Loading...
HomeMy WebLinkAboutCUPA REPORT 7-24-18BAKERSFIELD FIRE DEPARTMENT Prevention Services Division Underground Storage Tank Program 2101 H Street DW Inspection Re o Bakersfield, CA 93301 Permission to Inspect: one: 661 - 326 -3979 Fax: 661 -852 -2171 f Business Name: FASTRIP 3362 (15 -021- 003024) Date: 07/24/2018 (EPA ID# CAL000282729) Address Name: 6401 South H Street, Bakersfield, CA 93304 661 831 -4709 Inspector Name: Kris Karns ICC# 829402 Inspection Type: Routine Report: Final NVO = No Violation Observed OUT = Out of Compliance NA = Not Applicable UD = Undetermined COS = Corrected On Site RPT = Repeat Violation Violation Program Requirement Q0 ) .o SOC Comments No as z o z v a 05 o> File Review Facility Tank Information 2030021 Facility has a valid Permit Tank 1 - 12000 - Reg - DW to Operate from the ® ❑ ❑ ❑ ❑ ❑ None Tank 2 - 12000 - Sup - DW CUPA - 23 CCR 16 2712(i); Tank 3 - 12000 - Dies - DW HSC 6.7 25284 2010010 UST Operating Permit Application for Facility information and Tank information ® ❑ ❑ ❑ ❑ ❑ None submitted /maintained - 23 CCR 16 2791; HSC 6.7 25286(x) . 2010001 Current BOE number .submitted to the CUPA ® ❑ ❑ ❑ ❑ F-1 None and /or CERS - HSC 6.7 25286(c) 2030011 UST compliance statement and /or Designated Operator ® ❑ ❑ ❑ ❑ ❑ None current certification submitted - 23 CCR 16 2715(a), 2715(b) 2030046 A complete and accurate response plan has been submitted, approved and ® ❑ ❑ ❑ ❑ (� None maintained - 23 CCR 16 2632, 2634(e), 2641(h), 2712(i) 2030041 A complete and accurate plot plan has been submitted, approved and ® ❑ ❑ ❑ ❑ ❑ Minor maintained - 23 CCR 16 2632 d (1) (C), 2711(a)(8) 2010006 Owner /Operator has not made false statements or representation on any ® ❑ ❑ ❑ ❑ ❑ None required document - HSC 6.7 25299 2010003 Owner /Operator has a DO and /or informed the CUPA of any change (s) ® ❑ ❑ ❑ ❑ ❑ None within 30 days - 23 CCR 16 2715(x) Violation Program Requirement 4- 0 0.0 SOC Comments No 0 > a Q) 0 CL 4) 4., I- cc 0) 0 z 0 z Testing 2030002 Owner/Operator has tested and certified leak None detection equipment annually - 23 CCR 16 2638 2030048 Secondary containment testing conducted every 36 months in accordance H ❑ ❑ ❑ ❑ ❑ None with requirements - 23 CCR 16 2637 2030055 Spill buckets have been tested annually as None required - HSC 6.7 25284.2 2010009 Secondary containment test results submitted to the CUPA within 30 days ❑ ❑ ❑ None after the test - 23 CCR 16 2637(e) 2030064 CUPA was poperly notified within the prescribed number of None hours prior to testing - 23 CCR 16 26370, 2638(e), 2643(g), 2644.1(a)(4) Install/Repair 2060009 Permits obtained to install, replace, repair, or ❑ ❑ ❑ ❑ None modify part of the UST system - 23 CCR 16 2712 UST System Observation General Monitoring 2030003 Leak detection system maintains continuous RD monitoring that activates E El None ❑ an audible and visual Yes alarm - 23 CCR 16 2632, 2634, 2636, 2666 2030016 The annular space of the tank, piping and sumps RD are continuously monitored and activates [:j ❑ None ❑ the alarm - 23 CCR 16 Yes 2631(g), 2632(c)(2)(A)&(8), 2633(c), 2636(o 2030017 Product piping outside the UDC is fail-safe and shuts down the pump or ❑ None restricts flow - 23 CCR 16 2636M(5) 2030018 Turbine sump monitor activates an audible and RD visual alarm or stops the ❑ ❑ ❑ ❑ ❑ None ❑ flow of at the dispenser - Yes 23 CCR 16 2636(0 (1) Underground Storage Tank Program - DW Inspection Report v 2.0 Violation Program Requirement 0 .0 SOC Comments No a� R z o z CL a Ov ao o> 2030019 Monitoring system in the UDCs activates an audible and visual alarm ® ❑ ❑ ❑ ❑ ❑ None or stops the flow at the UDC - 23 CCR 16 2636 (0(1) 2030043 Leak detection equipment RD properly programmed or properly operated - 23 ® ❑ ❑ ❑ ❑ ❑ None ❑ CCR 16 2632, 2634, 2636, Yes 2666 2060005 System constructed with a monitoring system capable of detecting entry ® ❑ ❑ ❑ ❑ ❑ None into secondary containment - HSC 6.7 25291(b 2060014 Correct leak detection equipment installed for RD the type of system ® ❑ ❑ ❑ ❑ ❑ None ❑ present - 23 CCR 16 2638, Yes HSC 6.7 25290.1, 25290.2, 25291 2060015 Sensor located in the RD proper position /location - ® ❑ 0 r-j ❑ r-1 None ❑ 23 CCR 16 2630(4), 2641(a) Yes 2030062 Facility is in compliance RD with not tampering with or disabling leak detection ® ❑ ❑ ❑ ❑ ❑ None ❑ devices.or alarms - HSC Yes 6.7 25299 a 9) 2060022 System constructed with a monitoring system capable of detecting entry ® ❑ ❑ ❑ ❑ n None into secondary containment - HSC 6.7 25290.2(d) 2030034 Tag /sticker on affixed monitoring equipment being certified, repaired, ® ❑ ❑ ❑ ❑ ❑ None or replaced - 23 CCR 16 2638(0 VPH Monitoring VPH 2030065 Interstitial monitoring of the annular spaces of the RD UST is properly ❑ ❑ ® ❑ ❑ ❑ None ❑ maintained - HSC 6.7 Yes 25290.1(e) 2060023 System constructed with a monitoring system capable of detecting entry into secondary ❑ ❑ ® ❑ ❑ ❑ None containment - HSC 6.7 25290.1(d) Underground Storage Tank Program - DW Inspection Report v 2.0 Violation Program Requirement 4- 0 Q).O SOC Comments No 0 > . 4 13 0 CL Q) O Z 0 Z D L) W Line Leak Detector 2060012 Line leak detector installed on pressurized RD piping system - HSC 6.7 F-1 1-1 F-1 ❑ F-I None ❑ 25290.1(h), 25290.2(8), Yes 252910, 25292(e), 2636(0(2) 2030026 Line leak detectors detect a 3 gph leak and/or RD audible and visual alarm ❑ ❑ ❑ ❑ ❑ None ❑ function properly - 23 Yes CCR 16 26360(6), 2666(c) 2030027 Turbine shuts down when a leak is detected or RD when line leak detector is ❑ F-1 E ❑ None ❑ disconnected - 23 CCR 16 Yes 2666(c) 2030025 Pressurized piping able to detect a 3.0 gph leak RD within an hour, and ❑ F-1 ❑ None F-1 restricts the flow or Yes alarms - 23 CCR 16 2636(1) (2) Secondary Containment 2060010 UST storing a hazardous RD substance has secondary Z ❑ ❑ ❑ F-1 ❑ None ❑ containment - HSC 6.7 Yes 25292 Underground Storage Tank Program - DW Inspection Report v 2.0 Violation Program Requirement 4- 40 ).o SOC Comments No 0 > 1�-- M a (1) 0 F- 0. '4.) ';� 00 Z 0 Z D Q.- > 2030008 UDC, sumps, and/or other secondary containment in good None condition and/or are free of debris/liquid - HSC 6.7 25290.1, 25290.2, 25291 2030040 Secondarily contained RD piping maintained to allow None ❑ liquid to drain into sump - Yes 23 CCR 16 2630(d), 2641(a) 2060006 Secondary containment piping slopes back to the None collection sump - 23 CCR 16 263(c) 2030047 Secondary containment maintained tight and has been confirmed by testing Z RE] ❑ ❑ ❑ None - 23 CCR 16 2662; HSC 6.7 25290.1(c)(2), 25290.2(c)(2), 25291(a), 25292(e) 2030060 Entry fittings in secondary containment for UST system maintained None tight/sealed - 23 CCR 16 2630, 2635(d), 2636(c), 2666 2060020 Spill bucket is installed and has a functional drain RP valve or other means to None ❑ remove liquid - 23 CCR 16 Yes 2635(b), 2665 2030054 Spill bucket maintained in RP good condition and free of E RE] ❑ ❑ ❑ None ❑ debris and/or liquid - 23 Yes CCR 16 2635(b), 2715(c)(2) 2060019 Spill bucket to has a minimum capacity of five None gallons - 23 CCR 16 2635(b), 2665 Overfill 2030035 UST system is operated to prevent unauthorized RP release, including spills Z None ❑ and overfills - HSC 6.7 Yes 25292.1 (aj 2030036 Overfill prevention system has not been overridden RP and meets overfill None ❑ requirements - 23 CCR 16 Yes 2635(b)(2), 2665 Underground Storage Tank Program - DW Inspection Report v 2.0 Violation Program Requirement 4- ' 0 0.2 SOC Comments No < a U) 0 � CL - 2 M u)75 Z 0 z 0 w > On Site Records Certifications 2030023 Required designated operators or contractors maintain a proper and Z None current ICC certification - 23 CCR 16 2715 2030024 Service technician, installer, and/ or employee maintain a Z F-1 F-1 ❑ ❑ ❑ None proper license - 23 CCR 162715 2030031 Employee or contractor obtained and maintained proper manufacturer ❑ F-1 ❑ ❑ None certification - 23 CCR 16 2715 2010007 Submit/maintain current Certificate of Financial Responsibility /mechanism of financial assurance - Z ❑ 1:1 F-1 F-1 ❑ None 23 CCR 16 2711; 23 CCR 18 2808.1, 