE: NONE SHEET NO.: 1 OF 6 i z 0 �n LLJ cD o QCr- m ZD o Z_ H F— z ZD W d en Q m Z ---t 7¢ g'r 'Q CO LTJ z O IY 3zC Q a LLI 0 MLLE U U PLOT DATE: Sep 15, 2016 JOB No: 14292 FILE NAME: 142K -0 -0 -SS CV SCALE: NONE SHEET NO.: 1 OF 6 STANDARD NOTES 1.GENERAL CONTRACTOR WILL FURNISH ALL MATERIALS, TOOLS. LABOR, EQUIPMENTAND SUPERVISION NECESSARY TO COMPLETE INSTALLATION. UNDERGROUND SERVICE ALERT (USA) SHALL BE NOTIFIED AT LEAST 2 WORKING DAYS BEFORE CONSTRUCTION. TELEPHMEEIA 227-2600 OR USA TO L CONTRACTOR TO CALL F OCATEAND POTHOLE ALL MARKED UTILITIES THAT CROSS OR ARE WITHIN 5' HORIZONTAL DISTANCE OF SEWER AND STORM DRAIN LINES. VERTICAL AND HOHRONTAL LOCATION SHALL BE ASCERTAINED BY THE CONTRACTOR AHEAD OF ANY EXCAVATIONS TO VERIFY THAT THE PROPOSED DESIGN DOES NOT CONFLICT WITH ANY UTILITIES. IN THE EVENT A CONFLICT EXISTS THE ENGINEER SHALL BE NOTIFIED IN ORDER TO REDESIGN THE ALIGNMENT. IF RELOCATION OF EXISTING UTILITIES IS DEEMED NECESSARY ME CONTRACTOR SHALL BE COMPENSATED FOR INSTRUCTED RELOCATION. IF REDESIGN OF THE ALIGNMENT REQUIRES ADDITIONAL FITTINGS, PIPE OR EXCAVATION THE CONTRACTOR SHALL BE COMPENSATED FOR REVISION. IN THE EVEN A UTILITY IS DAMAGED THE CONTRACTOR SHALL BE WHOLLY RESPONSIBLE FOR ITS REPAIR, CONTRACTOR SHALL VERIFY LOCATIONS AND ELEVATIONS OF EXISTING SEWER LINES THAT THE NEW SYSTEM TIES INTO PRIOR i0 TRENCHING. ANY DISCREPANCIES SHALL BE REPORTED i0 THE ENGINEER SO THAT MY NECESSARY ADJUSTMENTS MAY BE AIDE. UTILITIES SHALL RE THOROUGHLY RESEARCHED AND LOCATED BY CONTRACTOR PRIOR i0 TRENCHING. CROSSING UTILITIES SHALL BE DAYLIGHTED AND CHECKED FOR GRADE, BY CONTRACTOR PRIOR TO TRENCHING ALL EXISTING IMPROVEMENTS (CURB. GUTTER. SIDEWALK, CROSS GUTTER, FENCES. ETC.) THAT ARE REMOVED, DAMAGED, OR UNDERCUT SHALL BE REPAIRED OR REPLACED AS DIRECTED BY THE CITY ENGINEER. ALL EXISTING PAVING AND SURFACING REMOVED, DAMAGED, OR UNDERCUT SHALL BE REPLACED IN ACCORDANCE WITH THE CIN OF BAKERSFIELD STANDARD DRAWING STS, EXCEPT AS NOTED ON PLANS. 24 HOUR NOTICE: PRIOR TO THE START OF ANY PHASE OF CONSTRUCIT N. THE CRY CONSTRUCTION INSPECTION SECTION SHALL BE GIVEN AT 24 HOURS NOTICE. THE SECTION MAY SE NOTIFIED AT (881)9263049. COMPACTION TESTS SHALL BE THE RESPONSIBILITY OF THE DEVELOPER/SUBDIVIDER/CONTRACTOR. THE NUMBER AND LOCATION OF REQUIRED TESTS SHALL BE DETERMINED BY THE CITY ENGINEER. 2. STANDARD DETAILS THE FOLLOWING CITY OF BAKERSFIELD STANDARDS SHALL BE CONSIDERED PART OF THESE PLANS: SW -1, SW -2, SW -3, SW -5, SW -S SW -7, D-14 AND D -i6 3. VCP INSTALLATION MATERIALS: THE PIPE AND FITTINGS SHALL BE EXTRA STRENGTH VITRIFIED CLAY CONFORMING TO CURRENT ASTM SPECIFICATIONS CdM AND SHALL BE INSTALLED IN CONFORMANCE WITH THE PROVISIONS OF SECTION71 OF THE STANDARD SPECIFICATIONS OF THE STATE OF CALIFORNIA, DEPARTMENT OF TRANSPORTATION, CURRENT EDITION AND CURRENT ASTM SPECIFICATION C-12 JOINTS: THE PIPE AND FITTINGS SHALL HAVE A SOCKET END AND A SPIGOT END WITH COMPRESSION JOINTS CONFORMING TO THE CURRENT ASTM SPECIFICATION Cd 5 THE PIPE AND FITTINGS FOR B', W. 10', AND 12" SANITARY SEWER MAINS MAY BE PLAIN -END WITH COMPRESSION COUPLINGS CONFORMING TO THE CURRENT ASTM SPECIFICATION "M EXCEPTING THAT A STAINLESS STEEL SHEAR RING AS MANUFACTURED BY MISSION CLAY PRODUCTS CORPORATION FOR THE NMINUNE' BANOSEAL COMPRESSION COUPLING, OR APPROVED EQUAL, SHALL BE REQUIRED. THE PIPE AND FITTINGS FOR PRIVATE SMITARY SEWER HOUSE OR BUILDING LATERALS MAY BE PLAIN -END WITH COMPRESSION COUPLINGS CONFORMING WITH THE CURRENT ASTM SPECIFICATION "25 (STAINLESS STEEL SHEAR RINGS ARE NOT REQUIRED) 4. ABS PIPE INSTALLATION MATERIALS: PIPE AND FITTINGS SHALL MEET THE REQUIREMENTS OF THE CURRENT ASTM SPECIFICATIONS D-2680 AND 0-2751, PIPE AND FITTINGS SHALL BE HOMOGENOUS THROUGHOUT AND FREE FROM CRACKS, HOLES, FOREIGN INCLUSIONS OR OTHER INJURIOUS DEFECTS. FITTINGS SHALL BE INJECTION MOLDED AND SHALL BEINSIAL ED L IN LINE ON NEW PIPELINES' CUT -IN FIRINGS ARE NOT PERMITTED. JOINTS. USE ONLY SOLVENT WELDED JOINTS. THE ASSEMBLY OF JOINTS SHALL BE IN ACCORDANCE WITH THE MANUFACTURER'S RECOMMENDATIONS. WHERE ABS PIPE CONNECTS TO VCP, USE COUPLINGS APPROVED BY THE CITY OF BAKERSFIELD. INSTALLATION: PIPE AND FITTINGS SHALL BE INSTALLED IN ACCORDANCE WITH THE CURRENT ASTM SPECIFICATION D 321. ONLY CLASS 1, 11, AND III EMBEDMENT MATERVLLS SHALL BE CONSIDERED SUITABLE. 5. PVC PIPE INSTALLATION: MATERIALS: PIPE AND FITTINGS SHALL MEET THE REQUIREMENTS OF THE CURRENTASTM SPECIFICATION INWM FOR SDR W. PIPE AND FITTINGS SHALL BE HOMOGENOUS THROUGHOUT AND FREE FROM CRACKS, HOLES, FOREIGN INCLUSIONS OR OTHER INJURIOUS DEFECTS. FITTINGS SHALL BE INJECTION MOLDED AND SHALL BE INSTALLED IN LINE ON NEW PIPELINES; CUT -IN FITTINGS ME NOT PERMITTED. JOINTS: USE ONLY ELASTOMERIC GASKET JOINTS. THE ASSEMBLY OF JOINTS SHALL BE IN ACCORDANCE WITH THE MANUFACTURERS RECOMMENDATIONS WHERE PVC PIPE CONNECTS TO VCP PIPE, USE COUPLINGS APPROVED BY THE CIN OF BAKERSFIELD. INSTALLATION: PIPE AND FITTINGS SHALL SE INSTALLED IN ACCORDANCE WITH THE CURRENT ASTM SPECIFICATION D-2321. ONLY CLASS 1, II, AND III EMBEDMENT MATERIALS WILL BE CONSIDERED SUITABLE. 6. REINFORCED CONCRETE PIPE WITH PVC LINING: PIPE WITH PCV LINING SHALL MEET THE FOLLOWING REQUIREMENTS: I.A. MATERIALS. REINFORCED CONCRETE PIPE (RCP) SHALL BE EITHER CLASS IV OR CLASS V WITH WALLS -EF OR 'C'. RCP SHALL MEET MTM G76 FOR STRENGTH, MTM C-361 OR AWAIA CXQ EXCEPT TEST PRESSURE SHALL BE 5 PSI FOR RUBBER GASKETS, AND LINER TESTS IN ACCORDMCE WITH THE PARAGRAPHS. P SHALL BE WET CASs VIBRATED ANO STEAM OR WATER CURED. JOINTS FOLLOWING ARND SPIGOT IPE HAL SHALL BE BELL AND SPIGOT DESIGN WITH A CONTAINED O-RING GASKET. PVC LINER SHALL BE CAST INTO THE WALL OF THE RCP AND SHALL COVER 360' OF THE PIPE. ALL WORK FOR AND IN CONNECTION WITH THE INSTALLATION OF THE LINING IN CONCRETE PIPE AND FIELD SEALING AND WELDING OF JOINTS SHALL BE DONE IN STRICT CONFORMITY WITH ALL APPLICABLE SPECIFICATIONS, INSTRUCTION AND RECOMMENDATIONS OF THE LINING MANUFACTURER LINER SHALL MEET THE FOLLOWING REQUIREMENTS: I.B. PHYSICAL PROPERTIES OF LINER. ALL PLASTIC LINER PLATE SHEETS. WELDING STRIPS AND OTHER ACCESSORY ITEMS SHALL HAVE THE FOLLOWING PHYSICAL PROPERTIES WHEN TESTED AT 77' s 5 (25'C t 3). PROPERTY INITIALP( M. 1.C) TENSILE STRENGTH 2200 PSI MIN. 21M PSI MIN. (15 MPA MIN.) (14.5 MPA MIN.) ELONGATIONAT BREAK "% MIN, 200% MIN. SHORE DUROMETER. TYPE D (WITH RESPECT TO INITIAL LEST RESULT) ISEC. 50.60 t COSEC. 3550 35 WEIGHT CHANGE ±IS TENSILE SPECIMENS SHALL BE PREPARED MD TESTED IN ACCORDANCE WITH ASTM D412 USING DIE S. WEIGHT CHANGE SPECIMENS SHALL BE 1 -INCH (25MM) BY X;NCH (75MM) SAMPLES. SPECIMENS FOR TESTING OF INITIAL PHYSICAL PROPERTIES MAY BETAKEN FROM LINER PLATE SHEET AND WELDING STRIP AT ANY TIME PRIOR TO FINAL ACCEPTANCE OF THE WORK. LINER PLATE LOCKING EXTENSIONS EMBEDDED IN CONCRETE SHALL WITHSTAND A TEST PULL OF ALL LEAST IN POUNDS PER LINEAR INCH (1800 KOM), APPLIED PERPENDICULARLY TO THE CONCRETE SURFACE FOR A PERIOD OF ONE MINUTE, WITHOUT RUPTURE OF THE LOCKING EXTENSIONS OR WITHDRAWAL FROM EMBEDMENT. THIS TEST SHALL BE MADE ATA TEMPERATURE OF 70' -80' F (21' - 27'C)INCLUSW. ALL PLASTIC LINER PLATE SHEETS INCLUDING LOCKING EXTENSIONS ALL JOINT CORNER AND WELDING STRIPS SHALL BE FREE OF CRACKS, CLEAVAGES, OR OTHER DEFECTS ADVERSELY AFFECTING THE PROTECTIVE CHARACTERISTICS OF THE MATERIAL. THE ENGINEER MAYAUTHORIZE THE REPAIR OF SUCH DEFECTS BY APPROVED METHODS. INE LINING SHALL HAVE GOOD IMPACT RESISTANCE, SHALL BE FLEXIBLE AND SHALL HAVE AN ELONGATION SUFFICIENT TO BRIDGE UP TO'/.INCH (6 MM) SETTLING CRACKS, WHICH MAY OCCUR IN THE PIPE OR IN THE JOINT AFTER INSTALLATIONS, WITHOUT DAMAGE TO THE LINING. IC. CHEMICAL RESISTANCE OF THE LINER:' AFTER CONDITIONS i0 CONSTANT WEIGHT AT 110' F (43' C), TENSILE SPECIMENS AND WEIGHT CHANGE SPECIMENS SHALL BE EXPOSED TO THE FOLLOWING SOLUTIONS FOR A PERIOD OF 112 DAYS AT]7'Ft (25'C3.3). AT 28 -DAY INTERVALS, TENSILE SPECIMENS ANO WEIGHT CHANGE SPECIMENS SHALL BE REMOVED FROM EACH OF THE CHEMICAL SOLUTIONS MD TESTED IN ACCORDANCE WITH SECTION 7-2.03(1.0) PARA. 2 ABOVE. IF ANY SPECIMEN FATS TO MEET THE 112 -DAY REQUIREMENTS BEFORE COMPLETION OF THE I IZ4)AY EXPOSURE, THE MATERIAL WILL BE SUBJECT TO REJECTION, CHEMICALSOLUTIW CONCENTRATION SULFURIC ACID 20%" SODIUM HYDROXIDE 5% AMMONIUM HYDROXIDE 5%" NITRIC ACID 1%" FERRIC CHLORIDE 1% 1% SOAP OAK DETERGENT u m (LINEAR ALKYL BENZYL SULFONAM OR LAS) 0.1% BACTERIOLOGICAL BOD NOT LESS THAN 700 PPM m THIS IS TO BE USED AS A PRE-WALIFICATION TEST AND WHEN MATERIAL FORMULATIONS ME CHANGED. 