HomeMy WebLinkAboutUST PLAN CHECK 3.5.19UST PLAN CHECK
3/15/2018
PLAN CHECK TYPE UST Installation
FACILITY NAME �;�'�L l S U �',t .4 U c .5��
FACILITY ADDRESS
PERMIT NUMBER HTE NUMBER
SCOPE OF
WORK,
SUMMARY
Page
No. GENERAL APPLICATION
CERTIFICATION
Service Request Updated
Correct Fee Paid
Contractor Information Complete on Application
Contractor Signed Application
Owner Information Complete
Equipment List Completed
Scope of Work Completed
Application signed by Owner or Owner Signature Authority Form submitted
Three sets of Plans submitted
All subcontractors identified
CSLB License is appropriate S-698-171 Exp:
C61 -D40 is valid only for calibration work if issued after January 18, 2001
CSLB License Number:
Hazardous Substance Removal Certification (required
for installation and removal) Exp:
Active Worker's Compensation Exp: j 2 65 r�
The following MUST be conducted by a Qualified Installer: Installation of an underground storage tank and /or connected piping and
completion of all work on the tank /piping manufacturer's installation checklist.
Qualified Installers must possess or work under the direct and personal supervision of an individual physically present at the work site
who possesses all of the following: A valid, current contractor's license issued by the Contractor's State License Board, a valid, current
certificate of training from the manufacturer(s) of the component(s) being installed and a valid and current ICC UST
Installation /Retrofitting certificate.
ICC UST Installer / Retrofitter Certification Submitted
Exp:
Name:
Exp:
Name:
Exp:
Name:
Exp:
Name:
Exp:
Name:
Exp:
Name:
Exp:
Name:
UST Plan Check Page 1 of 10
UST PLAN CHECK
The following MUST be conducted by a Qualified Service Technician : All work related to UST leak detection monitoring equipment,
(installation, repair, replacement, maintenance and calibration), Annual Monitoring Certification, Secondary Containment Testing
(including initial testing of newly installed secondary containment systems).
Qualified Service Technicians must possess or work under the direct and personal supervision of an individual physically present at the
work site who possesses all of the following: CSLB license as defined by 23 CCR 2715 (i)(1) or a Tank Tester's license issued to the
individual by SWRCB, valid UST ICC Service Technician certificate, valid and current certificate of training from the manufacturer(s) of the
component(s) being tested, repaired, or serviced. In the event that no training or certification exists, the local agency may approve
comparable alternate training or certification.
ICC Service Technician Certification Submitted
Exp: Name:
Exp: Name:
Exp: Name:
Exp: Name:
Exp: Name:
Exp: Name:
Exp: Name:
Contractor License is appropriate Exp:
C61 -D40 is valid only for calibration work if issued after January 18, 2001
CSLB License Number:
Monitoring Equipment Manufacturer Certification Submitted
Manufacturer:
Exp: Name:
Exp: Name:
Exp: Name:
Exp: Name:
Exp: Name:
Exp: Name:
Exp: Name:
Tank Manufacturer Training Certification Submitted
Manufacturer:
Exp: Name:
Exp: Name:
Exp: Name:
Exp: Name:
Exp: Name:
Pipe Manufacturer Training Certification Submitted
Manufacturer:
Exp: Name:
Exp: Name:
UST Plan Check Page 2 of 10
UST PLAN CHECK
3/15/2018
PLAN CHECK TYPE UST Installation
FACILITY NAME
Manufacturer:
Under Dispenser Containment Manufacturer Training Certification Submitted
Manufacturer:
Exp:
Name:
Exp:
Name:
Exp:
Name:
Exp:
Name:
Exp:
Name:
Containment Sump Manufacturer
Training Certification Submitted
Manufacturer:
Exp:
Name:
Exp:
Name:
Exp:
Name:
Exp:
Name: -
Exp:
Name:
Transition Sump (vent,
etc.) Manufacturer Training Certification Submitted
Manufacturer:
Exp:
Name:
Exp:
Name:
Exp:
Name:
Exp:
Name:
Exp:
Name:
Spill Containment Manufacturer
Training Certification Submitted
Manufacturer:
Exp:
Name:
Exp:
Name:
Exp:
Name:
Exp:
Name:
Exp:
Name:
Other UST Component
Manufacturer Training Certification Submitted
Manufacturer:
Exp:
Name:
Exp:
Name:
Manufacturer:
Exp:
Name:
Exp:
Name:
UST Plan Check Page 3 of 10
UST PLAN CHECK
3/15/2018
PLAN CHECK TYPE UST Installation;
FACILITY NAME S L S Q2U s �✓�-
Name(s) of Qualified Individual(s) with all required
certifications:
UST Plan Check Page 4 of 10
North arrow
Scale of drawing
Building(s), neighboring buildings, streets
V111
and property lines- -where applicable
Dispenser island(s)
Guard posts /bollards
Tank Size Tank Size Tank Size
#1 #3 #5
#2 #4 #5
Indicate Slope on Piping Toward Tank
(inches per foot and direction)
�-
Location of Monitoring Panel
Location of Overfill Alarm
Location of Emergency Shut Off(s)
Location of any Proposed or Existing
AZ
(observation, monitor, etc.)
PARTS LIST
Status
Notes /Comments
UST Plan Check Page 4 of 10
UST PLAN CHECK
UST Plan Check Page 5 of 10
3/15/2018
PLAN CHECK TYPE
UST Installation
FACILITY NAME
L.I-YS gt) 15 7-A
Parts list to be included on the drawings
(must include make and model number
and correspond to side view and /or end
view drawings by number or letter).
