HomeMy WebLinkAbout1700 mt vernon inspector reportUNIFIED PROGRAM INSPECTION CHECKLIST
L'h
Underground Storage Tank Program t
:
_r.
BAKERSFIELD FIRE DEPARTMENT
Prevention Services Division
2101 H Street
Bakersfield, CA 93301
Phone: 661- 326 -3979
Fax: 661- 852 -2171
Facility Name:
Kern Medical Center
Date of Inspection:
Time In:
Time Out:
Address:
1700 Wit Vernon Ave. Bakersfield, CA. 93305
Inspected by: Esther Duran
ICC# 5296325 -UI
Contact:
Leann Victory
Type of Inspection:
Annual Compliance ❑Re- inspection ❑ Complaint
Phone:
(661)326 -2000 (24 hr.)
Permission for Inspection Granted by:
Tank ID
#1
Size
10,000
Contents
DSL
Construction
Tank Monitoring:
DW: Continuous Interstitial Monitoring
❑ Dry ❑ Brine/Hydrostatic ❑ Vacuum /Pressure.
❑
❑
❑
SW: SIR and Line Test every 2 years.
❑
❑
❑
SW: ATG 0.1 annual.
❑
❑
❑
El
SW: ATG 0.2 monthly.
❑
❑`
❑
❑
SW: Continuous In -Tank Leak Detection (CITLD).
❑
❑
❑
SW: Tank Gauging.
❑
❑
❑
SW: Vadose /GW Monitoring.
❑
❑
❑
Other Description:
❑
❑"
❑
- Piping .Monitoring:
DW Suction: Continuous Interstitial at UDC and Tank Sump.
❑
❑
❑
DW Pressurized: Interstitial at UDC and Turbine Sump and 3.0 gph LLD,
❑ Annual Line Test or ❑ Auto - shutdown and Failsafe.
❑
❑
❑
0,
DW VPH Monitoring: Includes lines, sumps, fill pipe, vapor lines, etc.
❑
❑
❑
SW Conventional Suction: Triennial 0.1 gph line test., and daily
monitoring.
El
El
SW Pressurized: Line 0.1 gph annual or 0.2 gph monthly line test and
LLD with Auto - Shutdown.
❑
❑
❑
0:
SW or DW Safe Suction.
❑
❑
❑
❑�
SW: Vadose Zone or GW Monitoring.
❑
❑
❑
❑
DW or SW: Gravity Flow Pipe.
❑
❑
Other Description:
❑
❑
❑
❑
References to the Health and Safety Code, the California Code of Regulations and the Code of Federal Regulations throughout this Hppenaix are
intended to be useful but are not necessarily exhaustive of all legal references that might apply or be relevant to a specific compliance determination.
Laws and regulations are subject to change, so the references contained herein may not be up to date. It is the responsibility of the owner and operator
to know and comply with all applicable legal requirements.
UNDERGROUND STORAGE TANK COMPLIANCE INSPECTION REPORT
Facilit� Name: Date:
Bakersfield Fire Department — Prevention Services Division, 2101 H Street, Bakersfield, CA 93301 (661) 326-3979
VI/
If in compliance, check the box. Check NA if not applicable.
If a violation, determine if Minor, Class 11, or Class 1, or To
Violations
Be Determined (TBD) if uncertain and will be determined
Jater.
