HomeMy WebLinkAbout2929 E Brundage 989 Re-test 2017Testing and Inspection Certificate
Tanknology Inc.
11000 North MoPac Expressway, Suite 500, Austin, TX 78759
800-800-4633 www.tanknology.com Page 1 of 1
Test Date 12/6/2017 Tanknology WO#SC1-3437459
Test Purpose COMPLIANCE Customer PO#
Customer Location
PENSKE TRUCK LEASING
P.O. BOX 7635
READING, PA 19603
PENSKE CA-094 (CA-094/0198-10)
2929 E. BRUNDAGE
BAKERSFIELD, CA 93307
Attn: BRIAN YAZEMBOSKI Attn: Jorge Or David
(610) 603-8450
(661) 322-3146
Test / Inspection Description Item Tested Date
Tested Result
Dispenser Containment (UDC) See test report for details 12/6/2017 Pass
Tanknology Representative: JEFFREY KERTIS Technician: Franscico Castro
Telephone: (800) 964-0010 Technician Certification: (See forms)
SWRCB, January 2002 Page 1 of 1
Secondary Containment Testing Report Form
This form is intended for use by contractors performing periodic testing of UST secondary containment systems. Use the appropriate
pages of this form to report results for all components tested. The completed form, written test procedures, and printouts from tests (if
applicable), should be provided to the facility owner/operator for submittal to the local regulatory agency.
1. FACILITY INFORMATION
Facility Name: PENSKE CA-094 Date of Testing: 12/6/2017
Facility Address: 2929 E. BRUNDAGE , BAKERSFIELD, CA 93307
Facility Contact: Jorge Or David Phone: 661-322-3146
Date Local Agency Was Notified of Testing: 12/28/2017
Name of Local Agency Inspector (if present during testing): peter
2. TESTING CONTRACTOR INFORMATION
Company Name: TANKNOLOGY INC.
Technician Conducting Test: Franscico Castro
Credentials: CSLB Licensed Contractor SWRCB Licensed Tank Tester
License Type: A / UT License Number: 743160 / 8026747
Manufacturer
Manufacturer Training
Component(s)Date Training Expires
VPLT PRECISION EQUIPMENT 2/1/2019
3. SUMMARY OF TEST RESULTS
Component Pass Fail Not
Tested
Repairs
Made
UDC # 2 Sat/ X
UDC # 2 Sat/ X
Component Pass Fail Not
Tested
Repairs
Made
If hydrostatic testing was performed, describe what was done with the water after completion of tests:
CERTIFICATION OF TECHNICIAN RESPONSIBLE FOR CONDUCTING THIS TESTING
To the best of my knowledge, the facts stated in this document are accurate and in full compliance with legal requirements
Technician's Signature:Date:12/6/2017
WO: 3437459
SB 989 TEST WATER LEFT ONSITE.
SWRCB, January 2002 Page 1 of 1
7. UNDER-DISPENSER CONTAINMENT (UDC) TESTING
Test Method Developed By: UDC Manufacturer Industry Standard Professional Engineer
Other (Specify)
Test Method Used By: Pressure Vacuum Hydrostatic
Other (Specify)
Test Equipment Used: VPLT Equipment Resolution: 0.00001 in.
UDC Manufacturer:
UDC Material:
UDC Depth:
Height from UDC Bottom to Top
of Highest Piping Penetration:
Height from UDC Bottom to
Lowest Electrical Penetration:
Condition of UDC prior to
testing:
Portion of UDC Tested1
Does turbine shut down when
UDC sensor detects liquid (both
product and water)?*
Turbine shutdown response time
Is system programmed for fail-
safe shutdown?*
Was fail-safe verified to be
operational?*
Wait time between applying
pressure/vacuum/water and
starting test
Test Start Time:
Initial Reading (RI):
Test End Time:
Final Reading (RF):
Test Duration:
Change in Reading (RF-RI) :
Pass/Fail Threshold or Criteria:
Test Result:
Was sensor removed for testing?
Was sensor properly replaced and
verified functional after testing?
UDC #2 Sat
ENVIRON
Fiberglass
32.00
6.00
8.00
OK
4"ABOVE
Yes No NA
00:00:00 sec
Yes No NA
Yes No NA
15 min
08:40:00
0.37870 in.
08:55:00
0.37800 in.
15 min
-0.00070 in.
+/- 0.00200
Pass
Yes No NA
Yes No NA
UDC #2 Sat
ENVIRON
Fiberglass
32.00
6.00
8.00
OK
4"ABOVE
Yes No NA
00:00:00 sec
Yes No NA
Yes No NA
1 min
08:56:00
0.37800 in.
09:11:00
0.37700 in.
15 min
-0.00100 in.
+/- 0.00200
Pass
Yes No NA
Yes No NA
UDC #
Yes No NA
sec
Yes No NA
Yes No NA
min
+/-
Yes No NA
Yes No NA
UDC #
Yes No NA
sec
Yes No NA
Yes No NA
min
+/-
Yes No NA
Yes No NA
Comments — (include information on repairs made prior to testing, and recommended follow-up for failed tests)
1 If the entire depth of the UDC is not tested, specify how much was tested. If the answer to any of the questions indicated with an asterisk (*) is "NO" or "NA", the entire UDC must
be tested.
WO: 3437459
INSPECTOR ONSITE.
Site Diagram
(This site diagram is for reference only and is not drawn to scale)
Work Order:3437459
Site ID / Name:CA-094/0198-10 / PENSKE CA-094
Address:2929 E. BRUNDAGE
City:BAKERSFIELD State:CA Zip:93307
W.O.# SC1-3437459