HomeMy WebLinkAbout2018 FMC RESULTS10/9/2018 SA004, AT&T Annual Precision Line Testing Notification (BKFDCA12), Bakersfield
https://mail.sa.tait.com/owa/?ae=Item&t=IPM.Appointment&id=PSI.LgAAAAAaRHOQqmYRzZvIAKoAL8RaAwAe4ThZgnHuTb1WdTtldYiuAAAAA%2bj…1/1
SA004, AT&T Annual Precision Line Testing Notification (BKFDCA12), Bakersfield
Simplex Communication Sent: Thursday, June 20, 2013 1:47 PM
Required:RENUK, ALLEN L [ar273x@att.com] ; SANDERS, SEAN T [ss155w@att.com] ; CHAMBERS-OLIVER, KAMBRIN [kc9892@att.com] ;
ATTCATesting@taitenv.onmicrosoft.com; HAYN, CINDY H (ATTSI)' (ch1921@att.com) ; Brian Harmon; Carlos Cardenas; Jennifer
Pruitt; ATT @ Calhaz (ATT@calhaz.com); Maria Figueroa; Pat Banbury
When:Thursday, October 04, 2018 9:00 AM-11:00 AM.Location:1918 M STREET, BAKERSFIELD, CA 93301-4635
Show time as:Busy
Accepted:No attendees have accepted.Tentative:No attendees marked their acceptance Tentative.Declined:No attendees have declined.
Categories:CUPA NOT NOTIFIED; Precision Line Testing; Legacy S Site
Attachments:RE: ***Scheduling Request*** ... (18 KB ) ; Relayed: ***Scheduling Reques... (5 KB ) ; ***Scheduling Request*** AT&T... (923KB ) ; Bakersfield Permit Applica~1.pdf (2 MB )
There is an AT&T Annual Precision Line Test scheduled for this location on the date and time indicated.
SA004 1918 M STREET BAKERSFIELD 93301-4635
TEST DUE DATE 10/11/2018
Same technician for Line Test and Annual MC/SB
Must count the number of solenoid valves on-site.
PERMIT REQUIRED for TESTING
Please contact the Compliance Manager with any ques
10/9/2018 SA004, AT&T Annual Monitor Certification & Spill Bucket Testing Notification (BKFDCA12), Bakersfield
https://mail.sa.tait.com/owa/?ae=Item&t=IPM.Appointment&id=PSI.LgAAAAAaRHOQqmYRzZvIAKoAL8RaAwAe4ThZgnHuTb1WdTtldYiuAAAAA%2bj…1/1
SA004, AT&T Annual Monitor Certification & Spill Bucket Testing Notification
(BKFDCA12), Bakersfield
Simplex Communication Sent: Thursday, June 20, 2013 1:47 PM
Required:RENUK, ALLEN L [ar273x@att.com] ; SANDERS, SEAN T [ss155w@att.com] ; CHAMBERS-OLIVER, KAMBRIN [kc9892@att.com] ;ATTCATesting@taitenv.onmicrosoft.com; HAYN, CINDY H (ATTSI)' (ch1921@att.com) ; Brian Harmon; Carlos Cardenas; JenniferPruitt; ATT @ Calhaz (ATT@calhaz.com); Maria Figueroa; Pat Banbury
When:Thursday, October 04, 2018 9:00 AM-11:00 AM.
Location:1918 M STREET, BAKERSFIELD, CA 93301-4635Show time as:Busy
Accepted:No attendees have accepted.
Tentative:No attendees marked their acceptance Tentative.
Declined:No attendees have declined.
Categories:Annual Monitoring Certification & Spill Bucket Testing; Legacy S Site
Attachments:RE: ***Scheduling Request*** ... (18 KB ) ; Relayed: ***Scheduling Reques... (5 KB ) ; ***Scheduling Request*** AT&T... (923
KB ) ; Bakersfield Permit Applica~1.pdf (2 MB )
There is an AT&T Annual monitor certification and spill bucket test scheduled for this location on the date and time
indicated.
SA004 1918 M STREET BAKERSFIELD 93301-4635
TEST DUE DATE 10/11/2018
PERMIT REQUIRED for TESTING
Please contact the Compliance Manager with any ques
10/11/2018 RE: ***Scheduling Request*** AT&T, Annual Testing - SA004 (MC, SB & PL) & SA098 (MC)
https://mail.sa.tait.com/owa/?ae=Item&t=IPM.Note&id=PSI.LgAAAAAaRHOQqmYRzZvIAKoAL8RaAwAe4ThZgnHuTb1WdTtldYiuAAAAA%2bj2AAAB.…1/2
RE: ***Scheduling Request*** AT&T, Annual Testing - SA004 (MC, SB & PL) &
SA098 (MC)
Kristopher Karns [kkarns@bakersfieldfire.us]
Sent:Thursday, September 06, 2018 7:34 AMTo:Carlos CardenasCc:Matt Denison; Jennifer Pruitt
Thanks for the heads up, those dates and
10/11/2018 RE: ***Scheduling Request*** AT&T, Annual Testing - SA004 (MC, SB & PL) & SA098 (MC)
https://mail.sa.tait.com/owa/?ae=Item&t=IPM.Note&id=PSI.LgAAAAAaRHOQqmYRzZvIAKoAL8RaAwAe4ThZgnHuTb1WdTtldYiuAAAAA%2bj2AAAB.…2/2
ccardenas@tait.com | www.tait.com
This email message, including any attachment(s), is intended only for the recipient(s) named above. It may contain information that is confidential, privileged, or protected by
law. The unlawful use, distribution, or publication of this information is strictly prohibited. If you receive this communication in error, please notify the sender immediately by
return email and delete the original message, including all attachment(s).
&(56 &DOLIRUQLD(QYLURQPHQWDO5HSRUWLQJ6\VWHP,' ,GHQWLILFDWLRQ,&& ,QWHUQDWLRQDO&RGH&RXQFLO< <HV1 1R1$ 1RW$SSOLFDEOH
81'(5*5281'6725$*(7$1.