91 01
'M�
H
71
15
I
gwo
.10
-
I11 A6
1 view',
F e
')el
UST Permit to Operate is current. HSC 25284(a), 25299(a)(1) 25299 (b)(1)
El
Transfer of permit and/or change of information provided within
30 days of ownership/information changes. HSC 25284(b) (c); T23
14:1""
all
CCR 2712(d)
09 a
El 3
UST form information current/correct for facility, including BOE
-ro %her C.;'V/-tT
number. HSC25286(a)
-rhaltvah C"5
04
Fees are paid up-to-date. HSC 25285(C), 25287
El
El 5
Monitoring Plan approved for current owner with appropriate
El
content and level of detail. T23 CCR 2632(d), 2634 (d), 2641(h)
06
Current Emergency Response Plan submitted with appropriate
F1
content and level of detail. T23 CCR 2632(d), 2634 (d), 2641(h)
Plot Plan/Site Map submitted with appropriate content and
EJ
level of detail. T23 CCR 2632(d), 2634(d), 2641(h), 2711(a)(8)
08
Owner/Operator agreement submitted, if required. HSC 25284(a)(3)
09
Certification of Compliance and Designated Operator
El
Certification submitted by current tank owner. T23 CCR 2715
010
Certificate of Financial Responsibility submitted and is current
for the permit period. HSC 25292.Z 25299.30-25299,34; T23 CCR 2711; 2808. 1;
2809-2809.2
011
Monitoring system certification (most recent) conducted within
pesrDwF 15-3 Avf
allowable timeframe (sensors and console). Results submitted
El
and show all required components with passing results. Hsc
1 25284. 1(a)(4)(c); T23 CCR 2638
012
Spill-bucket test results (most recent) conducted within
allowable time frame. Results submitted and indicate a passing
test. HSC 25284.2
013
Leak Detector testing conducted within allowable time frame.
The most recent annual certification submitted and shows
RD
RD
RD
El
passing results. 40 CFR 280.40(a)(2), 280.43(g)(1)&(2), 280.44(a); HSC 25292(e);
T23 CCR 2638, 264 1 Y)
Nri
r ' 4
Secondary containmerittesting conducted within allowable
time frame. Most recent testing results submitted and indicate
a passing test. HSC 25284. 1(a)(4)(B); T23 CCR 2637(a)
015
Pipe and/or tank integrity testing conducted within allowable
time frame. Most recent testing results submitted and indicate
passing results. 40 CFR 280.33, 280.40, 280.41, 280.44; T23 CCR 2636(o,
(c)(3), (d) (e)
___2643(b)(3),
016
Repaired tanks/piping are tightness tested within 30 days of
RD
RD
RD
RD
the rep ir. 40 CFR 280.33, T23 CCR 2661
017
ELD test conducted within allowable time frame. Most recent
test results submitted and passing results achieved. T23 CCR
2644.1
018
The corrosion protection system is checked by a corrosion
specialist within six months of instal lation/repair and at least
RP
RP
RP
every three years thereafter; results show protection to be
RP
adequate. Impressed current inspected every 60-calendar
days. 40 CFR 280.31, 280.70, T23 CCR 2635(a)(2)
019
Tank Lining recertification is current (within 10 years of lining
and every 5 years thereafter) and compliant. 40 CFR280.21(b)(1)(fij;
RP
RP
RP
RP
T23 CCR 2663(h)
Bakersfield Fire Department — Prevention Services Division, 2101 H Street, Bakersfield, CA 93301 (661) 326-3979
VI/
Facility Name:
UNDERGROUND STORAGE TANK COMPLIANCE INSPECTION REPORT
Date:
Y
Q
�
Genera/
NO Tank systems meet current construction standar,
for type of system. HSC 25288
X2 Hazardous substance tanks have secondary cor
CFR 280,42(b); T23 CCR 2631
W2 Electronic monitoring system has audible and vi:
operatin condition. T23 CCR 2632, 2634, 2636
23 Monitor console programmed appropriately for rr
option used. T23 CCR 2638, 2643, 2643.1
024 Tank systems in temporary closure meet require
280.70, T23 CCR 2670 & 2671
❑25 Overfill Prevention mechanism present and oper
according to type: ❑Flapper valve ❑ Audible -vis
❑ball float. ❑ AN alarm and Ball Float 40 CFR 280.