2809-2809.2; HSC 6.7 25292.2; HSC 6.75 25299.30-25299.34 Designated Operator 2010004 Copies of DO inspections for last 12 months and list of trained employees Z None maintained - 23 CCR 16 2715 2030013 Designated operator properly conducted the monthly inspection and Z ❑ ❑ 1:1 ❑ ❑ None the reports are complete - 23 CCR 16 2715 2030010 DO notified operator of any condition observed during the monthly Z ❑ ❑ ❑ ❑ F-1 None inspection that may require action - 23 CCR 16 2715(d) 2030012 DO employee training performed, current for at least one employee on Z ❑ ❑ ❑ ❑ ❑ None site, and a log kept - 23 CCR 16 2715(c)(6), 27150 Underground Storage Tank Program - DW Inspection Report v 2.0 Violation Program Requirement 4- 0 .2 c, SOC Comments No a C0 0 a. 00 Z 0 Z .- Q> Logs 2030001 Leak detection alarm logs, maintenance and RD records of appropriate E ❑ ❑ ❑ ❑ ❑ None ❑ follow-up actions Yes maintained - 23 CCR 16 2632, 2634, 2712(b) Maintenance/Tests 2010008 Monitoring, maintenance, repairs, linings, and RD upgrade records 2 ❑ 1:1 ❑ ❑ ❑ None ❑ maintained for the proper Yes time period - 23 CCR 16 2712(b) Documentation 2030033 Failure to maintain on site an approved monitoring E-1 ❑ 1:1 1:1 ❑ None plan - 23 CCR 16 2632, 2634, 2711, 2712(1) 2030037 Written agreement between the tank owner and tank operator to monitor the tank system 0 ❑ ❑ ❑ E-1 ❑ None is maintained - 23 CCR 16 2620(b); HSC 6.7 25284(a)(3) 2030061 Suspected or actual unauthorized release RD reported in appropriate ❑ F-1 None ❑ time frame - HSC 6.7 Yes 29294,29295 General Operating Requirements Permit Condition/Approval 2030039 Compliance with all operating permit E ❑ ❑ ❑ ❑ E-1 None conditions - 23 CCR 16 2712, HSC 6.7 25299 2030059 UST system maintained in accordance with exclusion/exemption F-1 ❑ ❑ ❑ ❑ None status - HSC 6.7 25281.6, 25283.5 2030014 Owner/Operator received approval and has implemented a training E-1 ❑ E E-1 ❑ F-1 None program at an unstaffed facility - 23 CCR 16 2715(0(2) 2030015 Facility exhibited that the method used to monitor the tank meets the monitoring methods in None 2643(f) - 23 CCR 16 2643 Underground Storage Tank Program - DW Inspection Report v 2.0 Violation Program Requirement 0 0.0 SOC Comments No M a 0 F- IL 4 .0 2 1z 00 z 0 z D 0 W Red Tag 2030045 Red Tag information is legible and has not been ❑ 11 0 ❑ 1:1 ❑ None tampered with - 23 CCR 16 2 717. 1 (g) 2030044 Facility did not allow for deposit of petroleum into a UST that has a red tag ❑ F-1 0 ❑ 1:1 ❑ None affixed to the fi ll - 23 CCR 162717.1(0 Install/Repair 2060024 UST system is made of or lined with materials that are compatible with the Z F-1 ❑ F-1 ❑ F-1 None substance stored - 23 CCR 16 2631.1 2060021 Striker plate installed and positioned correctly - 23 ❑ ❑ ❑ F-1 ❑ None CCR 16 2631(c), 2662(d) I I I I I 0 There were no violations noted for this inspection. ❑This report shall serve as a "NOTICE TO COMPLY" for Minor Violations, and a "NOTICE OF VIOLATION" for Major violations. You are, hereby, ordered to correct the above noted violations within 30 days, or according to correction summaries provided. Formal enforcement and/or penalty assessment may be initiated for any violations noted, and for those not corrected in a timely manner. (NOTE: If this is a preliminary report, a final report will follow.) -,LA Date: (e Inspectors Signature: Inspector: Enter # of Violations: RD: Q RP: C) Check one box for facility Significant Operational Status (SOC) to be reported to SWRCB and US EPA: Z SOC with both Release Detection and Release Detection (Facility has no Release Prevention and no Release Prevention Violations) F-1 Not in SOC (Facility has both Release Prevention and Release Detection Violations) ❑SOC with Release Detection only (Facility has no Release Detection violations but one or more Release Prevention violations) F-1 SOC with Release Prevention only (Facility has no Release Prevention violations but one or more Release Detection violations) Underground Storage Tank Program - DW Inspection Report v 2.0