HomeMy WebLinkAboutFINAL ELD 5-29-2019Exclusive Providers for MDleak® MSleak® DPleak® and
PHDleak® Testing Technologies
Page 1 of 3
Test Type:
Facility Name: Job #: 3952
Prepared For: PO #: NA
Site Address:
City: Primary Test Leak Rate: 0.005 gph
State and Zip: CA 93306 Secondary Test Leak Rate: 0.1 gph
Start Date:End Date:
SYSTEM TK-1 87 TK-2 91 TK-3 DSL
Product Primary:PASS PASS PASS
Product Secondary:PASS PASS PASS
Vent Primary:PASS PASS PASS
Vent Secondary:PASS PASS PASS
VR Primary:PASS PASS NA
VR Secondary:PASS PASS NA
Tank:PASS PASS PASS
Turbine Sump:PASS PASS PASS
Turbine Sump Elect:PASS PASS PASS
Turbine Head:PASS PASS PASS
Fill/Vapor Sump:PASS PASS PASS
UDC's:PASS PASS PASS
Fill Bucket Primary:PASS PASS PASS
Vapor Bucket Primary:PASS PASS NA
Fill Spill Bucket Hydo:PASS PASS PASS
Vapor Bucket Hydro:PASS PASS NA
Vent Box:PASS PASS PASS
Certifying Field Technician: Ricardo Gonzalez State Lic. # :
Certification Leak Rate: 0.005 gph
Certifying Technician Signature: Date:
Statement Confirmed by: Date:
Complete Fueling Solutions
Facility Certification CONFIDENTIAL
California ELD New Construction Test MSleak
Countryside Village
5900 Comanche Drive
Bakersfield
This is a statement to confirm that the components listed above,at the time of testing,have been tested to a leak
sensitivity listed above by using one or more of the following DPleak®,MDleak®and PHDleak®EPA aproved Methods.
The DPleak®,MDleak®and PHDleak®Methods are the most versatile and comprehensive testing procedures offered to
the petroleum industry.All petroleum owners and contractors which utilize the DPleak®,MDleak®and PHDleak®Method
can be assured that their facility has passed the Nation's highest standard in preventative leak detection.
5/30/2019
5/30/20195/29/2019
5/31/2019
Office use only
I declare under penalty of perjury that I am a licensed tank tester in the DPleak®,MDleak®and PHDleak®method,a
method listed by the NWGLDE organization and that the information contained in this report is true and correct to the best
of my knowledge.
If you have any questions on the testing please do not hesitate to call. @ 855-255-5325.
04-1695
Exclusive Providers for MDleak® MSleak® DPleak® and
PHDleak® Testing Technologies
Page 2 of 3
5900 Comanche Drive Log of Repaired Leak/s
CONFIDENTIAL
TK-1 87 TK-2 91 TK-3 DSL
Tank Volume: 20000 10000 10000
Manufacture: Modern Modern Modern
Interstice: Dry Dry Dry
Depth To Tank: 69"73"68"
Tank Dia: 10 ft 10 ft 10 ft
Depth to Fuel:
Tank Sump Boots Turbine
Bravo Smith Red Jacket
5
Gilbarco
OPW
Smith
Smith
Smith
Fire-Flex
PhilTite
EVR: Healy
Reference #Date Time Status System Component Manufacture
134 5/29/19 11:39 Leak Final TK-1 87 Sump Turbine Coupler on product line leaking.
140 5/29/19 11:48 Leak Final TK-1 87 Sump Turbine Coupler on product line leaking.
142 5/29/19 11:50 Leak Final TK-2 91 Sump Turbine Riser to turbine sump
143 5/29/19 11:51 Leak Final TK-3 DSL Sump Fill/Vapor Extractor tee to tank leaking.
Reference #Date Time Status System Component Manufacture
None
Vapor Return / Vent:
UDC/Dispensers Information
Depth to Ground Water:
Manufacture:
NA
Log of Repaired Leaks
Log of Unrepaired Leaks
Tank Information
Containment Boots:
Piping Information
Manufacture
Spill Buckets:
Number of Dispensers:
Manufacture:
Shear Valve Manufacture:
Flex:
Product Lines:
Exclusive Providers for MDleak® MSleak® DPleak® and
PHDleak® Testing Technologies
Page 3 of 3
5900 Comanche Drive Reference Addendum CONFIDENTIAL
Site Photo