280.21(d); T23 CCR 2635(b)(2), 2631 d 4
Spill prevention device is present and functional
condition and drain mechanism operational if ap
280.20 c 1 1, 280.21(d); T23 CCR 2635(b)(1);2665
27 Piping and piping penetration boots within sump:
good condition. HSC 25288(x), 25292.1
8 All sumps, spill buckets, and UDC's free from de
HSC 25291(e), 25290.1, 25290.2; T23 CCR 2635(b)(1)(C)
29 Areas around vents appear to be free from sign:
releases. HSC 25288(a), 25290.1, 25290.2, 25295.5
0 Release Detection methods are present and me
standards. See LG -113. 40 CFR 280.40(x)(3)
1 All sensors are correct for the type of system an,
40 CFR 280.40(a) 2 , 280.43 1 & 2 ; HSC 25290.1(e ), 25290.2, 2
2 All sensors are located in the proper position /loc
280.40(a)(2), 280.43(g)(1) &(2); HSC 25290.1, 25290.2, 25291; T23 f
2632(c);2641(a)
33 All secondary containment, including UDC shall
with a continuous monitoring system that either
AN alarm or stops the flow of product at the disl
detects a leak. T23 CCR 2636 (0(1)
Tank Monitoring
4 Interstitial monitoring conducted properly. 40c,
280.43 1 & 2 ; T23 CCR 2632 c 2 ; 2634 d (1
035 ❑ VPH monitoring conducted properly. HSC 25290
O SIR
036 SIR and Biennial 0.1 gph tank test performed pr
280.41, 280.43; T23 CCR 2643, 2646.1
❑37 Non - passing SIR monitoring report results are n
investigated properly. 40 CFR 280.41(x), 280.43(h)(1),(2);
Bakersfield Fire Department — Prevention Services Division, 2101 H Street, Bakersfield, CA 93301 (661) 326 -3979
On'-, Site 'Review
This Inspection is being conducted during the an
monitoring certification. o YES NO
The service technician has provided ICC Certific
manufacturers training documentation, and poss
tester's license or works under a CSLB contractc
O YES O NO
y. nTnk/PrprngCoporaents N
NJonrtorrng any
-C' 2
2, te's� h \ �• < i �(` iq �' tCu`k`. t i
Bakersfield Fire Department — Prevention Services Division, 2101 H Street, Bakersfield, CA 93301 (661) 326 -3979
UNDERGROUND STORAGE TANK COMPLIANCE INSPECTION REPORT
FC2%A ILy
Ivai 1 ic.
NMI
i 6 x
�
Y f
O Automatic Tank Gauging (ATG) / Continuous In -Tank Leak
Detection CITLD
038
ATG or CITLD 0.2 gph monthly test performed properly. 40 CFR
RD
RD
RD
RD
280.43; T23 CCR 2643(b)(1), 2643 (b) (5)
9
ATG generates a hard copy printout of all data reported
including time and date, tank I.D., fuel depth, water depth,
temperature, liquid volume and duration of test. If installed after
El
1/1/95 printout includes calculated leak rate and leak threshold.
T23 CCR 2643 b 1
O Manual Tank Gauging (SW tanks </ =1000 gal. ONLY)
040
Weekly manual tank gauging performed properly. 40 CFR 280.43;
RD
RD
RD
RD
T23 CCR 2645
041
Tank Integrity test performed, if necessary. 40 CFR 280.43; T23 CCR
RD
RD
RD
RD
2645
O Vadose Zone and/or Groundwater Monitoring
❑42
Monitoring system is installed and monitored properly. 40CFR
RD
RD
RD
RD.
280.43; T23 CCR 2647 -48
OTank Exemption
043
Tanks /piping meet tank exemption criteria, and weekly visual
monitoring records are kept up-do-date. HSC 25283.5
'Pi a Monitorin
"t,M"'K �
. . .. ter.. •. a.. ....Y ,.. .,._-
"c'!,0�,� �ra�.., w ...ta �=�rn,. ru.3 s .,. �,..� t 3 w, o-,ia „8 «.,. a3t' .✓u..,..
O Continuous Monitoring System
. - -..,r-
v . A
. .. - ., "
s- ...hr .
