HomeMy WebLinkAbout5201 WHITE LANE (4)A 55
MONITORING SYSTEM CERTIFICATION
For Use By All Jurisdictions Within the State ofCalifornia Y
Authority Cited. Chapter 6.7, Health and Safety Code; Chapter 16, Division 3, Title 23, California Code ofRegulations
This form must be used to document testing and servicing of monitoring equipment. A separate certification or report must be prepared for each
monitoring system control panel by the technician who performs the work. A copy ofthis form must be provided to the tank system owner /operator.
The owner /operator must submit a copy ofthis form to the local agency regulating UST systems within 30 days oftest date.
A. General Information
Facility Name: GOOD SAMARITAN
Site Address: 6201 WHITE LANE
Bldg. No.:
City: BAKERSFIELD, CA Zip: -
Facility Contact Person: Contact Phone No.: ( )
Make/Model of Monitoring System: TLS -350 Date of Testing/Servicing; 10 -21 -11
B. Inventory of Equipment Tested/Certified
Check the appropriate boxes to indicate specific equipment inspected /serviced:
Tank ID: DIESEL
in -Tank Gauging Probe. Model: MAG -1
Annular Space or VaultSensor. Model: 420
Piping Sump / Trench Sensor(s). Model: 208
Fill Sump Sensor(s). Model:
Mechanical Line Leak Detector. Model:
Electronic Line Leak Detector. Model:
Tank Overfill / High -Level Sensor. Model: FLAPPER
Other (specify equipment type and model in Section E on Page 2).
Tank ID:
In -Tank Gauging Probe. Model:
Annular Space or Vault Sensor. Model:
Piping Sump / Trench Sensor(s). Model:
Fill Sump Sensor(s). Model:
Mechanical Line Leak Detector. Model:
Electronic Line Leak Detector. Model:
Tank Overfill / High -Level Sensor. Model:
Other (specify equipment type and model in Section E on Page 2).
Tank ID: Tank ID:
In -Tank Gauging Probe. Model: In -Tank Gauging Probe. Model:
Annular Space or Vault Sensor. Model: Annular Space or Vault Sensor. Model:
Piping Sump / Trench Sensor(s). Model: Piping Sump / Trench Sensor(s). Model:
Fill Sump Sensor(s). Model: Fill Sump Sensor(s). Model:
Mechanical Line Leak Detector. Model: Mechanical Line Leak Detector. Model:
Electronic Line Leak Detector. Model: Electronic Line Leak Detector. Model:
Tank Overfill / High -Level Sensor. Model: Tank Overfill / High -Level Sensor. Model:
Other (specify equipment type and model in Section E on Page 2). Other (specify equipment type and model in Section E on Page 2).
Dispenser ID: Dispenser ID:
Dispenser Containment Sensor(s). Model: Dispenser Containment Sensor(s). Model:
Shear Valve(s). Shear Valve(s).
Dispenser Containment Float(s) and Chain(s). Dispenser Containment Float(s) and Chain(s).
Dispenser ID: Dispenser ID:
Dispenser Containment Sensor(s). Model: Dispenser Containment Sensor(s). Model:
Shear Valve(s). Shear Valve(s).
Dispenser Containment Float(s) and Chain(s). Dispenser Containment Float(s) and Chain(s).
Dispenser ID: Dispenser ID:
Dispenser Containment Sensor(s). Model: Dispenser Containment Sensor(s). Model:
Shear Valve(s). Shear Valve(s).
Dispenser Containment Float(s) and Chain(s). Dispenser Containment Float(s) and Chain(s).
Ifthe facility contains more tanks or dispensers, copy this form. Include information for every tank and dispenser at the facility.