021,725,1*6<67(0&(57,),&$7,21)2503DJHRI
7KLVIRUPPXVWEHXVHGWRGRFXPHQWWHVWLQJDQGVHUYLFLQJRIXQGHUJURXQGVWRUDJHWDQN867PRQLWRULQJHTXLSPHQW$FRS\
RIWKLVIRUPPXVWEHSURYLGHGWRWKH867RZQHURURSHUDWRU7KHRZQHURURSHUDWRUPXVWVXEPLWDFRS\RIWKLVIRUPWRWKHORFDO
DJHQF\UHJXODWLQJWKH867VZLWKLQGD\VRIWKHGDWHRIWKHPRQLWRULQJV\VWHPFHUWLILFDWLRQ
, )$&,/,7<,1)250$7,21
&(56,''DWHRI0RQLWRULQJ6\VWHP&HUWLILFDWLRQ
%XVLQHVV1DPH(Same as Facility Name or DBA-Doing Business As)
%XVLQHVV6LWH$GGUHVV &LW\ =,3&RGH
,, 81'(5*5281'6725$*(7$1.6(59,&(7(&+1,&,$1,1)250$7,21
1DPHRI&RPSDQ\3HUIRUPLQJWKH&HUWLILFDWLRQ 3KRQH
0DLOLQJ$GGUHVV
1DPHRI8676HUYLFH7HFKQLFLDQ3HUIRUPLQJWKH&HUWLILFDWLRQ(Print as shown on the ICC Certification)
&RQWUDFWRU7DQN7HVWHU/LFHQVH ,&&&HUWLILFDWLRQ ,&&&HUWLILFDWLRQ([SLUDWLRQ'DWH
0RQLWRULQJ6\VWHP7UDLQLQJDQG&HUWLILFDWLRQV(List all applicable certifications.) ([SLUDWLRQ'DWH
,,, 5(68/762)7(67,1*6(59,&,1*
Indicate and attach the following reports if the monitoring equipment is capable of generating either.<11$0RQLWRULQJ6\VWHP6HWXS$ODUP+LVWRU\5HSRUW
:DVDQ\PRQLWRULQJHTXLSPHQWUHSODFHG"
(If “Yes,” identify the specific devices replaced and list the manufacturer and model for all replacement parts in section IV below.)
:DVGDPDJHGHEULVRUOLTXLGIRXQGLQVLGHDQ\VHFRQGDU\FRQWDLQPHQWV\VWHPV"
(If “Yes,” describe what was found in section IV below.)
,VDOOPRQLWRULQJHTXLSPHQWRSHUDWLRQDOSHUPDQXIDFWXUHU¶VVSHFLILFDWLRQV"
(If “No,” describe why in section IV below.)
,9 &200(176
If directed to use this section, describe how and when the issues were or will be corrected.
9 &(57,),&$7,21%<8676(59,&(7(&+1,&,$1&21'8&7,1*7+,67(67,1*
,KHUHE\FHUWLI\WKDWWKHHTXLSPHQWLGHQWLILHGLQWKLVGRFXPHQWZDVLQVSHFWHGVHUYLFHGLQDFFRUGDQFHZLWK&DOLIRUQLD&RGHRI
5HJXODWLRQV7LWOH'LYLVLRQ&KDSWHU6HFWLRQDQGDOOLQIRUPDWLRQFRQWDLQHGKHUHLQLVWUXHDQGDFFXUDWH$WWDFKHGWR
WKLVFHUWLILFDWLRQLVLQIRUPDWLRQHJPDQXIDFWXUHUV
FKHFNOLVWVPRQLWRULQJV\VWHPVHWXSDODUPKLVWRU\UHSRUWHWFQHFHVVDU\
WRYHULI\WKDWWKLVLQIRUPDWLRQDQGWKHVLWHSODQVKRZLQJWKHOD\RXWRI867V\VWHPLVFRPSOHWHDQGDFFXUDWH
8676HUYLFH7HFKQLFLDQ6LJQDWXUH
%XLOGLQJ
SA004
10023349 10/4/2018
Pacific Bell Telephone Co. dba AT&T California SA004
1918 M St.Bakersfield 93301
TAIT Environmental Services, Inc.(714) 560-8222
701 N. Parkcenter Dr., Santa Ana, CA 92705
PATRICK C. BANBURY
588098 5254955 1/4/2019
VEEDER ROOT A20465 6/5/2019
PATRICK C. BANBURY
,' ,GHQWLILFDWLRQ6: 6LQJOH:DOOHG93+ 9DFXXP3UHVVXUH+\GURVWDWLF//' /LQH/HDN'HWHFWRU
81'(5*5281'6725$*(7$1.
021,725,1*6<67(0&(57,),&$7,21)2503DJHRI
9, ,19(1725<2)(48,30(17&(57,),('
A separate Monitoring System Certification Form must be prepared for each monitoring system control panel.
0DNHRI0RQLWRULQJ6\VWHP&RQWURO3DQHO 0RGHORI0RQLWRULQJ6\VWHP&RQWURO3DQHO 6RIWZDUH9HUVLRQ,QVWDOOHG
Check the appropriate boxes to indicate specific equipment inspected/serviced.
0RQLWRULQJ'HYLFH8VHG'HYLFH0RGHO0RQLWRULQJ'HYLFH8VHG'HYLFH0RGHO
7$1.,'
(By tank number, stored product, etc.)
7$1.,'
(By tank number, stored product, etc.)
,Q7DQN*DXJLQJ(SW Tank),Q7DQN*DXJLQJ(SW Tank)
$QQXODU6SDFHRU9DXOW6HQVRU$QQXODU6SDFHRU9DXOW6HQVRU
93+6HQVRU93+6HQVRU
3URGXFW3LSLQJ 3URGXFW3LSLQJ
0HFKDQLFDO//'0HFKDQLFDO//'
(OHFWURQLF//'(OHFWURQLF//'
93+6HQVRU3LSLQJ93+6HQVRU3LSLQJ
6XPS6HQVRU6XPS6HQVRU
93+6HQVRU6XPS93+6HQVRU6XPS
)LOO3LSLQJ )LOO3LSLQJ
93+6HQVRU3LSLQJ93+6HQVRU3LSLQJ
6XPS6HQVRU6XPS6HQVRU
93+6HQVRU6XPS93+6HQVRU6XPS
9HQW3LSLQJ 9HQW3LSLQJ
93+6HQVRU3LSLQJ93+6HQVRU3LSLQJ
6XPS6HQVRU6XPS6HQVRU
93+6HQVRU6XPS93+6HQVRU6XPS
9DSRU5HFRYHU\3LSLQJ 9DSRU5HFRYHU\3LSLQJ
93+6HQVRU3LSLQJ93+6HQVRU3LSLQJ
6XPS6HQVRU6XPS6HQVRU
93+6HQVRU6XPS93+6HQVRU6XPS
0RQLWRULQJ'HYLFH8VHG
'HYLFH0RGHO0RQLWRULQJ'HYLFH8VHG
'HYLFH0RGHO
7$1.,'
(By tank number, stored product, etc.)
7$1.,'
(By tank number, stored product, etc.)
