HomeMy WebLinkAbout430 CALIFORNIA AVENUE (5)MONITORING SYSTEM CERTIFICATION
For Use By All Jurisdictions Within the State of California
Authority Cited: Chapter 6.7, Health and Safety Code; Chapter 16, Division 3, Title 23, California Code ofRegulations
This form must be used to document testing and servicing of monitoring equipment. A separate certification or report must be prepared for each
monitoring system control panel by the technician who performs the work. A copy of this form must be provided to the tank system owner /operator.
The owner /operator must submit a copy of this form to the local agency regulating UST systems within 30 days of test date.
A. General Information
Facility Name: HP Go -Go
Site Address: 430 E. California Avenue
Facility Contact Person: Alondra
Make /Model of Monitoring System: Veeder Root TLS 350
B. Inventory of Equipment Tested/Certified
Check the appropriate boxes to indicate speciric equipment inspected/serviced:
Bldg. No.:
City: Bakersfield Zip: 93304
Contact Phone No.: (661) 835 -8044
Date of Testing/Servicing: 2/24 /2011
Tank ID: 1 unleaded Tank ID: 2 supreme
Z In= lank Gauging Probe. Model: 847390 -309 Z In= Tank Gauging Probe. Model: 847390 -309
N Annular Space or Vault Sensor. Model: 794390 -420 Z Annular Space or Vault Sensor. Model: 794390 -420
N Piping Sump /Trench Sensor(s). Model: 794380 -208 Z Piping Sump/ Trench Sensor(s). Model: 794380 -208
Fill Sump Sensor(s). Model: Fill Sump Sensor(s). Model:
N Mechanical Line Leak Detector. Model: FX1 V Z Mechanical Line Leak Detector. Model: FX1 V
Electronic Line Leak Detector. Model: Electronic Line Leak Detector. Model:
N "Tank Overfill / High -Level Sensor. Model: 847390 -309 Z Tank Overfill / High -Level Sensor. Model: 847390 -309
Other (specify equipment type and model in Section E on Page 2). Other (specify equipment type and model in Section E on Page 2).
Tank ID: Tank ID:
In -Tank Gauging Probe. Model: In= Tank Gauging Probe. Model:
Annular Space or Vault Sensor.. Model: Annular Space or Vault Sensor. Model:
Piping Sump /Trench Sensor(s). Model: Piping Sump / Trench Sensor(s). Model:
Fill Sump Sensor(s). Model: Fill Sump Sensor(s). Model:
Mechanical Line Leak Detector. Model: Mechanical Line Leak Detector. Model:
Electronic Line Leak Deteotor. Model: Electronic Line Leak Detector. Model:
Tank Overfill / High -Level Sensor. Model: Tank Overfill / High -Level Sensor. Model:
Other (specify equipment type and model in Section E on Page 2). Other (specify equipment type and model in Section E on Page 4
Dispenser ID: Dispenser ID:
Dispenser Containment Sensor(s). Model: Dispenser Containment Sensor(s). Model:
Shear Valve(s). Shear Valve(s).
Dispenser Containment Floa(s) and Chain(s). Dispenser Containment Float(s) and Chain(s).
Dispenser ID: Dispenser ID:
Dispenser Containment Sensor( -). Model: Dispenser Containment Sensor(s). Model:
Shear Valve(s). Shear Valve(s).
Dispenser Containment Flout(s) and Cham(.$). Dispenser Containment Floats) and Chain(s).
Dispenser ID: Dispenser ID:
Dispenser Containment Sensor(s). Model: Dispenser Containment Sensor(s). Model:
Shear Valve(s). Shear Valve(s).
Dispenser Containment F7oat(s) and Chain(s). Dispenser Containment Float(s) and Chain(s).
If the facility contains more tanks or dispensers, copy this form, Include information for every tank and dispenser at the facility.
