MONITORING SYSTEM CERTIFICATION
For Use By All Jurisdictions Within the State ofCalifornia
Authority Cited: Chapter 6.7, Health and Safety Code; Chapter 16, Division 3, Title 23, California Code ofRegulations
This form must be used to document testing and servicing of monitoring equipment. A separate certification or report must be prepared for each J
monitoring system control panel by the technician who performs the work. A copy of this form must be provided to the tank system owner /operator.
The owner /operator must submit a copy of this form to the local agency regulating UST systems within 30 days oftest date.
A. General Information
Facility Name: CHEVRON
Site Address: 5609 STINE ROAD
Facility Contact Person: LOUNG CHAO
Bldg. No.:
City: BAKERSFIELD Zip: _
Contact Phone No.: (661) 345 -6208
Make/Model of Monitoring System: TLS -350 Date ofTesting/Servicing: 4/5/2012
B. Inventory of Equipment Tested /Certified
Tank ID: UNL87
i Dispenser ID: 3/4
Tank ID: UNL911DIESEL
Dispenser Containment Sensor(s). Model: 406
In -Tank Gauging Probe. Model: MAG -1 In -Tank Gauging Probe. Model: MAG -1
Annular Space or Vault Sensor. Model: 420 Annular Space or Vault Sensor. Model: 420
Piping Sump / Trench Sensor(s). Model: 208 Piping Sump / Trench Sensor(s). Model: 208
Fill Sump Sensor(s). Model: Fill Sump Sensor(s). Model:
Mechanical Line Leak Detector. Model: RED JACKET Mechanical Line teal: Detector. Model: RED JACKET
Electronic Line Leak Detector. Model: Electronic Line Leak Detector. Model:
Tank Overfill / High -Level Sensor. Model: MAG -1 Tank Overfill / High - Level Sensor. Model: MAG -1
Other (specify equipment type and model in Section E on Page 2). Other (specify equipment type and model in Section E on Page 2).
Tank lD .-. DIESEL/91. Tank ID:
In -Tank Gauging Probe. Model: 01n -TankGauging Probe. Model: MAGA
H Annulai Space or Vault Sensor. Model: 420 Annular Space or Vault Sensor. Model:
R-Piping Sump / Trench Sensor(s). Model: 208 Piping Sump / Trench Sensor(s). Model:
TillSutnp Seitsor(s). Model: Fill Sump Sensor(s). Model:
Mechanical Line Leak Detector. Model: RED JACKET Mechanical Line Leak Detector. Model:
Electronic Line LeakDetector. Model: Electronic Line Leak Detector. Model:
Tank Overfill / High -Level Sensor. Model: MAG-1 Tank Overfill / High -Level Sensor. Model:
Other (specify equipment type and model in Section E on Page 2). Other (specify equipment type and model in Section E on Page 2).
Dispenser 111): 112 i Dispenser ID: 3/4
Disp'en'ser Containment Sensor(s). Model: 406 Dispenser Containment Sensor(s). Model: 406
Shear Valve(s). Shear Valve(s).
Dispenser Containment Float(s) and Chain(s). Dispenscr Containment Float(s) and Chain(s).
Dispenser ID: 516 Dispenser ID: 718
Dispenser Containment Sensor(s). Model: 406 Dispenser Containment Sensor(s). Model: 001
Shear Valve(s). Shear Valve(s).
Dispenser Containment Float(s) and Chain(s). Dispenser Containment Float(s) and Chain(s).
Dispenser ID: 9/10 Dispenser ID:
spenscr Containment Sensor(s). Model: 001 Dispenser Containment Sensor(s). Model:
hear Valve(s).. Shear Valve(s).
Dlspetser Containment Float(s) and Chain(s). DispenserContainment Float(s) and Chain(s).
Ittie facility contains more tanks or dispensers, copy this form. Include information for every tank and dispenser at the facility.