,Q7DQN*DXJLQJ(SW Tank),Q7DQN*DXJLQJ(SW Tank)
$QQXODU6SDFHRU9DXOW6HQVRU$QQXODU6SDFHRU9DXOW6HQVRU
93+6HQVRU93+6HQVRU
3URGXFW3LSLQJ 3URGXFW3LSLQJ
0HFKDQLFDO//'0HFKDQLFDO//'
(OHFWURQLF//'(OHFWURQLF//'
93+6HQVRU3LSLQJ93+6HQVRU3LSLQJ
6XPS6HQVRU6XPS6HQVRU
93+6HQVRU6XPS93+6HQVRU6XPS
)LOO3LSLQJ )LOO3LSLQJ
93+6HQVRU3LSLQJ93+6HQVRU3LSLQJ
6XPS6HQVRU6XPS6HQVRU
93+6HQVRU6XPS93+6HQVRU6XPS
9HQW3LSLQJ 9HQW3LSLQJ
93+6HQVRU3LSLQJ93+6HQVRU3LSLQJ
6XPS6HQVRU6XPS6HQVRU
93+6HQVRU6XPS93+6HQVRU6XPS
9DSRU5HFRYHU\3LSLQJ 9DSRU5HFRYHU\3LSLQJ
93+6HQVRU3LSLQJ93+6HQVRU3LSLQJ
6XPS6HQVRU6XPS6HQVRU
93+6HQVRU6XPS93+6HQVRU6XPS
VEEDER ROOT TLS-350 PLUS 123.01
SA004U001
L1: 794390-420/NA
L3: 794380-208/174617
L2: 794380-208/797241
,' ,GHQWLILFDWLRQ93+ 9DFXXP3UHVVXUH+\GURVWDWLF8'& 8QGHU'LVSHQVHU&RQWDLQPHQW
81'(5*5281'6725$*(7$1.
021,725,1*6<67(0&(57,),&$7,21)2503DJHRI
0RQLWRULQJ'HYLFH8VHG'HYLFH0RGHO0RQLWRULQJ'HYLFH8VHG'HYLFH0RGHO
9(1775$16,7,216803,' 9(1775$16,7,216803,'
6XPS6HQVRU6XPS6HQVRU
93+6HQVRU93+6HQVRU
8'&,' 8'&,'
(OHFWURQLF6HQVRU(OHFWURQLF6HQVRU
0HFKDQLFDO'HYLFH0HFKDQLFDO'HYLFH
93+6HQVRU93+6HQVRU
8'&,' 8'&,'
(OHFWURQLF6HQVRU(OHFWURQLF6HQVRU
0HFKDQLFDO'HYLFH0HFKDQLFDO'HYLFH
93+6HQVRU93+6HQVRU
8'&,'8'&,'
(OHFWURQLF6HQVRU(OHFWURQLF6HQVRU
0HFKDQLFDO'HYLFH0HFKDQLFDO'HYLFH
93+6HQVRU93+6HQVRU
8'&,' 8'&,'
(OHFWURQLF6HQVRU(OHFWURQLF6HQVRU
0HFKDQLFDO'HYLFH0HFKDQLFDO'HYLFH
93+6HQVRU93+6HQVRU
2WKHU0RQLWRUHG&RPSRQHQW,' 2WKHU0RQLWRUHG&RPSRQHQW,'
2WKHU(Specify in section VII.)2WKHU(Specify in section VII.)
2WKHU0RQLWRUHG&RPSRQHQW,' 2WKHU0RQLWRUHG&RPSRQHQW,'
2WKHU(Specify in section VII.)2WKHU(Specify in section VII.)
2WKHU0RQLWRUHG&RPSRQHQW,' 2WKHU0RQLWRUHG&RPSRQHQW,'
2WKHU(Specify in section VII.)2WKHU(Specify in section VII.)
Include information for every underground storage tank component monitored by this monitoring system control panel. If the monitoring system
control panel monitors more components than this form accommodates, additional copies of these pages may be attached.
9,, &200(176
Use this section to provide additional comments about the inventory of the equipment certified.
SA004U001
SA004U001
SA004U001
Piping Transition Sump Overfill Alarm
Day Tank Containment
SA004U001
SA004U001
TLM Probe
Generator Floor
Other: L4: Piping Transition Sump Sensor 794380-208/NA.
Other: L5: Day Tank Containment Sensor 794380-208/930304.
Other: L6: Generator Room Floor Sensor 794380-208/930141.
Other: Overfill Alarm 790091-001.
Other: TLM Probe 846390-109/729482
< <HV1 1R1$ 1RW$SSOLFDEOH
81'(5*5281'6725$*(7$1.
021,725,1*6<67(0&(57,),&$7,21)2503DJHRI
9,,, 021,725,1*6<67(0$1'352*5$00,1*
This section must be completed if a monitoring panel is used to perform leak detection monitoring.<11$
$UHWKHYLVXDODQGDXGLEOHDODUPVRSHUDWLRQDO"
:HUHDOOVHQVRUVYLVXDOO\LQVSHFWHGIRUNLQNVDQGEUHDNVLQWKHFDEOHVDQGIRUUHVLGXDOEXLOGXSWRHQVXUHWKDWIORDWVPRYHIUHHO\
IXQFWLRQDOO\WHVWHGDQGFRQILUPHGRSHUDWLRQDO"
:HUHDOOVHQVRUVLQVWDOOHGDWORZHVWSRLQWRIVHFRQGDU\FRQWDLQPHQWDQGSRVLWLRQHGVRWKDWRWKHUHTXLSPHQWZLOOQRWLQWHUIHUHZLWK
WKHLUSURSHURSHUDWLRQ"
:DVPRQLWRULQJV\VWHPVHWXSUHYLHZHGWRHQVXUHSURSHUVHWWLQJV"
:DVWKHPRQLWRULQJSDQHO¶VEDFNXSEDWWHU\YLVXDOO\LQVSHFWHGIXQFWLRQDOO\WHVWHGDQGFRQILUPHGRSHUDWLRQDO"
'RHVWKHIORZRIIXHOVWRSDWWKHGLVSHQVHULIDOHDNLVGHWHFWHGLQWKHXQGHUGLVSHQVHUFRQWDLQPHQW"
'RHVWKHWXUELQHDXWRPDWLFDOO\VKXWGRZQLIWKHSLSLQJVHFRQGDU\FRQWDLQPHQWPRQLWRULQJV\VWHPIDLOVWRRSHUDWHRULVHOHFWULFDOO\
GLVFRQQHFWHG"
'RHVWKHWXUELQHDXWRPDWLFDOO\VKXWGRZQLIWKHSLSLQJVHFRQGDU\FRQWDLQPHQWPRQLWRULQJV\VWHPGHWHFWVDOHDN"
:KLFKVHQVRUVLQLWLDWHSRVLWLYHVKXWGRZQ"(Check all that apply.)6XPS8QGHU'LVSHQVHU&RQWDLQPHQW
,IDODUPVDUHUHOD\HGWRDUHPRWHPRQLWRULQJVWDWLRQLVDOOFRPPXQLFDWLRQVHTXLSPHQWHJPRGHPRSHUDWLRQDO"
For any answer of “N” above, describe in Section IX how and when these deficiencies were or will be corrected.