C. Certification -I certify that the equipment identified in this document was inspected/serviced in accordance with the manufacturers'
guidelines. Attached to this Certification is information (e.g. manufacturers' checklists) necessary to verify that this information is
correct and a Plot Plan showing the layout of monitoring equipment. For any equipment capable o nerating such reports, I have also
attached a copy of the report; (check all that apply): ® System set -up Alarm h report
Technician Name (print): RICH PHILLIPS Signature:
Certification No.: A29084/1035169 -UT License. No.: 61/ D40 809850
Testing Company Name: RICH ENVIRONMENTAL Phone No.: (661) 326 -8402
Testing Company Address: 5643 BROOKS COURT BAKERSFIELD,CA 93308 Date of Testing/Servicing: 10 -21 -11
Page 1 of 5
UN -036 —1/4 www.unidoes.org Rev. 01117/08
Monitoring System Certification
I D. Results of Testing/Servicing
Software Version Installed: 15.01
Complete the following checklist:
Yes No* Is the audible alarm operational?
Yes No* Is the visual alarm operational?
Yes No* Were all sensors visually inspected, functionally tested, and confirmed operational?
Yes No* Were all sensors installed at lowest point of secondary containment and positioned so that other equipment will
not interfere with their proper operation?
Yes No* If alarms are relayed to a remote monitoring station, is all communications equipment (e.g., modem)
N/A operational?
Yes No* For pressurized piping systems, does the turbine automatically shut down if the piping secondary containment
N/A monitoring system detects a leak, fails to operate, or is electrically disconnected? If yes: which sensors initiate
positive shut -down? (Check all that apply) Sump /Trench Sensors; Dispenser Containment Sensors.
Did you confirm positive shut -down due to leaks and sensor failure /disconnection? Yes; No.
Yes No* For tank systems that utilize the monitoring system as the primary tank overfill warning device (i.e., no
N/A mechanical overfill prevention valve is installed), is the overfill warning alarm visible and audible at the tank
fill point(s) and operating properly? If so, at what percent of tank capacity does the alarm trigger? %
Yes* No Was any monitoring equipment replaced? If yes, identify specific sensors, probes, or other equipment replaced
and list the manufacturer name and model for all replacement parts in Section E, below.
Yes* No Was liquid found inside any secondary containment systems designed as dry systems? (Check all that apply)
Product; Water. Ifyes, describe causes in Section E, below.
Yes No* Was monitoring system set -up reviewed to ensure proper settings? Attach set up reports, ifapplicable
Yes No* I Is all monitoring equipment operational per manufacturer's specifications?
In Section E below, describe how and when these deficiencies were or will be corrected.
E. Comments: SUCTION SYSTEM TO GENERATOR NO P.O.S
Page 2 of 5
UN -036 — 214 www.unidocs.org Rev. 01/17108
twonitoring System Certification
F. In -Tank Gauging / SIR Equipment:
qqtq
r
Check this box if tank gauging is used only for inventory control.
Check this box if no tank gauging or SIR equipment is installed.
This section must be completed if in -tank gauging equipment is used to perform leak detection monitoring.
Complete the following checklist:
Yes No* Has all input wiring been inspected for proper entry and termination, including testing for ground faults?
Yes No* Were all tank gauging probes visually inspected for damage and residue buildup?
Yes No* Was accuracy of system product level readings tested?
Yes No* Was accuracy of system water level readings tested?
Yes No* Were all probes reinstalled properly?
Yes No* I Were all items on the equipment manufacturer's maintenance checklist completed?
In Section H, below, describe how and when these deficiencies were or will be corrected.
G. Line Leak Detectors (LLD):
rmmnlete the fallnwino checklist:
Check this box if LLDs are not installed.
Yes D No* For equipment start -up or annual equipment certification, was a leak simulated to verify LLD performance? rO
N/A Check all that apply) Simulated leak rate: 3 gp.h.; 0.1 g p.h ; 0.2 g.p.h.
Yes No* Were all LLDs confirmed operational and accurate within regulatory requirements?
Yes No* Was the testing apparatus properly calibrated?
Yes No* For mechanical LLDs, does the LLD restrict product flow if it detects a leak?
N/A
Yes No* For electronic LLDs, does the turbine automatically shut off if the LLD detects a leak?