C': CeitifiCatlOn - I certify that the equipment identified in this document was inspected /serviced in accordance with the manufacturers'
guidelines. Attached to this Certification is information (e g. manufacturers' checklists) necessary to verify that this information is
eorrectand a Plot Plan showing the layout of monitoring a ui ment. For an equipment ca able f generating such reports, I have alsogYgPYeqPPggP
attached a copy of the report; (check all that apply): System set -up ® Alarm ry report
a.
Technician Name (print): RICH PHILLIPS Signature:
i Certification No.: A29084 / 1035169 -UT License. No.: C611 D40 809850
UriTesting Company Name: RICH ENVIRONMENTAL Phone No.: (661) 392 -8687
Testing Company Address: 5643 BROOKS CT. BAKERSFIELD, CA 93308 Date ofTesting/Servicing: 415112
Page 1 of 5
UN -036 — 1/4 www.unidoes.org Rev. 01/17/08
s
11.
y,
n,SeMioq E below, describe how and when these deficiencies were or will be corrected.
E '.comments•
a
i .
Monitoring System Certification
A Results of Testing/Servicing
Software Version Installed: 329.01
Comnlete the following checklist:
q jv
Yes No* Is the audible alarm operational?
Yes No* Is the visual alarm operational?
Yes No* Were all sensors visually inspected, functionally tested, and confirmed operational?
Yes No* Were all sensors installed at lowest point of secondary containment and positioned so that other equipment will
not interfere with their proper operation?
Yes No* If alarms are relayed to a remote monitoring station, is all communications equipment (e.g., modem)
N/A operational?
Yes No* For pressurized piping systems, does the turbine automatically shut down if the piping secondary containment
N/A monitoring system detects a leak, fails to operate, or is electrically disconnected? If yes: which sensors initiate
positive shut -down? (Check all that apply) ® Sump/Trench Sensors; Dispenser Containment Sensors.
Did you confirm positive shut -down due to leaks and sensor failure /disconnection? ® Yes; No.
Yes No* For tank systems that utilize the monitoring system as the primary tank overfill warning device (i.e., no
N/A mechanical overfill prevention valve is installed), is the overfill warning alarm visible and audible at the tank
fill point(s) and operating properly? If so, at what percent oftank capacity does the alarm trigger? %
Yes* No Was any monitoring equipment replaced? If yes, identify specific sensors, probes, or other equipment replaced
and list the manufacturer name and model for all replacement parts in Section E, below.
Yes* No Was liquid found inside any secondary containment systems designed as dry systems? (Check all that apply)
Product; Water. If yes, describe causes in Section E, below.
Yes No* Was monitoring system set -up reviewed to ensure proper settings? Attach set up reports, ifapplicable
t] No* Is all monitoring equipment operational per manufacturer's specifications?
I
r -
Page 2 of 5
UN -036 — 2/4 www.unidocs.org Rev. 01/17/08
Nsywe
Monitoring System Certification
F. In -Tank Gauging / SIR Equipment: ® Check this box iftank gauging is used only for inventory control.
Check this box if no tank gauging or SIR equipment is installed.
This:section must be completed if in -tank gauging equipment is used to perform leak detection monitoring.
Complete the following checklist:
Yes No* Has all input wiring been inspected for proper entry and termination, including testing for ground faults?
Yes No* Were all tank gauging probes visually inspected for damage and residue buildup?
Yes No* Was accuracy of system product level readings tested?
Yes 1 No* Was accuracy ofsystem water level readings tested?
Yes No* Were all probes reinstalled properly?
Yes No* Were all items on the equipment manufacturer's maintenance checklist completed?
In Section H, below, describe how and when these deficiencies were or will be corrected.
G. Line Leak Detectors (LLD): Check this box if LLDs are not installed.
Cmm lofo Ap fnllnwino rhnnlrlich
Yes No* For equipment start-up or annual equipment certification, was a leak simulated to verify LLD performance?
E; N/A Check all that apply) Simulated leak rate: ® 3 g.p.h.; 0.1 g.p.h ; 0.2 g.p.h.
Yes No* Were all LLDs confirmed operational and accurate within regulatory requirements?
ISI"Yes., No* Was the testing apparatus properly calibrated?