,; &200(176
; ,17$1.*$8*,1*7(67,1*
&KHFNWKLVER[LIWDQNJDXJLQJLVXVHGRQO\IRULQYHQWRU\FRQWURO(Do not complete this section.)
<11$&KHFNWKLVER[LI12WDQNJDXJLQJHTXLSPHQWLVLQVWDOOHG (Do not complete this section.)
This section must be completed if in-tank gauging is used to perform leak detection monitoring.
+DVDOOLQSXWZLULQJEHHQLQVSHFWHGIRUNLQNVDQGEUHDNVLQWKHFDEOHVDQGIRUSURSHUHQWU\DQGWHUPLQDWLRQLQFOXGLQJWHVWLQJIRU
JURXQGIDXOWV"
:HUHDOOLQWDQNJDXJLQJSUREHVYLVXDOO\LQVSHFWHGIRUGDPDJHDQGUHVLGXHEXLOGXSWRHQVXUHWKDWIORDWVPRYHIUHHO\IXQFWLRQDOO\
WHVWHGDQGFRQILUPHGRSHUDWLRQDO"
:DVDFFXUDF\RIV\VWHP¶VSURGXFWOHYHOUHDGLQJVWHVWHG"
:DVDFFXUDF\RIV\VWHP¶VZDWHUOHYHOUHDGLQJVWHVWHG"
:HUHDOOSUREHVUHLQVWDOOHGSURSHUO\"
:HUHDOOLWHPVRQWKHHTXLSPHQWPDQXIDFWXUHU¶VPDLQWHQDQFHFKHFNOLVWFRPSOHWHG"
For any answer of “N” above, describe in Section XI how and when these deficiencies were or will be corrected.
;, &200(176
Backup Generator System.
*3+ *DOORQV3HU+RXU< <HV1 1R1$ 1RW$SSOLFDEOH93+ 9DFXXP3UHVVXUH+\GURVWDWLF,' ,GHQWLILFDWLRQ
81'(5*5281'6725$*(7$1.
021,725,1*6<67(0&(57,),&$7,21)2503DJHRI
;,, /,1(/($.'(7(&7257(67,1*
&KHFNWKLVER[LIOLQHOHDNGHWHFWRUV//'DUH127LQVWDOOHG(Do not complete this section.)<11$This section must be completed if LLDs are installed.
:DVDOHDNVLPXODWHGWRYHULI\//'SHUIRUPDQFH"
(Check all that apply.)6LPXODWHGOHDNUDWHYHULILHG*3+*3+*3+
:DVWKHWHVWLQJDSSDUDWXVSURSHUO\FDOLEUDWHG"
)RUHPHUJHQF\JHQHUDWRUWDQNV\VWHPVGRHVWKH//'FUHDWHDQDXGLEOHDQGYLVXDODODUPZKHQDOHDNLVGHWHFWHG"
)RUPHFKDQLFDO//'VGRHVWKH//'UHVWULFWWKHIORZWKURXJKWKHSLSHZKHQDOHDNLVGHWHFWHG"
)RUHOHFWURQLF//'VGRHVWKHWXUELQHDXWRPDWLFDOO\VKXWRIIZKHQDOHDNLVGHWHFWHG"
)RUHOHFWURQLF//'VGRHVWKHWXUELQHDXWRPDWLFDOO\VKXWRIILIDQ\SRUWLRQRIWKHPRQLWRULQJV\VWHPLVGLVDEOHGRUGLVFRQQHFWHG"
)RUHOHFWURQLF//'VGRHVWKHWXUELQHDXWRPDWLFDOO\VKXWRIILIDQ\SRUWLRQRIWKHPRQLWRULQJV\VWHPPDOIXQFWLRQVRUIDLOVDWHVW"
)RUHOHFWURQLF//'VKDYHDOODFFHVVLEOHZLULQJFRQQHFWLRQVEHHQYLVXDOO\LQVSHFWHGIRUNLQNVDQGEUHDNV"
:HUHDOOLWHPVRQWKHHTXLSPHQWPDQXIDFWXUHU¶VPDLQWHQDQFHFKHFNOLVWFRPSOHWHG"
:HUHDOO//'VFRQILUPHGRSHUDWLRQDOZLWKLQUHJXODWRU\UHTXLUHPHQWV"
For any answer of “N” above, describe in Section XIII how and when these issues were or will be corrected.
;,,, &200(176
;,9 9$&88035(6685(+<'5267$7,&021,725,1*(48,30(177(67,1*
&KHFNWKLVER[LI93+PRQLWRULQJLV127XVHG(Do not complete this section.)
This section must be completed if VPH monitoring is used to perform leak detection monitoring.
6\VWHP7\SH0DUNDOOWKDWDSSO\9DFXXP3UHVVXUH+\GURVWDWLF
6HQVRU,'&RPSRQHQW60RQLWRUHG%\7KLV6HQVRU 6HQVRU)XQFWLRQDOLW\
7HVW
,QWHUVWLWLDO&RPPXQLFDWLRQ
7HVW
3DVV )DLO 3DVV )DLO
3DVV)DLO3DVV)DLO
3DVV)DLO3DVV)DLO
3DVV)DLO3DVV)DLO
3DVV)DLO3DVV)DLO
3DVV)DLO3DVV)DLO
3DVV)DLO3DVV)DLO
3DVV)DLO3DVV)DLO
3DVV)DLO3DVV)DLO
3DVV)DLO3DVV)DLO
3DVV)DLO3DVV)DLO
3DVV)DLO3DVV)DLO
+RZZDVLQWHUVWLWLDOFRPPXQLFDWLRQYHULILHG"6LPXODWHG/HDNDW)DU(QGVRIWKH,QWHUVWLWLDO6SDFH9LVXDO,QVSHFWLRQ
2WKHU(Describe the method in section XV below.)*DXJH
:DVWKHYDFXXPRUSUHVVXUHUHVWRUHGWRRSHUDWLQJOHYHOVLQDOOLQWHUVWLWLDOVSDFHV"<HV1R(Describe the reason in section XV below.)
