HomeMy WebLinkAbout2018 CUPA REPORTBakersfield Fire Department Prevention
2101 H St
Bakersfield CA. 93301
661 - 326 -3911
B B R 5 P 7 D
FIRE
AItTA1 T
Underground Storage Tank Program
SW Inspection Report
NOTICE TO COMPLY/NOTICE OF VIOLATION
Business Name: Wholesale Fuels, Inc 1001 (15- 021- 03393)
Date: 1 1/06/2018 (CAL000147010)
Address Name: 2200 East Brundage Lane, Bakersfield, CA 93307
(661) 327 -4900
Inspector Name: Kris Karns ICC# 829402
Inspection Type: Routine
[Report : Final
NVO = No Violation Observed OUT = Out of Compliance NA = Not Applicable UD = Undetermined
COS = Corrected On Site RPT = Repeat Violation
Violation
Program Requirement
a ,o
SOC
Comments
No
2 CU
z
O
Z
�•
°-
M
o>
File Review
Facility Tank Information
2030021
Facility has a valid Permit
Tank 1 -10000 - Clear Diesel - SW
to Operate from the
Tank 2- 10000 - Dyed Diesel - SW
CUPA - 23 CCR 16 2712(1);
Tank 3 - 20000 - Clear Diesel - SW
HSC 6.7 25284
®
None
Tank 4 - 20000 - Regular - SW
Tank 5 - 20000 - Dyed Diesel - SW
Tank 6 - 20000 - Dyed Diesel - SW
2010010
UST Operating Permit
Application for Facility
information and Tank
information
®
❑
❑
❑
❑
❑
None
submitted /maintained - 23
CCR 16 2711; HSC 6.7
25286(a
2010001
Current BOE number
submitted to the CUPA
®
❑
❑
D
❑
❑
None
and /or CERS - HSC 6.7
25286(c)
2030011
UST compliance
statement and /or
Designated Operator
®
❑
❑
❑
❑
❑
None
current certification
submitted - 23 CCR 16
2715(a), 2715(b
2030046
A complete and accurate
response plan has been
submitted, approved and
®
❑
❑
❑
❑
❑
None
maintained - 23 CCR 16
2632, 2634(e), 2641(h),
2712(1
2030041
A complete and accurate
plot plan has been
submitted, approved and
®
❑
❑
❑
❑
❑
None
maintained - 23 CCR 16
2632 (d)(1)(C ), 2711(a)(8)
2010006
Owner /Operator has not
made false statements or
representation on any
®
❑
❑
❑
❑
❑
None
required document - HSC
6.7 25299
Bakersfield Fire Department Prevention
2101 H St
Bakersfield CA. 93301
661 -326 -3911
B E_ R S_F I D
FIRE
ARTAI T
Underground Storage Tank Program
SW Inspection Report
NOTICE TO COMPLY/NOTICE OF VIOLATION
Violation
Program Requirement
°, o
a
SOC
Comments
No
0
IM 0
z
0
z
D
U
W
Q
2010003
Owner /Operator has a
DO and /or informed the
CUPA of any change (s)
®
❑
❑
❑
❑
❑
None
within 30 days - 23 CCR
16 2715(a)
Testing
2030002
Owner /Operator has
tested and certified leak
®
❑
❑
❑
❑
❑
None
detection equipment
annual) - 23 CCR 16 2638
2030048
Secondary containment
testing conducted every
36 months in accordance
®
❑
❑
❑
❑
❑
None
with requirements - 23
CCR 16 2637
2030055
Spill buckets have been
tested annually as
®
❑
❑
❑
❑
❑
None
required - HSC 6.7 25284.2
2010009
Secondary containment
test results submitted to
the CUPA within 30 days
®
❑
❑
❑
❑
❑
None
after the test - 23 CCR 16
2637(e)
2030042
0.1 gph annual line test
RD
performed and passed for
pressurized piping without
❑
❑
®
❑
❑
❑
None
❑
fail safe or shut down - 23
Yes
CCR 16 26360(4)
2030050
0.1 gallon per hour piping
integrity test conducted
RD
every three years (pre-
❑
❑
®
❑
❑
❑
None
❑
January 1984) - 23 CCR
Yes
16 2643(d)
