Secondary Containment Testing Report Form
Thisfirm is intendedfor use by contractors performing periodic testing ofUST secondary containment systems. Use the
appropriate pages of'thisform to report results for all components tested. The completedform, written test procedures, and
printouts from tests (ifapplicable), should be provided to thefacility owner /operator for submittal to the local regidatay agency.
1. FACILITY INFORMATION
Facility Name: Metro Gas Date of Testing: 5/15/1.2
Facility Address: 4600 Stine Rd., Bakersfield, CA 93313
Facility Contact: Mike Phone:
Date Local Agency Was Notified of Testing : 5/8/12
Name of Local Agency Inspector (ifpresent during testing): Ernie Medina
2. TESTING CONTRACTOR INFORMATION
Company Name: Kern County Construction, Inc.
Technician Conducting Test: Josh Simmons
Credentials: x CSLB Licensed Contractor SWRCB Licensed Tank Tester
License Type: A, B, Flaz License Number:481053
Manufacturer Training
Manufacturer Com onent (s) Date Training Expires
3. SUMMARY OF TEST RESULTS
Component Pass Fail Not
Tested
Repairs
Made Component Pass Fail NotNot Repairs
Made
87 West STP X 1_I CI
CI
CJ Cl
CI CI
D CI
CI 11 CI
u
I I' hydrostatic testing was performed, describe what was done with the water after completion of tests:
Water returned to test tank for re -use.
CERTIFICATION OF TECHNICIAN RESPONSIBLE FOR CONDUCTING THIS TESTING
To the best ol'my knowledge, thefacts stated in this document are accurate and infull compliance with legal requirernents
Technician's Signature: Da
16
SWRCB, January 2002
8. PIPPING SUMP TESTING
Page of —
Test Method Developed By: Sump Manufacturer x Industry Standard Professional Engineer
Other (Specify)
Test Method Used: Pressure Vacuum x Hydrostatic
Other ( Specifv)
Test Equipment Used: Incon ts- stts Equipment Resolution:.00I
nFk Sump #87 West Sump #` Sump # Sump #
Sump Diameter: 48"
Sump Depth: 55"
Sump Material: FRP
Height from `rank Top to Top of
1- 1ighest Piping Penetration: 22"
Height from 'rank Top to Lowest
Electrical Penetration: 28"
Condition of sump prior to testing: good
Portion of Sump Tested' 1/2
Does turbine shut down when
sump sensor detects liquid (both x Yes No NA
Yes No Yes No x Yes No NA
product and water)?
NA NA
Turbine shutdown response time 3 sec
Is system programmed for fail -safe
Shutdown?
x Yes No NA Yes No NA Yes No NA Yes No NA
Was fail -safe verified to be
operational'?*
x Yes No NA Yes No NA Yes No NA Yes No NA
Wait time between applying
pressure /vacuum /water and starting 15 min.
test:
Test Start Time: 9:04 9:20
Initial Reading (RI): 2.763 2.763
Test End Time: 9:19 9:35
Final Reading (R1:): 2.764 2.763
rest Duration: 15 min
Change in Reading (Rr -Rl): 001
Pass /Fail Threshold or Criteria: 002
Test Result: x Pass Fail Pass Fail Pass Fail Pass Fail
Was sensor removed for testing? x Yes No NA Yes No NA Yes No NA Yes No NA
Was sensor properly replaced and
verified functional after testing? x Yes No NA Yes No NA Yes No NA Yes No NA
Comments — (include information on repairs made prior to testing, and recommendedfollow- up.forfailed tests)
Fibery-lass Collar.
If the entire depth of the sump is not tested, specify how much was tested. If the answer to any of the questions indicated with an
asterisk ( *) is "NO" or "NA ", the entire sump must be tested. (See SWRCB LG -160)