Business Name: Mesa Marin Chevron (15-021-003331)
Date: 05/25/2018 (EPA ID# CAL000349806)
Address Name: 11101 Highway 178, Bakersfield, CA 93306
(661) 366-4886
Inspector Name: Kris Karns ICC# 829402
Inspection Type:
Report :
NVO = No Violation Observed OUT = Out of Compliance NA = Not Applicable UD = Undetermined
COS = Corrected On Site RPT = Repeat Violation
Violation No
Program Requirement
NVO
OUT
NA
UD
COS
RPT
Degree of Violation
SOC
Comments
File Review
Facility Tank Information
2030021
Facility has a valid Permit to Operate from the CUPA - 23 CCR 16 2712(i); HSC 6.7 25284
Tank 1 - 12000 - Reg - DW
Tank 2 - 12000 - Sup - DW
Tank 3 - 12000 - Dies - DW
2010010
UST Operating Permit Application for Facility information and Tank information submitted/maintained - 23 CCR 16 2711; HSC 6.7 25286(a)
2010001
Current BOE number submitted to the CUPA and/or CERS - HSC 6.7 25286(c)
2030011
UST compliance statement and/or Designated Operator current certification submitted - 23 CCR 16 2715(a), 2715(b)
2030046
A complete and accurate response plan has been submitted, approved and maintained - 23 CCR 16 2632, 2634(e), 2641(h), 2712(i)
2030041
A complete and accurate plot plan has been submitted, approved and maintained - 23 CCR 16 2632(d)(1)(C), 2711(a)(8)
2010006
Owner/Operator has not made false statements or representation on any required document - HSC 6.7 25299
2010003
Owner/Operator has a DO and/or informed the CUPA of any change (s) within 30 days - 23 CCR 16 2715(a)
Testing
2030002
Owner/Operator has tested and certified leak detection equipment annually - 23 CCR 16 2638
2030048
Secondary containment testing conducted every 36 months in accordance with requirements - 23 CCR 16 2637
2030055
Spill buckets have been tested annually as required - HSC 6.7 25284.2
2010009
Secondary containment test results submitted to the CUPA within 30 days after the test - 23 CCR 16 2637(e)
2030064
CUPA was poperly notified within the prescribed number of hours prior to testing - 23 CCR 16 2637(f), 2638(e), 2643(g), 2644.1(a)(4)
Install/Repair
2060009
Permits obtained to install, replace, repair, or modify part of the UST system - 23 CCR 16 2712
UST System Observation
General Monitoring
2030003
Leak detection system maintains continuous monitoring that activates an audible and visual alarm - 23 CCR 16 2632, 2634, 2636, 2666
RD
Yes
2030016
The annular space of the tank, piping and sumps are continuously monitored and activates the alarm - 23 CCR 16 2631(g), 2632(c)(2)(A)&(B), 2633(c), 2636(f)
RD
Yes
2030017
Product piping outside the UDC is fail-safe and shuts down the pump or restricts flow - 23 CCR 16 2636(f)(5)
2030018
Turbine sump monitor activates an audible and visual alarm or stops the flow of at the dispenser - 23 CCR 16 2636(f)(1)
RD
Yes
2030019
Monitoring system in the UDCs activates an audible and visual alarm or stops the flow at the UDC - 23 CCR 16 2636(f)(1)
2030043
Leak detection equipment properly programmed or properly operated - 23 CCR 16 2632, 2634, 2636, 2666
RD
Yes
2060005
System constructed with a monitoring system capable of detecting entry into secondary containment - HSC 6.7 25291(b)
2060014
Correct leak detection equipment installed for the type of system present - 23 CCR 16 2638; HSC 6.7 25290.1, 25290.2, 25291
RD
Yes
2060015
Sensor located in the proper position/location - 23 CCR 16 2630(d), 2641(a)
RD
Yes
2030062
Facility is in compliance with not tampering with or disabling leak detection devices or alarms - HSC 6.7 25299(a)(9)
RD
Yes
2060022
System constructed with a monitoring system capable of detecting entry into secondary containment - HSC 6.7 25290.2(d)
2030034
Tag/sticker on affixed monitoring equipment being certified, repaired, or replaced - 23 CCR 16 2638(f)
VPH Monitoring VPH
2030065
Interstitial monitoring of the annular spaces of the UST is properly maintained - HSC 6.7 25290.1(e)
RD
Yes
2060023
System constructed with a monitoring system capable of detecting entry into secondary containment - HSC 6.7 25290.1(d)
Line Leak Detector
2060012
Line leak detector installed on pressurized piping system - HSC 6.7 25290.1(h), 25290.2(g), 25291(f), 25292(e), 2636(f)(2)
RD
Yes
2030026
Line leak detectors detect a 3 gph leak and/or audible and visual alarm function properly - 23 CCR 16 2636(f)(6), 2666(c)
RD
Yes
2030027
Turbine shuts down when a leak is detected or when line leak detector is disconnected - 23 CCR 16 2666(c)
RD
Yes
2030025
Pressurized piping able to detect a 3.0 gph leak within an hour, and restricts the flow or alarms - 23 CCR 16 2636(f)(2)
RD
Yes
Secondary Containment
2060010
UST storing a hazardous substance has secondary containment - HSC 6.7 25292
RD
Yes
2030008
UDC, sumps, and/or other secondary containment in good condition and/or are free of debris/liquid - HSC 6.7 25290.1, 25290.2, 25291
2030040
Secondarily contained piping maintained to allow liquid to drain into sump - 23 CCR 16 2630(d), 2641(a)
