HomeMy WebLinkAbout#7725 CUPA REPORT 7.5.18Underground Storage Tank Program DW Inspection Report Permission to Inspect: &"C-5 BAKERSFIELD FIRE DEPARTMENT Prevention Services Division 2101 H Street Bakersfield, CA 93301 Phone: 661-326-3979 Fax: 661-852-2171. Business Name: FASTRIP #19 7725 (15-021-100269) Date: 07/05/2018 (EPA ID# CAL000282748) Address Name: 4901 SO. UNION AVE (#725), BAKERSFIELD, CA 93307 (661) 397-9387 Inspector Name: Kris Karns ICC# 829402 Inspection Type: Routine I F Report: Final = No Violation Observed OUT = Out of Compliance NA = Not Applicable UD = Undetermined FNVO = Corrected On Site RPT = Repeat Violation Violation Program Requirement 46 C 0 0) = SOC Comments No D a 0 0. 42 R Z 0 z I D (.) I W a > File Review Facility Tank Information 2030021 Facility has a valid Permit Tank 1 -12000 - Reg - DW to Operate from the None Tank 2 - 12000 - Sup - DW CUPA - 23 CCR 16 2712(i); Tank 3 - 12000 - Dies - DW HSC 6.7 25284 2010010' UST Operating Permit Application for Facility information and Tank information None submitted/maintained - 23 CCR 16 2711; HSC 6.7 25286(a) 2010001 Current BOE number submitted to the CUPA F-1 ❑ F-1 ❑ None and/or CERS - HSC 6.7 25286(c) 2030011 UST compliance statement and/or Designated Operator Z ❑ ❑ ❑ F-1 None current certification submitted - 23 CCR 16 2715(a), 2715(b) 2030046 A complete and accurate response plan has been submitted, approved and E ❑ F-1 F] None maintained - 23 CCR 16 2632, 2634(e), 2641(h), 2712(i) 2030041 A complete and accurate plot plan has been submitted, approved and ❑ F-1 Minor maintained - 23 CCR 16 2632(d)(1 (C), 2711(a)(8) 2010006 Owner/Operator has not made false statements or representation on any ❑ ❑ ❑ ❑ None required document - HSC 6,725299 L 2010003 Owner/Operator has a DO and/or informed the CUPA of any change (s) ❑ F-1 ❑ ❑ ❑ None within 30 days - 23 CCR 16 2715(a) Violation Program Requirement 4- 0 0).0 soc Comments No 0 > a 0 a. 14) 0 0 z 0 z 05 Testing 2030002 Owner/Operator has tested and certified leak None detection equipment annually - 23 CCR 16 2638 2030048 Secondary containment testing conducted every 36 months in accordance None with requirements - 23 CCR 16 2637 2030055 Spill buckets have been tested annually as None required - HSC 6.7 25284.2 2010009 Secondary containment test results submitted to the CUPA within 30 days ❑ None after the test - 23 CCR 16 2637(e) 2030064 CU PA was poperly notified within the prescribed number of None hours prior to testing - 23 CCR 16 2637(0, 2638(e), 2643(g), 2644.1(a) (4) Install/Repair 2060009 Permits obtained to install, replace, repair, or Z RE] ❑ F] E] None modify part of the UST system - 23 CCR 16 2712 1 UST System Observation General Monitoring 2030003 Leak detection system maintains continuous RD monitoring that activates ❑ El ❑ ❑ ❑ None ❑ an audible and visual Yes alarm - 23 CCR 16 2632, 2634, 2636, 2666 2030016 The annular space of the tank, piping and sumps RD are continuously monitored and activates None ❑ the alarm - 23 CCR 16 Yes 2631(g), 2632(c)(2)(A)&(B), 2633(c), 26360 2030017 Product piping outside the UDC is fail-safe and shuts down the pump or Z ❑ None restricts flow - 23 CCR 16 2636(0(5) 2030018 Turbine sump monitor RD activates an audible and visual alarm or stops the None ❑ flow of at the dispenser - Yes 23 CCR 16 2636(0(1) Underground Storage Tank Program - DW Inspection Report v 2.0 Violation Program Requirement ° o SOC Comments No O M Q' p p a 00 z O z c) W of 2030019 Monitoring system in the UDCs activates an audible and visual alarm ® ❑ ❑ ❑ ❑ ❑ None or stops the flow at the UDC -23 CCR 16 2636 (0(1) 2030043 Leak detection equipment RD properly programmed or properly operated - 23 ® ❑ ❑ ❑ ❑ ❑ None ❑ CCR 16 2632, 2634, 2636, Yes 2666 2060005 System constructed with a monitoring system capable of detecting entry ® ❑ ❑ ❑ ❑ ❑ None into secondary containment - HSC 6.7 25291(b 2060014 Correct leak detection equipment installed for RD the type of system ® ❑ ❑ ❑ ❑ ❑ None ❑ present - 23 CCR 16 2638, Yes HSC 6.7 25290.1, 25290.2, 25291 2060015 Sensor located in the RD proper position /location - ® ❑ ❑ ❑ ❑ ❑ None ❑ 23 CCR 16 2630(d), 2641(a) Yes 2030062 Facility is in compliance RD with not tampering with or disabling leak detection ® ❑ ❑ ❑ ❑ ❑ None ❑ devices or alarms - HSC Yes 6.7 25299(a)(9) 2060022 System constructed with a monitoring system capable of detecting entry ® ❑ ❑ ❑ ❑ ❑ None into secondary containment - HSC 6.7 25290.2(d) 2030034 Tag /sticker on affixed monitoring equipment being certified, repaired, ® ❑ ❑ ❑ ❑ ❑ None or replaced - 23 CCR 16 2638( VPH Monitoring VPH 2030065 Interstitial monitoring of RD the annular spaces of the UST is properly ❑ ❑ ® ❑ ❑ ❑ None ❑ maintained - HSC 6.7 Yes 25290.1(e) 2060023 System constructed with a monitoring system capable of detecting entry into secondary ❑ ❑ ® ❑ ❑ ❑ None containment - HSC 6.7 25290.1(d) Underground Storage Tank Program - DW Inspection Report v 2.0 Violation Program Requirement 4- 0 0 (1) SOC Comments No M a 0) 0 M = 2 cc a)-6 Z 0 Z M C.) W 4) > Line Leak Detector 2060012 Line leak detector installed on pressurized RD piping system - HSC 6.7 None ❑ 25290,1(h), 25290.2(g), Yes 25291(o, 25292(e), 2636(1) (2) 2030026 Line leak detectors detect a 3 gph leak and/or RD audible and visual alarm E:1 ❑ None ❑ function properly - 23 Yes CCR 16 2636(0(6), 2666(c) 2030027 Turbine shuts down when RD a leak is detected or when line leak detector is ❑ RE ❑ ❑ ❑ None ❑ disconnected - 23 CCR 16 Yes 2666(c) 2030025 Pressurized piping able to detect a 3.0 gph leak RD within an hour, and None ❑ restricts the flow or Yes alarms - 23 CCR 16 2636(0(2) Secondary Containment 2060010 UST storing a hazardous RD substance has secondary None ❑ containment - HSC 6.7 Yes 25292 Underground Storage Tank Program - DW Inspection Report v 2•0 Violation Program Requirement 4- 0 0.0 SOC Comments No 0 > D d a o C* � M - 4) s- 0 Z 0 Z 2030008 UDC, sumps, and/or other secondary containment in good ❑ ❑ ❑ None condition and/or are free of debris/liquid - HSC 6.7 25290.1, 25290.2, 25291 2030040 Secondarily contained RD piping maintained to allow Z F] ❑ E] Ej None ❑ liquid to drain into sump - Yes 23 CCR 16 2630(d), 2641(a 2060006 Secondary containment piping slopes back to the None collection sump - 23 CCR 16 263(c) 2030047 Secondary containment maintained tight and has been confirmed by testing Z None - 23 CCR 16 2662, HSC 6.7 25290. 1 (c) (2), 25290.2(c)(2), 25291(a), 25292(e) 2030060 Entry fittings in secondary containment for UST system maintained Z None tight/sealed - 23 CCR 16 2630, 2635(d), 2636(c), 2666 2060020 Spill bucket is installed RP and has a functional drain valve or other means to Z None ❑ remove liquid - 23 CCR 16 Yes 2635(b), 2665 2030054 Spill bucket maintained in RP good condition and free of Z E] Ej None ❑ debris and/or liquid - 23 Yes CCR 16 2635(b), 2715(c)(2) 2060019 Spill bucket to has a minimum capacity of five Z None gallons - 23 CCR 16 2635(b), 2665 Overfill. 2030035 UST system is operated RP to prevent unauthorized release, including spills Z None ❑ and overfills - HSC 6.7 Yes 25292.1 (a) 2030036 Overfill prevention system RP has not been overridden and meets overfill ❑ ❑ ❑ ❑ ❑ None ❑ requirements - 23 CCR 16 Yes 2635(b)(2)1 2665 1 1 Underground Storage Tank Program - DW Inspection Report v 2.0 Violation Program Requirement 4- 0 0 4) SOC Comments No 0 > 1�- M a 0 (L = 42 M M -6 z 0 z M 0 w of On Site Records Certifications 2030023 Required designated operators or contractors maintain a proper and None current ICC certification - 23 CCR 16 2715 2030024 Service technician, installer, and/ or employee maintain a Z ❑ ❑ ❑ ❑ ❑ None proper license - 23 CCR 162715 2030031 Employee or contractor obtained and maintained proper manufacturer Z ❑ ❑ ❑ ❑ F-1 None certification - 23 CCR 16 2715 2010007 Submit/maintain current Certificate of Financial Responsibility/mechanism of financial assurance - Z ❑ ❑ F-1 1:1 ❑ None 