HomeMy WebLinkAbout2023 Baker 3-11-19 CUPABakersfield Fire Department Prevention
Tank Program
2101 H St
Inspection Report
Bakersfield CA. 93301
661-326-3911
FIR
AE
r
Underground Storage
SW
NOTICE TO COMPLY/NOTICE OF VIOLATION
Business Name: Fiesta Liquor & Gas (15-021-104482)
Date: 03/11/2019 (CAL000420198)
Address Name: 2023 Baker St
Bakersfield, CA 93305
Inspector Name: Peter Armagost - ICC#8856813
Inspection Type: Routine �]
Report :Final
NVO = No Violation Observed OUT = Out of Compliance NA = Not Applicable UD = Undetermined
COS = Corrected On Site RPT = Repeat Violation
Violation
Program Requirement
( o;
SOC
Comments
No
o
Q
o
o
(L
a ) c
z
o
z
o>
File Review
Facility Tank Information
2030021
Facility has a valid Permit
Tank 1 -12000 -Premium
to Operate from the
®
❑
❑
❑
❑
❑
None
Tank 2-12000- REG
CUPA - 23 CCR 16 2712(i);
Tank 3- 12000- MID
HSC 6.7 25284
2010010
UST Operating Permit
Application for Facility
information and Tank
information
®
❑
❑
❑
❑
❑
None
submitted/maintained - 23
CCR 16 2711; HSC 6.7
25286(a)
2010001
Current BOE number
submitted to the CUPA
®
❑
❑
❑
❑
❑
None
and/or CERS - HSC 6.7
25286(c)
UST compliance
2030011
statement and/or
Designated Operator
®
❑
❑
❑
❑
❑
None
current certification
submitted - 23 CCR 16
2715(a), 2715(b
A complete and accurate
2030046
response plan has been
submitted, approved and
®
❑
❑
❑
❑
[]
None
maintained - 23 CCR 16
2632, 2634(e), 2641(h),
2712(i)
A complete and accurate
2030041
plot plan has been
submitted, approved and
®
❑
❑
❑
❑
❑
None
maintained - 23 CCR 16
2632 d (1)(C), 2711 a 8)
Owner/Operator has not
2010006
made false statements or
representation on any
®
❑
❑
❑
❑
❑
None
required document - HSC
6.7 25299
Bakersfield Fire Department Prevention Underground Storage
Tank Program... F:... s...r
FIRE
2101 H St ARM SW
Inspection Report
Bakersfield CA. 93301 NOTICE TO COMPLY/NOTICE OF VIOLATION .
661-326-3911
Violation
Program Requirement
o
SOC
Comments
No
o
F_
�, o
z
z
°
o
D
�
o'>
2010003
Owner/Operator has a
DO and/or informed the
CUPA of any change (s)
®
❑
❑
❑
❑
❑
None
within 30 days - 23 CCR
16 2715(a)
Testing
2030002
Owner/Operator has
FMC was due Dec 2018 and
tested and certified leak
❑
®
❑
❑
❑
❑
None
completed late on 3/11/19
detection equipment.
annual) - 23 CCR 16 2638
2030048
Secondary containment
Secondary containment testing was due
testing conducted every
11/2018 and completed late on 3/11/19
36 months in accordance
❑
®
❑
❑
❑
❑
None
with requirements - 23
CCR 16 2637
Spill buckets have been
Spill bucket testing was due Dec 2018
2030055
tested annually as
❑
®
❑
❑
❑
❑
None
and completed late on 3/11/19
required - HSC 6.7 25284.2
2010009
Secondary containment
test results submitted to
the CUPA within 30 days
®
❑
❑
❑
❑
❑
None
after the test - 23 CCR 16
2637(e)
2030042
RD
0.1 gph annual line test
performed and passed for
pressurized piping without
❑
El®
El
❑
None
El
fail safe or shut down - 23
Yes
CCR 16 2636( (4)
0.1 gallon per hour piping
RD
2030050
integrity test conducted
every three years (pre-
❑
❑
®
❑
❑
❑
None
❑
January 1984) - 23 CCR
Yes
16 2643(d)
2030051
Piping integrity test or
overfill integrity test
conducted every two
❑
❑
®
❑
❑
❑
None
years (pre -January 1,
1984) - 23 CCR 16 2643(e)
All 3 UST's past due on lining test
2030029
Lined or repaired steel
RP
tank was inspected within
10 years of lining and
❑
❑
❑
❑
❑
None
every 5 years after - 23
Yes
CCR 16 2663
2030028
Tank lining certification
submitted to the CUPA
within 30 days, proper
®
❑
❑
❑
❑
❑
None
tests and inspector used -
23 CCR 16 2663
2030067
ELD testing conducted
every 36 months on U STs
located within 1,000 feet
❑
❑
®
❑
❑
F-]
None
of a public drinking well -
23 CCR 16 2644.1 a 3
Bakersfield Fire Department Prevention
-,
Underground Storage
Tank Program
g
�,...