C. Certification - I certify that the equipment identified in this document was inspected/serviced in accordance with the manufacturers'
guidelines. Attached to this Certification is information (e.g. manufacturers' checklists) necessary to verify that this information is
correct and a Plot Plan showing the layout of monitoring equipment. For any equipment capable of generating such reports, I have also
attached a copy of the report; (check all that apply): ® System set -up ® Alarm history report
Technician Name (print): Jerry Rangel Signature:
Certification No.: ICC# 5309489 -UT V/R #B35460 License. N .. 5328 A -haz
Testing Company Name: Redwine Testing Services, Inc. Phone No.: (661) 834 -6993
Site Address: .P.O. Box 1567, Bakersfield. CA. 93302
Page 1 of 3
Date of Testing/Servicing: 2/24 /2011
Monitoring System Certification
D. Results of Testing/Servicing
Software Version Installed: 14.01
Complete the following checklist:
Yes No* Is the audible alarm operational?
Yes No* Is the visual alarm operational?
Yes No* Were all sensors visually inspected, functionally tested, and confirmed operational?
Yes No* Were all sensors installed at lowest point of secondary containment and positioned so that other equipment will
not interfere with their proper operation?
Yes No* If alarms are relayed to a remote monitoring station, is all communications equipment (e.g., modem)
N/A operational?
Yes No* For pressurized piping systems, does the turbine automatically shut down if the piping secondary containment
N/A monitoring system detects a leak, fails to operate, or is electrically disconnected? If yes: which sensors initiate
positive shut -down? (Check all that apply) ® Sump/Trench Sensors; ® Dispenser Containment Sensors.
Did you confirm positive shut -down due to leaks and sensor failure /disconnection? ® Yes; No.
Yes No* For tank systems that utilize the monitoring system as the primary tank overfill warning device (i.e., no
N/A mechanical overfill prevention valve is installed), is the overfill warning alarm visible and audible at the tank
fill point(s) and operating properly? If so, at what percent of tank capacity does the alarm trigger? %
Yes* No Was any monitoring equipment replaced? If yes, identify specific sensors, probes, or other equipment replaced
and list the manufacturer name and model for all replacement parts in Section E, below.
Yes* No Was liquid found inside any secondary containment systems designed as dry systems? (Check all that apply)
Product; Water. If yes, describe causes in Section E, below.
Yes No* Was monitoring system set -up reviewed to ensure proper settings? Attach setup reports, if applicable
Yes No* 1 Is all monitoring equipment operational per manufacturer's specifications?
V In Section E below, describe how and when these deficiencies were or will be corrected.
E. Comments: The monitor was reprogrammed for sensor out. UDC sensors were not tested due to access issues.
There is no overfill alarm outside the building (no flappers on the drop tubes either).
Page 2 of 3
Mohitoring System Certification
F. In -Tank Gauging / SIR Equipment: N Check this box if tank gauging is used only for inventory control.
Check this box if no tank gauging or SIR equipment is installed.
This section must be completed if in -tank gauging equipment is used to perform leak detection monitoring.
Complete the following checklist:
Yes No* Has all input wiring been inspected for proper entry and termination, including testing for ground faults?
Yes No* Were all tank gauging probes visually inspected for damage and residue buildup?
Yes No* Was accuracy of system product level readings tested?
Yes No* Was accuracy of system water level readings tested?
Yes No* Were all probes reinstalled properly?
Yes No* Were all items on the equipment manufacturer's maintenance checklist completed?
In the Section H, below, describe how and when these deficiencies were or will be corrected.
G. Line Leak Detectors (LLD):
Complete the following checklist:
Check this box if LLDs are not installed.
Yes No* For equipment start -up or annual equipment certification, was a leak simulated to verify LLD perfonnance?
N/A Check all that apply) Simulated leak rate: 3 g.p.h.; 0.1 g.p.h ; [10.2 g.p.h.
Yes No* Were all LLDs confirmed operational and accurate within regulatory requirements?
Yes No* Was the testing apparatus properly calibrated?
Yes No* For mechanical LLDs, does the LLD restrict product flow if it detects a leak?
N/A
Yes No* Foi- electronic LLDs, does the turbine automatically shut off if the LLD detects a leak?
N/A
Yes No* For electronic LLDs, does the turbine automatically shut off if any portion of the monitoring system is disabled
N/A or disconnected?
Yes No* For electronic LLDs, does the turbine automatically shut off if any portion of the monitoring system malfunctions
N/A or fails a test?
Yes No:' For electronic LLDs, have all accessible wiring connections been visually inspected?