2030051
Piping integrity test or
overfill integrity test
conducted every two
❑
❑
®
❑
❑
❑
None
years (pre- January 1,
1984 ) - 23 CCR 16 2643(e)
2030029
Lined or repaired steel
RP
tank was inspected within
10 years of lining and
®
❑
❑
❑
❑
❑
None
❑
every 5 years after - 23
Yes
CCR 16 2663
2030028
Tank lining certification
submitted to the CUPA
within 30 days, proper
®
❑
❑
❑
❑
❑
None
tests and inspector used -
23 CCR 16 2663
2030067
ELD testing conducted
every 36 months on USTs
located within 1,000 feet
❑
❑
®
❑
❑
❑
None
of a public drinking well -
23 CCR 16 2644.1 a 3
Bakersfield Fire Department Prevention
2101 H St
Bakersfield CA. 93301
661-326-3911
FIRE
H T
Underground Storage Tank Program
SW Inspection Report
NOTICE TO COMPLY/NOTICE OF VIOLATION
Violation
Program Requirement
46 r-
.0
SOC
Comments
No
0
>
D
a
0
(L
Q)o
z
0
z
M
2010005
ELD testing results sent
to the board and the
CUPA within 60 days of
El
E]
N
0
El
R
None
completion of the test - 23
CCR 16 2644. 1 (a) (5)
2030056
SIR Report submitted
annually to the CUPA - 23
El
El
0
R
R
R
None
CCR 16 2646. 16)
2030064
CUPA was properly
notified within the
prescribed number of
None
hours prior to testing - 23
CCR 16 2637(o, 2638(e),
2643(g), 2644. 1(a)(4)
Install/Repair
2060009
Permits obtained to
install, replace, repair, or
R
RE]
Ej
None
modify part of the UST
system - 23 CCR 16 2712
UST System Observation
General Monitoring
2030003
Leak detection system
maintains continuous
RD
monitoring that activates
N
El
El
El
R
R
None
[:1
an audible and visual
Yes
alarm - 23 CCR 16 2632,
2634,2636,2666
2030017
Product piping outside the
UDC is fail-safe and shuts
down the pump or
None
restricts flow - 23 CCR 16
2636(0(5)
2030018
Turbine sump monitor
RD
activates an audible and
visual alarm or stops the
None
flow of at the dispenser -
Yes
23 CCR 16 2636(0(1)
2030019
Monitoring system in the
UDCs activates an
audible and visual alarm
El
E]
R
None
or stops the flow at the
UDC - 23 CCR 16
2636(0(1)
2030043
Leak detection equipment
Failure of the T-1 (87 STP 208 Sensor)
properly programmed or
RD
Replaced and re-tested new 208 it was
properly operated - 23
El
N
None
N
confirmed operational, violation was
CCR 16 2632, 2634, 2636,
Yes
corrected on site.
2666
2060005
System constructed with
a monitoring system
capable of detecting entry
None
into secondary
containment - HSC 6.7
25291(b)
Bakersfield Fire Department Prevention
2101 H St
Bakersfield CA. 93301
661-326-3911
H R S 11 1
FIRE
Underground Storage Tank Program
SW Inspection Report
NOTICE TO COMPLY/NOTICE OF VIOLATION
Violation
Program Requirement
a
o 0.0
SOC
Comments
No
>j >
M
C1
0
(L
0)0
Z
0
z
D
0
W
(D
2060014
Correct leak detection
equipment installed for
RD
the type of system
Z
1:1
1:1
❑
❑
❑
None
❑
present - 23 CCR 16 2638,
Yes
HSC 6.7 25290.1, 25290.2,
252
2060015
Sensor located in the
RD
proper position/location -
Z
❑
None
❑
23 CCR 16 2630(d), 264 1 (a)
Yes
2030062
Facility is in compliance
with not tampering with or
RD
disabling leak detection
Z
1:1
❑
None
❑
devices or alarms - HSC
Yes
6.7 25299(a)(9)
2030034