�<4_
DW piping (gravity, suction, pressure) in the turbine sump has
continuous monitoring system that activates an audible and
RD
RD
RD
RD
❑
visual alarm or restricts or stops flow at dispenser. T23 CCR
2636 1
❑45
DW piping in the UDC is continuously monitored and method
either shuts down the -flow of product to the dispenser or
activates an AN alarm. T23 CCR 2636(0(1)
O Line Integrity Testing for Pressurized Piping
046
An annual 0.1 gph line integrity test is performed properly.
(Either third party or by Enhanced Line Leak Detection) T23 CCR
RD
RD'
RD
RD
2636 (4
❑47
In lieu of the annual tightness test for DW pressurized piping,
the monitoring system for all product piping outside the
dispenser is fail -safe and shuts down the pump when a leak is
RD
RD
RD
RD
detected and the monitoring system shuts down the pump or
flow restriction occurs when a leak is detected in the UDC. T23
CCR 2636(0(5)
O Line Leak Detectors (LLD)
❑48
LLD's installed, annually tested, and operational on DW
pressurized piping that detects a 3.0 -gph leak, and restricts or
RD
RD
RD
RD
shuts off flow of product. T23 CCR 2636(0(2)
O DW Emergency Generator Tank
❑49
LLD activates AN alarm and monitoring system is checked
RD
RD
RD
RD
dal/v. T23 CCR 2636(0(2)
0
In lieu of LLD, continuous monitoring system of DW emergency
generator tank activates AN alarm, system is checked daily,
❑
and logs are kept. T23 CCR 2636 (0(6)
ra
.cu. tqc r ...
S
�Yc.
f .. ...,
v f
O Line Integrity Testing
051
SW pressurized piping: annual 0.1 gph line integrity test or a
monthly 0.2 gph line integrity test is performed properly. 40 CFR
RD
RD
RD
RD
280.41, 280.44; T23 CCR 2643(c)(2),(3)
052
SW conventional suction system: 0.1 gph line integrity test is
RD
RD
RD
RD
LA
performed every three years. 40 CFR 280.40, 280.41; T23 CCR 2643(d)
Bakersfield Fire Department — Prevention Services Division, 2101 H Street, Bakersfield, CA 93301 (661) 326 -3979
UNDERGROUND STORAGE TANK COMPLIANCE INSPECTION REPORT
Facility Name: Date:
n
5
053
SW conventional suction system: inspections conducted for
presence of air in the pipeline. Daily monitoring records are
kept. T23 CCR 2643(d)
054
SW gravity flow piping: biennial 0.1 gph integrity test or overfill
tank integrity test is conducted within allowable time frames.
T23 CCR 2643(e
O Safe Suction (SS) System
�55
Piping meets the SS requirements. 40 CFR 280.41; T23 CCR 2636(x)(3)
RD
RD
RD
RD
❑
A -D
O LLD for Pressurized Piping
056
LLD's installed, annually tested and operational on SW
pressurized piping. Pump shuts down when a leak occurs and
RD
RD
RD
RD
when the LLD fails or is disconnected. T23 CCR 2666
057
LLD's installed, annually tested, and operational on SW
AN
emergency generator systems; LLD is connected to an
alarm. 40 CFR 280.40(a)(2), 280.43(g)(1),(2), 280.44(a); T23 CCR 2666
Corrosion Protection .
