HomeMy WebLinkAboutCUPA REPORT 9-5-18Bakersfield Fire Department Prevention
2101 H St �t4'
Bakersfield CA. 93301
661-326-3911
FIRE
MTN T
Underground Storage Tank Program
SW Inspection Report
NOTICE TO COMPLY/NOTICE OF VIOLATION
Business Name: HOWARD'S MINI MART 3351 (15-021-46941) —[Date:
9/5/2018 (CAL000282722)
Address Name: 33200 Panama Lane, Bakersfield, CA 93313
(661) 833-1561
Inspector Name: Kris Karns ICC# 829402
Inspection Type: Routine
:Final
NVO = No Violation Observed OUT = Out of Compliance NA = Not Applicable UD = Undetermined
COS = Corrected On Site RPT = Repeat Violation
Violation
Program Requirement
' 8 4) cc
-
SOC
Comments
No
0
>
a
0
M
4) 4.0
L. W
(W 0
z
0
z
File Review
Facility Tank Information
2030021
Facility has a valid Permit
Tank 1 -12000 - Sup - SW
to Operate from the
Tank 2- 12000 - Reg - SW
CUPA - 23 CCR 16 2712(1);
Tank 3 - 12000 - Dies - SW
HSC 6.7 25284
None
Tank 4 - 12000 -Reg 2 - DW
2010010
UST Operating Permit
Application for Facility
information and Tank
information
None
submitted/maintained - 23
CCR 16 2711; HSC 6.7
25286(a)
2010001
Current BOE number
submitted to the CUPA
None
and/or CERS - HSC 6.7
25286(c)
2030011
UST compliance
statement and/or
Designated Operator
❑
❑
❑
❑
❑
None
current certification
submitted - 23 CCR 16
2715(a), 2715(b)
2030046
A complete and accurate
response plan has been
submitted, approved and
Z
❑
None
maintained - 23 CCR 16
2632, 2634(e), 2641(h),
2712(i)
2030041
A complete and accurate
plot plan has been
submitted, approved and
E
❑
❑
❑
❑
❑
None
maintained - 23 CCR 16
2632(d)(1 C), 2711(a)(8)
2010006
Owner/Operator has not
made false statements or
representation on any
None
required document - HSC
6.725299
Bakersfield Fire Department Prevention
2101 H St
Bakersfield CA. 93301
661 - 326 -3911
8__ E--R,-S_ F "I __P
FIRE
�1 RTM r
Underground Storage Tank Program
SW Inspection Report
NOTICE TO COMPLY /NOTICE OF VIOLATION
Violation
Program Requirement
° o
SOC
Comments
No
Oj
D
d
o
O
a
Q)o
Z
O
z
v
®j
2010003
Owner /Operator has a
DO and /or informed the
CUPA of any change (s)
®
❑
❑
❑
❑
[]
None
within 30 days - 23 CCR
16 2715(a)
Testing
2030002
Owner /Operator has
tested and certified leak
®
❑
❑
❑
❑
(�
None
detection equipment
annual) - 23 CCR 16 2638
2030048
Secondary containment
testing conducted every
36 months in accordance
®
❑
❑
❑
❑
❑
None
with requirements - 23
CCR 16 2637
2030055
Spill buckets have been
tested annually as
®
❑
❑
❑
❑
❑
None
required - HSC 6.7 25284.2
2010009
Secondary containment
test results submitted to
the CUPA within 30 days
®
❑
❑
❑
❑
❑
None
after the test - 23 CCR 16
2637(e)
2030042
0.1 gph annual line test
RD
performed and passed for
pressurized piping without
❑
❑
®
❑
❑
❑
None
❑
fail safe or shut down - 23
Yes
CCR 16 26360(4)
2030050
0.1 gallon per hour piping
RD
integrity test conducted
every three years (pre-
❑
❑
®
❑
❑
❑
None
❑
January 1984) - 23 CCR
Yes
16 2643(d
2030051
Piping integrity test or
overfill integrity test
conducted every two
❑
❑
®
❑
❑
❑
None
years (pre - January 1,
1984) - 23 CCR 16 2643(e)
2030029
Lined or repaired steel
RP
tank was inspected within
10 years of lining and
®
❑
❑
❑
❑
❑
None
❑
every 5 years after - 23
Yes
CCR 16 2663
2030028
Tank lining certification
submitted to the CUPA
within 30 days, proper
®
❑
❑
❑
❑
❑
None
tests and inspector used -
23 CCR 16 2663
2030067
ELD testing conducted
every 36 months on USTs
located within 1,000 feet
❑
❑
®
❑
❑
❑
None
of a public drinking well -
