Loading...
HomeMy WebLinkAbout3015 wilson alarm report 2018 ANNEXSimplexGrinnell BE SAFE INSPECTION AND TESTING FORM SR Number: 42734636 Task Number: 3015 Wilson Rd. SERVICE ORGANIZATION Name: SimplexGrinnell Address: 2788 N. Larkin City, St., Zip: Fresno, CA ,93727 Representative: Jesus Salgado License No.: 986047 Telephone: 559 -348 -0614 MONITORING ENTITY Contact: SimplexGrinnell Telephone: (888) 746 -7539 Monitoring Account Ref. No.: 203 -7207 TYPE TRANSMISSION McCulloh Multiplex X Digital Reverse Polarity RF Other (Specify) _ DATE: November 21, 2018 TIME: PROPERTY NAME (USER) Name: Kern County Housing 6 Story Annex Address: 3015 Wilson Rd. City, St., Zip: Bakersfield, CA, 93304 Owner Contact: Irving Garcia Telephone: 661 - 387 -4304 Occupied as: Kern County Housing Authority APPROVING AGENCY Contact: N/A Telephone: N/A SERVICE Weekly Monthly Quarterly Semiannually X Annually Other (Specify) System Type: ( X ) Local; ( ) Auxiliary; ( X ) Remote Station; ( ) Proprietary; ( ) Emergency Voice / Alarm Control Unit Manufacturer: _ Simplex Model No.: 41000 Circuit Style: A & B Number of Circuits: Unknown Software Rev.: 12.08.02 CFIG: 31 Last Date System Had Any Service Performed: January 18, 2018 Last Date That Any Software or Configuration Was Revised: 17- March -2017 Quantity of Devices Installed 14 0 134 0 13 7 ALARM - INITIATING DEVICES AND CIRCUIT INFORMATION Circuit Style A A A A Alarm verification feature is disabled X Rev. D Quantity of Devices Tested 14 0 134 0 13 7 enabled Manual Fire Alarm Boxes (PSSA) Ion Detectors (ISD) Smoke Sensors (ASD) Duct Detectors (DSD) Heat Detectors (HD) Water Flow Switches (WF) (Specify) (Specify) (Specify) Page 1 of 9 PRIOR TO ANY TESTING NOTIFICATIONS ARE MADE Yes No vvno I 1111c Monitoring Entity X SimplexGrinnell 8:OOAM Building Occupants X Staff /Residents 8:OOAM Building Management X M.O.D 8:OOAM Other (Specify) AHJ Notified of Any Impairments SYSTEM TESTS AND INSPECTIONS TYPE Visual Functional Comments Control Unit X X Pass Interface Equipment X X Pass Lamps/LEDs X X Pass Fuses X X Pass Primary Power Supply X X Pass Trouble Signals X X Pass Disconnect Switches X X Pass Ground Fault Monitoring X X Pass SECONDARY POWER TYPE Visual Functional Comments Battery Condition u Good - Batteries Installed August 2016 Load Voltage X Pass- Combined Voltage 26.49VDC Discharge test X Pass-25.89VDC Charger test X Pass- 27.44VDC TRANSIENT SUPPRESSORS N/A REMOTE ANNUNCIATOR Pass -1S Floor Maintenance Room NOTIFICATION APPLIANCES Audible X X Pass Visible X X Pass Speakers X X Pass Voice Clarity N/A INITIATING AND SUPERVISORY DEVICE TESTS AND INSPECTIONS Device Visual Functional Factory Measured Location & Serial Number Type Check Test Setting Setting Pass Fail See attached detailed report. Date of Last Sensitivity Test: Unknown EMERGENCY COMMUNICATION EQUIPMENT Visual Functional Comments Phone Set * Not Installed Phone Jacks Not Installed Off -Hook Indicators Not Installed Amplifier(s) Not Installed Tone Generator(s) Not Installed Call -in Signal Not Installed System Performance Not Installed Page 3of9 PROPERTY NAME: Kern County Housing Authority 8 Story Annex DATE: November 21.2O18 ADDRESS: 3015 Wilson Road Bakersfield, T�KA�^ ' INITIATING AND SUPERVISORY DEVICE TESTS AND INSPECTIONS (SUPPLEMENTAL SHEET) � Visual Functional Measured Location 3&Serial Number Device Type Check Test Address Setting Pass Fail 2woFL Storage. HD X X N2:yN1-074 2 'L Storage 2 'L Storage 2 'L Stair #1 2 'L Corridor 2 2 Nu FL Elevator Lobby PSD X X. N2:N11-067 2 Nu FL Corridor PSO X X N2:yW1-057 2"" FL Corridor 2 P0D X X N2:M1-054 ^ FL Corridor - --------- 2wuFL Stair #2 PGSA