For any answer of “Fail” above, describe in Section XV how and when these issues were or will be corrected.
;9 &200(176
81'(5*5281'6725$*(7$1.
021,725,1*6<67(0&(57,),&$7,21)2503DJHRI
;9, 021,725,1*6,7(3/$1
'DWHVLWHPDSZDVSUHSDUHG
If you already have a site plan that shows all required information, you may include it, rather than this page, with your Monitoring System
Certification Form. The site plan must show the general layout of tanks and piping and clearly identify locations of the following equipment,
if installed: 1) monitoring system control panels; 2) in-tank liquid level probes (if used for leak detection); 3) devices monitoring tank
annular spaces or vault; 4) devices monitoring product piping; 5) devices monitoring fill piping; 6) devices monitoring vent piping; 7) devices
monitoring vapor recovery piping; 8) devices monitoring vent/transition sumps; 9) devices monitoring under-dispenser containment; 10)
line leak detectors; and 11) devices monitoring any other secondary containment areas.
/(*(1'
10/4/2018
81'(5*5281'6725$*(7$1.
63,//&217$,1(57(67,1*5(3257)2503DJHRI
7\SHRI$FWLRQ,QVWDOODWLRQ7HVW5HSDLU7HVW0RQWK7HVW
, )$&,/,7<,1)250$7,21
&(56,''DWHRI6SLOO&RQWDLQHU7HVW
%XVLQHVV1DPH(Same as Facility Name or DBA-Doing Business As)
%XVLQHVV6LWH$GGUHVV &LW\ =,3&RGH
,, 81'(5*5281'6725$*(7$1.6(59,&(7(&+1,&,$1,1)250$7,21
1DPHRI8676HUYLFH7HFKQLFLDQ3HUIRUPLQJWKH7HVW(Print as shown on the ICC Certification.) 3KRQH
&RQWUDFWRU7DQN7HVWHU/LFHQVH ,&&&HUWLILFDWLRQ ,&&&HUWLILFDWLRQ([SLUDWLRQ'DWH
6SLOO&RQWDLQHU7HVWLQJ7UDLQLQJDQG&HUWLILFDWLRQV(List applicable certifications.)
,,, 63,//&217$,1(57(67,1*,1)250$7,21
7HVW0HWKRG8VHG0DQXIDFWXUHU*XLGHOLQHV(Specify)
,QGXVWU\&RGHRU(QJLQHHULQJ6WDQGDUG (Specify)
(QJLQHHUHG0HWKRG(Specify)
Attach the testing procedures and all documentation required to determine the results.RI$WWDFKHG3DJHV
7$1.,'(By tank number, stored product, etc.)
6SLOO&RQWDLQHU0DQXIDFWXUHU
0HWKRGRI&DWKRGLF3URWHFWLRQ1RQ0HWDOOLF1RQ0HWDOOLF1RQ0HWDOOLF1RQ0HWDOOLF
,VRODWLRQ,VRODWLRQ,VRODWLRQ,VRODWLRQ
2WKHU(Specify in V.)2WKHU(Specify in V.)2WKHU(Specify in V.)2WKHU(Specify in V.)
,QVLGH'LDPHWHURI6SLOO&RQWDLQHU(Inches)
'HSWKRI6SLOO&RQWDLQHU(Inches)
'RHVWKHVSLOOFRQWDLQHUKDYHDJDOORQFDSDFLW\"<HV1R<HV1R<HV1R<HV1R
0HWKRGWR.HHS6SLOO&RQWDLQHU(PSW\'UDLQ9DOYH'UDLQ9DOYH'UDLQ9DOYH'UDLQ9DOYH
2QVLWH3XPS2QVLWH3XPS2QVLWH3XPS2QVLWH3XPS
2WKHU(Specify in V.)2WKHU(Specify in V.)2WKHU(Specify in V.)2WKHU(Specify in V.)
,9 6800$5<2)7(67,1*5(68/76
6SLOO&RQWDLQHU7HVW5HVXOWV3DVV)DLO3DVV)DLO3DVV)DLO3DVV)DLO
9 &200(176
Any items marked “Fail” above must be explained in this section. Any additional comments may also be provided here.
9, &(57,),&$7,21%<8676(59,&(7(&+1,&,$1&21'8&7,1*7+,67(67,1*
,KHUHE\FHUWLI\WKDWWKHVSLOOFRQWDLQHUVZHUHWHVWHGLQDFFRUGDQFHZLWK&DOLIRUQLD&RGHRI5HJXODWLRQV7LWOH'LYLVLRQ
&KDSWHU6HFWLRQDQGDOOWKHLQIRUPDWLRQFRQWDLQHGKHUHLQLVDFFXUDWH
8676HUYLFH7HFKQLFLDQ6LJQDWXUH
If the facility has more components than this form accommodates, additional copies of this page may be attached.
&(56 &DOLIRUQLD(QYLURQPHQWDO5HSRUWLQJ6\VWHP,' ,GHQWLILFDWLRQ867 8QGHUJURXQG6WRUDJH7DQN,&& ,QWHUQDWLRQDO&RGH&RXQFLO
WC135
10032505 10/9/2018
Pacific Bell Telephone Co. dba AT&T California
350 Alameda Del Prado Novato 94949
Gage Hart (714) 560-8222
588098 8361014 06/12/2019
Hydrostatic
Tape Measure
WC135U001
Phil-Tite
11"
15"
Test Start Time 9:07AM
Begin Level 14"
Test End Time 10:07AM
End Level 14"
Gage Hart
I50301
OCT 5, 2018 6:35 AM
# 1:BKFDCA12 SA004 S-S
I50302
OCT 5, 2018 6:35 AM
# 2:1918 M ST.
I50303
OCT 5, 2018 6:35 AM
# 3:BAKERSFIELD,CA 93301
I50304
OCT 5, 2018 6:35 AM
# 4:661-631-2540
I51700
OCT 5, 2018 6:35 AM
SYSTEM TYPE AND LANGUAGE FLAG
SYSTEM UNITS
U.S.