�`„� S �..._ ...
FIRE
SW
2101 H St
�,�
R t
Inspection Report
NOTICE
TO COMPLY/NOTICE OF VIOLATION
Bakersfield 933
661-326-3911
Violation Program Requirement
6.o
SOC Comments
o
_
_
o
�
LNo �o
o
z
oz
o>
2010005 ELD testing results sent
to the board and the
CUPA within 60 days of
E]❑
®
❑
E]❑
None
completion of the test - 23
CCR 16 2644.1 a 5
2030056 SIR Report submitted
annually to the CUPA - 23
❑
❑
®
❑
❑
E]
None
CCR 16 2646.1
2030064 CUPA was properly
notified within the
prescribed number of
®
❑
❑
❑
❑
❑
None
hours prior to testing - 23
CCR 16 26370, 2638(e),
2643(g), 2644.1 a 4
Install/Repair
2060009 Permits obtained to
install, replace, repair, or
®
❑
❑
❑
❑
❑
None
_ modify part of the UST
s stem - 23 CCR 16 2712
UST System Observation
General Monitoring
2030003
Leak detection system
maintains continuous
RD
monitoring that activates
®
❑
❑
❑
❑
[]
None
❑
an audible and visual
Yes
alarm - 23 CCR 16 2632,
2634, 2636, 2666
2030017
Product piping outside the
UDC is fail-safe and shuts
®
El
El
El
❑
None
down the pump or
restricts flow - 23 CCR 16
2636(1)(5
Turbine sump monitor
2030018
RD
activates an audible and❑
visual alarm or stops the
®
❑
❑
El
El
❑
None
flow of at the dispenser -
Yes
23 CCR 16 2636 f) 1
Monitoring system in the
2030019
UDCs activates an
audible and visual alarm
®
❑
❑
❑
7
❑
None
or stops the flow at the
UDC -23 CCR 16
2636(0'1)
Leak detection equipment
2030043
RD
properly programmed or❑
®
El
❑
El
❑
None
properly operated - 23
Yes
CCR 16 2632, 2634, 2636,
2666
System constructed with
2060005
a monitoring system
capable of detecting entry
®
❑
❑
❑
E]
❑
None
into secondary
containment - HSC 6.7
25291(b)
Underground Storage
SW
NOTICE TO COMPLY/NOTICE OF VIOLATION
Violation
Program Requirement
° o
SOC
Comments
No
oO
z
z
M
U)�,
o
o
2060014
Correct leak detection
equipment installed for
RD
the type of system
®
❑
❑
❑
❑
❑
None
❑
present - 23 CCR 16 2638;
Yes
HSC 6.7 25290.1, 25290.2,
25291
2060015
Sensor located in the
RD
proper position/location -
®
❑
❑
❑
❑
❑
None
❑
23 CCR 16 2630(d), 2641(a)
Yes
2030062 Facility is in compliance RD
with not tampering with or
disabling leak detection ® El El ❑ ❑ None ❑
devices or alarms - HSC Yes
6.7 25299 a 9
2030034 Tag/sticker on affixed
monitoring equipment
being certified, repaired, ® ❑ El El None
or replaced - 23 CCR 16
2638
Cathodic Protection
2030009 Impressed -current system Cathodic Protection testing was
RP
due on 3/2016
is turned on and
functioning properly and ❑ ® ❑ ❑ ❑ ❑ None ❑
inspected as required - 23 Yes
CCR 16 2635 a 2
Single Walled Tank Monitoring
2030004 Automatic tank gauge RD
tests the tank at least
once per month at 0.1 ® El❑ ❑ ❑ ❑ None [_1
gallons per hour - 23 CCR Yes
16 2643 b 2
2030005 The 0.2 gallons per hour RD
continuous in tank leak
detection test is being ® ❑ ❑ ❑ ❑ ❑ None El
conducted - 23 CCR 16 Yes
2643 b 5
2030006 Monthly 0.2 gallons per
hour automatic tank RD
gauging test on a single ® ❑ ❑ ❑ ❑ ❑ None ❑
wall tank is being Yes
conducted - 23 CCR 16
2643 b 1
2060002
Automatic tank
gauging/continuous in
RD
tank leak detection
®
❑
❑
❑
❑
❑
None
❑
system installed/properly
Yes
functioning - 23 CCR 16
2643; HSC 6.7 25292(a)
RD
2030030
Weekly manual tank
gauging performed in
accordance to the
EJ
El®
❑
❑
❑
None
F-1
required specifications -
Yes
23 CCR 16 2645
Bakersfield Fire Department Prevention
Underground Storage
Tank Program
A..`.