❑58
Metal Tanks and piping components have corrosion protection,
RP
RP
RP
RP
or are isolated from the backfill. 40 CFR 280.20, 280.21
059
Corrosion protection equipment turned on, functioning properly
RP
RP
RP
RP
and provides continuous protection. 40 CFR 280.3 1 (a), (b)(1); T23 CCR
2635
060
Cathodic protection system is tested within 6 months of
installation and then every 3 years. 40 CFR 280.31(a) & (b)(1); T23 CCR
RP
RP
RP
RP
2635 a (2
061
Impressed current systems checked every 60- calendar days
RP
RP
RP
RP
and records are up-to-date. 40 CFR 280.31(c); T23 CCR 2635(a)(2)
On -situ Pa erwork
2
Permit and conditions available on- site. Facility is operated
El
according to permit and conditions. HSC 25293; 25299; T23 CCR 2712(i)
3
Monitoring and response plans are on -site and are the
❑
approved version. T23 CCR 2712(i); 2632;2634; 2641
L64
Site plan depicts current site conditions and has all required
❑
elements. T23 CCR 2632(4)
065
All release detection records for monitoring method are
available, up -to -date, and appropriate for leak detection
RD
RD
RD
RD
❑
method. 40 CFR 280.41, 280.45
066
All monitoring /testing records /documents are available for the
❑
required timeframe. (3 years, 6'/2 years, five years, life of tank) T23 CCR
2712
❑6.7
Equipment maintenance records /logs available. T23 CCR 2712(b)
❑
8
Alarm logs /tapes available and appropriate follow -up actions
r1E:1
occurred. T23 CCR 2712(b); 2632; 2634
0769
Visual observation logs available, up -to -date, and appropriate
❑
follow -up actions to problems occurred. T23 CCR 2712(b); 2642
0
Designated UST Operator monthly reports available and
❑
complete. T23 CCR 2715
71
Employee training records available and training appropriate
❑
072
and up -to -date. T23 CCR 2715
Suspected or actual unauthorized releases are recorded
'°
j�5tn I� L c�o5
frames including non-
and /or reported within allowed time 9
R
RD
RD
RD
❑
passing test results. Leak and Spill Logs available. 40 CFR 280.50,
T23 CCR, 2650, 2652
3
Financial Responsibility Certificate and mechanisms (CFO
Letter, etc.) on -site and up -to -date. HSC 25292.2, 25299.30- 25299.34; T23
L
El
L
CCR 2711; T23 2808.1; 2809 - 2809.2
Bakersfield Fire Department — Prevention Services Division, 2101 H Street, Bakersfield, CA 93301 (661) 326 -3979
UNDERGROUND STORAGE TANK COMPLIANCE INSPECTION REPORT
Facility Name: Date:
On -Site Observation of Periw c Tesf n
4 Spill- bucket testing conducted appropriately and a passing test
achieved.
075 Secondary Containment testing conducted appropriately and a
nassina test achieved.
SOC AND RED TAG
►2
aggee yy.��
i �
Ste. '...i
{" vU MUM
rF 5
c
A ■ i
i ■ $ t ? & 2 § k „ Y, $ �.`Y��" 4 1 � \14� �� d��t'N , ii �
A
■a 'i � Y �� y � � 1. MSL��,xaacam. ^
a. This facility is in compliance with Release Detection (RD) requirements only. (No
violations in boxes marked RD, but one or more in boxes marked RP.)
b. This facility is in compliance with Release Prevention (RP) requirements only. (No
violations in boxes marked RP, but one or more in boxes marked RD.)
❑
c. This facility is in compliance with BOTH Release Detection (RD) and Release
Prevention (RP) requirements. (No violations in boxes marked RD or RP.)
d. This facility is NOT in compliance with both Release Detection (RD) and Release
Prevention (RP) requirements. (One or more violations marked in (both) boxes RD
and RP.)
El
,. , y •.:
•;-, - , ,,, I G111 .�;^R". %5+'u,'.w.:sns-.+ ,.✓.< :.a'.`$rW.ss�."�c»+�,* hi:,'+Sagw'.. a r"`f ,. ?im.. . - �' 1' .� :r::
L>'..�4�V i
A Red Tag was issued to this facility based on the results of this inspection.
Red Ta #
L
Reason for Red Tag (Choose one):
1. Violation that causes or threatens to cause a liquid release. CCR 2717(a)(1)
2. Violation that impairs the ability of an UST system to detect a leak. CCR 2717(x)(2)
3. Chronic violation or committed by a recalcitrant violator. CCR 2717(x)(3)
Item Inspection Comments:
Bakersfield Fire Department — Prevention Services Division, 2101 H Street, Bakersfield, CA 93301 (661) 326 -3979