SYSTEM LANGUAGE
ENGLISH
SYSTEM DATE/TIME FORMAT
MON DD YYYY HH:MM:SS xM
I50F00
OCT 5, 2018 6:35 AM
MON DD YYYY HH:MM:SS xM
I10200
OCT 5, 2018 6:35 AM
BKFDCA12 SA004 S-S
1918 M ST.
BAKERSFIELD,CA 93301
661-631-2540
SYSTEM CONFIGURATION
SLOT BOARD TYPE POWER ON RESET CURRENT
1 4 PROBE / G.T. 163858 162765
2 INTERSTITIAL BD 201571 200899
3 UNUSED 9807749 9744713
4 UNUSED 9779270 9727413
5 UNUSED 9773701 9731372
6 UNUSED 9777894 9736337
7 UNUSED 9762690 9731110
8 UNUSED 9771838 9731569
9 COMBO I/O BOARD 9933 9942
10 COMBO I/O BOARD 9955 9964
11 UNUSED 9777370 9744685
12 UNUSED 9766698 9736899
13 UNUSED 9769260 9735325
14 UNUSED 9767566 9737031
15 UNUSED 9766910 9735521
16 UNUSED 9765364 9736046
COMM 1 FAXMODEM BOARD 40262 40235
COMM 2 UNUSED 9774427 9746632
COMM 3 UNUSED 9760324 9733947
COMM 4 UNUSED 9766571 9727736
COMM 5 UNUSED 9764941 9733881
COMM 6 UNUSED 9764496 9722093
I60100
OCT 5, 2018 6:36 AM
TANK CONFIGURATION
DEVICE LABEL CONFIGURED
1 DIESEL TK#SA004U001 ON
2 OFF
3 OFF
4 OFF
I60200
OCT 5, 2018 6:36 AM
TANK PRODUCT LABEL
TANK PRODUCT LABEL
1 DIESEL TK#SA004U001
2
3
4
I60300
OCT 5, 2018 6:36 AM
TANK PRODUCT CODE
TANK PRODUCT LABEL
1 DIESEL TK#SA004U001 1
2 2
3 3
4 4
I60400
OCT 5, 2018 6:36 AM
TANK FULL VOLUME
TANK PRODUCT LABEL GALLONS
1 DIESEL TK#SA004U001 20149
2 0
3 0
4 0
I60700
OCT 5, 2018 6:36 AM
TANK DIAMETER
TANK PRODUCT LABEL INCHES
1 DIESEL TK#SA004U001 114.00
2 0.00
3 0.00
4 0.00
I60900
OCT 5, 2018 6:36 AM
TANK THERMAL COEFFICIENT
TANK PRODUCT LABEL
1 DIESEL TK#SA004U001 0.000450
2 0.000000
3 0.000000
4 0.000000
I61200
OCT 5, 2018 6:36 AM
TANK MANIFOLDED PARTNERS
TANK PRODUCT LABEL SIPHON MANIFOLDED TANKS LINE MANIFOLDED TANKS
1 DIESEL TK#SA004U001 NONE NONE
2 NONE NONE
3 NONE NONE
4 NONE NONE
I62100
OCT 5, 2018 6:36 AM
TANK LOW PRODUCT LIMIT
TANK PRODUCT LABEL GALLONS
1 DIESEL TK#SA004U001 9000
2 0
3 0
4 0
I62200
OCT 5, 2018 6:36 AM
TANK HIGH PRODUCT LIMIT
TANK PRODUCT LABEL GALLONS
1 DIESEL TK#SA004U001 19141
2 0
3 0
4 0
I62300
OCT 5, 2018 6:36 AM
TANK OVERFILL LEVEL LIMIT
TANK PRODUCT LABEL GALLONS
1 DIESEL TK#SA004U001 18134
2 0
3 0
4 0
I62400
OCT 5, 2018 6:36 AM
TANK HIGH WATER LEVEL LIMIT
TANK PRODUCT LABEL INCHES
1 DIESEL TK#SA004U001 2.0
I62800
OCT 5, 2018 6:36 AM
TANK MAXIMUM VOLUME LIMIT
TANK PRODUCT LABEL GALLONS
1 DIESEL TK#SA004U001 20149
2 0
3 0
4 0
I62900
OCT 5, 2018 6:36 AM
TANK DELIVERY REQUIRED LIMIT
TANK PRODUCT LABEL GALLONS
1 DIESEL TK#SA004U001 9000
2 0
3 0
4 0
I70300
OCT 5, 2018 6:37 AM
LIQUID TYPE
SENSOR LOCATION TYPE
1 ANNULAR SPACE TRI-STATE (SINGLE FLOAT)
2 FILL SUMP TRI-STATE (SINGLE FLOAT)
3 PIPING SUMP TRI-STATE (SINGLE FLOAT)
4 TRANSITION SUMP TRI-STATE (SINGLE FLOAT)
5 DAY TANK CONTAINMENT TRI-STATE (SINGLE FLOAT)
6 GEN ROOM FLOOR TRI-STATE (SINGLE FLOAT)
7 TRI-STATE (SINGLE FLOAT)
8 TRI-STATE (SINGLE FLOAT)
I90200
OCT 5, 2018 6:38 AM
SOFTWARE REVISION LEVEL
VERSION 123.01
SOFTWARE# 346123-100-B
CREATED - 02.06.21.13.00
S-MODULE# 330160-002-A
SYSTEM FEATURES:
PERIODIC IN-TANK TESTS
ANNUAL IN-TANK TESTS
CSLD
I11100
OCT 5, 2018 6:38 AM
BKFDCA12 SA004 S-S
1918 M ST.
BAKERSFIELD,CA 93301
661-631-2540
PRIORITY ALARM HISTORY
ID CATEGORY DESCRIPTION ALARM TYPE STATE DATE TIME
T 1 TANK DIESEL TK#SA004U001 HIGH WATER ALARM CLEAR 10-04-18 11:00AM
T 1 TANK DIESEL TK#SA004U001 PROBE OUT CLEAR 10-04-18 10:56AM
T 1 TANK DIESEL TK#SA004U001 OVERFILL ALARM CLEAR 10-04-18 10:56AM
T 1 TANK DIESEL TK#SA004U001 PROBE OUT ALARM 10-04-18 10:56AM
T 1 TANK DIESEL TK#SA004U001 OVERFILL ALARM ALARM 10-04-18 10:55AM
T 1 TANK DIESEL TK#SA004U001 LOW PRODUCT ALARM CLEAR 10-04-18 10:55AM
T 1 TANK DIESEL TK#SA004U001 HIGH WATER ALARM ALARM 10-04-18 10:44AM
T 1 TANK DIESEL TK#SA004U001 PROBE OUT CLEAR 10-04-18 10:40AM
T 1 TANK DIESEL TK#SA004U001 PROBE OUT ALARM 10-04-18 10:39AM
T 1 TANK DIESEL TK#SA004U001 LOW PRODUCT ALARM ALARM 10-04-18 10:39AM
L 6 OTHER GEN ROOM FLOOR FUEL ALARM CLEAR 10-04-18 10:34AM
L 6 OTHER GEN ROOM FLOOR FUEL ALARM ALARM 10-04-18 10:30AM
L 5 OTHER DAY TANK CONTAINMENT FUEL ALARM CLEAR 10-04-18 10:23AM
L 5 OTHER DAY TANK CONTAINMENT FUEL ALARM ALARM 10-04-18 10:21AM
L 4 OTHER TRANSITION SUMP FUEL ALARM CLEAR 10-04-18 10:11AM
L 4 OTHER TRANSITION SUMP FUEL ALARM ALARM 10-04-18 10:09AM
L 3 STP SUMP PIPING SUMP FUEL ALARM CLEAR 10-04-18 10:08AM
L 3 STP SUMP PIPING SUMP FUEL ALARM ALARM 10-04-18 10:03AM
L 2 OTHER FILL SUMP FUEL ALARM CLEAR 10-04-18 10:03AM
L 2 OTHER FILL SUMP FUEL ALARM ALARM 10-04-18 9:59AM
L 1 ANNULAR ANNULAR SPACE FUEL ALARM CLEAR 10-04-18 9:57AM
L 1 ANNULAR ANNULAR SPACE FUEL ALARM ALARM 10-04-18 9:54AM
I 3 INPUT GEN RUN EXTERN INPUT ALARM CLEAR 9-26-18 1:47PM
I 3 INPUT GEN RUN EXTERN INPUT ALARM ALARM 9-26-18 1:09PM
I 3 INPUT GEN RUN EXTERN INPUT ALARM CLEAR 9-19-18 6:51AM
I 3 INPUT GEN RUN EXTERN INPUT ALARM ALARM 9-19-18 5:37AM
I 3 INPUT GEN RUN EXTERN INPUT ALARM CLEAR 8-13-18 11:21AM
I 2 INPUT PUMP RUN EXTERN INPUT ALARM CLEAR 8-13-18 11:19AM
I 2 INPUT PUMP RUN EXTERN INPUT ALARM ALARM 8-13-18 11:09AM
I 3 INPUT GEN RUN EXTERN INPUT ALARM ALARM 8-13-18 10:45AM
I 3 INPUT GEN RUN EXTERN INPUT ALARM CLEAR 8-07-18 6:29AM
I 3 INPUT GEN RUN EXTERN INPUT ALARM ALARM 8-07-18 5:23AM
I 3 INPUT GEN RUN EXTERN INPUT ALARM CLEAR 7-10-18 6:33AM
I 3 INPUT GEN RUN EXTERN INPUT ALARM ALARM 7-10-18 5:28AM
L 5 OTHER DAY TANK CONTAINMENT FUEL ALARM CLEAR 6-18-18 10:07AM
L 5 OTHER DAY TANK CONTAINMENT FUEL ALARM ALARM 6-18-18 10:06AM
L 6 OTHER GEN ROOM FLOOR FUEL ALARM CLEAR 6-18-18 10:04AM
L 6 OTHER GEN ROOM FLOOR FUEL ALARM ALARM 6-18-18 10:02AM
T 1 TANK DIESEL TK#SA004U001 PROBE OUT CLEAR 6-18-18 9:42AM
T 1 TANK DIESEL TK#SA004U001 OVERFILL ALARM CLEAR 6-18-18 9:41AM
T 1 TANK DIESEL TK#SA004U001 PROBE OUT ALARM 6-18-18 9:41AM
T 1 TANK DIESEL TK#SA004U001 OVERFILL ALARM ALARM 6-18-18 9:40AM
T 1 TANK DIESEL TK#SA004U001 LOW PRODUCT ALARM CLEAR 6-18-18 9:40AM
T 1 TANK DIESEL TK#SA004U001 HIGH WATER ALARM CLEAR 6-18-18 9:38AM
T 1 TANK DIESEL TK#SA004U001 HIGH WATER ALARM ALARM 6-18-18 9:33AM
T 1 TANK DIESEL TK#SA004U001 LOW PRODUCT ALARM ALARM 6-18-18 9:17AM
T 1 TANK DIESEL TK#SA004U001 PROBE OUT CLEAR 6-18-18 9:17AM
T 1 TANK DIESEL TK#SA004U001 PROBE OUT ALARM 6-18-18 9:16AM
L 4 OTHER TRANSITION SUMP FUEL ALARM CLEAR 6-18-18 9:06AM
L 4 OTHER TRANSITION SUMP FUEL ALARM ALARM 6-18-18 9:06AM
I11200
OCT 5, 2018 6:39 AM
BKFDCA12 SA004 S-S
1918 M ST.
BAKERSFIELD,CA 93301
661-631-2540
NON-PRIORITY ALARM HISTORY
ID CATEGORY DESCRIPTION ALARM TYPE STATE DATE TIME
T 1 TANK DIESEL TK#SA004U001 HIGH WATER WARNING CLEAR 10-04-18 11:00AM
T 1 TANK DIESEL TK#SA004U001 DELIVERY NEEDED CLEAR 10-04-18 10:55AM
T 1 TANK DIESEL TK#SA004U001 HIGH WATER WARNING ALARM 10-04-18 10:44AM
T 1 TANK DIESEL TK#SA004U001 DELIVERY NEEDED ALARM 10-04-18 10:39AM
SYSTEM PRINTER ERROR CLEAR 10-04-18 8:47AM
SYSTEM PRINTER ERROR ALARM 10-04-18 8:47AM
SYSTEM PRINTER ERROR CLEAR 6-18-18 10:22AM
SYSTEM PRINTER ERROR ALARM 6-18-18 10:22AM
T 1 TANK DIESEL TK#SA004U001 DELIVERY NEEDED CLEAR 6-18-18 9:40AM
T 1 TANK DIESEL TK#SA004U001 HIGH WATER WARNING CLEAR 6-18-18 9:38AM