Yes , No* For mechanical LLDs, does the LLD restrict product flow if it detects a leak?
N/A
Yes No* For electronic LLDs, does the turbine automatically shut off ifthe LLD detects a leak?
N/A
10 Yes No* For electronic LLDs, does the turbine automatically shut off if any portion of the monitoring system is disabled
II r N/A or disconnected?
I
Yes No* For electronic LLDs, does the turbine automatically shut off if any portion of the monitoring system malfunctions
0 N/A or fails a test?
Yes El No For electronic LLDs, have all accessible wiring connections been visually inspected?
N/A
Yes No* Were all items on the equipment manufacturer's maintenance checklist completed?
r 1n Section H, below, describe how and when these deficiencies were or will be corrected.
L .Comments:
L
f ; Page 3 of 5
UK -036 — 3/4 www.unidoes.org Rev. 01/17/08
Monitoring System Certification Form: Addendum for Vacuum/Pressure Interstitial Sensors
I. Results ofVacuum/Pressure Monitoring Equipment Testing
q-54% /
This page should be used to document testing and servicing of vacuum and pressure interstitial sensors. A copy of
this' 'focal must be included with the Monitoring System Certification Form, which must be provided to the tank
system owner /operator. The owner /operator must submit a copy of the Monitoring System Certification Form to the
local agency regulating UST systems within 30 days of test date.
Manufacturer: Model: System Type: Pressure; Vacuum
Sensor M
Component(s) Monitored by this Sensor:
Sensor Functionality Test Result: Pass; Fail Interstitial Communication Test Result: Pass; Fail
Component(s) Monitored by this Sensor:
Sensor Functionality Test Result: Pass; Fail Interstitial Communication Test Result: Pass; Fail
Component(s) Monitored by this Sensor:
Sensor Functionality Test Result: Pass; Fail Interstitial Communication Test Result: Pass; Fail
Component(s) Monitored by this Sensor:
Sensor Functionality Test Result: Pass; Fail Interstitial Communication Test Result: Pass; Fail
t. •. • Component(s) Monitored by this Sensor:
Sensor Functionality Test Result: Pass; Fail Interstitial Communication Test Result: Pass; Fail
Component(s) Monitored by this Sensor:
Sensor Functionality Test Result: Pass; Fail Interstitial Communication Test Result: Pass; Fail
Component(s) Monitored by this Sensor:
Sensor Functionality Test Result: Pass; Fail Interstitial Communication Test Result: Pass; Fail
Component(s) Monitored by this Sensor:
Sensor Functionality Test Result: Pass; Fail Interstitial Communication Test Result: Pass; Fail
Component(s) Monitored by this Sensor:
Sensor Functionality Test Result: Pass; Fail Interstitial Communication Test Result: Pass; Fail
Components) Monitored by this Sensor:
Sensor Functionality Test Result: Pass; Fail Interstitial Communication Test Result: Pass; Fail
How was.interstitial communication verified?
Leak Introduced at Far End of Interstitial Space;' Gauge; Visual Inspection; Other (Describe in Sec. J, below)
Was vacuum/pressure restored to operating levels in all interstitial spaces? Yes No (Ifno, describe in Sec. J, below)
J. .
i
Comments: NONE OF THESE SENSORS ARE PRESENT AT THIS SITE.
Page 4 of 5
If the sensor successfully detects a simulated vacuum/pressure leak introduced in the interstitial space at the furthest point from the
sensor, vacuum/pressure has been demonstrated to be communicating throughout the interstice.
UN,4,3,6A -1/1 www.unidoes.org Rev. 01/26/06
jniwing System C-6diribitibn
1.
UST moliitorjag sito -.)P.Ian
Site Address: r,Mv D 7-3IC.(
raw 14P .............. ........
I .......
10A , ....
5.-,
robc.
Crt IV r1a r& IC
I . . . I I . . . . . . . . . . . . . . . . . . . I . . . . . . . . . . . . . . . . . . . -AY AIA
I ........... I .................... .... ............
I..., ...... I ......... I .............
I ......... ............. ..............