'VOLUMETRIC PERCENTAGES OF CONCENTRATED C.P. GRADE REAGENTS. I.D. DETAILS AND DIMENSIONS OF LINEAR SHEETS: LINER SHEETS SHALL BE A MINIMUM OF 0,N5 INCH IAS MM IN THICKNESS. LOCKING EXTENSIONS OF THE SAME MATERIAL AS THAT OF THE LINER SHALL BE INTEGRALLY EXTRUDED WITH THE SHEET. I.E. INSTALLATION OF LINING: INSTALLATION OF LINING, INCLUDING PREHEATING OF SHEETS IN COLD WEATHER AND THE WELDING OF ALL JOINTS, SHALL BE DONE IN ACCORDANCE WITH THE RECOMMENDATIONS OF THE LINER MANUFACTURER. COVERAGE OF THE LINING SHALL NOT BE LESS THAT THE MINIMUM SHOWN ON THE PLANS. THE LINING SHALL BE INSTALLED WITH THE LOCKING EXTENSIONS RUNNING PARALLEL WITH THE LONGITUDINAL AXIS OF THE PIPE. THE LINING SHALL BE HELD SNUGLY IN PLACE AGAINST INNER FORMS LOCKING EXTENSION SHALL TERMINATE NOT MORE THAN 1-12 INCHES (38 MM) FROM THE END OF THE INSIDE SURFACE OF THE PIPE CT JOINT FLAPS USED SHALL EXTENAPPROXIMAELY 4 INCHES IN MM BEYOND THE END OF TME INSIDE SURFACE. CONCRETE POURED AGAINST LINING SHALL BE VIBRATED, SPADED OR COMPACTED IN A CAREFUL MANNER $O AS TO PROTECT THE LINING AND PRODUCE DENSE, HOMOGENOUS CONCRETE, SECURELY ANCHORING TIE LOCKING EXTENSIONS INTO THE CONCRETE. IN REMOVING FORMS, CARE SHOULD BE TAKEN i0 PROTECT THE LINING FROM DAMAGE SHARP INSTRUMENTS SHALL NOT BE USED TO PRY FORMS FROM LINED SURFACES. WHEN FORMS ME REMOVED, ANY NAILS THAT REMAIN IN THE LINING SHALL BE PULLED. WITHOUT TEARING THE LINING, AND THE RESULTING HOLES CLEARLY MARKED. ALL NAIL AND TIE HOLES AND ALL CUT, TORN AND SERIOUSLY ABRADED AREAS IN THE LINING SHALL BE PATCHED, PATCHES MADE ENTIRELY WITH WELDING STRIP SHALL SE FUSED TO THE LINER OVER THE ENTIRE PATCHED AREA LARGER PATCHES MAY CONSIST OF SMOOTH LINER SHEET APPLIED OVER THE DAMAGED AREA WITH ADHESIVE, ALL EDGES MUST BE COVERED WITH WELDING STRIP FUSED TO THE PATCH AND THE SOUND LINING ADJOINING THE DAMAGED AREA. HOT JOINT COMPOUNDS, SUCH AS COAL TAR, SHALL NOT BE POURED OR APPLIED TO THE LINING. THE CONTRACTOR SHALL TAKE ALL NECESSARY MEASURES TO PREVENT DAMAGE TO INSTALLED LINING FROM EQUIPMENT MND MATERIALS USED IN OR TAKEN THROUGH THE WORK 1.F. APPLICATION TO CONCRETE PIPE- SPECIAL REQUIREMENTS: THE LINING SHALL BE SET FLUSH WITH THE INNER EDGE OF THE BELL OR BACOT END OF THE PIPE SECTION AND SHALL EXTEND TO THE OPPOSITE END OR TO APPROXIMATELY 41NCHES (IN MM) BEYOND THE OPPOSITE END DEPENDING UPON THE TYPE OF LINING JOINT TO BE MADE WITH THE JOINING CONCRETE PIPE. WHEREVER CONCRETE PIPE OR CMT -IN -PUCE STRUCTURES PROTECTED WITH LINING, JOIN STRUCTURES NOT SO LINED (SUCH AS BRICK STRUCTURES, CONCRETE PIPE OR CAST -IN-PLACE STRUCTURES WITH CLAY LINING OR CLAY PIPE), THE LINING SHALL BE EXTENDED OVER AND MOUND THE END OF THE PIPE AND BACK INTO THE STRUCTURE FOR NOT LESS THAN 4INCHES (WOMM). THIS PROTECTING CAP MAY BE MOLDED OR FABRICATED FROM THE LINING MATERIAL BUT NEED NOT BE LOCKED INTO THE PIPE. WHERE A PIPE LATERAL (NOTE OF PLASTIC LINED CONCRETE) IS INSTALLED THROUGH LINED CONCRETE PIPE, THE SEAL BETWEEN THE LINED PORTION AND THE LATERAL SHALL BE PER THE MANUFACTURER'S RECOMMENDATIONS. LINED CONCRETE PIPE MAY BE CURED BY STANDARD CURING METHODS. CARE SHALL BE EXERCISED IN HANDLING, TRANSPORTING AND PLACING LINED PIPE TO PREVENT DAMAGE TO THE LINING. NO INTERIOR HOOKS OR SLINGS SHALL BE USED IN LIFTING PIPE. ALL HANDLING OPERATION SHALL BE DONE WITH THE EXTERIOR SLING OR WITH A SUITABLE FORK LIFT, ON PIPE HAVING A 360" LINER COVERAGE, THE LONGITUDINAL EDGES OF THE SHEET SHALL BE BUTT WELDED. WHEN PIPE TUBES ARE FURNISHED, THESE ARE SHOP -WELDED JOINTS. NO PIPE WITH DAMAGED LINING WILL BE ACCEPTED UNTIL THE DAMAGE HAS BEEN REPAIRED TO THE SATISFACTION OF THE ENGINEER. I.G. REM JOINTS IN LINING FOR CONCRETE PIPE: THE JOINT BETWEEN SECTIONS OF LINED PIPE SHALL BE PREPARED IN THE FOLLOWING MANNER: IF REQUIRED, THE INSIDE JOINT SHALL BE FILLED AND CAREFULLY POINTED WITH CEMENT MORTAR IN SUCH A MANNER THAT THE MORTAR SHALL NOT, AT MY PONT, EXTEND INTO ME PIPE BEYOND THE STRAIGHT LINE CONNECTING THE SURFACES OF THE ADJACENT PIPE SECTIONS PIPE JOINTS MUST BE DRY BEFORE LINING JOINTS ME MADE. ALL MORTAR AND OTHER FOREIGN MATERIAL SHALL BE REMOVED FORM LINING SURFACES ADJACENT TO THE PIPE JOINT, LEAVING THE CLEAN AND DRY. TYPE P-1: THE JOINT SHALL BE MADE WITH SPATE 4 -INCH (IN MM) DONT STRIP AND TWO WELDING STRIPS. THE 4 -INCH (IN MM) JOINT STRIP SHALL BE CENTERED OVER THE JOINT, HEAT SEALED i0 THE LINING, THEN WELDED ALONG EACH EDGE TO ADJACENT LINER SHEETS WITH A 14NCH (25 -MM) WELD STRIP. THE 4 -INCH (I W41M) JOINT STRIP SHALL LAP OVER EACH SHEET MINIMUM OF %INCH (13 MM) TYPE R2: THE JOINT SHALL BE MADE WITH THE JOINT FLAP WITH LOCKING EXTENSIONS REMOVED AND EXTENDING APPROXIMATELY 4 INCHES IN MM BEYOND THE PIPE END. THE JOINT FLM SHALL OVERLAP THE LIVING N THE ADJACENT PIPE SECTION MINIMUM OF Y.INCH 13 MM AND BE HEAiSEALED IN PLACE PRIOR i0 WELDING. THE FIELD JOINT SHALL BE COMPLETED BY WELDING THE FLM i0 THE LINING OF THE ADJACENT PIPE USING 1 -INCH (25 MM) WELD STRIP. CARE SHOULD BE TAKEN TO PROTECT HE FLAP FROM DAMAGE. EXCESSIVE TENSION AND DISTORTION IN SENDING BACK THE FLAP TO EXPOSE THE PIPE JOINT DURING LAYING THE JOINT MORTARNG SHALL BE AVOIDED. THE TEMPERATURES BELOW W F (10 C). HEATING OF THE LINER MAY BE REQUIRED TO AVOID DAMAGE. THE JOINT FLM OR STRIP ON BEVELED PIPE SHALL BE TRIMMED TO A MOM (MEASURED FORM THE END OF THE SPIGOT) OF APPROXIMATELY 41NCHES (IN MM) FOR THE ENTIRE CIRCUMFERENTIAL LENGTH OF THE LINING. ALL WELDING OF JOINTS IS TO BE IN STRICT CONFORMANCE WITH THE SPECIFICATIONS AND INSTRUCTIONS OF THE LINING MMUFACTURER. WELDING SHALL FUSE BOTH SHEETS AND WELD STRIP TOGETHER TO PROVIDE CONTINUOUS JOINT EQUAL IN CORROSION RESISTANCE AND IMPERMEABILITY TO THE LINER PLATE. HOT-AIR WELDING TOOLS SHALL PROVIDE EFFLUENT AIR TO THE SHEETS TO BE JOINED AT A TEMPERATURE BETWEEN 500 AND 600 F) 260 AND 316 C), WELDING TOGS SHALL SE HELD APPROXIMATELY '% INCH (13 MM) FROM AND MOVED BACK AND FORTH OVER THE JUNCTION OF THE TWO MATERIALS TO BE JOINED. THE WELDING TOOL SHALL BE MOVED SLOWLY ENOUGHAS THE WELD PROGRESSES TO CAUSE A SMALL BEAD OF MOLTEN MATERIAL TO SE VISIBLE ALONG BOTH EWES AND IN FRONT OF THE WELD STRIP. THE FOLLOWING SPECIAL REOUIREMENTS SHALL "PLY WHEN THE LINER COVERAGE IS 360 DEGREES: WHEN GROUNDWATER IS ENCOUNTERED THE LINING JOINT SHALL NOT BE MME UNTIL PUMPING OF GROUNDWATER HAS BEEN DISCONTINUED FOR AT LEAST THREE DAYS AND NO VISIBLE LEAKAGE IS EVIDENT AT THE JOINT. WHEN WELDING THE DOWNSTREAM SIDE OF A JOINT STRIP OR FLM, DO NOT WELD S TO S INCHES (150 TO 2W MM) AT THE PIPE INVERT TO PROVIDE RELIEF OF POTENTIAL FUTURE GROUNDWATER BUILD-UP. i.H. MPLICATON i0 CAST-IN-PVCE CONCRETE SiRUCNRES - SPECW. REQUIREMENTS: LINER SHEETS SHALL BE CLOSELY FITTED AND PROPERLY SECURED TO THE INNER FORMS. SHEETS SHALL BE CUT M FIT CURVED AND WARPED SURFACES USING A MINIMUM NUMBER OF SEPARATE PIECES. UNLESS OTHERWISE SHOWN ON THE PLANS, THE LINING SHALL BE RETURNED AT LEAST 31NCHES (75 MM) AT THE SURFACES OF CONTACT BETWEEN THE CONCRETE STRUCTURE AN ITEMS NOT OF CONCRETE (INCLUDING MANHOLE FRAMES, DATE GUIDES, CLAY PIPE OR BRICK MANHOLES AND CLAY OR CAST IRON PIPES). THE SAME PROCEDURE SHALL BE FOLLOWED AT JOINTS WHERE THE TYPE OF PROTECTIVE LINING IS CHARGED OR THE NEW WORK IS BUILT TO JOIN EXISTING UNLINED CONCRETEAT EACH RETURN, THE RETURNED