2101 H St
,� ft rpt
r
SW
Inspection Report
Bakersfield CA. 93301
NOTICE TO COMPLY/NOTICE OF VIOLATION
661-326-3911
Violation
Program Requirement
° o
SOC
Comments
Noo
_
z
_
o
a.
0 o,
Z
o
o>
2030022
Groundwater and/or
vadose zone monitoring
❑
❑
®
❑
❑
❑
None
conducted as required -
23 CCR 16 2647, 2648
Single Walled
Piping Monitoring
2030052
Piping monitored hourly
T-1 (91) & T-3 (89) need
and a 0.2 gph monthly or
RD
precision line test
0.1 gph annual line
❑
®
❑
❑ ❑
❑
None
integrity test is performed
Yes
- 23 CCR 16 2641(a),
2643(c
Line Leak
Detector
2060012 Line leak detector
installed on pressurized
RD
piping system - HSC 6.7None
®
El
❑
El F-1
❑
F -125290.1(h),
25290.2(g),
Yes
252910, 25292(e),
26360(2)
2030026 Line leak detectors detect
a 3 gph leak and/or
RD
audible and visual alarm
®
❑
❑
❑ ❑
❑
None
❑
function properly - 23
Yes
CCR 16 26360(6),
2666(c)
2030027 Turbine shuts down when
RD
a leak is detected or
when line leak detector is
®
❑
❑
❑ ❑
❑
None
❑
disconnected - 23 CCR 16
Yes
2666 c
2030025 Pressurized piping able to
detect a 3.0 gph leak
RD
within an hour, and
®
❑
❑
❑ ❑
❑
None
❑
restricts the flow or
Yes
alarms - 23 CCR 16
2636 (0(2)
Suction Piping
2030053 Suction piping sloped to
drain back into storage
RD
tank, one check valve and
❑
❑
®
❑ ❑
❑
None
❑
inspections conducted -
Yes
23 CCR 16 2636(a)(3),
2641(b)
Secondary Containment
2030008 UDC, sumps, and/or
other secondary
containment in good
®
❑
❑
❑ ❑
❑
None
condition and/or are free
of debris/liquid - HSC 6.7
25290.1, 25290.2, 25291
Bakersfield Fire Department Prevention
Tank Program
2101 H St
Inspection Report
Bakersfield CA. 93301
661-326-3911
rFIRE
A � rMV r
Underground Storage
SW
NOTICE TO COMPLY/NOTICE OF VIOLATION
Violation
Program Requirement
° ,o
SOC
Comments
No
o
_
o
a-
o
Z
o
z
=
o>
2030047
Secondary containment
T-2 (87) Direct bury spill bucket failed
maintained tight and has
been confirmed by testing
❑
®
❑
❑
❑
❑
None
- 23 CCR 16 2662; HSC 6.7
25290.1(c)(2), 25290.2(c)(2),
25291(a), 25292(e)
2030060
Entry fittings in secondary
containment for UST
system maintained
®
❑
1:1
❑
Cj
❑
None
tight/sealed - 23 CCR 16
2630, 2635(d), 2636(c),
2666
2060020
Spill bucket is installed
RP
Past due on annual testing
and has a functional drain
valve or other means to
❑
®
❑
❑
❑
❑
None
remove liquid - 23 CCR 16
Yes
2635(b), 2665
2030054
Spill bucket maintained in
RP
good condition and free of
®
❑
❑
❑
❑
❑
None
❑
debris and/or liquid - 23
Yes
CCR 16 2635(b), 2715 c (2
2060019 Spill bucket to has a
minimum capacity of five ® ❑ ❑ ❑ ❑ ❑ None
gallons - 23 CCR 16
2635(b), 2665
Overfill
2030035
UST system is operated
RP
to prevent unauthorized
release, including spills ® ❑ ❑
❑
❑
❑
None
F-1
and overfills - HSC 6.7
Yes
25292.1 a
Overfill prevention system
Failure to conduct OPI as required by
RP 10/13/18.