Tag/sticker on affixed
monitoring equipment
being certified, repaired,
Z
❑
❑
None
or replaced - 23 CCR 16
2638(o
Cathodic Protection
2030009
Impressed-current system
is turned on and
RP
functioning properly and
Z
❑
None
❑
inspected as required - 23
Yes
CCR 16 2635(a)(2)
Single Walled
Tank Monitoring
2030004
Automatic tank gauge
tests the tank at least
RD
once per month at 0.1
None
❑
gallons per hour - 23 CCR
Yes
16 2643(b)(2)
2030005
The 0.2 gallons per hour
continuous in tank leak
RD
detection test is being
Z
❑
❑
❑
None
❑
conducted - 23 CCR 16
Yes
2643(b)(5)
2030006
Monthly 0.2 gallons per
hour automatic tank
RD
gauging test on a single
El
El
El
❑
None
❑
wall tank is being
Yes
conducted - 23 CCR 16
2643(b)(1)
2060002
Automatic tank
gauging/continuous in
RD
tank leak detection
❑
EJ
❑
❑
❑
None
❑
system installed/properly
Yes
functioning - 23 CCR 16
2643, HSC 6.7 25292(a)
2030030
Weekly manual tank
gauging performed in
RD
accordance to the
None
❑
required specifications -
Yes
23 CCR 16 2645
Bakersfield Fire Department Prevention
2101 H St
Bakersfield CA. 93301
661-326-3911
gA
B E R S F D
FIRE
�RSr T
Underground Storage Tank Program
SW Inspection Report
NOTICE TO COMPLY/NOTICE OF VIOLATION
Violation
Program Requirement
0 0.0
SOC
Comments
No
a
0
CL
00
Z
0
Z
0
W
2030022
Groundwater and/or
vadose zone monitoring
None
conducted as required -
23 CCR 16 2647, 2648
Single Walled
Piping Monitoring
2030052,
Piping monitored hourly
and a 0.2 gph monthly or
RD
0.1 gph annual line
None
[:1
integrity test is performed
Yes
- 23 CCR 16 2641(a),
2643(c)
Line Leak
Detector
2060012
Line leak detector
installed on pressurized
RD
piping system - HSCI 6.7
E
❑
❑
❑
❑
❑
None
❑
25290. 1 (h), 25290.2(g),
Yes
25291(1), 25292(e),
2636(0(2)
2030026
Line leak detectors detect
Failure of the T-1 (Clear Diesel) PLLD,
a 3 gph leak and/or
RD
was not capable of detecting a leak rate
audible and visual alarm
None
E
of 3gph @ 10 PSI.
function properly - 23
Yes
CCR 16 2636(0(6),
2666(c)
2030027
Turbine shuts down when
a leak is detected or
RD
when line leak detector is
None
❑
disconnected - 23 CCR 16
Yes
2666(c)
2030025
Pressurized piping able to
detect a 3.0 gph leak
RD
within an hour, and
❑
❑
❑
None
❑
restricts the flow or
Yes
alarms - 23 CCR 16
2636 t)(2)
Suction Piping
2030053
Suction piping sloped to
drain back into storage
RD
tank, one check valve and
z
❑
E:i
❑
None
❑
inspections conducted -
Yes
23 CCR 16 2636(a) (3),
2641(b)
Secondary Containment
2030008
UDC, sumps, and/or
other secondary
containment in good
None
condition and/or are free
of debris/liquid - HSC 6.7
25290.1, 25290.2, 25291
2030047
Secondary containment
maintained tight and has
been confirmed by testing
E
❑
❑
None
- 23 CCR 16 2662, HSC 6.7
25290.1(c)(2), 25290.2(c)(2),
25291(a), 25292(e)
Bakersfield Fire Department Prevention
2101 H St
Bakersfield CA. 93301
661-326-3911
En;7- ED
R S F I
FIRE
JJTr T
Underground Storage Tank Program
SW Inspection Report
NOTICE TO COMPLY/NOTICE OF VIOLATION
Violation
Program Requirement
4-
0 0
4)
SOC
Comments
No
F-
=)
<
a
CQ
0
F-
0.