N/A
Yes No* For electronic LLDs, does the turbine automatically shut off if any portion of the monitoring system is disabled
N/A or disconnected?
Yes No* For electronic LLDs, does the turbine automatically shut off if any portion ofthe monitoring system malfunctions
N/A or fails a test?
Yes No* For electronic LLDs, have all accessible wiring connections been visually inspected?
N/A
Yes No* Were all items on the equipment manufacturer's maintenance checklist completed?
In Section M, below, describe how and when these deficiencies were or will be corrected.
H. Comments: SUCTION SYSTEM. NO LEAK DETECTORS
UN -036 — 314
Page 3 of 5
www.unidocs.org Rev. 01/17/08
SOFTWARE REVISION LEVEL
VERSION 15.01
SOFTWARE# 346015 -100 -0
CREATED - 97.10.23.08.56
S- MODULEO 330161 -001 -A
SYSTEM FEATURES:
PERIODIC IN -TANK, TESTS
ANNUAL IN -TANK TESTS
0.20 GAL /HR PLLDPRECISIONTESTSPECIAL
YSTEM SETUP
T 21. 2011 9:29 AM
YSTEM UNITS
U.S.
YSTEM LANGUAGE
ENGLISH
YSTEM DATE /TIME FORMAT
N DD YYYY HH:NIM:SS xM
EMORIAL CENTER
201 WHITE LANE
IKERSFIELD CA
15- 398 -1800
IIFT TIME I DISABLED
jIFT TIME 2 DISABLED
lIFT TIME 3 DISABLED
RIFT TIME 4 DISABLED
INK PERIODIC WARNINGS
ISABLED
INK ANNUAL WARNINGS
ISABLED '
NE PERIODIC WARNINGS
ISABLED
NE ANNUAL WARNINGS
PSABLED
RINT TC VOLUMES
VABLEI> -
MP COMPENSATION
II.UE (DEG F ) : 60.0
LICK HEIGHT OFFSET
SABLED
PROTOCOL DATA FORMAT
I GHT
3YLIGHT SAVING TIME
TABLED
WRT DATE
R WEE SUN
ART
O0;'':,
CD HATE
7T WEEK 6 SUN
9D TIME
k0000 AM
I
I- DIRECT LOCAL PRINTOUT
SABI,ED
STEM SECURITY
DE : 000000
t
COMMUNICATIONS SETUP
PORT SETTINGS:
COMM BOARD 2 (RS-232)
BAUD RATE 1200
PARITY ODD
STOP BIT 1 STOP
DATA LENGTH: 7 DATA
AUTO TRANSMIT SETTINGS:
AUTO LEAK ALARM LIMIT
DISABLED -
AUTO HIGH WATER LIMIT
DISABLED
AUTO OVERFILL LIMIT
DISABLED
AUTO LOW PRODUCT
DISABLED
AUTO THEFT LIMIT
DISABLED
AUTO DELIVERY START
DISABLED
AUTO DELIVERY END
DISABLED
AUTO EXTERNAL INPUT ON
DISABLED
AUTO EXTERNAL INPUT OFF
DISABLED
AUTO SENSOR FUEL ALARM
DISABLED
AUTO SENSOR WATER ALARM
DISABLED
AUTO SENSOR OUT ALARM
DISABLED
RS -232 SECURITY
CODE : 000000
RS -232 END OF MESSAGE
DISABLED
IN -TANK SETUP
T I:DIESEL 2
PRODUCT CODE 1
THERMAL COEFF :.000450
TANK, DIAMETER 63.00
TANK PROFILE I PT
FULL VOL 999
FLOAT SIZE: 4.0 IN. 8496
WATER WARNING 2.0
HIGH WATER LIMIT: 3.0
MAX OR LABEL VOL: 999
OVERFILL LIMIT 901/0
899
HIGH PRODUCT 95%
949
DELIVERY LIMIT 10i
99
LOW PRODUCT 80
LEAK ALARM LIMIT: 99
SUDDEN LOSS LIMIT: 50
TANK TILT 1.00
MANIFOLDED TANKS
TO: NONE
LEAK MIN PERIODIC: 0%
0
LEAK MIN ANNUAL 0%G
0
PERIODIC TEST TYPE
STANDARD
ANNUAL TEST FAIL
ALARM DISABLED
PERIODIC TEST FAIL
ALARM DISABLED
GROSS TEST FAIL
ALARM DISABLED
ANN TEST AVERAGING: OFF
PER TEST AVERAGING: OFF
TANK TEST NOTIFY: OFF
T14K TST SIPHON BREAK:OFF
DELIVERY DELAY : 15 MIN
x,
GOOD SAMARITAN
5201 WHITE LM
8MKERSFIELD 4A
10/21 /2011 12:37 Pm
SUMP LEAK TEST REPORT
DSLS
TEST STARTED 12:22 PM
TEST STARTED 10/21/2011
BEGIN LEUEL 3.0370 IN
END TIME 12:37 PM
END DATE 10/21/2011 !