I . . I .
1 . F4
IF, r.6
VO or
I ....... I .... .. ......
I ........
I ........ I ...... ..........
I ............
I ......
I)atomap was drawn: I
Instructiola
If you already have a di4gram that -shows all'.mquired information, you may include it rather than this page, with your Monitoring
System C;ertifN IDnyoursite-plan, show -tht-&=W :layout oftanksmd pipffig.. Clearly identify locations of the following
equipment, if installed-, monitoring system control paneils, sonors monitoring tank annular spaces, sumps, dispenser pans, spill
Couwner% or,other secondary cobtaininva arm; inwima:cai a - 1,*r,e k deteca)rg, and in-tank liquid level- probes (if used
for leak detection). In the•sparA pkovidod, note the .49c phis Sire Plan prepared.
iUN-06-4/4
if .
rage 1 ;,f , __ ,
www,oWd6morg Rev. DIMM
a
a
t
q1:_R1(0
SWRCB, January 200k
Spill Bucket Testing Report Form
Thisform is intendedfor use by contractors performing annual testing ofUSTspill containment structures. The completedform and
printoutsfrom tests (ifapplicable), should be provided to thefacility owner /operatorfor submittal to the local regulatory agency.
1. FACILITY INFORMATION
Facility Name: CHEVRON I Date of Testing: 4/5/12
Facility Address: 5609 STINE ROAD, BAKERSFIELD
Facility Contact: LOUNG CHAO Phone:
Date Local Agency Was Notified of Testing : 3/2/12
NameofLocal Agency Inspector (fpresent during testing):
2. TESTING CONTRACTOR INFORMATION
Company Name: RICH ENVIRONMENTAL
Technician Conducting Test: RICH PHILLIPS
Credentials: CSLB Contractor X ICC Service Tech. SWRCB Tank Tester Other (Specie)
License Number(s): 1035169 -UT
3. SPILL BUCKET TESTING INFORMATION
Test Method Used: X Hydrostatic Vacuum Other
Test Equipment Used: VISUAL Equipment Resolution: 0
w, ..d .w...,. , ,.......,..
Identify Spill Bucket (By Tank
Number, Stored Product, etc.)
1
UNL87
2
DIESEL
3
RE -TEST 91 FILL
4
Bucket Installation Type: X Direct Bury
Contained in Sump
X Direct Bury
Contained in Sump
X Direct Bury
0 Contained in Sump
Direct Bury
Contained in Sum
tticket Diameter:' 12 12 12
Pub et' Depth: 14 14 14
WWsittime between applying
vacuum/water and start oftest: 30 MIN 30 MIN 30 MIN
Test Stmt Time (T): 9:30 2:00 4:30
Initial Reading (Rj): 14 14 14
Test End Time (TF): 10:30 3:00 5:30
Final Reading (RF): 14 14
Test Duration (TF — Tj): 1 -HOUR 1 -HOUR 1 -HOUR
Change in Reading (RF - R,): 000 000 000
Pass/Fail Threshold or
Criteria: 0.00 0.00 0.00
Test Result:
16 I X Pass Fail X Pass 0 Fail X Pass Fail 0 Pass Fail
CO_MK16WS —(include information on repairs made prior to testing, and recommendedfollow -upforfailed tests)
IUJNL91 - .REMOVED DRAIN VALVE (PHIL -TITE) CLEANED -UP - PASSED
CERTIFICATION OF TEC CLAN RESPONSIBLE FOR CONDUCTING THIS TESTING
t'likreby certify that all the information rained in this report is true, accurate, and infull compliance with legal requirements.
Technician's Signature: Date: 4/5/12
State laws and regulations do not currently require testing to be performed by a qualified contractor. However, local requirements
may be more stringent.
RICH ENVIRONMENTAL .