2030036
has not been overridden
❑ ® ❑
❑ ❑ ❑
None
and meets overfill
requirements - 23 CCR 16
Yes
2635 b2 , 2665
On
Site Records
Certifications
2030023
Required designated
operators or contractors
maintain a proper and
®
❑
❑
❑
❑
❑
None
current ICC certification -
23 CCR 16 2715
2030024
Service technician,
installer, and/ or
employee maintain a
®
❑
❑
❑
❑
❑
None
proper license - 23 CCR
162715
2030031
Employee or contractor
obtained and maintained
proper manufacturer
®
❑
❑
❑
❑
❑
None
certification - 23 CCR 16
2715
Violation
Program Requirement
° o
SOC
Comments
No
z
o
Z
_
o
a� �
�o
o>
2010007
Submit/maintain current
Certificate of Financial
Responsibility/mechanism
of financial assurance -
®
❑
❑
❑
❑
❑
None
23 CCR 16 2711; 23 CCR
18 2808.1, 2809-2809.2;
HSC 6.7 25292.2; HSC
6.75 25299.30-25299.34
Positive statement of
2030007
compatibility for UST
system components
x
submitted and maintained
on site - 23 CCR 16 26316)
Operator
Designated
2010004
Copies of DO inspections
for last 12 months and list
of trained employees
®
❑
❑
❑
❑
❑
None
maintained - 23 CCR 16
2715
D.O. not keeping accurate records of
2030013
Designated operator
compliance testing dates
properly conducted the
monthly inspection and
El®
❑
El❑
❑
None
the reports are complete -
23 CCR 16 2715
Failing to address compliance issues
2030010
DO notified operator of
any condition observed
during the monthly
❑
®
❑
❑
❑
❑
None
inspection that may
require action - 23 CCR 16
2715(d)
Last D.O .employee training was in
2030012
DO employee training
2015
performed, current for at
El®
El❑
❑
❑
None
least one employee on
site, and a log kept - 23
CCR 16 2715 c 6 , 2715
Logs
No alarms logged
2030001
Leak detection alarm
logs, maintenance and
records of appropriate
®
❑
❑
❑
❑
None
follow-up actions
maintained - 23 CCR 16
2632, 2634, 2712(b)
2030020
Unburied fuel piping
RD
visually inspected at least
❑
❑
®
❑
❑
❑
None
❑
monthly and log kept -
Yes
HSC 6.7 25281.5 b 3
2030049
Suction pipe monitored
daily and results logged -
❑
❑
®
❑
El
None
23 CCR 16 2643(d
2030057
When SIR results indicate
RD
failure: The facility met all
❑
❑
®
❑
❑
❑
None
[:1orrective
caction
Yes
requirements - 23 CCR 16
2646.1 d)
Bakersfield Fire Department Prevention
Tank Program
2101 H St
Inspection Report
Bakersfield CA. 93301
661-326-3911
4
FIRE
ARM r
Underground Storage
SW
NOTICE TO COMPLY/NOTICE OF VIOLATION
Violation
Program Requirement
° ,o
SOC
Comments
No
o
_
a
o
o
a
L
�o
z
o
z
D
0
o'>
2030058
All Statistical Inventory
RD
Reconciliation (SIR)
❑
❑
❑
❑
❑
❑
None
❑
requirements met - 23
Yes
CCR 16 2646.1
Maintenance/Tests
2010008
Monitoring, maintenance,
Unable to find records for SB989
repairs, linings, and
RD
testing, tank lining, last 3 FMC
upgrade records
❑
®
❑
❑
❑
❑
None
❑
maintained for the proper
Yes
time period - 23 CCR 16
2712(b)
Bakersfield Fire Department Prevention
Underground Storage
Tank Program
FI
2101 H St
r
SW
Inspection Report
Bakersfield CA. 93301
NOTICE TO COMPLY/NOTICE OF VIOLATION
661-326-3911
Violation
Program Requirement
° .o'
SOC
Comments
No
O
=
a
0
m
0
a
a)
o.