END LEVEL 2.5295 IN
LEAK THRESHOLD 0.002 IN
TEST RESULT FAILED ,
f
GOOD SAMARITAN
5201 WHITE LN
BAKEPSFI£LD GA
10/21x2011 12:55 PM
SUMP LM,' TEST REPORT
DSLS
TEST STARTED 12:40 PM
TEST STARTED 10/21/2011
BEGIN LEUEL 2.9055 IN
END TIME 12:55 PM
END DATE tO/21/2011
END LEVEL 2.7619 IN
LEAK THRESHOLD 0.002 IN
TEST RESULT FAILED
lz
4415
S
LEAK TEST METHOD
TEST ON DATE : ALL TANK
APR 3, 1999
START TIME : 2:00 AM
TEST RATE :0.20 GAL /HR
DURATION 2 HOURS
z
LEAK TEST REPORT FORMAT
E NORMAL
t
LIQUID SENSOR SETUP
L 1 :DIESEL 2 A14NULAR
TRI—STATE (SINGLE FLOAT)
CATEGORY : ANNULAR SPACE
L 2:DIESEL 2 SUMP
TRI —STATE (SINGLE FLOAT)
a CATEGORY : PIPING SUMP
6
EXTERNAL INPUT SETUP
NONE
OUTPUT RELAY SETUP
ALARM HISTORY REPORT
SENSOR ALARM
L 1:DIESEL 2 ANNULAR
ANNULAR SPACE
FUEL ALARM
JUN 2. 2010 11:21 AM
FUEL ALARM
JUN 2. 2010 11 :21 AM
FUEL ALARM
JUN 2, 2010 11:20 AM
ALARM HISTORY REPORT
SENSOR ALARM.---- -
L2:DIESEL 2 SUMP
PIPING SUMP
FUEL ALARM
DEC 18, 2010 5:54 PM
FUEL ALARM
JUN 2. 2010 10:24 AM
FUEL ALARM
JAN 18. 2010 2:58 PM
MONITOR CERT. FAILURE REPORT
SITE NAME: GOOD SAMARITAN
ADDRESS: 5201 WHITE LANE
CITY: BAKERSFIELD, CA
REPAIRS: NONE
PARTS INSTALLED: NONE
DATE: 10 -21 -11
TECHNICIAN: RICH
SIGNATURE:
LAO 3
THE ABOVE NAMED PERSON TAKES FULL RESPONSIBILITY OF NOTIFYING
THE APPROPRIATE PARTY TO HAVE CORRECTIVE ACTION TAKEN TO REPAIR
THE ABOVE LISTED PROBLEMS AND NOTIFYING RICH ENVIRONMANTAL FOR
ANY NEEDED RETESTING. THIS ALSO RELEASES RICH ENVIRONMENTAL OF
ANY FINES OR PENALTIES OCCURING FROM NON - COMPLIANCE.
A COPY OF THIS DOCUMENT HAS BEEN LEFT ON -SITE FOR YOUR
CONVIENENCE.