RD
Yes
2060006
Secondary containment piping slopes back to the collection sump - 23 CCR 16 263(c)
2030047
Secondary containment maintained tight and has been confirmed by testing - 23 CCR 16 2662; HSC 6.7 25290.1(c)(2), 25290.2(c)(2), 25291(a), 25292(e)
2030060
Entry fittings in secondary containment for UST system maintained tight/sealed - 23 CCR 16 2630, 2635(d), 2636(c), 2666
2060020
Spill bucket is installed and has a functional drain valve or other means to remove liquid - 23 CCR 16 2635(b), 2665
RP
Yes
2030054
Spill bucket maintained in good condition and free of debris and/or liquid - 23 CCR 16 2635(b), 2715(c)(2)
RP
Yes
2060019
Spill bucket to has a minimum capacity of five gallons - 23 CCR 16 2635(b), 2665
Overfill
2030035
UST system is operated to prevent unauthorized release, including spills and overfills - HSC 6.7 25292.1(a)
RP
Yes
2030036
Overfill prevention system has not been overridden and meets overfill requirements - 23 CCR 16 2635(b)(2), 2665
RP
Yes
On Site Records
Certifications
2030023
Required designated operators or contractors maintain a proper and current ICC certification - 23 CCR 16 2715
2030024
Service technician, installer, and/ or employee maintain a proper license - 23 CCR 16 2715
2030031
Employee or contractor obtained and maintained proper manufacturer certification - 23 CCR 16 2715
2010007
Submit/maintain current Certificate of Financial Responsibility/mechanism of financial assurance - 23 CCR 16 2711; 23 CCR 18 2808.1, 2809-2809.2; HSC 6.7 25292.2; HSC 6.75 25299.30-25299.34
Designated Operator
2010004
Copies of DO inspections for last 12 months and list of trained employees maintained - 23 CCR 16 2715
2030013
Designated operator properly conducted the monthly inspection and the reports are complete - 23 CCR 16 2715
2030010
DO notified operator of any condition observed during the monthly inspection that may require action - 23 CCR 16 2715(d)
2030012
DO employee training performed, current for at least one employee on site, and a log kept - 23 CCR 16 2715(c)(6), 2715(f)
Logs
2030001
Leak detection alarm logs, maintenance and records of appropriate follow-up actions maintained - 23 CCR 16 2632, 2634, 2712(b)
RD
Yes
Maintenance/Tests
2010008
Monitoring, maintenance, repairs, linings, and upgrade records maintained for the proper time period - 23 CCR 16 2712(b)
RD
Yes
Documentation
2030033
Failure to maintain on site an approved monitoring plan - 23 CCR 16 2632, 2634, 2711, 2712(i)
2030037
Written agreement between the tank owner and tank operator to monitor the tank system is maintained - 23 CCR 16 2620(b); HSC 6.7 25284(a)(3)
2030061
Suspected or actual unauthorized release reported in appropriate time frame - HSC 6.7 29294, 29295
RD
Yes
General Operating Requirements
Permit Condition/Approval
2030039
Compliance with all operating permit conditions - 23 CCR 16 2712; HSC 6.7 25299
2030059
UST system maintained in accordance with exclusion/exemption status - HSC 6.7 25281.6, 25283.5
2030014
Owner/Operator received approval and has implemented a training program at an unstaffed facility - 23 CCR 16 2715(f)(2)
2030015
Facility exhibited that the method used to monitor the tank meets the monitoring methods in 2643(f) - 23 CCR 16 2643
Red Tag
2030045
Red Tag information is legible and has not been tampered with - 23 CCR 16 2717.1(g)
2030044
Facility did not allow for deposit of petroleum into a UST that has a red tag affixed to the fill - 23 CCR 16 2717.1(f)
Install/Repair
2060024
UST system is made of or lined with materials that are compatible with the substance stored - 23 CCR 16 2631.1
2060021
Striker plate installed and positioned correctly - 23 CCR 16 2631(c), 2662(d)
There were no violations noted for this inspection.
This report shall serve as a “NOTICE TO COMPLY” for Minor Violations, and a “NOTICE OF VIOLATION” for Major violations. You are, hereby, ordered to correct the above noted violations
within 30 days, or according to correction summaries provided. Formal enforcement and/or penalty assessment may be initiated for any violations noted, and for those not corrected in
a timely manner. (NOTE: If this is a preliminary report, a final report will follow.)
Inspectors Signature: ___________________________________ Date: _________________
Inspector: Enter # of Violations: RD: _____ RP: ______
Check one box for facility Significant Operational Status (SOC) to be reported to SWRCB and US EPA:
SOC with both Release Detection and Release Detection (Facility has no Release Prevention and no Release Prevention Violations)
Not in SOC (Facility has both Release Prevention and Release Detection Violations)
SOC with Release Detection only (Facility has no Release Detection violations but one or more Release Prevention violations)
SOC with Release Prevention only (Facility has no Release Prevention violations but one or more Release Detection violations)