5643 BROOKS CT. BAKERSFIELD, CA. 93308
OFFICE (661)392 -8687 FAX (661)392 -0621
PRODUCT LINE LEAK DETECTOR TEST
WORK SHEET
W /0#:
FACILITY NAME: CHEVRON
FACILITY ADDRESS: 5609 STINE ROAD, BAKERSFIELD
PRODUCT LINE TYPE: PRESSURE
45996
PRODUCT LEAK DETECTOR TYPE TEST TRIP PASS
BELOW P.S.I. OR
SERIAL NUMBER 3 G.P.H. FAIL
UNL87 L/D TYPE. RED JACKET YES 10 PASS
SERIAL #
PREM91 L/D TYPE: RED JACKET YES 12 PASS
SERIAL #
DIESEL LID TYPE: RED JACKET YES 10 PASS
SERIAL #
L/D TYPE: YES PASS
SERIAL # NO FAIL
I CERTIFY THE ABOVE TESTS WERE CONDUCTED ON THIS DATE ACCORDING TO RED
JACKET PUMPS FIELD TEST APPARATUS TESTING PROCEDURE AND LIMITATIONS.
THE MECHANICAL LEAK DETECTOR TEST PASS / FAIL IS DETERMINED BY USING A
LOW FLOW THRESHOLD TRIP RATE OF 3 GALLONS PER HOUR OR LESS AT 10 P.S.I. I
ACKNOWLEDGE THAT ALL DATA COLLECTED IS TRUE AND CORRECT TO THE BEST
OF MY KNOWLEDGE.
TECHNICIAN RICH PHIL
SIGNATURE: DATE: 4/5/12
FTWARE REV I S I0N LEVEL. '
RsIOIV 330.01 TANK CHART SECURITY
PTWARE# 346330-100 -B DISABLED
IEATED - 10.07.23.17.25 *
MODULE# 330160-004 -a CUSTOM ALARMS
RS -232 END OF I$SSAGE
STEM FEATURES: DISABLED
PERIODIC IN -TANK TESTS DISABLED
ANNUAL IN -TANK TESTS SERVICE NOTICE
ISD DISABLED
ISO 3166 COUNTRY
CODE:
P'IASS /DENSITY
DISABLED
IIV -TANY, SETUP
STEM SETUP
T 1:87
R 5. 2012 11:28 AM PRODUCT GODS I
THERMAL COEFF :.000700
TANK DIAMETER 85.00
TANK PROFILE 1 PT
STEM UNITS FULL VOL 12048
I.S.
STEM LANGUAGE
NGLISH FLOAT SIZE: 4.0 IN.
STEM DATE /TIME FORMAT COMMUNICATIONS SETUPWDiD, 'YYYY HH:MM:SS xM WATER WARNINGNG 2.0
HIGH WATER LIMIT: 3.0
U 1 °STIPJE
p 1TT NE `RD PORT SETTINGS: MAX OR LABEL VOL: 12048
n+ idR , PTELD -CA OVERFILL LIMIT 90%:
10843COMMBOARD1 (ED I M )
RS -232 SECURITY HIGH PRODUCT 95%
y IpFT ` T,1ME' 1 .: DISABLED
I I 'f i ME 2 D'! SABLED CODE : D I SABLE`U DELIVERY
11445
LI I °11 T
I TIME 3 DISABLED COMM BOARD : 3 (RS -232) 1204
I1F TIME 4 DISABLED BAUD RATE : 1200
NK PER TST NEEDED WRN PARITY : ODD
STOP BIT : 1 STOP
LOW PRODUCT 500
LEAK ALARM LIMIT: 99
SABLED
ANN TST NEEDED WRN DATA LENGTH: 7 DATA SUDDEN LOSS LIMIT: 99
0.00INK
SABLED RS -232 SECURITY
CODE : DISABLED
TANK TILT
PROBE OFFSET 0.00
NE RE- ENABLE METHOD
Sa LINE TEST AUTO TRANSMIT SETTINGS: SIPHON MANIFOLDED TANKS