LINER SHALL BE SEALED TO THE ITEM IN CONTACT WITH THE PLASTICAJNED CONCRETE. IF THE LINER CANNOT BE SEALED WITH ADHESIVE BECAUSE OF THE JOINT AT THE RETURN BEING TOO NDE OR ROUGH OR BECAUSE OF SAFETY REGULATIONS, THE JOINT SPACE SHALL BE DENSELY CAULKED WITH LEAD WOOL OR OTHER APPROVED CAULKING MATERIAL TO A DEPTH OF 2 INCHES (50 MM) AND FINISHED WITH A MINIMUM OF I INCH (925 MM) OF AN "PROVED CORROSION RESISTANT MATERIAL. Il TESTING AND REPAIRING DAMAGED SURFACES AFTER THE PIPE IS INSTALLED IN THE TRENCH, ALL SURFACES COVERED WITH LINING INCLUDING WEIRS SHALL BE TESTED WITH AN APPROVED, CONTRACTOR SUPPLIED, ELECTRICAL HOLIDAY DETECTOR (TINKER 8 RASOR MODEL W. AP -W WTH POWER PACK OR APPROVED EQUAL) WITH THE INSTRUMENT SET BETWEEN 18,000 AND 22,000 VOLTS. ALL WELDS SHALL BE PHYSICALLY TESTED BY NONDESTRUCTIVE PROVING METHOD. ALL PATCHES OVER HOLES, OR REPAIRS TO THE LINER WHEREVER DAMAGE HAS OCCURRED, SHALL BE ACCOMPLISHED IN ACCORDANCE WITH SECTION 7-2M(1.E) PARA 8 ABOVE. EACH TRANSVERSE WELDING STRIP WHICH EXTENDS TO A LOWER EDGE OF THE LINER WILL BE TESTED BY THE PURCHASING AGENCY. THE WELDING STRIPS SHALL EXTEND 21NCHES (50MM) BELOW THE LINER TO PROVIDE A TAB, A 10 -POUND (SIG) PULL WILL BE APPLIED TO EACH TAB. THE FORCE WILL BE APPLIED NORMAL i0 THE FACE OF THE STRUCTURE BY MEANS OFA SPRING BALANCE LINER ADJOINING THE WELDING STRIP WILL BE HEIR AGAINST THE CONCRETE DURING APPLICATION OF THE FORCE. THE 10-P W (5 KG) PULL WILL BE MAINTAINED IF A WELD FAILURE DEVELOPS, UNTIL NO FURTHER SEPARATION OCCURS. DEFECTIVE WELDS WILL BE RETESTED AFTER REPAIRS HAVE BEEN MADE. TABS SHALL BE TRIMMED AWAY NEATLY BY THE INSTALLER OF THE LINER AFTER THE WELDING STRIP HAS COMBED INSPECTION. INSPECTION SHALL BE MADE WITHIN 2 DAYS AFTER THE JOINT HAS BEEN COMPLETED IN ORDER TO PREVENT TEARING THE PROJECTING WELD STRIP AND CONSEQUENT DAMAGE TO THE LINER FROM EQUIPMENT AND MATERIALS USED IN OR TAKEN THROUGH THE WORK SHOP DRAWINGS: CONTRACTOR SHALL SUBMIT MANUFACTURER INFORMATION SHOWING DIMENSIONAL MATERIAL AND JOINT CRITERIA TO THE ENGINEER FOR REVIEW. PIPE TRENCH CLASSIFICATION. RCP CLASS N SHALL. BE INSTALLED PER ASTM TRENCH DESIGNATION "C'. RCP CLASS V SHALL BE INSTALLED PER ASTM TRENCH DESIGNATION'D'. PVC FOR PIPE SIZES 18'AW LESS. POLY VINYL CHLORIDE PIPE SHALL MEET THE FOLLOWING REQUIREMENTS: 1. MATERIAL PVC PIPE SHALL MEET OR EXCEED ALL REQUIREMENTS SET FORTH IN ASTM D 3034 WITH SDR OF W. ELASTOMERIC SEALS AND JOINTS SHALL CONFORM TO ASTM D 3212 AND ASTM F 4". 2. TESTING: MANUFACTURING TESTING METHODS SHALL CONFORM i0 ASTM F -6T91 -WALL . CERTIFICATES OF COMPLIANCE SHALL BE MADE AVAILABLE 70 THE ENGINEER. 3. INSTALLATION: INSTALLATION OF PIPE SHALL FOLLOW MANUFACTURERS GUIDELINES, THESE SPECIFICATIONS AND ASTM D 2321 YJNDERGROUND INSTALLATION OF FLEXIBLE THERMOPLASTIC SEWER PIPE-. 4. FIELD TESTS: INFIELD PRESSURE TESTS SHALL CONFORM TO THESE SPECIFICATIONS AND THE FOLLOWING: DEFLECTION MEASUREMENT OF PVC PIPE. AFTER 30 DAYS OF INSTALLATION THE CONTRACTOR SHALL MEASURE PIPE DEFLECTION BY PULLING A GO -NO-GO 5% MANDREL. THE MANDREL SHALL BE PULLED THROUGH THE PIPE WITH ROPE BY ONE PERSON WITHOUT MECHANICAL ADVANTAGE. THE MANDREL SHALL HAVE VANES AT LEAST AS LONG AS THE PIPE DIAMETER. THE MANDREL SHALL BE USED IN STRICT CONFORMANCE WITH PIPE AND MANDREL MANUFACTURER'S RECOMMENDATIONS. THE MANDREL DIAMETER WILL BE CALCULATED USING THE FOLLOWING FORMULA: MANDREL DIAMETER = BASE PIPE I.D.-(Y/100X BASE PIPE ILD) WHERE Y = ALLOWABLE DEFLECTION IN % (5%) BASE ID =ACTUAL INSIDE PIPE DIAMETER (PROVIDED BY PIPE MANUFACTURER) THE MANDREL SHALL HAVE AN COD NUMBER OF VMES WITH SEVEN (7) MINIMUM. THE MINIMUM LENGTH OF THE CIRCULAR PORTION OF THE MANDREL SHALL SE EQUAL TO THE NOMINAL DIAMETER OF THE PIPE. MY SECTION OF INSTALLED PIPE THAT FAILS THE MANDREL TEST SHALL BE EXCAVATED. RE -BACKFILLED, RE -COMPACTED AND RETESTED UNTIL THE MANDREL TEST CAN BE PASSED. RE -ROUNDING WILL NOT BE ALLOWED. PIPE TRENCH CLASSIFICATION. PVC PIPE SHALL BE INSTALLED PER CITY STANDARD S-39, AS MODIFIED ON THE CONTRACT PLANS. COMPACTION ABOVE THE PIPE ZONE SHALL BE SHOWN ON THE PLANS. CONNECTION SEAL TO PVC LINED SEWERLINE OR MANHOLE 1. THE CORED ROLE SHALL BE APPROXIMATELY 3 INCHES GREATER THAN THE OUTSIDE DIAMETER OF THE CONNECTING LINE. THE CORED HOLE SHALL BE DESIGNED TO CUT HOLE WITH MINIMUM DAMAGE TO THE REINFORCING STEEL, PIPE, OR PLASTIC LINER. 2. PRIOR TO THE INSTALLATION OF THE PVC BOOT ON THE CONNECTION, THE PLASTIC LINER MOUND THE PIPE AT THE CORED HOLE SHALL SE CLEMED PER THE PLASTIC LINER MANUFACTURER'S RECOMMENDATION. THE END OF THE CONNECTING LINE SHALL BE SEALED TO THE PVC BOOT NTH SIKA 4 !)MU PRIMER AND SIKA FLEX IA SEALANT OR AN APPROVED EQUAL. 3. THE PVC BOOT SHALL BE ORDERED SO IT WILL FIT SNUGLY TO THE OUTSIDE WALL OF THE CONNECTION. 4. THE PVC BOOT AND WELD STRIPS SHALL BE INSTALLED AND TESTED FOR HOLIDAYS PER THE PLASTIC LINER MMUFACTURER'S RECOMMENDATION. 5. THE CONNECTING LINE SHALL BE CENTERED IN THE CORED HOLE AND PLACED SO ITIS FLUSH WITH THE INSIDE WALL OF THE RCP. 6. THE PVC BOOT WELD STRIPS SHALL BE MANUFACTURED BY AMERON, INC. OR ANAPPROVED EQUAL BY THE CITY ENGINEER. 7. TRENCH EXCAVATION THE EXCAVATION OF TRENCHES FOR PIPING LAID IN THE GROUND SHALL BE IN OPEN -CUT FROM THE SURFACE OF THE GROUND EXCEPT WHERE BORING IS REWIRED. THE TRENCHES SHALL BE OF WIDTH AS SHOWN ON STANDARD S-39 AND DETAILED SECTIONS ON THE PLANS FOR PROPER PIPE INSTALLATION. THE HOES FOR BELLS AND FITTINGS SHALL BE EXCAVATED BY HMD, TO A WIDTH PROVIDING UNIFORM BEARING ALONG THE LENGTH OF THE PIPE. IT IS THE INTENTION OF THESE REQUIREMENTS TO PROVIDE FIRM, UNIFORM SEARING FOR THE PIPE. CONTRACTOR SHALL PROVIDE TRENCHING IN ACCORDANCE WITH THE DETAILS SECTIONS PROVIDE IN THE PLANS. SELECTION OF TRENCH TYPES WILL BE AS REWIRED BY THE TYPE SOFT PIPE SELECTED FOR CONSR2UCTIO04. STORM DRAIN AND UTILITY CONDUIT INSTALLATIONS SHALL MEET CITY STANDARD 5-39. TRENCH LINES SHALL MEET ALL FEDERAL AND STATE SAFETY REQUIREMENTS. 8. BRACINGANDSHORING EXCAVATION SHALL BE SUPRORTEDAS SET FORTH IN THE RULES ORDERS AND REGULATIONS OF THE STATE DIVISION OF INDUSTRIAL SAFETY. IF THE CONTRACTOR DESIRES TO DEVIATE FROM THE SAFETY ORDERS, HE SHALL SUBMIT DATA BY REGISTERED CIVIL ENGINEER TO THE STATE DIVISION OF INDUSTRIAL SAFETY, JUSTIFYING THE ALTERNATE PROCEDURES TO BE USED. FAILURE TO COMPLY WITH ANY OF THESE RULES, ORDERS, MD REGULATIONS SHALL BE SUFFICIENT CAUSE FOR THE STATE DIVISION TO IMMEDIATELY SUSPEND ALL WORK. COMPENSATION FOR LOSSES INCURRED BY THE CONTRACTOR BY SUCH AN EMERGENCY SUSPENSION SHALL NOT BE ALLOWED. DURING BACKFILLING, THE BOTTOM OF THE SHORING SHALL BE KEPT ABOVE THE LEVEL OF THE BACKFILL AT ALL TIMES. SECTION 6422 OF THE CALIFORNIA LABOR CODE REQUIRES THE CONTRACTOR i0 SUBMIT TO THE ENGINEER A DETAILED PLAN, DRAWING THE DESIGN OF SHORING. BRACING, SLOPING OR OTHER PROVISIONS TO BE MADE BY THE CONTRACTOR FOR THE PURPOSE OF WORKER PROTECTION FROM THE HAZARD OF CAVING GROUND DURING THE EXCAVATION OF TRENCHES NECESSARY FOR THE CONSTRUCTION OF THE PROJECT. IF SUCH PLM VARIES FROM THE SHORING SYSTEM STANDARD ESTABLISHED BY THE CONSTRUCTION SAFETY ORDERS, THE PLANS SHALL BE PREPARED AND CERTIFIED BY REGISTERED CML OR STRUCTURAL ENGINEER; HOWEVER, USE OF SYSTEMS THAT ME LESS EFFECTIVE THAN THOSE REQUIRED BY THE CONSTRUCTION SAFETY ORDERS IS PROHIBITED W THIS PROJECT. 