PIPING
Status
Notes /Comments
Location of Product Piping and
fTermination
of Pipe
Location of Vapor Recovery Piping and
Termination of Pipe
Location of Vent Piping and Termination
of Pipe
f
Location of Chase Piping
Vent Termination (must be 5 feet from any
building or buildable property line)
Method(s) and location(s) of monitoring
f
for piping
Type of piping labeled (i.e.: rigid FRP,
Enviroflex, etc.)
Piping trench show the distances
between pipes to bottom, sides and
surface of trench.
Backfill material and type /thickness of
cap over trench
Crossover Detail
End View of Piping
f
Piping is UL listed
Piping monitoring application is
approved
Monitoring Equipment approved for
application
Page
No.
SIDE /TOP VIEW
OF TANK AND EXCAVATION
Status
Notes /Comments
Tank Manufacturer identified
Size of tank(s) in gallons on plans
Dimensions of excavation and tank(s)
UST Plan Check Page 5 of 10
UST PLAN CHECK
3/15/2018
PLAN CHECK TYPE UST Installation
FACILITY NAME
�' Method of attachment of sump to tank
UST Plan Check - Page 6 of 10
Distance from ends and sides of tank(s) to
r
sidewalls of excavation
Depth of backfill beneath tanks and type
of backfill material
�►,.
Type and thickness of cap above tank(s)
Location of sumps and /or bungs
Location of spill containment and lids
Risers
ATG(s) (tank level probe)
Turbine(s)
Compartments in Tank
Drop Tube
Overfill prevention device(s)
Any slab or deadman with location and
type of the tie down straps
Level or slope of tank
Hold down calculations for UST if water
present in area (calculations can be listed on a
Aj 4t
separate letter)
,S
Adapters
Sump lids and clamps (or other method of
securing to lid)
Sealant between sump and manway skirt
(if used)
Fill riser caps
VR Phase I riser caps
Location of Interstitial sensor, reservoir,
riser, riser cap and, where applicable, at
grade access box
V/-
Tank(s) is /are UL listed
Monitoring Equipment approved for
application
SIDE /TOP VIEW OF SUMPS
Notes /Comments
Status
�' Method of attachment of sump to tank
UST Plan Check - Page 6 of 10
PLAN CHECK TYPE
UST PLAN CHECK
3/15/2018
UST Installation
FACILITY NAME 5u L—t-ys gc1c VA- ✓ r S -r-4-
UST Plan Check Page 7 of 10
UST PLAN CHECK
3/15/2018
PLAN CHECK TYPE UST Installation
FACILITY NAME
V/
Sump Lid
Spill Containment
Spill Containment meets requirements
Sump Top Hat
Interface between the manway skirt and
sump top hat
Interface or connection between spill
buckets
SIDE /TOP VIEW OF UNDER DISPENSER CONTAINMENT (UDC)
Status
Notes /Comments
f
Type of UDC (FRP, Shallow, Deep, etc)
Termination of UDC secondary wall (if a
double wall UDC)
Penetration into UDC (depict type of
penetration fitting)
All piping and conduits as they go through
penetrations
Termination of secondary walls of pipe
V/--
inside the UDC
Attachment of pipes, etc. to UDC
infrastructure
Location of UDC liquid sensor
V/0^
Location of UDC interstitial sensor
Hydrostatic Double Wall Monitoring:
Type of liquid in interstice and directions
f
for labeling
Communication testing apparatus
location and type identified (ball valve,
manometer, etc.)
Flex connectors
Shear valves
Adequate labeling of components in plans
UDC is UL listed
Monitoring sensors are approved for
application
UST Plan Check Page 8 of 10
UST PLAN CHECK
3/15/2018
PLAN CHECK TYPE UST Installation
FACILITY NAME 541 1,.L.VS 8U Eal V-, 5 -r'-f-
SIDE /TOP VIEW OF PIPf TRANSITIONS AND PENETRATIONS
Notes /Comments
Status
Penetrations of underground piping into
basement or to ground surface -- include
the pipe or collar that provides a conduit
for the double wall pipe.
SIDE /TOP VIEW O'F VENT RISER /SUMP
Notes /Comments
Status
Tank vent termination is a minimum of 12
feet above grade
Depict the flex connectors and secondary
boots
Location of Vent Sump annular sensor
�!
Location of Vent Sump liquid sensor
Hydrostatic Double Wall Monitoring:
Type of liquid in interstice and directions
for labeling
Communication testing apparatus
location and type identified (ball valve,
manometer, etc.)
Transition from flexible or fiberglass
piping to above ground piping - include
protection from sunlight and elements, as
well as construction of aboveground
piping.
Vent Sump UL listed
Monitoring sensors are approved for
application
SIDE VIEW OF GUARD iPOS TS/BOLLARDS
Status
Notes /Comments
Bollards or guard posts to include:
construction, diameter, height, distance
between posts, distance from dispensers,
depth and diameter of footing.
VPH LAYOUT
Status
UST Plan Check
Notes /Comments
Page 9of10
UST PLAN CHECK
3/15/2018
PLAN CHECK TYPE UST Installbtion'rz
FACILITY NAME 5LJ -j-L L/S 0 0C,t/+ V1 s r -4�
New installations: Drawing and /or table
of proposed monitored zones (vacuum,
pressure, hydrostatic). Include vacuum
i,/' volume for each vacuum monitored zone.
UST REMOVAL
Status Notes /Comments
,A y Removal Application