NE PER TST NEEDED WRN AUTO LEAK ALARM LIMIT
T #: NONE
LINE MANIFOLDED TANKSSABLED
N)« ANN TST NEEDED WRN DISABLED T #: NONE
SABLED AUTO HIGH WATER LIMIT
DISABLED
AUTO OVERFILL LIMIT LEAK MIN PERIODIC: iNT TC VOLUhIES DISABLED 1204
ABL•ED AUTO LOW PRODUCT
MF',CDI4PENSATIOP! DISABLED LEAK MIN ANNUAL 10%
1204
4UE..;(DEG F ): 60.0 AUTO THEFT LIMIT
HEIGHT OFFSET DISABLED
AUTO DELIVERY START8ABUEDDISABLED PERIODIC TEST TYPEi "A 90y
3T +.y it AUTO DELIVERY END QUICK
P}tOTOGJOL` DATA FORMAT D I SABLED
AUTO EXTERNAL INPUT ON ANNUAL TEST FAIL
c TIGHT ,.., _... DISABLED ALARM DISABLEDY1: i GHT VING TIMESA. AUTO EXTERNAL INPUT OFFSABLED,
AI;REC.T LOCAL PRINTOUT DISABLED PERIODIC TEST FAIL
ALARM DISABLEDSABLI~D ' AUTO SENSOR FUEL ALARM
i I DISABLED1:
R4 PROTOCOL PREFIX AUTO SENSOR WATER ALARM GROSS TEST FAIL
ALARM DISABLEDDISABLED
AUTO SENSOR OUT ALARM
DISABLED ANN TEST AVERAGING: OFF
PER TEST AVERAGING: OFF
STEM SECURITY TANK TEST NOTIFY: OFF
DE : 000000
TNK.TST SIPHON BREAK:OFFINTENANCEHISTORY
SABLED DELIVERY DELAY : 15 MIN
PUMP THRESHOLD : 10.00%
2:91
RODUCT CODE 2 T 3:DIESEL 3iERMALCOEFF :.000700 PRODUCT CODE
THERMAL COEFF :.000450 LEAK TEST METHOD
3NK DIAMETER
aNK PROFILE
95.00
i PT TANK DIAMETER : 95.00 VEST ON DATE ALL TANK 04
FULL VOL 6016 TANK PROFILE 1 PT
FULL VOL 4008 3, 2010MAR3, 2:3a AMTIME : -11TESTRATE
OAT SIZE: 4.0 IN. FLOAT SIZE: 4.0 IN,
0.20HOULDURATION
ATER WARNING 2.0 2.0 TST EARLY•STOP:DISABLED
IGH WATER LIMIT: 3.0 WATER WARNING
HIGH WATER LIMIT: 3.0 TEST kEPORT FORMATLEAKENHANCEDAXORLABELVOL:
VERFILL LIMIT
9016
90% MAX'OR LABEL VOL: 4008
7214 OVERFILL LIMIT
iIGH PRODUCT '` 95%
7615
3609
HIGH PRODUCT
q„ „DELIVERY LIMIT : 601
395%
DELIVERY LIMIT 10%
400
OW PRODUCT
EAK ALARM LIMIT:
500
99 LOW PRODUCT 300
UDDEN LOSS LIMIT: 5G LEAK ALARM LIMIT: 99
50ANKTILT
ROBE OFFSET
0.00
0.00
SUDDEN LOSS LIMIT:
TANK TILT 0.00 LIQUID SENSOR SETUP - PROBE OFFSET 0•D0
jIPHON MANIFOLDED TANKS
G #: NONE SIPHON MANIFOLDED TANKS L 1:67 ANNULAR
TRI -STATE (SINGLE FLOAT)
LINE MANIFOLDED TANKS T #: NONE CATEGORY : ANNULAR SPACE
TV: NONE LINE MANIFOLDED TANKS
T #: NONE
LEAK MIN PERIODIC: 10%
LEAK 111N PERIODIC: lok L 2:91 - DIESEL ANNULARSINGLEFLOAT) 801 TRI -STATE