2 = w
Z
0
Z
>
2030060
Entry fittings in secondary
containment for UST
system maintained
E-1
❑
❑
❑
F-1
None
tight/sealed - 23 CCR 16
2630, 2635(d), 2636(c),
2666
1
1
1
2060020
Spill bucket is installed
Failure of the T-3 Clear Diesel, Phil Tite
and has a functional drain
RP
Direct Burial Spill Bucket.
valve or other means to
❑
Z
None
Z
remove liquid - 23 CCR 16
Yes
2635(b), 2665
2030054
Spill bucket maintained in
RP
good condition and free of
Z
E:]
❑
❑
E:]
❑
None
❑
debris and/or liquid - 23
Yes
CCR 16 2635(b), 2715(c)(2)
2060019
Spill bucket to has a
minimum capacity of five
Z
None
gallons - 23 CCR 16
2635(p), 2665
Overfill
2030035
UST system is operated
to prevent unauthorized
RP
release, including spills
Z
None
❑
and overfills - HSC 6.7
Yes
25292.1 (a)
2030036
Overfill prevention system
has not been overridden
RP
and meets overfill
Z
1:1
❑
❑
1-1
F-1
None
❑
requirements - 23 CCR 16
Yes
2635(b)(2), 2665
On Site Records
Certifications
2030023
Required designated
operators or contractors
maintain a proper and
Z
F-1
1:1
❑
❑
F-1
None
current ICC certification -
23 CCR 16 2715
2030024
Service technician,
installer, and/ or
employee maintain a
Z
❑
❑
❑
❑
F-1
None
proper license - 23 CCR
162715
2030031
Employee or contractor
obtained and maintained
proper manufacturer
Z
r-]
❑
❑
❑
❑
None
certification - 23 CCR 16
2715
2010007
Submit/maintain current
Certificate of Financial
Responsibility /mechanism
of financial assurance -
Z
El
El
❑
F-1
❑
None
23 CCR 16 2711; 23 CCR
18 2808.1, 2809-2809.2,
HSC 6.7 25292.2; HSC
6,75 25299.30-25299.34
Bakersfield Fire Department Prevention
2101 H St
Bakersfield CA. 93301
661-326-3911
B E R S F I D
FIRE
N TM T
Underground Storage Tank Program
SW Inspection Report
NOTICE TO COMPLY/NOTICE OF VIOLATION
Violation
Program Requirement
0.— 00
SOC
Comments
No
0
>
1—
=)
O
0-
2 4.0
0z o
0
z
D
L)
W
2030007
Positive statement of
compatibility for UST
system components
0
❑
❑
❑
❑
❑
submitted and maintained on
site - 23 CCR 16 263 1
Designated
Operator
2010004
Copies of DO inspections
for last 12 months and list of
trained employees
Z
❑
❑
❑
[:1
[:1
None
maintained - 23 CCR 16
2715
2030013
Designated operator
properly conducted the
monthly inspection and the
None
reports are complete - 23
CCR 16 2715
2030010
DO notified operator of any
condition observed during
the monthly inspection that
0
❑
1:1
On
❑
None
may require action - 23 CCR
16 2715(d)
2030012
DO employee training
performed, current for at
least one employee on site,
None
and a log kept - 23 CCR 16
2715(c)(6), 2715(f)
Logs
2030001
Leak detection alarm logs,
maintenance and records of
appropriate follow-up
0
❑
1:1
❑
None
actions maintained - 23
CCR 16 2632, 2634,
2712(b)
2030020
Unburied fuel piping
RD
visually inspected at least
None
❑
monthly and log kept - HSC
Yes
6.7 25281.5(b)(3)
2030049
Suction pipe monitored
daily and results logged -. 23
❑
❑
Z
❑
❑
❑
None
CCR 16 2643(d)
2030057
When SIR results indicate
failure: The facility met all
RD
corrective action
Z
❑
None
❑
requirements - 23 CCR 16
Yes
2646.1(d)
2030058
All Statistical Inventory
RD
Reconciliation (SIR)
None
❑
requirements met - 23 CCR
Yes
162646.1
Maintenance/Tests
2010008
Monitoring, maintenance,
repairs, linings, and upgrade
RD
records maintained for the
Z
❑
❑
❑
❑
❑
None
❑
proper time period - 23 CCR
Yes
16 2712(b)
Bakersfield Fire Department Prevention
2101 H St
Bakersfield CA. 93301
661-326-3911
B E R S F I« D
FIRE
ABTA T
Underground Storage Tank Program
SW Inspection Report
NOTICE TO COMPLY/NOTICE OF VIOLATION