9. TRENCHBACKFILL TRENCHES SHALL NOT BE LEFT OPEN FARTHER THAN THREE HUNDRED (300) FEET IN ADVANCE OF PIPE LAYING OPERATIONS OR TWO HUNDRED (200) FEET TO THE REM THEREOF, UNLESS OTHERWISE PERMITTED BY THE ENGINEER ALL WORK SHALL CONFORM TO THE APPLICABLE SECTIONS OF THE STANDARD SPECIFICATIONS, DATED JULY, 1982. BEDDING CLASS SHALL BE AS SPECIFIED IN THE PIPE OPTIONS. STORM DRAIN AND UTILITY CONDUIT INSTALLATIONS SHALL BE IN ACCORDANCE WITH CIN STANDARD ST -22, EXCEPT THAT COMPACTION SHALL BE NO LESS THAN NINETY PERCENT (90%) UP TO THIRTY INCHES (301) FROM FINISHED GRADE. BACKFILL MATERIALS IN THE PIPE ZONE SHALL SE PLACED IN LAYERS NOT TO EXCEED TWELVE (12) INCHES SIMULTANEOUSLY, ON EACH SIDE OF THE PIPE, IN SUCH A MANNER AS NOT TO DAMAGE OR DISTURB THE PIPE OR IT ALIGNMENT AND GRADE. BACKFILL MATERIAL ABOVE THE PIPE ZONE SHALL SE FREE OF DELETERIOUS MATERIALS AND LUMPS OR STONES EXCEEDING THREE (3) INCHES IN GREATEST DIMENSION AND SHALL BE PLACED IN LAYERS NOT EXCEEDING EIGHTEEN (18) INCHES. EACH LAYER SHALL BE THOROUGHLY COMPACTED BY VIBRATORY OR MECHANICAL TAMPING, OR ANY COMBINATION OF THESE METHODS. FLOODING AND JETTING SHALL NOT BE ALLOWED. THERE MUST SE AT LEAST ONE FOOT OF COVER OVER THE PIPE BEFORE COMPACTION ABOVE THE PIPE ZONE WILL BE ALLOWED. IMPORTED BEDDING AND BACKFILL MATERIAL SHALL BE OBTAINED, AND MY EXCESS SEWING AND BACKFILL MATERIAL SHALL BE DISPOSED, BY MY LEGAL MEANS AT THE DISPOSAL OF THE CONTRACTOR. THE CONTRACTOR MAY SUBMIT TO THE ENGINEER SIEVE ANALYSIS FOR UTILIZATION OF INSITU MATERIALS. ACHIEVING FIRM BEDDING BELOW PIPE SPRINGLINE. CONTRACTOR SHALL PROVIDE 'FIRM BEDDING' SUPPORT FOR THE PIPE BELOW THE SPRWGLINE. FIRM BEDDING MEANS THAT THE PIPE MUST BEST ON THE GRANULAR MATERIAL SPECIFIED PREVIOUSLY IN THE SPECIFICATIONS. BELL OR COUPLING HOLES SHALL BE CAREFULLY EXCAVATED AT PROPER INTERVALS, SO THAT NO PART OF THE LOAD IS SUPPORTED BY THE BELLS OR COUPLINGS. DURING BEDDING AND BACKFILLING, CONSOLIDATION OF MATERIAL AROUND AND UNDER BELLS AND COUPLINGS SHALL BE AVOIDED. CONTRACTOR SHALL SHOVELSLICE OR HAND TAMP BEDDING IN THE HAUNCH AREAS, AS THIS WILL MINIMIZE VOIDS BENEATH THE PIPE AND IN THE HAUNCH AREAS. SHOWLSLICING OR HAND TAMPING SHALL BE DONE BEFORE THE BEDDING IS BROUGHT UP TO THE QUARTER POINT OF THE PIPE. INITIAL SAGKFILL: SEWING WTERIAL'AS SPECIFIED BY ASTM 2321$ SHALL BE USED IN THE PIPE ZONE FOR INITIAL BACKFNL. AFTER THE PIPE HAS BEEN PROPERLY LAID AND INSPECTED, INITIAL BACKFILL SHALL BE PLACED ON BOTH SIDES AND OVER THE PIPE TO SUCH DEPTH THAT, AFTER THOROUGH CONSOLIDATION, THE FINAL DEPTH SHALL BE AT LEAST TO THE ELEVATION SHOWN ON THE PLANS. THE MATERIAL SHALL BE CONSOLIDATED BY VIBRATORY OR MECHANICAL TAMPING AND THE EQUIPMENT AND MANNER OF PUMPING MUST BE APPROVED IN WRITING BY THE ENGINEER PRIOR TO COMMENCING OPERATION. IMPACT EQUIPMENT MAY BE ALLOWED UNDER THE DIRECTION OF THE ENGINEER. HOWEVER THE CONTRACTOR IS RESPONSIBLE FOR MY DAMAGE RESULTING FROM THE USE OF THE EQUIPMENT. HYDRA -HAMMER WILL NOT BE PERMITTED. SUBSEQUENT BAGKPILL ABOVE THE LEVEL OF INITIAL BACKFILL THE TRENCH MAY BE BACKFILL WITH NATIVE MATERIAL RESULTING FROM TRENCH EXCAVATION OR AT THE OPTION OF THE CONTRACTOR SELECT IMPORTED MATERIALS MAY BE USED. NATIVE MATERIAL OR IMPORTED MATERIAL MAY BE COMPACTED BY TAMPING ANGOR ROLLING, USING EQUIPMENT AND METHODS APPROVED BY THE ENGINEER. WHEN THE CONTRACTOR COMPACTS BY TAMPING AND/OR ROLLING. THE BACKFILL MATERIAL SHALL BE PLACEO IN LAYERS NOT EXCEEDING EIGHTEEN (18) INCHES IN LOOSE DEPTH, EACH LAYER BEING THOROUGHLY COMPACTED BY TAMPING ANDIM ROLLING BEFORE SUCCEEDING LAYERS ARE PLACED. COMPACTION OF SUBSEQUENT BACKFILL WITHIN TWO AND ONE-HALF (2-12) FEET OF FINISHED PERMANENT SURFACING GRADE SHALL RE ACCOMPLISHED BY TAMPING AND/OR ROLLING AS SPECIFIED ABOVE. WHERE THE TRENCH IS WITHIN THE PAVEMENT ON STREETS THE BACKFILL WITHIN TWO AND ONE-HALF 2-12 FEET OF FINISHED PERMANENT GRADE SHALL BE COMPACTED TO NINETY PERCENT N%. RELATIVE COMPACTION. SUBSEQUENT BACKFILL PLACED BY TAMPING ANGOR ROLLING SHALL RE FREE FROM STONES OR LUMPS EXCEEDING THREE 3 INCHES IN GREATEST DIMENSIONS VEGETABLE MATTER OR OTHER UNSATISFACTORY MATERIALS. IN NO CASE SHALL JETTING M ALLOWED FOR BACKFILL COMPACTION WITHIN THE STREET. WHEN APPROVED BY THE ENGINEER, JETTING MAY BE USED IN NONSTREET AREAS. SACKFUL TESTING AND COMPACTION: TESTING OF BACKFILL MAMRWS AND COMPACTION SHALL BE IN ACCORDANCE WITH SECTION 19.'EARTHWORK'AND SECTION" TESTING, OF THE STANDARD SPECIFICATION, STATE OF CALIFORNIA DEPARTMENT OF PUBLIC WORKS, DIVISION OF HIGHWAYS. EACH LAYER OF BACKFILL MATERIAL SHALL MEET THE COMPACTION, SAND EQUIVALENT, AND GRADATION REQUIREMENTS BEFORE THE NEXT LAYER LM PLACED. EACH LAYER OF BACKFILL SHALL BE THOROUGHLY COMPACTED TO THE RELATIVE COMPACTION OF NOT LESS THAT IS SHOWN ON CITY OF BAKERSFIELD STANDARD "9 AS MODIFIED ON THE CONTRACT PLANS, EXCEPT THAT COMPACTION WITHIN THE ROADWAY STRUCTURAL BECTON SHALL BE NO LESS THAN NINETY PERCENT IN%) RELATIVE COMPACTION FOR THE TOP FINISHED 3P, AND SHALL BE DETERMINED BY CALIFORNIA TEST METHODS 216 OR 231, OR ASTM (CURRENT EDITION) DI MT AND ONE OF THE FOLLOWING D2922 OR D155S IF THE RELATIVE COMPACTION, AS DETERMINED BY TESTING, FAILS TO MEET THE SPECIFIED PERCENTAGE, THE TRENCH SHALL BE RE�EXCAVATED AND RECOMPACTED. COMPACTION TESTS WILL BE THE SUBDIVIDER RESPONSIBILITY. THE NUMBER AND LOCATIONS OF THE TESTS SHALL BE DETERMINED BY THE CITY ENGINEER. 10. SEWER PIPE INSTALLATION: SEWER PIPE SHALL CONFORM TO THE PLANS, AND THESE SPECIAL PROVISIONS. THE PRICE PER LINEAL FOOT SHALL INCLUDE BUT NOT BE LIMITED TO EXCAVATION, BEDDING AND BACKFILL. HANDLING OF MATERIALS. ALL PIPE, FITTINGS. SPECIALS AND CASTINGS MUST BE CAREFULLY HANDLED AT ALL TIMES. ONLY SUITABLE AND PROPER EQUIPMENT AND APPLIANCES SHALL BE USED FOR THE SAFE LOADING, HAULING, UNLOADING, HANDLING AND PLACING OF MATERIALS, SPECIAL CARE SHALL BE EXERCISED SO THAT PREFORMED RESILIENTJOINTS ON PIPE AND FITTINGS WILL NOT BE DAMAGED. ANY PIPE OR FITTING WITH A JOINT DAMAGED OR FLATTENED WILL CAUSE THAT PIPE OR FITTING TO BE REJECTED. PIPE LAYING. NO PIPE SHALL BE WD UNTIL THE ENGINEER INSPECTS AND APPROVED THE CONDITION OF THE BOTTOM OF THE TRENCH. PIPE SHALL BE INSTALLED IN STRICT ACCORDANCE NTH MANUFACTURERS RECOMMENDATIONS. PIPE LAYING SHALL BEGIN FROM THE DOWNSTREAM END OF THE TRUNK SEWER OR AS DIRECTED BY THE ENGINEER. PIPE LAYING SHALL PROCEED NTH EACH PIECE LANG TRUE TO LINE AND GRADE, MD IN SUCH A MANNER AS TO FORM A CLOSE CONCENTRIC JOINT NTH THE ADJOINING PIPE MD TO PREVENT SUDDEN OFFSETS IN THE FLOW LINE. AS THE WORK PROGRESSES, THE INTERIOR OF THE PIPE SHALL BE CLEARED OF ALL DIRT AND DEBRIS OF EVERY DESCRIPTION. PIPE SHALL NOT BE LAID WHEN THE CONDITION OF THE TRENCH OR THE WEATHER IS UNSUITABLE. AT TIMES WHEN WORK IS NOT IN PROGRESS. OPEN ENDS OF PIPE AND FITTINGS SHALL SE CLOSED. WITH BELLED END PIPE, BELL HOLES SHALL THEN BE EXCAVATED AT EACH JOINT TO FACILITATE THE JOINT OPERATIONS, AND SHALL BE ONLY OF SUFFICIENT SIZE FOR THAT PURPOSE. IN ORDER THAT BELL HOLES MAY BE PROPERLY LOCATED, NOT MORE THAN SIX (6) HOLES HALL BE EXCAVATED MEAD OF ACTUAL PIPE LAYING, ON ACCOUNT OF THE VARIATIONS IN JOINT CONSTRUCTION OPERATIONS. CURING PIPE. THE CONTRACTOR SHALL PERFORM ALL WORK OF CUTTING PIPE AND SPECIAL CASTING NECESSARY TO THE ASSEMBLY, ERECTION, AND COMPLETION OF THE WORK. ALL PIPE SHALL BE CUT TO FIT ACCURATELY, WITH SMOOTH EDGES AND FACES. THE CONTRACTOR SHALL BE RESPONSIBLE FOR THE CORRECTNESS OF CUTTING AND NO ADDITIONAL COMPENSATION WILL BE ALLOWED FOR MY MATERIALS WHICH ARE DAMAGED OR INCORRECTLY WT. PIPELINE TESTING. ALL SEWERS SHALL BE TESTED FOR TIGHTNESS WHEN COMPLETED AND READY FOR SERVICE. TESTING SHALL BE CONDUCTED IN ACCORDANCE WITH THE UNIFORM PLUMBING CODE AIR TEST METHODS UPC SEC. 318-6(4), OR THE WATER EXFILTRATION TEST OR AIR PRESSURE TEST PER SECTION 306-1.4 TESTING PIPELINES' OF THE 1994 EDITIONS, STANDARD SPECIFICATIONS' FOR PUBLIC WORKS CONSTRUCTION, AND CHAPTER 1.3 OF THE CITY OF BAKERSFIELD SUBDIVISION DESIGN MANUAL, AND THE PIPE SUPPLIER'S REQUIREMENTS. THE CONTRACTOR SHALL NOTIFY THE ENGINEER 24 HOURS PRIOR TOANY TESTING. CLEMING PIPE LINES. CARE SHALL BE EXERCISED IN LAYING OF PIPE LINES TO EXCLUDE DIRT AND MY OTHER FOREIGN MATERIAL. WHEN PIPE LAYING S INTERRUPTED, AS AT NIGHT, THE PIPE ENDS SHALL BE SUITABLY CLOSED. UPON COMPLETION AND BEFORE PLACING INTO SERVICE, ALL LINES SHALL BE FLUSHED AND MANDRELLED TO REMOVE ANY DIRT OR FOREIGN MATERIALS WHICH WOULD CLOG PUMPS EQUIPMENT SPRAY HEADS ETC. THE CONTRACTOR SHALL MAKE PROVISIONS FOR PREVENTING FOREIGN MATERIAL FROM BEING FLUSHED INTO AN EXISTING SEWER LINE, SEWER LATERALS. SEWER LATERALS SHALL CONFORM TO THIS IN EVERY REGARD. EXISTING SEWER LATERALS SHALL BE LOCATED BY THE CONTRACTOR AND CONNECTED TO AND EXTENDED OR RECONSTRUCTED ACCORDING TO THE PLANS. COMPRESSION COUPLINGS MAY BE UTILIZED FOR CONNECTING TO EXISTING LATERALS. POSITIVE GRADE TO THE TRUNK SEWER SHALL BE MAINTAINED AND INVERT GRADES SETAS CALLED ON THE PLANS. SEWER WYES SHALL BE INSTALLED W THE TRUNK IN ACCORDANCE WITH THE PIPE MMUFACTURER'S RECOMMENDATIONS. PAYMENT FOR SEWER LATERALS WILL BE PAIN AS SEWER FOR THE APPROPRIATE DIAMETERS. 