23 CCR 16 2711; 23 CCR 18 2808.1, 2809-2809.2; HSC 6.7 25292.2; HSC 6.75 25299.30-25299.34 Designated Operator 2010004 Copies of DO inspections for last 12 months and list of trained employees Z F-] ❑ None maintained - 23 CCR 16 2715 2030013 Designated operator properly conducted the monthly inspection and Z ❑ ❑ ❑ ❑ ❑ None the reports are complete - 23 CCR 16 2715 2030010 DO notified operator of any condition observed during the monthly Z F-1 ❑ 1:1 ❑ ❑ None inspection that may require action - 23 CCR 16 2715(d) 2030012 DO employee training performed, current for at least one employee on F-1 ❑ F-1 ❑ ❑ None site, and a log kept - 23 CCR 16 2715(c)(6), 2 715(o Underground Storage Tank Program - DW Inspection Report v 2.0 Violation Program Requirement 0 00 4) SOC Comments No D a V) 0 1— a. = 2 cc m-6 Z 0 Z M > Logs 2030001 Leak detection alarm logs, maintenance and RD records of appropriate Z ❑ ❑ ❑ ❑ F-1 None ❑ follow-up actions Yes maintained - 23 CCR 16 2632, 2634, 2712(b) Maintenance/Tests 2010008 Monitoring, maintenance, repairs, linings, and RD upgrade records None ❑ maintained for the proper Yes time period - 23 CCR 16 2712(b) Documentation 2030033 Failure to maintain on site an approved monitoring Z El None plan - 23 CCR 16 2632, 2634, 2711, 2712(i)_ 2030037 Written agreement between the tank owner and tank operator to monitor the tank system Z None is maintained - 23 CCR 16 2620(b); HSC 6.7 25284(a)(3) 2030061 Suspected or actual RD unauthorized release reported in appropriate ❑ El Z None [_1 time frame - HSC 6.7 Yes 29294,29295 General Operating Requirements Permit Condition/Approval 2030039 Compliance with all operating permit None conditions - 23 CCR 16 2712; HSC 6.7 25299 2030059 UST system maintained in accordance with exclusion/exemption None status - HSC 6.7 25281.6, 25283.5 2030014 Owner/Operator received approval and has implemented a training ❑ f-1 Z None program at an unstaffed facility - 23 CCR 16 2715(0(2) 2030015 Facility exhibited that the method used to monitor the tank meets the monitoring methods in None 2643(f) - 23 CCR 16 2643 Underground Storage Tank Program - DW Inspection Report V Violation Program Requirement 4- 0 0 CD SOC Comments No a 0 F_ M 10 1. 0_6 Z 0 z D 0 W > Red Tag 2030045 Red Tag information is legible and has not been ❑ ❑ E ❑ ❑ ❑ None tampered with - 23 CCR 16 2797.9 (g) 2030044 Facility did not allow for deposit of petroleum into a UST that has a red tag 1:1 ❑ E ❑ r-1 ❑ None affixed to the fill - 23 CCR 162717.1(0 Install/Repair 2060024 UST system is made of or lined with materials that are compatible with the Z ❑ ❑ ❑ ❑ ❑ None substance stored - 23 CCR 16 2631.1 1 2060021 Striker plate installed and positioned correctly - 23 ❑ ❑ ❑ ❑ None CCR 16 2631(c), 2662(d) 0 There were no violations noted for this inspection. ❑This report shall serve as a "NOTICE TO COMPLY" for Minor Violations, and a "NOTICE OF VIOLATION" for Major violations. You are, hereby, ordered to correct the above noted violations within 30 days, or according to correction summaries provided. Formal enforcement and/or penalty assessment may be initiated for any violations noted, and for those not corrected in a timely manner. (NOTE: If this is a preliminary report, a final report will follow.) t Inspectors Signature: 1( Date: Inspector: Enter # of Violations: RD: 0 RP: - 6 Check one box for facility Significant Operational Status (SOC) to be reported to SWRCB and US EPA: Z SOC with both Release Detection and Release Detection (Facility has no Release Prevention and no Release Prevention Violations) F-1 Not in SOC (Facility has both Release Prevention and Release Detection Violations) ❑SOC with Release Detection only (Facility has no Release Detection violations but one or more Release Prevention violations) r_1 SOC with Release Prevention only (Facility has no Release Prevention violations but one or more Release Detection violations) Underground Storage Tank Program - DW Inspection Report v 2.0