CATEGORY : ANNULAR SPACE
LEAK MIN ANNUAL 10%
801 LEAK 11114 ANNUAL ADO
PERLODIC TESL TYPE L 3:67 STP
QUICK PERIODIC TEST TYPE CATEGORY
AT :(
STPGSUMPLOAT)
QUICK
ANNUAL' TEST FAIL
ALARM DISABLED ANNUAL TEST FAIL
ALARM DISABLED L 4:91 STP SINGLE FLOAT)
PERIOItgC' TEST FAIL TR1-STATE
CATEGORY : STP SUMP
ALARM DISABLED PERIODIC
AST
FAIL
DISABLED
GROSS TEST FAIL
ALARI1 D 1 SABLED GF.OSS TEST FA I L L 5 :DSL STP
TRI -STATE (SINGLE FLOAT}
ALARM DISABLED CATEGORY STP SUMP
R;NN:TEST AVERAGING:
PER TEST AVERAGING:
OFF
OFF ANN TEST AVERAGING: OFF
PER TEST AVERAGING: OFF
TANK TEST NOTIFY: OFF
TANK TEST NOTIFY: OFF
TNK TST SIPHON BREAK:OFF TNK TST SIPHON BREAK :OFF
DELIVERY DELAY :
PUMP THRESHOLD
15 MIN
10.00% DELIVERY DELAY 15 MIN
PUMP THRESHOLD 10.00%
toe•+•
L}sqa[* /---
OUTPUT RELAY SETUP
R 1:87
TYPE
STANDARD
NORMALLLV CLOSED
TANK 9: 1
LIQUID SENSOR ALMS
L I:FUEL ALARML3:FUEL ALARM
L 1:SENSOR OUT ALARML3:SENSORtOUT ALARM
ISD SITE ALARMS
ISD GROSS PRES FAILISDDEGRDPRESFAILISDVAPORLEAKFAILISDVPPRESFAIL
ISD VP STATUS FAIL
ISD HOSE ALARMS
ALL:FLOW COLLECT FAIL
R 2:91
TYPE:
STANDARD
NORMALLY CLOSED
TANK >t : 2
F, t
r• L I GUft SENSOR ALMSL, , 2,: FUEL "ALARM
k }. I:' 4':,FUEL ALARM
L`'4`:SENSOR
OUUT
T ALARM.
ISD SITE ALARMS
ISD GROSS PRES FAILISDDEGRDPRESFAILISDVAPORLEAKFAILISDVPPRESFAIL
ISD VP STATUS FAIL
ISD HOSE ALARMS
ALL:FLOW COLLECT FAIL
R 3:DIESEL
TYPE:
STANDARD
NORMALLY CLOSED
TANK 4: 3
LIQUID SENSOR ALMSt2 ;,FUEL ALARM
5':'FUEL ALARM _
t
L,::SENSOR OUT AL
SE3OR OUT ALARM
pVFRY4 ,FILL
9A. NDARD '
dORMADLY:OPEN
NONE
N =TANK ALARMS
ALL-'OVERFILL ALARMALL:HIGH PRODUCT ALARMALL:MAX PRODUCT ALARM
SMARTSENSOR SETUP
s 1:CARBON CANISTOR
CATEGORY VAPOR VALVE
s 2:VAPOR PRESSURE
CATEGORY VAPOR PRESSURE
s 3 :DISP 1 -2
CATEGORY AIR FLOW METER
s 4:DISP 3 -4
CATEGORY AIR FLOW METER
3 5:DISP 5 -6
CATEGORY AIR FLOW METER
s 6:DISP 7 -8
CATEGORY AIR FLOW METER
s 7:DISP 9 -10
CATEGORY AIR FLOW METER
s 8:ATM
CATEGORY ATM P SENSOR
EVRi1SD SETUP
EVR TYPE: BALANCE
BALANCE NOZZLE TYPE
VST
VAPOR PROCESSOR TYPE
VEEDER -ROOT POLISHER
ANALYSIS TIMES
TIME: 10:00 All
DELAY MINUTES: 1
ACCEPT HIGH ORVR:
ENABLED
ISD HOSE TABLE
ID- SERIAL NUML %BEL
ID FP FL HL AA RR
01 01 01 02 01 02
02 02 02 02 01 02