11. SYSTEM TESTING: A MANDREL TEST AND PRESSURE TEST SHALL BE PERFORMED ON INSTALLED PIPE IN ACCORDANCE WITH THE CITY OF BAKERSFIELD SUBDIVISION MANUAL AND THE RECOMMENDATIONS OF THE MANUFACTURER, PRIOR TO FINAL ACCEPTANCE, ALL SEWER LINES SHALL BE INSPECTED WITH VIDEO EQUIPMENT DESIGNS FOR THIS PURPOSE. THE TELEVISION CAMERA SHALL HAVE THE CAPABILITY OF ROTATING 360', IN ORDER TO VIEW AND RECORD THE TOP AND SIDES OF THE PIPE, AS REQUIRED. THE VIDEO INSPECTION SHALL BE WITNESSED BY THE CITY'S CONSTRUCTION INSPECTOR, WHO WILL ALSO INITIAL AND DATE THE -CHAIN OF CUSTODY' FORM. THE SUBDIVIDER SHALL IMMEDIATELY NOTIFY CITY OF MY PIPE LOCATIONS REVEALED TO BE NOT IN COMPLIANCE WITH THE SPECIFICATIONS. A RECORDED VIDEO CASSETTE, THE COMPLETED 'CHAIN OF CUSTODY' FORM AND THE WRITTEN LOG (WHICH INCLUDES THE STATIONING, BASED ON THE STATIONING OF THE APPROVED PLANS, OF ALL CONNECTED LATERALS) OF TME INSPECTION SHALL BE PROVIDED FOR VIEWING, AND SHALL BE APPROVED BY THE CITY ENGINEER PRIOR TO ACCEPTANCE. AFTER ACCEPTANCE, THE VIDEO CASSETTE SHALL BECOME THE PROPERTY OF THE CITY. 12. WE FITTINGS SHALL BE INJECTION MOLDED INLINE TYPE AND SHALL BE USED FOR ALL LATERAL CONNECTIONS AND SHALL BE ROTATED A MINIMUM OF 23 DEGREES ABOVE THE HORIZONTAL PLANE RUNNING THROUGH THE CENTERLINE OF THE MAIN. ANLL LATERALS SHALL BE 4' IN DIAMETER EXCEPT AS NOTED ON PLANS, EXTENDING A MINIMUM OF 4' BEYOND THE PROPERTY LINE OR RIGHT -0F WAY LINE NTH 30' OF COVER AT FLOW LINE. SURFACE MARKERS FOR SEWER LATERALS SHALL BE INSTALLED AT THE PROPERTY LINE OR RIGHT -0F -WAY LINE AS SHOWN IN THE SEWER LATERAL MARKER DETAIL, C.O.B. STD. DEE SW -1. LATERALS SHALL BE A MINIMUM OF 2.25' DEEP AND A MAXIMUM OFT DEEP AT PROPERTY LINE OR RIGHT-OF-WAY LINE MD MINIMUM OF 2.5' DEEP AT FLOW LINE. 13. ALL SEWER STUBS SHALL BE CLOSED WITH A STANDARD PLASTIC PLUG. SOLVENT WELDED IT ALL MANHOLES SHALL BE CONSTRUCTED IN ACCORDANCE NTH THE CITY OF BAKERSFIELD STANDARD DRAWINGS 54, SS AND. 3-21 AND SECTIONS M1.02H AND 71-1.W OF THE STANDARD SPECIFICATIONS OF THE STATE OF CALIFORNIA DEPARTMENT OF TRANSPORTATION, CURRENT EDITION. ALL CLEANOUTS SHALL BE CONSTRUCTED IN ACCORDANCE WITH THE CITY OF SAKERSFIELD STANDARD DRAWINGS S -M MANHOLES SHALL BE TYPE A' FOR PIPES UNDER 48" IN DIAMETER AND TYPE'S' FOR PIPES 48" IN DIAMETER OR LARGER. UNLESS NOTED OTHERWISE. THE BOTTOM MANHOLE BARREL AT THE MANHOLE FOUNDATION SHALL BE SET ON A 2" MORTAR BED OR SET W KEW -SEAL, IN A GROOVED FOUNDATION. 15. STORMDRAINPIPE STORM DRAIN PIPE. CONTRACTOR SHALL UTILIZE RLP PIPE, CLASS 111 NTH RUBBER GASKET JOINTS PER ASTM SPECIFICATION G76, UNLESS OTHERWISE NOTED ON THE CONTRACT PLANS. REINFORCED CONCRETE PIPE. REINFORCED CONCRETE PIPE SHALL CONFORM TO THE PROVISIONS IN SECTION 65, 'REINFORCED CONCRETE PIPE', OF THE STANDARD SPECIFICATIONS AND THESE SPECIAL PROVISIONS. EXCEPT WHERE OTHERWISE DESIGNED BY CLASSIFICATION ON THE PLANS OR IN THE SPECIFICATIONS, JOINTS FOR CULVERT AND DRAINAGE PIPES SHALL CONFORM TO THE PLANS OR SPECIFICATIONS FOR STANDARD JOINTS. HYDROSTATIC TESTS SPECIFIED BY SECTION M-1.08 'LAYING SIPHON AND PRESSURE PIPE', OF THE STANDARD SPECIFICATIONS WILL NOT BE REQUIRED. REINFORCED CONCRETE PIPE SHALL HAVE RUBBER GASKETED JOINTS CONFORMING TO SECTION 65-1.MS,'RUBBER GASKETED JOINTS'. OF THE STANDARD SPECIFICATIONS. RMWNG OF MATERIALS: ALL PIPE, FITTINGS, SPECT L$ AND CASTINGS MUST BE CAREFULLY HANDLED AT ALL TIMES. ONLY SUITABLE AND PROPER EQUIPMENT AND APPLIANCES SHALL BE USED FOR THE SAFE LOADING HAULING UNLOADING HANDLING AND PLACING OF MATERIALS SPECIAL CME SHALL BE EXERCISED SO THAT PREFORMED RESILIENT JOINTS ON PIPE AND FITTINGS WILL NOT BE DAMAGED ANY PIPE OR FITTING WITH A JOINT DAMAGED OR FLATTENED WILL CAUSE THAT PIPE OR FITTING TO BE REJECTED. PIPE LAYING: NO PIPE SHALL BE LAID UNTIL THE ENGINEER INSPECTS AND APPROVES THE CONDITION OF THE BOTTOM OF THE TRENCH. PIPE SHALL SE INSTALLED IN STRICT ACCORDANCE WITH THE MANUFACTURER'S RECOMMENDATIONS. PIPE LAYING SHALL BEGIN FROM THE DOWNSTREAM END OF THE STORM GRAIN OR AS DIRECTED BY THE ENGINEER. PIPE LAYING SHALL PROCEED WITH EACH PIECE LAID TRUE TO LINE AND GRADE, AND IN SUCH A MANNER AS TO FORM A CLOSE CONCENTRIC JOINT WITH THE ADJOINING PIPE AND TO PREVENT SUDDEN OFFSETS IN THE FLOW LINE. AS THE WORK PROCESSES THE INTERIOR OF THE PIPE SHALL BE CLEARED OF ALL DIRTAND DEBRIS OF EVERY DESCRIPTION. PIPE SHALL NOT BE LAID WHEN THE CONDITION OF THE TRENCH OR THE WEATHER IS UNSUITABLE. AT TIMES WHEN WORK IS NOT IN PROGRESS, OPEN ENDS OF PIPE AND FITTINGS SHALL BE CLOSED. WITH BELLED END PIPE BELL HOLES SHALL THEN BE EXCAVATED AT EACH JOINT i0 FACILITATE THE JOINT OPERATIONS AND SHALL BE ONLY SUFFICIENT SIZE FOR THAT PURPOSE. IN ORDER THAT BELL HOLES MAY BE PROPERLY LOCATED, NOT MORE THAN SIX (6) HOES SHALL BE EXCAVATED AHEAD OF ACTUAL PIPE LAYING, ON ACCOUNT OF THE VARIATIONS IN JOINT CONSTRUCTION OPERATIONS. THE CONTRACTOR SHALL MAKE PROVISIONS FOR PREVENTING FOREIGN MATERIAL FROM BEING FLUSHED INTO AN EXISTING DRAIN LINE. CUTTING PIPE: THE CONTRACTOR SHALL PERFORM ALL WORK OF CUTTING PIPE AND SPECIAL CASTING NECESSARY TO THE ASSEMBLY, ERECTION, AND COMPLETION OF THE WORK. ALL PIPE SHALL BE CUT TO FIT ACCURATELY, WITH SMOOTH EDGES AND FACES. THE CONTRACTOR SHALL BE RESPONSIBLE FOR THE CORRECTNESS OF CUTTING AND NOT ADDITIONAL COMPENSATION WILL BE ALLOWED FOR ANY MATERIALS WHICH ME DAMAGED OR INCORRECTLY CUT. 16, BORED) JACKED PIPE: CASING OR SMOOTH OUTSIDE WALLED PIPE FOR BOREDUACKED PIPE SHALL BE INSTALLED. IT SHALL HAVE EVEN BEARING THROUGHOUT ITS LENGTH AND SHALL SLOPE TOWARD ONE END, SPACE BETWEEN CASING AND PIPELINE SHALL BE BACKFILLED WITH SMD. IF THE PIPE AND CASING ARE INSTALLED BY BORING, THE SPACE MOUND THE CASING ALSO SHALL BE BACKFILLED WITH GROUT OR SAND. THE ENDS OF SPACE BETWEEN THE CASING AND THE PIPE SHALL BE SEALED WITH GROUT. THE STRENGTH OF PIPE DESIGNATED IN THE PLANS OR SPECIFICATIONS IS DETERMINED FOR VERTICAL LOAD ONLY ANY ADDITIONAL STRENGTH REQUIRED BY SORINGUACKING OPERATIONS SHALL BE FURNISHED AT THE CONTRACTOR'S EXPENSE. THE CONTRACTOR SHALL SUBMIT TO THE ENGINEER FOR APPROVAL ALL PLANS OF SORINGUACKING OPERATIONS PRIOR TO BORING OR JACKING. BORINWACKING OPERATIONS SHALL BE CONWCTED IN A SAFEMD EFFICIENT MANNER, CONSISTENT WITH CURRENTACCEPTED PROCEDURES- WATER BORING SHALL NOT BE PERMITTED. THE CASING PIPE SHALL BE JACKED WITH SUCH PRECISION THAT WILL ALLOW THE REPLACEMENT OF THE PIPELINE TO THE LINE AND GRADE AS INDICATED ON THE PIANS, UPON COMPLETION OF THE INSTALLATION OF THE CASING AND INSTALLATION OF THE PIPELINE TO GRADE. THE VOID BETWEEN THE CASING OR RC PIPE AND THE EXCAVATION SI Wl BE COMPLETELY FILLED WITH SAND, COMPACTED BY THE USE OF AIR-BLOWNG SMD EQUIPMENT OR ANY OTHER MEANS ACCEPTABLE TO THE ENGINEER UPON HIS APPROVAL. IT IS THE CONTRACTOR'S RESPONSIBILITY TO MAINTAIN A SME OPERATION AT ALL TIMES. SHOULD THE TUNNEL HEADING OPERATIONS RESULT IN DANGEROUS OR UNREASONABLE SLOUGHING OF MATERIAL WHICH MAY JEOPARDIZE THE SAFETY OF WORKERS OR THE STABILITY OF THE SOIL AND ROADWAY MOVE THE CONTRACTOR SHALL FURNISH AND INSTALL SREASTBOMDING AND OR FACE CLOSURE WITH SUFFICIENT JACKS TO INHIBIT THE SLOUGHING AND/OR CLOSING THE WORK FACE. THE CONTRACTOR BEFORE RESUMING WORK, SHALL FURNISH THE ENGINEER WITH A DETAILED PLAN OF PRECEDING WITH THE WORK, FOR HIS REVIEW AND APPROVAL. ANY MD ALL EXPENSES THEREFORE WILL BE CONSIDERED AS INCLUDED IN THE BID PRICE AND NO ADDITIONAL COMPENSATION WILL BE MADE THEREFORE. 