23 CCR 16 2644.1 a 3
Bakersfield Fire Department Prevention Underground Storage Tank Program
2101 H St B___ E W. -D SW Inspection Report
FIRE .' -
Bakersfield CA. 93301 N T NOTICE TO COMPLY/NOTICE OF VIOLATION
661-326-3911
Violation
Program Requirement
4-
0 ro-
SOC
Comments
No
a
(1)
0
(L
as
O)o
z
0
z
M
0
W
2010005
ELD testing results sent
to the board and the
CUPA within 60 days of
❑
❑
0
❑
❑
❑
None
completion of the test - 23
CCR 162644.1(a)(5)
2030056
SIR Report submitted
annually to the CUPA - 23
Z
None
CCR 16 2646. 16)
2030064
CUPA was properly
notified within the
prescribed number of
None
hours prior to testing - 23
CCR 16 26370, 2638(e),
2643(g), 2644. 1 (a) (4)
Install/Repair
2060009
Permits obtained to
install, replace, repair, or
0
❑
F-1
❑
❑
❑
None
modify part of the UST
sVstem - 23 CCR 16 2712
UST System Observation
General Monitoring
2030003
Leak detection system
maintains continuous
RD
monitoring that activates
None
❑
an audible and visual
Yes
alarm - 23 CCR 16 2632,
2634, 2636, 2666
2030017
Product piping outside the
UDC is fail-safe and shuts
down the pump or
E
E]
None
restricts flow - 23 CCR 16
2636(0 (5) -
2030018
Turbine sump monitor
RD
activates an audible and
visual alarm or stops the
❑
❑
❑
❑
R
None
❑
flow of at the dispenser -
Yes
23 CCR 16 2636(0) 1)
1
2030019
_
Monitoring system in the
UDCs activates an
audible and visual alarm
Z
None
or stops the flow at the
UDC -23 CCR 16
2636 (1
2030043
Leak detection equipment
RD
properly programmed or
properly operated - 23
None
❑
CCR 16 2632, 2634, 2636,
Yes
2666
2060005
System constructed with
a monitoring system
capable of detecting entry
Z
❑
None
into secondary
containment - HSC 6.7
2529 1 (b)
Bakersfield Fire Department Prevention
2101 H St
Bakersfield CA. 93301
661-326-3911
B_ E__R_S _F I
FIRE
r
Underground Storage Tank Program
SW Inspection Report
NOTICE TO COMPLY/NOTICE OF VIOLATION
Violation
Program Requirement
%6-
0 0
SOC
Comments
No
0
>
0
C0
0
0.
z
0
z
D
v
cr
>
2060014
Correct leak detection
equipment installed for
RD
the type of system
❑
❑
❑
❑
F-1
None
[:1
present - 23 CCR 16 2638;
Yes
HSC 6.7 25290.1, 25290.2,
252
2060015
Sensor located in the
RD
proper position/location -
Z
❑
❑
❑
❑
F-1
None
[_1
23 CCR 16 2630(d), 2641(a)
Yes
2030062
Facility is in compliance
RD
with not tampering with or
disabling leak detection
❑
❑
❑
❑
❑
None
❑
devices or alarms - HSC
Yes
6.7 25299(a)(9)
2030034
Tag/sticker on affixed
monitoring equipment
being certified, repaired,
E
El
F-1
None
or replaced - 23 CCR 16
2638(o
Cathodic Protection
2030009
Impressed-current system
RP
is turned on and
functioning properly and
F-1
None
❑
inspected as required - 23
Yes
CCR 16 2635(a)(2)
Single Walled
Tank Monitoring
2030004
Automatic tank gauge
RD
tests the tank at least
once per month at 0.1
❑
❑
❑
❑
F-1
None
❑
gallons per hour - 23 CCR
Yes
16 2643(b)(2)
2030005
The 0.2 gallons per hour
RD
continuous in tank leak
detection test is being
0
❑
❑
1:1
❑
❑
None
❑
conducted - 23 CCR 16
Yes
2643(b)(5)
2030006
Monthly 0.2 gallons per
hour automatic tank
RD
gauging test on a single
F-1
❑
❑
❑
❑
None
[:1
wall tank is being
Yes
conducted - 23 CCR 16
2643(b)(1)
2060002
Automatic tank
gauging/continuous in
RD
tank leak detection
❑
❑
❑
❑
None
F-1
system installed/properly
Yes
functioning - 23 CCR 16
2643; HSC 6.7 25292La)
2030030
Weekly manual tank
RD
gauging performed in
accordance to the
❑
❑
E
❑
❑
❑
None
F-1
required specifications -
Yes
23 CCR 16 2645