m��l-u/u ,w ' FL Annex Pump -------- 16/ FL Electrical Room P8D X X mu:xxl-uul ' FL ''-- -------� ' FL '''~'''--''-''-- ''--m -------- 16' L Communication Room -------- ' FL Communication Room ------- . FL Corridor 1 16' FL Laundry Room HD X X N2:M1-005 ' FL ^~~`'~~'- -------' ' FL Stair #1 Vestibule ------- / FL Women's '`e""°"''' HD X X N2:Ml-006 ------- 16' FL Trash Room HD X X N2:MI-002 . FL Elevator Lobby PSD ' FL Corridor 1 -------' ' FL Corridor I ------- ' FL Corridor 1 -------- 1 '3' FL Corridor 1 South Exit PSSA X X N2: M 1 -039 3";"u FL Corridor _ 3N'j FL Stair #1 , FL Elevator ____ ~ FL Corridor - ~ FL Corridor - -------- -T�D —FL Corridor 3 P8D X X N2:M1-095 ~ FL Stair ''- -------' Z ' L Stair #1 Vestibule –�Tff —FL - �___� �__-_� _--- _- Page 5 Of 9 PROPERTY ADDRESS: 3015 Wilson Road Bakersfield, CA, 93304 INITIATING AND SUPERVISORY DEVICE TESTS Location & Serial Number Device Type 8/HFL Room OD3A P8O 8''FL Room 6O2A pSD 0"'FL Room 8O1A P8D 5/'FL Room 5D4A P8D 5/'FL Room 5O7A PSO 5/'FL Room 5O0A PSO nFL Room 5O8/\ P8O _�n�F�LRoorn�O0A P8[J PG[) Room 51OA P8D Room 515A P8O -7A P8O P8D 4"-'FL Room 403A pSD ' '-''--m 404A PSD 4"' FL Room 405A PSD ' '-''--m 407A PSD 4/'FL Room 4O8A P8D 4"' FL Room 409A PSO ' '-R-- 4'nFL Room 41OA P8O 4"' FL Room 413A P8D ' FL Room 415A PSD - '- Room ---' 3NuFL Room 3O1A P8D 3Nu '- "Room ---'' 3 FL Room 305 ~ '- Room ---' 3nuFL Room 3O8A p8[) 3N" FL Room 309A PSO 3NL' 'L Room 31 ' 3 'L Room 312 3'�'u FL Room 315A P8D u"- FL Room 314* Pou 2 Nu FL Room 201A PSO 2 Nu .L Room 203 2 Nu FL Room 206A PSD 6 Story Annex DATE: November 21, TIME: (SUPPLEMENTAL SHEET) pouu,,v Measured Range Setting N2:N11-175 N2:N11'177 N2:N11-178 N2:W41-149 N2:yN1-144 N2:W41-150 N2:yW1-151 N2:yW1-148 N2:M1-142 N2:YW1-152 N2:yW1-141 N2:W41'140 N2:yW1-118 N2:M1-117 N2:W41-110 N2:M1-1 19 ------- N2:M1'115 N2:Ml-114-------- N2:N11-121 N2:W41-113 ------- N2:[Nl-122 N2:M1-111 N2:MI-110-------- -------- mu:xxl-uu/ -------` ------- N2:yNl-0*1 ________ N2:yW1-088 N2:W41-080 .`2.."..-094 ________ N2:W11-072 ______ N2:N11-064 N2:Ml-062 - 2018 AND Visual oxocx Functional INSPECTIONS Test Pass Fail x x x x x x x X, x x x x x x x x x x x x x x x x x x x x x x x x x x x x x x x x x X, x x x x x x x x x x �d I x To add more sheets, copy this page and paste itbo the end of this document Page 7 Of 9 PROPERTY NAME: Kern County Housinq Authority 6 Story Annex ADDRESS: 3015 Wilson Road Bakersfield, CA, 93304 INITIATING AND SUPERVISORY DEVICE TESTS Location & Serial Number Device Type _3RD FL Hall by Room 315A A/V 2 FL Hall by Room 201A A/V 2 Nu FL Elevator Lobby A/V 2 Nu FL Stair #1 A/V 2 Nu FL Hall by Room 205A A/V 2 Nu FL Hall by Room 209A A/V 2 Nu FL Hall by Room 210A A/V 2 Nu FL Hall by Room 215A A/V 1ST FL Hall by Laundry A/V 1 FL Stair #1 A/V 1 FL Elevator Lobby A/V 15 FL Hall by Room 101A A/V f5 FL Hall by Room 102A A/V 1 �5' FL Hall by Room 104A A/V 1'5' FL Hall by Room 109A A/V 116' FL Pantry Area VSIG 1 S' FL Activity Room A/V 16T FL Men's Restroom VSIG 1 FL Women's Restroom VSIG .161 FL Fire Pump Room FPOP 1 S-r FL Fire Pump Room FPOP 1 FL Fire Pump Room FPOP FL Corridor 2 PSD Penthouse elevator room PSD Penthouse elevator room HD 2018 Pass AND Visual Check Function2 INSPE( Test X X X X X X X X X X. X X X X X X X X X X X X X X X X X X. X X X X X X X X X X X X X X X X X X. X X X X DATE: November 21, TIME: '.TIONS (SUPPLEMENTAL SHEET) it Factory Measured Range Setting N2: M 1 -023 N2: M 1 -024 N2:M1 -025 N2:M1 -065 N2:M1 -202 N2:M1 -203 2018 Pass Fail ) X X X X X X X X X X X X X X X X X X X X LjX To add more sheets, copy this page and paste it to the end of this document. Page 9 of 9