Z
0
z
M
U
W
p>
2010002
Records of cathodic
protection systems testing
®
❑
❑
❑
❑
❑
None
maintained - 23 CCR 16
2635, 2712(b)
Documentation
2030033
Failure to maintain on site
an approved monitoring
®
❑
El
❑
El
❑
None
plan - 23 CCR 16 2632,
2634, 2711, 2712(i
2030037
Written agreement
between the tank owner
and tank operator to
monitor the tank system
®
El
❑
❑
❑
None
is maintained - 23 CCR 16
2620(b); HSC 6.7
25284(a) (3)
Suspected or actual
RD
2030061
unauthorized release
reported in appropriate
E]
El®
El
ElF-1
None
❑
time frame - HSC 6.7
Yes
29294, 29295
General Operating
Requirements
Permit Condition/Approval
2030039 Compliance with all
Correct all and any violations
operating permit
El®
El
❑
❑
None
Within 30 days
conditions - 23 CCR 16
2712; HSC 6.7 25299
2030059 UST system maintained
in accordance with
exclusion/exemption
❑
❑
®
❑
❑
❑
None
status - HSC 6.7 25281.6,
25283.5
2030014 Owner/Operator received
approval and has
implemented a training
❑
❑
®
❑
❑
❑
None
program at an unstaffed
facility - 23 CCR 16
2715 (0(2)
2030015 Facility exhibited that the
method used to monitor
the tank meets the
®
❑
❑
❑
❑
❑
None
monitoring methods in
2643 - 23 CCR 16 2643
Red Tag
2030045 Red Tag information is
legible and has not been
❑
❑
®
❑
❑
❑
None
tampered with - 23 CCR
16 2717.1 )
2030044 Facility did not allow for
deposit of petroleum into
a UST that has a red tag
❑
❑
®
❑
❑
❑
None
affixed to the fill - 23 CCR
16 2717.1(1)
Violation
Program Requirement
° o
SOC
Comments
No
>
_
o
z
a-
ao
o
z
_
o>
Install/Repair
2030066
Repaired and retested the
system due to a failed
ELD test when located
❑
❑
®
❑
❑
❑
None
within 1000' of public well
- HSC 6.7 25292.4(d),
25292.5(c)
2060018
Existing SW piping is
constructed of FRP,
RP
cathodically protected
®
❑
❑
❑
❑
❑
None
❑
steel, or steel clad with
Yes
FRP - 23 CCR 16 2666(b);
HSC 6.7 25292(e)(2)
Striker plate installed and
2060021
positioned correctly - 23
❑
❑
N
❑
❑
❑
None
CCR 16 2631(c), 2662(d)
2060004
Corrosion protection
installed for USTs and
RP
cathodic protection
®
❑
❑
❑
❑
❑
None
❑
system meets the
Yes
consensus standards - 23
CCR 16 2635(a)(2 A
❑ There were no violations noted for this inspection.
®This report shall serve as a "NOTICE TO COMPLY" for Minor Violations, and a "NOTICE OF VIOLATION" for
Major violations. You are, hereby, ordered to correct the above noted violations within 30 days, or according to
correction summaries provided. Formal enforcement and/or penalty assessment may be initiated for any
violations noted, and for those not corrected in a timely manner. (NOTE: If this is a preliminary report, a final report
will follow.)
Inspectors Signature:
Date: 3/11/19
Inspector: Enter # of Violations: RD: RP:
Check one box for facility Significant Operational Status (SOC) to be reported to SWRCB and US EPA:
❑ SOC with both Release Detection and Release Detection (Facility has no Release Prevention and no Release
Prevention Violations)
❑ Not in SOC (Facility has both Release Prevention and Release Detection Violations)
❑SOC with Release Detection only (Facility has no Release Detection violations but one or more Release Prevention
violations)
❑ SOC with Release Prevention only (Facility has no Release Prevention violations but one or more Release Detection
violations)