03 03 03 02 02 02
04 04 04 02 02 02
05 05 05 02 03 02
06 06 06 02 03 02
07 07 07 02 04 02
08 08 08 02 04 02
09 09 09 02 055 02
10 16 10 02 05 02
iAt)`ILI
ISD AIRFLOW METER MAP
HOSE MAP
ID- SERIAL NUML %BEL
2
1 42051• DISP 1 -2
2 36945 DISP 3 -4
MHH
3 40078 DISP 5 -6
201
4 40343 DISP 7 -8
U U
5 42057 DISP 9 -10
202
ISD FUEL GRADE HOSE MAP
1 2 3 4
FP MHH MHH MHH MHH AA
01 201 101 901 U U 1
02 202 102 902 U U 1
03 203 103 903 U U 2
04 204 104 904 U U 2
05 205 105 905 3 U 3
06 206 106 906 3 U 3
07 207 107 907 U U 4
09 208 108 908 U U 4
09 209 109 909 U U 5
16 210 110 910 U U 5
LABEL TABLE
1: UNASSIGNED
2: BLEND3
3: REGULAR
4: MID GRADE -
5: PREMIUM
6: GOLD
7: BRONZE
8: SILVER
9: BLEND2
10: BLEND4
PMC; SETUP
PMC VERSION: 01.03
VAPOR PROCESSOR TYPE
VEEDER-ROOT POLISHER
ALP;iRll H I STORY REPORT
SENSOR ALARM - - - --
L 1:87 ANNULAR
ANNULAR SPACE
SENSOR.OUT ALARM
APR S. 2012 9:56 AM
FUEL ALARM
APR 5, 2012 9:31 AM
SENSOR OUT ALARM
MAR 7. 2011 9 :39 AM
15, 2,012 9:29 AM
APR
SElySOR OUT
1ALA
9"! 39 F,r1
lw1AR
ALARM HISTORY REPORT
SENSOR ALARM - - - --
L 3:87 STP
STP SUMP
SENSOR OUT ALARM
APR 5. 2012 9:56 AM
FUEL ALARM
APR 5, 2012 9:30 AM
SENSOR OUT ALARM
MAR 7. 2011 9:39 AM
ALARM HISTORY REPORT
SENSOR ALARM - -- --
L- A:.91 STP
STP . SW
SENSOR OUT ALARM
APR 5. 20t2 9:56 AM
FUEL ALARM
APR 5, 2012 9:30 AM
SENSOR OUT ALARM
MAR 7, 2011 9:39 AM
STF SUIhP
rr
SENSOR OUT ALARM
APR 5. 2012 9:56 AM
FUEL ALARM
APR 5, 2012 9:29 AM
SENSOR OUT ALARM
MAR 7, 2011 9:39 AM
ALARM y 1gTOR`
REPQRZ
NSaR
L 2: 91 SPACE
ANNU OR GUT ALA9Cq 56 AC1
BENS 2012
AFR 5,
FUEL
rd
Sa9 to
r .
LISggb .
MONITOR CERT. FAILURE REPORT
SITE NAME: CHEVRON DATE : 4/5/12
THE FOLLOWING COMPONENTS WERE REPLACED/REPAIRED TO COMPLETE
TESTING.
REPAIRS: CLEANED 91 FILL BUCKET AND RE- TESTED - PASSED SECOND TEST
LABOR:
PARTS INSTALLED :
NAME • TITLE:
SIGNATURE:
THE ABOVE NAMED PERSON TAKES FULL RESPONSIBILITY OF NOTIFYING
THE APPROPRIATE PARTY TO HAVE CORRECTIVE ACTION TAKEN TO REPAIR
THE ABOVE LISTED PROBLEMS AND NOTIFYING RICH ENVIRONMENTAL FOR
ANY NEEDED RETESTING. THIS ALSO RELEASES RICH ENVIRONMENTAL OF
ANY FINES OR PENALTIES OCCURING FROM NON - COMPLIANCE.
A COPY -OF THIS DOCUMENT HAS BEEN LEFT ON -SITE FOR YOUR
CONVIENENCE. i