17. MINOR STRUCTURES: MINOR STRUCTURES: PORTLAND CEMENT CONCRETE MINOR STRUCTURES SHALL CONFORM, IN DESIGN, MATERIALS, AND CONSTRUCTION TO THE PROVISIONS OF SECTIONS 70-1.02 H OF THE STANDARD SPECIFICATIONS AND THESE SPECIAL PROVISIONS. MANHOLES SHALL CONFORM TO THE CITY OF BAKERSFIELD STANDARDS S7 AND SHO. DROP INLETS SHALL CONFORM TO THE CITY OF BAKERSPELD STANDARD 5IZ TEMPORARY INLET GRATES SHALL CONFORM TO DETAILS ON THE PLANS. THE PRECAST CYLINDER, TAPER, AND ECCENTRIC FLAT TOP SECTIONS SHALL MEET THE STRENGTH REOUIREMENT OF ASTM. C978. EACH SUCCESSIVE MANHOLE SECTION SHALL BE SET ON A BED OF PORTLAND CEMENT GROUT OR'KENT SEAL' TO MAKE WATERTIGHT JOINT, SHALL SE NEATLY POINTED ON THE INSIDE, MD SHALL BE SET PLUMB. 16. ADJUSTSURVEYMMUMENTENCASFAIENTS SURVEY MONUMENT MD FRAME MD COVER WITH ENCASEMENTS SHALL BE ADJUSTED OR INSTALLED NEW TO FINISH GRADE AT THE THE SURFACE OF THE CONCRETE SHALL BE PROTECTED FROM PUBLIC TRAFFIC FORA MINIMUM OF THREE DAYS. AT THE OPTION OF THE CONTRACTOR, MINOR CONCRETE CONTAINING A MINIMUM OF SEVEN STACKS OF CEMENT PER CUBIC YARD MAY BE USED AND THE TIME REQUIRED FOR PROTECTION OF THE CONCRETE SURFACE FROM PUBLIC TRAFFIC SHALL BE REDUCED TO A MINIMUM OR ONE DAV THE MONUMENT WILL BE SET BY OTHERS. THE OWNER WILL PROVIDE SURVEYS. CONTRACTOR SHALL GIVE THE OWNER 24 HOURS NOTICE WHEN SURVEYS ME REQUIRED. ANY MONUMENT FRAME OR COVER DAMAGED BY THE CONTRACTOR OR HIS OPERATIONS SHALL BE REPLACED BY THE CONTRACTOR AT NO COST TO THE OWNER. AN OPEN STREET PERMIT SHALL BE OBTAINED FROM THE CITY OF BAKERSFIELD PUBLIC WORKS DEPARTMENT FOR ANY WORK PERFORMED WITHINACCEPTED STREET RIGHT-OF-WAY. UNLESS SECURED BV A SUBDIVISION AGREEMENT, A DEPOSIT BASED ON APPROVED ENGINEERS ESTIMATE FOR THE WORK PERFORMED WITHIN THE RIGHT-OF-WAY AND INSURANCE SHALL BE POSTED PRIOR TO ISSUANCE OF THE PERMIT. R U, U m !o K d ¢ a Z FILE NAME: w SCALE: 0 m 2 OF 111111 m w u m > i5 9 Sm$ m Zq m¢2r 0 . e O m x ;03: m N m d W LL = R U, U m !o K d ¢ PLOT DATE: Sep 15, 2016 a Z FILE NAME: w SCALE: 0 m 2 OF m w u m > i5 9 Sm$ m Zq m¢2r 0 . e O m x ;03: m N m d W LL = U U) O • mm - cZ C W ¢w 4 m F-- c_Z C m PLOT DATE: Sep 15, 2016 JOB NO.: Z FILE NAME: 142VOZSDSs-WTES SCALE: 0 SHEET NO.: 2 OF U) > Lu 0 o m U) O cZ C _ F-- c_Z C j N ¢Q a J m :52 Q :5 2' 3ow �i LLJ tSw g O 0 plLLi, U Z PLOT DATE: Sep 15, 2016 JOB NO.: 14292 FILE NAME: 142VOZSDSs-WTES SCALE: NONE SHEET NO.: 2 OF ju Know what's below. 0811 before you dig. 1 357 355 1 353 1 351 349 347 345 16+00 —L 16+00 CONSTRUCTION KEY NOTES (THIS SHEET ONLY): �i EXISTING SSCO TO BE REMOVED, TIE INTO EXIST. 6' SANITARYSEWTR / STfi: 1}ibWt AVS.Iao Vr1.21 =.MLN -4.< 4d t- la _' 7?IV• V" S fi�'V� NNY:i'999682 / of 7 -SO° 30'26.OVW 30.00' — — — — — — — — — --T I 17+00 17 11+4Or4A , fy7°Is 1W"%� VAV ,,V. M" Gk1j i470•41 0011111 EXISTING GRADED it SLfr CENTERLWE R1M;=[i.l.l �" SS t.RTEMA- A4V•�A E$N 3�•t.t ' 30' 0' 30' ON- SITES PER SEPARATE PERMIT LEGEND BCR BEGIN CURB RETURN BSW 940KOFS97EWALK GB CHAIN LIW FENCE CR GROWN OF ROAD C&G CURB B GUTTER DI CM DRAINAGE INLET EP EDGE OF PAVEMENT ECR END CURB RETURN (000.00) EXISTING ELEVATION FH FIRE HYDRANTASSEMBLY FL FLOWUNE FTG TOP OF FOOTING ELEVATION SO STORMORMN GB GRADE SREM SDMH STORM GRAIN MANHOLE GV GATE VALVE STREET LIGHT (ARTERIAL) INV. INVERT STREETLIGHT(LOCAL) P PAVEMENT W WATER UNE TC TOPOFCURB 0 WATER METER 000-00 PROPOSED ELEVATION WV N WATER VALVE SS SANRARYSEWER G GAS LME SSW SANRARYSEWERMANHOLE ® 'R'VALUE Sbmw SLOPE, INFOOTPERFOOT A SIREETSIGN STA STATION ® SURVEYMONUMENT ' RMT -996.11' ST"•:}p{03-,V AI 'Lr JIA46"EB966P MW -6'£9/9T9 Seri —— _ PROPERTY LINE T,1JV• VM 6�M1 3M1.14 'j'NN7�Il 201 Lf OC bT• t5 RIM se�.s� Qlft Q V` 45 �" 65 6N s5 Lie lfi we 1I• 6. 58.00' 4"55 6"SS ILII INST4 ALL 4IINSTALL L��IPE D EKLSTWG ASPHAITPAVEMENT D EXISTING CONCRETE PROFILE LEGEND OUTSIDE OF PIPE INSIDE OF PIPE OUTSIDE OF PIPE J CLAUDIA AUTUMN DRIVE SEE SHEET 4 LOT 17 N89' 34' 49.00'W 39.59' 55 INV. 6" S 346,88 LOT 18 IE 1 5,6 fife 4 so 0.09roKK ([ `'�l"��►�' ("ASS ------ N'7 "� 1FG4 i`%• �cS i'7B E`¢I. l+cs bK6 ` —1-�i CONSTRUCTOH#1 STA:23+40.11, 35.00' LT INSTALL SSMH 35.00' RIM: 357.11 INV. 6' N 347.63 19+00 40+00 21+00 INV. 6"W 347.73 I I N89°29'31."W 2650.33' 22+00 23+00 _ 24+00 CENTERLI- NF/SEC116N LINE ST O CKDALE HIGHWAY 34i.tK Vtr. yl�Gi.Ie 2iAI1+A.�. Lti M 4uA 1S4•L� TyT zs1 INSTALL'W LF OF 6' o SS PIPE -- @S=00050 23+00 CITYRE� CO 357 1 355 1 353 I 351 1 349 1 347 1 345 1 T PLOT DATE: Sep 20, 2016 JOB NO.: 14292 FILE NAME: 14292.03_SUSS_STOCK SCALE: AS NOTED SHEET NO.: 3 OF 6 z O_ LU .5 a co Q O 2 z Iz ¢i W '..a Q JQ c z w me s¢m Q LL O �e w Of <o e U o X 3zN O a LU �wm J U cp PLOT DATE: Sep 20, 2016 JOB NO.: 14292 FILE NAME: 14292.03_SUSS_STOCK SCALE: AS NOTED SHEET NO.: 3 OF 6 15 Know what's below. Call before you dig. 1 357 355 1 353 351 1 349 347 1 345 CONSTRUCTION KEY NOTES (THIS SHEET ONLY): [D ADJUSTEXISDNGMANHOLE TOFMISH GRADE �2 EXISTING SSCO TO BE REMOVED, TIE INTO EXIST. 6• SANITARY SEWER ❑3 SEE SEPARATE STOCKDALE HWY UTILITY PLAN FOR 6- TIE-IN TO SANITARY SEWER MANHOLE STOCKDALE HIGHWAY SEE SHEET 3 LEGEND FTG BCR BEGIN CURB RETURN STORM DRAIN SSW BACKOFSOkWALK sow STORMORAMM4NHOLE GV GATE VALVE .—,� STREET UGHT(ARTERIAL) INV CHAIN LINK FENCE LU CR CROWNOFROAD L_—U W WATERLINE D) CURBBGUTTER in WATER METER NORTH D ME DRAINAGE INLET WATERVALVE 30' 0' 30' EP EDGE OF PAVEMENT '— -r--`� ECR END CURB RETURN ® (000.00) EXISTING ELEVATION SLOPE, IN FOOT PER FOOT FH � FIRE HYDRANTASSEMBLY STA FL FLOW LINE FTG TOP OF FOOTING ELEVATION SO STORM DRAIN GS GRAOEBREAK sow STORMORAMM4NHOLE GV GATE VALVE .—,� STREET UGHT(ARTERIAL) INV INVERT LU STREET UGHT(LOCAL) P PAVEMENT W WATERLINE TC TOP OF CURB in WATER METER 000.00 PROPOSED ELEVATION WV H WATERVALVE SS SANITARYSEWER G GAS LINE SSMH SANITARY SEWER MANHOLE ® 'R'VALUE 59.0000 SLOPE, IN FOOT PER FOOT INV. IBIS 350.66 STREETSIGN STA STATION ® SURVEY MONUMENT �' 35 , H S89° 10 00 CENTER UNE m +� -, - - 0"�--- � 34'40. DEXISTINGASPH (`PAVEMENT DEXISTING CONCRETE OUTSIDE OF PIPE 101M] - _ 22 589°34'42.24•E 36.73'_— CONSiRUCTMH#, � RIM'357.SSMH -- RIGHTOFWAY----------- INV. B'W397.73 (] E%IST, SSkti..; 0135530 ) I N T. RIM: 35605 - INV. 6'S 346.88 INV. B N 344.75 toT 6Nv a I ;.. asaa INSTALL 65LF OF6'0 I su8ven SS PIPE @ S�.0116 EYIST. SSW "� I -':19:356.70 STOCKDALE HIGHWAY SEE SHEET 3 (R]M-357.11 INSTALL 65 LF OF 6' 0 .SS PIPE Q S=GDJ 16 11+00 MADISON MICHELLE AVE CLAUDIA AUTUMN DRIVE IrN34311 B' S 343.50 ". 8'W 343 25 10" E 343.20 T OUTSIDE OF PIPE INSIDE OF PIPE 0 357 EXISTING GRADE @ �— _ CENTERLINE STA 16+22.63, --. � iL, ' Li INSTALL 'TYPE ADI / 355 w U 353 INSTALL 26 LF OF 18' 0 SO PIPE @$=0.8036 INV. 18'N .76 y1V.,B•5350.� 351 I 349 347 INSTALL4•SS I LATERAL 1 I 1 i 345 I 1 1 1. I 12+00 13+00 14+00 15+00 16+00 17+00 CIT1'RECORDSNO. i a STA 16+2263, 22.00 LT m o, LU LL M m CONSTRUCTCATCH r�aom ti 0 r m BASIN PER CITY STD m. = 2 10 N o _a 0-14, D-16, 8 SW -5 INV. IBIS 350.66 -6 EL Y LL TC 355.23 N m wD W FL 354.73 o LOT 17 LOT 16 LOT 15 LOT 14 LOT 13 INV.18'N350.76 INSTALL LL28LFFOOFSO LOT 10 m LOT 18 m c LOT 12 PIPE @ F1� PIPE @ o g » s N Q Q Z $ 8 8 8 I g $ 8 s O w tY c�r/ T ::3 :D LLl � e —1 J m LOT 11 m N89°34 9.00'W 39.59' ffi m a m y a 4' SS LATERAL m S69'30 4' TYP. + y 3s.az E 39.9e' a y a y a S89° 30' 39.42' 39.32' cc N __— --_ _-1TYJ— ------ 589° 35' S6.78'E —_—__ 39.06' m 8' ----- LINE— --_--__----_ y 589"34'41.78" y 35_90_ — _ — — — _ y — — — — _ _ i. m S89°35'5694"E 39 09' �' 35 , H S89° 10 00 CENTER UNE m +� -, - - 0"�--- � 34'40. DEXISTINGASPH (`PAVEMENT DEXISTING CONCRETE OUTSIDE OF PIPE 101M] - _ 22 589°34'42.24•E 36.73'_— CONSiRUCTMH#, � RIM'357.SSMH -- RIGHTOFWAY----------- INV. B'W397.73 (] E%IST, SSkti..; 0135530 ) I N T. RIM: 35605 - INV. 6'S 346.88 INV. B N 344.75 toT 6Nv a I ;.. asaa INSTALL 65LF OF6'0 I su8ven SS PIPE @ S�.0116 EYIST. SSW "� I -':19:356.70 STOCKDALE HIGHWAY SEE SHEET 3 (R]M-357.11 INSTALL 65 LF OF 6' 0 .SS PIPE Q S=GDJ 16 11+00 MADISON MICHELLE AVE CLAUDIA AUTUMN DRIVE IrN34311 B' S 343.50 ". 