Violation
Program Requirement
q
'8 0
SOC
Comments
No
0
>
1--
=)
<
a
0)
0
(L
0)75
Z
0
Z
:3
0
W
a) >
2010002
Records of cathodic
protection systems testing
0
❑
❑
1:1
❑
[:1
None
maintained - 23 CCR 16
2635, 2712(b)
Documentation
2030033
Failure to maintain on site
an approved monitoring plan
❑
El
1:1
❑
❑
. None
- 23 CCR 16 2632, 2634,
2711,2712(i)
2030037
Written agreement between
the tank owner and tank
operator to monitor the tank
❑
❑
❑
F-1
❑
None
system is maintained - 23
CCR 16 2620(b); HSC 6.7
25284(a)(3)
2030061
Suspected or actual
unauthorized release
RD
reported in appropriate time
F-1
❑
N
❑
F-1
F-1
None
❑
frame - HSC 6.7 29294,
Yes
29295
General Operating Requirements
Permit Condition/Approval
2030039
Compliance with all
operating permit conditions
❑
❑
❑
❑
❑
None
- 23 CCR 16 2712; HSC 6.7
25299
2030059
UST system maintained in
accordance with
❑
El
E
❑
r-]
❑
None
exclusion/exemption status -
HSC 6.7 25281.6, 25283.5
2030014
Owner/Operator received
approval and has
implemented a training
1-1
El
2
❑
❑
E 11
None
program at an unstaffed
facility - 23 CCR 16
2715(f)(2)
2030015
Facility exhibited that the
method used to monitor the
tank meets the monitoring
1:1
1:1
❑
None
methods in 2643(f) - 23
CCR 16 2643
Red Tag
2030045
Red Tag information is
legible and has not been
❑
El
[E
❑
❑
❑
None
tampered with - 23 CCR 16
2717.1(g)
2030044
Facility did not allow for
deposit of petroleum into a
UST that has a red tag
❑
❑
❑
1-1
❑
None
affixed to the fill - 23 CCR
16 2717.1(f)
Install/Repair
Bakersfield Fire Department Prevention " Underground Storage Tank Program
2101 H St B EFIRE %V7 SW Inspection Report
Bakersfield CA. 93301 ARM. r NOTICE TO COMPLY/NOTICE OF VIOLATION
661- 326 -3911
Violation
Program Requirement
a ,o
SOC
Comments
No
Oj
D
a
®
O
a
Q)0
Z
O
Z
M
U
W
2030066
Repaired and retested the
system due to a failed ELD
test when located within
❑
❑
®
❑
❑
❑
None
1000' of public well - HSC
6.7 25292.4(d), 25292.5(c)
2060018
Existing SW piping is
constructed of FRP,
RP
cathodically protected steel,
®
El
El
[:1
❑
None
E J
❑
or steel clad with FRP - 23
Yes
CCR 16 2666(b); HSC 6.7
25292(e)(2)
2060021
Striker plate installed and
positioned correctly - 23
❑
❑
❑
®
❑
❑
None
CCR 16 2631(c), 2662(d)
2060004
Corrosion protection
installed for USTs and
RP
cathodic protection system
N
❑
❑
❑
❑
❑
None
❑
meets the consensus
Yes
standards - 23 CCR 16
2635(a)(2)(A)
❑ There were no violations noted for this inspection.
®This report shall serve as a "NOTICE TO COMPLY" for Minor Violations, and a "NOTICE OF VIOLATION" for
Major violations. You are, hereby, ordered to correct the above noted violations within 30 days, or according to
correction summaries provided. Formal enforcement and/or penalty assessment may be initiated for any
violations noted, and for those not corrected in a timely manner. (NOTE: If this is a preliminary report, a final report
will follow.)
4
Inspectors Signature: Date:
Inspector:
Violations: RD: RP:
o ne box for fac I t y Sign f t Operational Status ( SOC ) to be reported to SWRC13 and US EPA:
❑ SOC with both Release Detection and Release Detection (Facility has no Release Prevention and no Release
Prevention Violations)
® Not in SOC (Facility has both Release Prevention and Release Detection Violations)
❑SOC with Release Detection only (Facility has no Release Detection violations but one or more Release Prevention
violations)
❑ SOC with Release Prevention only (Facility has no Release Prevention violations but one or more Release Detection
violations)