T 1 TANK DIESEL TK#SA004U001 HIGH WATER WARNING ALARM 6-18-18 9:33AM
T 1 TANK DIESEL TK#SA004U001 DELIVERY NEEDED ALARM 6-18-18 9:17AM
SYSTEM PRINTER ERROR CLEAR 10-11-17 10:31AM
SYSTEM PAPER OUT CLEAR 10-11-17 10:31AM
SYSTEM PRINTER ERROR ALARM 10-11-17 10:30AM
SYSTEM PAPER OUT ALARM 10-11-17 10:30AM
T 1 TANK DIESEL TK#SA004U001 HIGH WATER WARNING CLEAR 10-11-17 10:14AM
T 1 TANK DIESEL TK#SA004U001 DELIVERY NEEDED CLEAR 10-11-17 10:09AM
T 1 TANK DIESEL TK#SA004U001 HIGH WATER WARNING ALARM 10-11-17 10:01AM
T 1 TANK DIESEL TK#SA004U001 DELIVERY NEEDED ALARM 10-11-17 9:56AM
SYSTEM PRINTER ERROR CLEAR 8-03-17 12:11PM
SYSTEM PRINTER ERROR ALARM 8-03-17 12:10PM
T 1 TANK DIESEL TK#SA004U001 DELIVERY NEEDED CLEAR 8-03-17 11:58AM
T 1 TANK DIESEL TK#SA004U001 DELIVERY NEEDED ALARM 8-03-17 6:19AM
SYSTEM PRINTER ERROR CLEAR 8-03-17 6:04AM
SYSTEM PRINTER ERROR ALARM 8-03-17 6:03AM
T 1 TANK DIESEL TK#SA004U001 DELIVERY NEEDED CLEAR 12-29-16 8:23AM
T 1 TANK DIESEL TK#SA004U001 DELIVERY NEEDED ALARM 12-24-16 10:54PM
SYSTEM PRINTER ERROR CLEAR 10-25-16 10:36AM
SYSTEM PRINTER ERROR ALARM 10-25-16 10:36AM
T 1 TANK DIESEL TK#SA004U001 HIGH WATER WARNING CLEAR 10-25-16 9:24AM
T 1 TANK DIESEL TK#SA004U001 DELIVERY NEEDED CLEAR 10-25-16 9:19AM
T 1 TANK DIESEL TK#SA004U001 HIGH WATER WARNING ALARM 10-25-16 9:16AM
T 1 TANK DIESEL TK#SA004U001 DELIVERY NEEDED ALARM 10-25-16 9:09AM
T 1 TANK DIESEL TK#SA004U001 DELIVERY NEEDED CLEAR 6-22-16 8:38AM
T 1 TANK DIESEL TK#SA004U001 INVALID FUEL LEVEL CLEAR 6-22-16 5:43AM
T 1 TANK DIESEL TK#SA004U001 DELIVERY NEEDED ALARM 6-21-16 11:54AM
T 1 TANK DIESEL TK#SA004U001 INVALID FUEL LEVEL ALARM 6-21-16 11:53AM
SYSTEM PRINTER ERROR CLEAR 6-21-16 6:04AM
SYSTEM PRINTER ERROR ALARM 6-21-16 6:03AM
SYSTEM PRINTER ERROR CLEAR 6-20-16 2:47PM
SYSTEM PRINTER ERROR ALARM 6-20-16 2:47PM
T 1 TANK DIESEL TK#SA004U001 LOW TEMP WARNING CLEAR 6-20-16 2:33PM
T 1 TANK DIESEL TK#SA004U001 LOW TEMP WARNING ALARM 6-20-16 2:32PM
SYSTEM PRINTER ERROR CLEAR 6-20-16 9:16AM
SYSTEM PRINTER ERROR ALARM 6-20-16 9:15AM
T 1 TANK DIESEL TK#SA004U001 LOW TEMP WARNING CLEAR 2-02-16 8:40AM
T 1 TANK DIESEL TK#SA004U001 LOW TEMP WARNING ALARM 2-02-16 8:38AM
T 1 TANK DIESEL TK#SA004U001 HIGH WATER WARNING CLEAR 11-11-15 9:58AM
T 1 TANK DIESEL TK#SA004U001 HIGH PRODUCT ALARM CLEAR 11-11-15 9:56AM
I20600
OCT 5, 2018 6:40 AM
BKFDCA12 SA004 S-S
1918 M ST.
BAKERSFIELD,CA 93301
661-631-2540
TANK ALARM HISTORY
TANK 1 DIESEL TK#SA004U001
HIGH WATER ALARM OCT 4, 2018 10:44 AM
JUN 18, 2018 9:33 AM
OCT 11, 2017 10:01 AM
OVERFILL ALARM OCT 4, 2018 10:55 AM
JUN 18, 2018 9:40 AM
OCT 11, 2017 10:09 AM
LOW PRODUCT ALARM OCT 4, 2018 10:39 AM
JUN 18, 2018 9:17 AM
OCT 11, 2017 9:56 AM
HIGH PRODUCT ALARM NOV 11, 2015 9:51 AM
MAR 2, 2015 9:11 AM
DEC 2, 2014 10:29 AM
INVALID FUEL LEVEL JUN 21, 2016 11:53 AM
DEC 12, 2013 9:45 AM
AUG 29, 2012 3:13 AM
PROBE OUT OCT 4, 2018 10:56 AM
OCT 4, 2018 10:39 AM
JUN 18, 2018 9:41 AM
HIGH WATER WARNING OCT 4, 2018 10:44 AM
JUN 18, 2018 9:33 AM
OCT 11, 2017 10:01 AM
DELIVERY NEEDED OCT 4, 2018 10:39 AM
JUN 18, 2018 9:17 AM
OCT 11, 2017 9:56 AM
MAX PRODUCT ALARM NOV 11, 2015 9:52 AM
MAR 2, 2015 9:11 AM
JAN 30, 2013 3:27 PM
LOW TEMP WARNING JUN 20, 2016 2:32 PM
FEB 2, 2016 8:38 AM
MAR 2, 2015 9:13 AM
I30200
OCT 5, 2018 6:41 AM
BKFDCA12 SA004 S-S
1918 M ST.
BAKERSFIELD,CA 93301
661-631-2540
LIQUID ALARM HISTORY REPORT
SENSOR LOCATION
1 ANNULAR SPACE
OCT 4, 2018 9:54 AM FUEL ALARM
JUN 18, 2018 8:49 AM FUEL ALARM
OCT 11, 2017 9:46 AM FUEL ALARM
2 FILL SUMP
OCT 4, 2018 9:59 AM FUEL ALARM
JUN 18, 2018 8:54 AM FUEL ALARM
OCT 11, 2017 9:39 AM FUEL ALARM
3 PIPING SUMP
OCT 4, 2018 10:03 AM FUEL ALARM
JUN 18, 2018 9:00 AM FUEL ALARM
OCT 11, 2017 9:32 AM FUEL ALARM
4 TRANSITION SUMP
OCT 4, 2018 10:09 AM FUEL ALARM
JUN 18, 2018 9:06 AM FUEL ALARM
OCT 11, 2017 9:26 AM FUEL ALARM
5 DAY TANK CONTAINMENT
OCT 4, 2018 10:21 AM FUEL ALARM
JUN 18, 2018 10:06 AM FUEL ALARM
OCT 11, 2017 9:14 AM FUEL ALARM
6 GEN ROOM FLOOR
OCT 4, 2018 10:30 AM FUEL ALARM
JUN 18, 2018 10:02 AM FUEL ALARM
OCT 11, 2017 9:18 AM FUEL ALARM