8'W 343 25 10" E 343.20 T OUTSIDE OF PIPE INSIDE OF PIPE 0 357 EXISTING GRADE @ �— _ CENTERLINE STA 16+22.63, --. � iL, ' Li INSTALL 'TYPE ADI / 355 w U 353 INSTALL 26 LF OF 18' 0 SO PIPE @$=0.8036 INV. 18'N .76 y1V.,B•5350.� 351 I 349 347 INSTALL4•SS I LATERAL 1 I 1 i 345 I 1 1 1. I 12+00 13+00 14+00 15+00 16+00 17+00 CIT1'RECORDSNO. i PLOT DATE: Sep 20, 2016 .TOB NO.: 14292 FILENAME: M2SZ04jB_SD-55_CIA SCALE: AS NOTED SHEET NO.: 4 OF a m o, LU LL M m r�aom ti 0 r m m. = 2 m N o _a U -6 EL Y LL N m wD W o 4 m a 3 it o m a m PLOT DATE: Sep 20, 2016 .TOB NO.: 14292 FILENAME: M2SZ04jB_SD-55_CIA SCALE: AS NOTED SHEET NO.: 4 OF LU LL zo vii _a -6 EL LL W o vim, o zz c o g » s N Q Q Z U) Lij¢v8' U O w tY c�r/ T ::3 :D LLl � w a —1 J PLOT DATE: Sep 20, 2016 .TOB NO.: 14292 FILENAME: M2SZ04jB_SD-55_CIA SCALE: AS NOTED SHEET NO.: 4 OF OUTSIDE OF PIPE II LOT LOT LOT5 LOT4 LOT3 LOT2 _ LOT I LOT I J - + 00 A -A _S89° 40.69"E 39.43' y _ _ 4 — - S89°3440.69E 39.10 " `� y — _71, — _ _ 35.44' �" _ — — — — — — m 589° 34' 58. 569 340 16.60'E 39.68' y — — — �� j9:5980'E 39.33' --P 4 589340' iB.BO'E 39.1 P I _ \ w i, �� INSTALL 12"x12"x2' DEEP ROP�RIY �/� W �/) W SYd.�,... RIP -RAP WITH GUNI7E 'i S�oN�E w �' AT OUTFALL STRUCTURE W •L� DO 68 10'19+00 20+00 21+00 — — — — 1 22100 -F — _—� t -� — I— — 23+00 OR S _ _ \ 24 12 F SUMP DETAILS EE W' (E)SS — .,. — I \ SHEETS r _ 19— �.y_ IE)CS—IE166 E7S.5 Edo— ;a5 L i l �� �W/� p NO 25' 11.OL1'E 1394 01 J _ 24+00 05 tiS iE Su ES ;7 L — _ Vis+ _ — _ RMITOF WAY— _ _ _ _ _ _ _ _ _ _ _ _ _ _ -- `\\; � TSTA: 20+76.93 5.44' RT EXIST. SSMH _ \ \ EXIST SSMH RIM 355.75 \ I RIM 352.90 INV _6'3350&:: A INV. 6'N 348.30 INC. 4'E 35105 \y\ 1 INV. 6'5348.27 t ExlsT ssn;,. 357 355 CLA UDIA AUTUMN DRIVE IMv0DItoaIRWAViDP 357 IST. SSMH R :355.75 J 355 353 1 1 1 1 1 1 1 1 1 1 353 351 349 INSTALL4' SS LATERAL (TYP.) 351 349 347 I a -— 347 ;SNS ILF OF _ I 345 1 I 1 I- I I -1 1 1 345 19+00 20+00 24+00 25+00 3 NO. .�/VY, SY w� dO'0 N13JSo* 54v 33n LEGEND N F -- N w F LU LL � � r BCR BEGIN CURB RETURN FTG TOP OF FOOTING ELEVATION SO STOW DRAIN m Q vi SSW BACKOFSOEWALK GB GRADE BREAK SOMIN STORM DRAW MANHOLE Y EXISTING ASPHALT PAVEMENT ® ow m g o o w CHAIN LINK FENCE GV GATE VALVE . STREET UGHT(ARTERIAL) U)zz �z CR ON!O!R!T*� CROWN OF ROAD INV. INVERT ZD STREET LICHT(LOAL) EXISTING CONCRETE CSG CURBAGUTTER P PAVEMENT W WATERLINE Q Know what's below. DI DRAINAGE INLET TC TOP OF CURB la WATER METER 30' 0' 30' EP EDGE OF PAVEMENT ".W PROPOSED ELEVATION WV N WATER VALVE Q Call before you dig. 0 U U LEGEND ECR END CURB RETURNPROFILE SS S4NUARYSEWER G GASLINE OUTSIDE OF PIPE (800.00) EXISTING ELEVATION SSMH SANITARY SEWER MANHOLE ® 'W VALUE FH)w FIREHYDRANTASSEMD.Y S=.0000 SLOPE, IN FOOT PER FOOT A STREETSIGN FL FLOW LINE STA STATIN ® SURVEY MONUMENT INSIDE OF PIPE OUTSIDE OF PIPE II LOT LOT LOT5 LOT4 LOT3 LOT2 _ LOT I LOT I J - + 00 A -A _S89° 40.69"E 39.43' y _ _ 4 — - S89°3440.69E 39.10 " `� y — _71, — _ _ 35.44' �" _ — — — — — — m 589° 34' 58. 569 340 16.60'E 39.68' y — — — �� j9:5980'E 39.33' --P 4 589340' iB.BO'E 39.1 P I _ \ w i, �� INSTALL 12"x12"x2' DEEP ROP�RIY �/� W �/) W SYd.�,... RIP -RAP WITH GUNI7E 'i S�oN�E w �' AT OUTFALL STRUCTURE W •L� DO 68 10'19+00 20+00 21+00 — — — — 1 22100 -F — _—� t -� — I— — 23+00 OR S _ _ \ 24 12 F SUMP DETAILS EE W' (E)SS — .,. — I \ SHEETS r _ 19— �.y_ IE)CS—IE166 E7S.5 Edo— ;a5 L i l �� �W/� p NO 25' 11.OL1'E 1394 01 J _ 24+00 05 tiS iE Su ES ;7 L — _ Vis+ _ — _ RMITOF WAY— _ _ _ _ _ _ _ _ _ _ _ _ _ _ -- `\\; � TSTA: 20+76.93 5.44' RT EXIST. SSMH _ \ \ EXIST SSMH RIM 355.75 \ I RIM 352.90 INV _6'3350&:: A INV. 6'N 348.30 INC. 4'E 35105 \y\ 1 INV. 6'5348.27 t ExlsT ssn;,. 357 355 CLA UDIA AUTUMN DRIVE IMv0DItoaIRWAViDP 357 IST. SSMH R :355.75 J 355 353 1 1 1 1 1 1 1 1 1 1 353 351 349 INSTALL4' SS LATERAL (TYP.) 351 349 347 I a -— 347 ;SNS ILF OF _ I 345 1 I 1 I- I I -1 1 1 345 19+00 20+00 24+00 25+00 3 NO. .�/VY, SY w� dO'0 N13JSo* 54v 33n PLOT DATE: Sep 15, 2016 JOB NO.: 14292 FILE NAME: 14292 04_05_SD-% CLAL SCALE: AS NOTED SHEET NO.: 5 OF I N F -- N w F LU LL � � r o_ "' h m Q vi m v O(n lux Y W ow m g o o w is m w U)zz �z a o PLOT DATE: Sep 15, 2016 JOB NO.: 14292 FILE NAME: 14292 04_05_SD-% CLAL SCALE: AS NOTED SHEET NO.: 5 OF I N F -- w LU o_ "' W ow �o o U)zz �z ZD l (n Q ' Q Q ES _Q of ] yy 3ZN LLL hWm Q Q 0 U U PLOT DATE: Sep 15, 2016 JOB NO.: 14292 FILE NAME: 14292 04_05_SD-% CLAL SCALE: AS NOTED SHEET NO.: 5 OF SW -1 I STANDARD SEWER LATERAL /Q'pIT-A1�-xAY YjWgpp Yb wri rypW rmNi �PG1A5 ^ 2CYS p 9A a2' + 03' + 20' HINM SIATE �a A ✓r N w p U a `� "Ip M N AL STAKE AC MlU eatl gmabmeYkmgpanl qml m0 Y[oe T Am xa25'fYM 11Fay�25' AM �I �a MF T Nrbl� '7 uW "i c:F• AIN2O--uwTY CYM u AIMM WI^N.^a RLL SaeENr ll} (7 m m LW RAMP G.SAETFO CAP Q $ LA TVML a I 40' MM. r as'lrssJua mw x-rxlNW L U) NOTES: ,1'r IY (L'ma+abJ Npf Ap eyrW iY Z k U w r. srAw s' Mro alis FACE ALta scacR a rtRAL bid lAmrj Po� 2 Exaf NNWW W'dR ANA F.0 NAxaIUY L'OKfl Ar wad yj AANA SJ' MM9YUAI AT TLOINM£. PMJiERTY 1Y LAW f>sml a g J, LATEIMLs LtICAU w NAr w LAALCr Wm UWAN Tom~ /len eelas L �' YrnrN I mix ar.m h^T�i .am w rd p.mJNM PLAN STEEL PLATE OErAIL w STANDARD xaws aP�lan J gfillag N 9e ✓tm rgrm'� �YMIeR (A"D m1t3(KrJ Q SEWER LATERAL MARKEROF Nmn Mu*L Yd4 IM nb raw Sris sm YM NOTES. mei J SNA myhmya.+vlyw MkYW b1JaM—� LR Ma J✓ Nmnr sll Mtlm'A"N eldb ailS(6enJbiT C/) bnl W xasxW PA' b M1.6 gpA,w INI ✓ { fares/Wr CfIT CAIFORN13-D SW -1 l'+ la aR /pWYeWllk ilbN'Ye tYfenyY m NMbArMaYmAn PeAAa mf -A O9AYb (Lsml LSaR m+MN wrdawM nWoawwa Of SW -1 I STANDARD SEWER LATERAL D-14 I CATCH BASIN TYPE "All NOTES' YjWgpp Yb wri rypW rmNi �PG1A5 ^ 2CYS p 9A AWpjp ad Y Wb dVua . v �a A ✓r N w p U a `� "Ip TmNmMeLmW Am w p4a NWTmf m0 eatl gmabmeYkmgpanl qml m0 Y[oe T Am xa25'fYM ' baY�rmesY»an.'Ibr Nvwbu'f �I �a MF T Nrbl� '7 uW "i speb: NNmM1s m.b9w.awYA AIMM WI^N.^a ®iaW aln tNyw NR Y (7 m m imMb dY� mMWmRwANban daMY Q ! a ILYMNMM w1Y MbaxiYyA AAI r as'lrssJua mw x-rxlNW L U) aMY bl Py2NM wbmb YN4NN. ,1'r IY (L'ma+abJ Npf Ap eyrW iY Z k U w GNf k6r ('m! SfmNN N My tlq Pye vo'-bbl bid lAmrj Po� S NY mee'es nmv 1- afifip iqr a• c.Rx� wad yj Me w er MN AIM OW ,:M Oe hu.. [,•[u'u ml NnmbA MA Pe f>sml a g b Npr iN PN are bm IM qs 4rMI5e �MmwaJ P' Tom~ /len eelas L �' YrnrN I vpMy b r r oM ry I oeyh ar.m h^T�i PLAN VIEW S qm urs .. M Y mak ry M w rd p.mJNM PLAN STEEL PLATE OErAIL w piagt uOnil Wr AW fupvmgss xaws aP�lan J gfillag N 9e ✓tm rgrm'� �YMIeR (A"D m1t3(KrJ Q Nr 9wY A+e Nmn Mu*L Yd4 IM nb raw Sris sm YM NOTES. mei J SNA myhmya.+vlyw MkYW b1JaM—� LR Ma J✓ Nmnr sll Mtlm'A"N eldb ailS(6enJbiT C/) bnl W xasxW PA' b M1.6 gpA,w INI ✓ { fares/Wr P fm PYC NAaifp N.Yy Mb AjSn mmAtl l'+ la aR /pWYeWllk ilbN'Ye tYfenyY m NMbArMaYmAn PeAAa mf -A O9AYb (Lsml LSaR m+MN wrdawM nWoawwa Of LNMrmrmM1waliYaaaedw NM YrmI A.3Nn (NnJ xmarmW daNr norma f< 66I4eMdW __ _ 9idPIhW lYpamrdwgsra: mar � nap imr was l4d(oYJar WAW (xri n'xd NaJ --j A M s As sa{yn M a em. ynera Ne v nW Qri WP(adeJ RM bYa MYbOf m s Zl, w. Ma wNWmn dr nN, Rmd4 A9ia N'mwlWmVrrxYtl Wd ■EL AS Nn ° NA40r ird�J In� ab Y�r NNr AA k '�' ApimbW N Adm lAad(zr).N N1-mf2w M ardswm N Mb a®fq avn Lae Mbnabvo eMmar. ELE✓AnON ,� aac bx sp NMM9 AdaYAM is tl Ld (,115n1 Ar A5(QNa rar W:.Mm i i mmamwarmm. A,w Lxn NN.J ( rdwW STANDARD�.Pn. 1 IAl UN{sbrbNrdbeWs I 0.7 I IT [SePrba YfbalmllrnlxdPM,➢miel.5d (LSaI SEWER PIPE .yANi rMYew AM ld (aWYfd (IA1 QC CONNECTION eN zmme Nr aenr Sr Po+W aW aJMPdNna CRY OF TIN(919IMED SW -7 �" io'NYl WAn rd (zadAw Mb•... axMbAa.wsd(ewl CALFgiIA mWa dmAN yd INSIDE AND SECTION A -A a 1prMbmqufds mJnMhpaylpMl. w ¢C AO Nie) bd ®yaMmwAye wsawmriynldwhwahYM Kral it PoxN M. Ned Ap MOWYa drsaM e' ar> W metl'd TYN19axMLA •Mr-kMda m(zr)w STANDARD aNnn ° le.,w fM: apt m.rmw LAn aA en. 'a' . asPoYI hn SECTION A -A STANDARD.T,�. JUNCTION BOX • e� y..-IANmJw CATCH BASIN TWE A' OF BAKEF04ELD D-16 _r REINFORCING AROUND PIPE ora CffY DF BAKgBB.D D-14 CAtIQ"RM D-14 I CATCH BASIN TYPE "All SW -7 I STANDARD CONNECTION TO EXISTING SEWER MAIN NOTES' Mb �PG1A5 ^ 2CYS p 9A AWpjp ad Y Wb dVua . v �a A ✓r N w p U a `� "Ip TmNmMeLmW Am w p4a NWTmf m0 gmabmeYkmgpanl qml m0 Y[oe ' baY�rmesY»an.'Ibr Nvwbu'f speb: NNmM1s m.b9w.awYA ®iaW aln tNyw NR Y (7 m m imMb dY� mMWmRwANban daMY Q ! m ILYMNMM w1Y MbaxiYyA AAI Q N Q o U) aMY bl Py2NM wbmb YN4NN. O Z k U w GNf k6r ('m! SfmNN N My tlq Pye vo'-bbl rn S NY mee'es nmv 1- afifip iqr a• c.Rx� Me w er MN AIM OW ,:M Oe hu.. [,•[u'u ml NnmbA MA Pe m N g b Npr iN PN are bm IM qs 4rMI5e �MmwaJ P' vpMy b r r oM ry I oeyh PLAN VIEW S qm urs .. M Y mak ry M E— w piagt uOnil Wr AW fupvmgss iN J gfillag N 9e ✓tm rgrm'� f/1 Q Nr 9wY A+e mei J SNA myhmya.+vlyw MkYW C/) bnl W xasxW PA' b M1.6 gpA,w INI ✓ P fm PYC NAaifp N.Yy Mb AjSn mmAtl � m NMbArMaYmAn PeAAa mf -A Of LNMrmrmM1waliYaaaedw NM YrmI A.3Nn f< 66I4eMdW __ _ 9idPIhW lYpamrdwgsra: o --j A M s As sa{yn M a em. ynera Ne w m s Zl, w. Ma wNWmn dr nN, LU AS Nn Y�r NNr AA 2 M ELE✓AnON i i mmamwarmm. A,w Lxn STANDARD�.Pn. d I 0.7 I SEWER PIPE CONNECTION CRY OF TIN(919IMED SW -7 CALFgiIA yd INSIDE AND SW -7 I STANDARD CONNECTION TO EXISTING SEWER MAIN D-16 I JUNCTION BOX PUN AT SURFACE xnYln darbbN �AY eN d LnR Ldn Mesa P.Ca W N b a pod rt pNyeA 9YNa baa b0.23' aL es mMNpdN fiew T SW -2 I MANHOLE TYPE "A" rlsr a A <m>ef. Yrm Mb �PG1A5 ^ 2CYS p 9A ur(udr� F--tnJ+� �a A ✓r N w p U a `� "Ip ad Ymerd xr m wd m Nrsa .wdi PoNd Pores aAKW r.rfaxa NLr � ir>PoxAK;d . Ms iv f �A Ad WSN (7 m m SwW Y Q roMnLrw xW m INw SY (nAb Sd.L) Q N Q o U) ill 0.rr w"It. O Z k U w d rn aye xd NaAy Wtw ro nmrotr Ad Lr. Wrt nes dxwv ran E.I�Z m N g 3 I A I NdsdNW acr E— w YNAma +u PoN�M:w. iN J s mN f/1 Q Aram xrb PUN SELRgJ B -B mei J zrYr, n C/) Tal ix MILMN¢w q Sd/LSu/ � m Lr Pome3 (abWiRAWNOTES Of LNMrmrmM1waliYaaaedw NM YrmI A.3Nn f< 66I4eMdW __ _ 9idPIhW lYpamrdwgsra: o --j LPIQr/ aAwlo�M rJae+ w m s er Rp L N muW MYtlm'a'er NaW LU Aw yVy0Yw 0)ANAw. lA'PoWe)Yn Porlr y MMYM/fmmM NW 2 mM ipdLT(a6e)QC �� awNrry MYbyWNs d5F6 i i mmamwarmm. A,w Lxn - best robid (s.ilAwp rMr d I 0.7 I «I rr+NA i sFy.Mb.wmMmMhwaraym Maffi Ne e e STANDARD as Au e^f yd INSIDE AND ¢C AO Nie) bd Kral it PoxN M. Ned ar> W m(zr)w STANDARD aNnn LAn aA en. 'a' SECTION A -A JUNCTION BOX OF BAKEF04ELD D-16 D-16 I JUNCTION BOX PUN AT SURFACE xnYln darbbN �AY eN d LnR Ldn Mesa P.Ca W N b a pod rt pNyeA 9YNa baa b0.23' aL es mMNpdN fiew T SW -2 I MANHOLE TYPE "A" rlsr a A <m>ef. Yrm Mb �PG1A5 ^ 2CYS p 9A wM �a A ✓r N w p U a `� "Ip PLAN AT BOTTOM NOTES L N M M rmMn la Ne y(AN'k xfv✓s o/ AM gnKtWrm> MM1IM 3fmA✓ QenRufv4 Sb(I o{ ryob,nr: aTrmgrfofr: qpw f qYr 2 N aMAH mmkx pnn ✓rd b /.%d M xmt N n wseaJ aw amfT wd xoN a nmA[rm mM b mmm.e r Omar mrd a• .xm m A x dgoa J fle mat '!um'/ nmAde mlm.Tf M emsbrctal Aar,nwwm:.�,a,Asv�.Po N a a mm• �awMx I ++m Yes Mqa um rs A made. M M xd nm 'r -fm' a aro�rob caw '. gimme. rGwo M me.a a We pmmfY mrpvad mPa sa'r ya->orP arw efmWd ¢ sm srmAre ACAy sw-h Y ru„e. m�e, we Jm mWMe hfa: N drawl MW M vm+M fi,NnJ rvM Gee' hwN SIW MY bran fiMN bcq rtrrslanc STANDARD MANHOLE TWE 'A' "a is:. -`.?—III SW -3 I MANHOLE TYPE "A" INSIDE AND OUTSIDE DROP HIGH WATER LINE 334740 6' TRACT6144 BOTTOM EXIST.: 3339.40 1 L ROTT(W PROP_�3337.90 / \ SUMP CROSS SECTION DETAIL A -A a A <m>ef. Yrm bd, �PG1A5 ^ 2CYS p 9A s FMA IYC6 Na aMpwyb Aptre �a A ✓r N w p U a `� "Ip zQ' .rbE Lbwfe wx N wnNdr NwbI SLi �� IY Ad WSN (7 m m SwW Y Q roMnLrw xW m INw SY (nAb Sd.L) Q N Q o U) ill 0.rr w"It. O Z k U w Ls'r hill left rn aye xd NaAy Wtw ro nmrotr Ad Lr. Wrt nes dxwv ran E.I�Z m N g 3 I A Yatl./ aT Lw. E— w .bbYPo ANe 11 bps lJ iN J Sd as'e'cmnra f/1 Q Mft mei J INSIDE DROP C/) se morn/ NO ES � m Pa' 1 N enf M nbn Y a 9YaW Of SbdM Mesas' aNmMwgm.Wdi.A tWl f< arW N L➢b 'SNnM.NeeYan Sir d(babN¢ o --j pr Fa 5F6 awhenf d Fgna6w' m"dN w m s Y Lm amMRt Aw LW LU z aq xNLa.i aYFa 1N W Ler saL waPrdYayayN- 2 AO SrW,IY SNn MAa bh mi dYm ak i Mb S1 wAN Anh MrxMW Nrow <pm (ri. ymlMf A'. Rrw. d ' � � •LMrun dg tlawi MN maxda wT6IaN MMe w d wYnay Nrynwm LRM' m 5'.16f S fuMgMNfnnY wwMudYlpC&ofou WANNYMbMArbb�.q Aay MNS Pb'q STANDARD MANHOLE TYPE 'A' yd INSIDE AND sfaW4AY em OUTSIDE DROP OUTSIDE DROP CRY OF SAKERNIFE.D SW -3 CII fKNS moe fN L -0a. Y aeR COVERS FOR SW -3 I MANHOLE TYPE "A" INSIDE AND OUTSIDE DROP HIGH WATER LINE 334740 6' TRACT6144 BOTTOM EXIST.: 3339.40 1 L ROTT(W PROP_�3337.90 / \ SUMP CROSS SECTION DETAIL A -A SW -6 I STANDARD FRAMES AND COVERS DETAIL EXCAVATE 641 CU YO LOWER THE BOTTOM OF POND BY 1.5 FT @ 2:1 SIDE SLOPES PCQ W ed ro a Pm+M bd, �PG1A5 ^ 2CYS p 9A s FMA IYC6 Na aMpwyb Aptre �a A ✓r N w p U a `� "Ip ar20V /Y 9W +2 P.CC Ma S�m%iAw as' Ld 7 �� IY �� (7 m m III sr SECTION 6-6 Q SECTION A -A m Q N Q o U) ill 0.rr w"It. O Z k U w Ls'r hill left rn s*PfalM Ld pelaA mMLr mw M aY1Rd alts m N g e e �A A SEWER E— w .bbYPo ANe 11 bps lJ iN J I.0'Mfer^ 0.6Lf'I#Iw f/1 Q rv� rie. ares' MrA alts mei J ho L iM C/) NO MANHOLE mbAa CLEANOUT NOTES � m AN b,wrmw Marrbs ) rrJY Of dxr MamW+A YMprroeMw I w�:N Sphm f< P Y rAd bmn'r M+q b d w wv+ o --j Ma �+Lrremnx em,ayaram las w m s Y Lm amMRt Aw LW LU PLNAy.Maw.nyp d.r rWrAAm �x Man' L✓ Rn,,. 2 � e�nN � DETAIL 'A i AN Annr M+MYwYwfim Aes M ny5 RN[ wlt N4 Na4A1M r d Mane cAeY rb NAnY L¢fiy Nutl 4YLd pawn Mae wNM Ms wT6IaN MMe w d wYnay Nrynwm LRM' m 5'.16f S fuMgMNfnnY wwMudYlpC&ofou WANNYMbMArbb�.q Aay MNS Pb'q a /q M 011 l 0 Afx` A -M (btef.ebrd QnrS$ If. 2dxLd4wral$'NR mY wn dwpxawxelp MMYMb n �arsM Y mrYndw m,m STANDARD I Mdm Oma M.aM NAmYrAh FRAMES AND moe fN L -0a. Y aeR COVERS FOR M eip NAn am fXft-- MANHOLES Ar CLEANOUTS w.*s LAn aA en. 'a' fl LYeatr mnsMYmorMYry Mdps COY OF OAKRSELD SW -6 CALFfXiIIA nd.Nn drag w'=m+aw arYFain SW -6 I STANDARD FRAMES AND COVERS DETAIL EXCAVATE 641 CU YO LOWER THE BOTTOM OF POND BY 1.5 FT @ 2:1 SIDE SLOPES SW -5 I STANDARD EIGHT INCH CLEANOUT NO. "S * d PCQ W ed ro a Pm+M bd, �PG1A5 ^ 2CYS p 9A s FMA IYC6 Na aMpwyb Aptre �a A ✓r N w p U a `� "Ip ar20V /Y 9W +2 P.CC Ma S�m%iAw nraM N w (7 m m 0 Q LL m n m Q N Q o U) �.—za+zd meN.Fmrame —.-I O Z k U w sdrPw rn ssnrK rglb ''1r -xabe cn m N g i 2e 20 !r !r lino N AR E— w Mamr teed iN J P.n-o NM. f/1 Q PASRI3 mei J Z�< i¢m C/) Lu J � m srWxyp ramex Any Of �zN f< Lu o --j LL w m s LYEANOUT SEC nON CWPACRON DETAIL LU NOTES INMM✓NYwa/HW mWnd ywYypp ar/WkMbyb.N L4�Y 2 w p�'ifa wMM �1eQSI SyerNMYN. 65 avm/e rnNbr r AS'wA Sea N[ANnII wAN N amWaleLm Ay N} i OMeeiKaYNobmr'w.M mord tie sTI MYaIeen Pa.NM. dx RNroMa a5'dtN ✓Ppa 6i esniaT as' d 2ltemrd MmN 1AP WpnMmNkb Ay dNebwr LylfN S N mvaa M a de A: IA,Mx M M Iff. A$ > P1C Pea Agent bmmrmw MtmrmbYIXfY l2 FibN ftLW fea0.1E5'nn rQlr dKYmaYI dmrtl SFG Na dA,r abdprg ache 5OMs MAwmaCBfl,gow Nw mRnM A.wMxw w0.ylwyim aYM.Ma M+Nx. na ppnNulR STANDARD fix. sa M}PQMd wdrN Nam STANDARD EICNT INCH 2 rmdYMM_ ..wmro rgiimi CLEANOUT yn bvm YA _a mw e ys NA'n mNsan Anpif yR* w ST -IL SW -5 SW -5 I STANDARD EIGHT INCH CLEANOUT NO. "S * d �GoO bd, �PG1A5 ^ 2CYS p 9A 2 �a A ✓r N w p U a `� "Ip 0 PLOT DATE: Sep 15, 2016 JOB NO.: 14292 FILE NAME: 1421Q -6 -PETAL SCALE: AS NOTED SHEET NO.: 6 OF z F 0 N w (7 m m 0 Q LL m n m Q N Q o U) O Z k U w U) rn m y O Q h cn m N g m E— w C C iN J U f/1 Q Q mei J Z�< i¢m C/) Lu J � m Of �zN f< Lu o --j LL w m s LU m 2 i o d PLOT DATE: Sep 15, 2016 JOB NO.: 14292 FILE NAME: 1421Q -6 -PETAL SCALE: AS NOTED SHEET NO.: 6 OF z 0 w (7 0 Q m U) O U) cn g E— w C C iN J _ f/1 Q Q mei J Z�< i¢m C/) Lu J LOUm Of �zN f< Lu "wm --j LL m s LU PLOT DATE: Sep 15, 2016 JOB NO.: 14292 FILE NAME: 1421Q -6 -PETAL SCALE: AS NOTED SHEET NO.: 6 OF