N/A
Yes No* Were all items on the equipment manufacturer's maintenance checklist completed?
In the Section H, below, describe how and when these deficiencies were or will be corrected.
H. Comments: LLDs re not tested at this time due to across iss gg,
Page 3 of 3
Spill Bucket Testing Report Form
SWRCB, January 2006
Thisform is intended for use by contractors performing annual testing of USTspill containment structures. The completedform and
printouts from tests (if applicable), should be provided to thefacility owner /operator for submittal to the local regulatory agency.
1. FACILITY INFORMATION
Facility Name: HP Go -Go I Date of Testing: 02/24/11
Facility Address: 430 E. California Ave, Bakersfield, CA 93304
Facility Contact: Alondra Phone: 661 - 835 -8044
Date Local Agency Was Notified of Testing : 02/10/11
Name of Local Agency Inspector (ifpresent during testing):
2. TESTING CONTRACTOR INFORMATION
Company Name: Redwine Testing Services, Inc.
Technician Conducting Test: Jerry Rangel
Credentials': CSL.B Contractor ICC Service Tech. SWRCB Tank Tester Other (Specifi,)
License Number(s): Contractors Lic. 532878 A -Haz ICC# 5309489 -UT
3. SPILL BUCKET TESTING INFORMATION
Test Method Used: Hydrostatic Vacuum Other
Test Equipment Used: INCON TS -STS Equipment Resolution: 0.0000 in.
Identify Spill Bucket (BY Tank
Number, Stored Product, etc.)
UNL 87 FILL UNL 87 VAPOR UNL 91 FILL UNL 91 VAPOR
Bucket Installation Type: Direct Bury
Contained in Sump
Direct Bury
Contained in Sump
Direct Bury
Contained in Sump
Direct Bury
Contained in Sum
Bucket Diameter: 11 l I 11 11
Bucket Depth: 10 11 131/2 13 1/2
Wait time between applying
vacuum/water and start of test:
30 min 30 min 30 min 30 min
Test Start Time (Ti): 9:30 am 9:30 am 9:30 am 9:30 am
Initial Reading (R,): N/A 81/4 8'/2 93/4
Test End Time (T,:): 10:30 am 10:30 am 10:30 am 10:30 am
Final Reading (Rr): N/A 8 3/ 8' /s 93/4
Test Duration (TF — Tt): 1 hour 1 hour 1 hour 1 hour
Change in Reading (RF -R,): N/A None None None
Pass/Fail Threshold or
Criteria: No Drop in level No Drop in level No Drop in level No Drop in level
Test: Result Pass X Fatl X;tP,ass" Fatl'' X Pass Fail;; , X Pass; Fail `
Comments — (include information on repairs made prior to testing, and reconT.mendedfollow -up forfailed tests)
87 fill bucket is a visual failure, fill adaptor is not sealed to the fill riser.
CERTIFICATION OF TECHNICIAN RESPONSIBLE FOR CONDUCTING THIS TESTING
I hereby certify that all the information contained in this report is true, accurate, and infull compliance with legal requirements.
Technician's Signa Date:_02 /24/ 11
State laws and regulations do not currently require testing to be performed by a qualified contractor. However, local requirements
may be more stringent.
SYSTEM SETUP
FEB 24, 2011 10:39 AM
SYSTEM UNITS
U.S
SYSTEM LANGUAGE
ENGLISH
SYSTEM DATE 'TIME F,`Rt "lAT
MON DD YYYY HH :111: SS xt °1
HP 925 GO GO MARKET
430 E.CALIFORNIA AVE
BAKERSFIELD CA 93304
661 - 861 -8505
SHIFT TIME 1 DISABLED
SHIFT TIME 2 DISABLED
S H I FT TI 11E :3 : DISABLED
SHIFT TIME 4 DISABLED
PERIODIC TEST WARNINGS
DISABLED
ANNUAL TEST WARNINGS
DISABLED
PRINT TC VOLUI,IE
ENABLED
TEMP COMPENSATION
VALUE (DEG F ): 60.0
SYSTEM SECURITY
CODE : 000000
LEAK TEST t °IETHoD
TEST ON DATE : ALL TANK
JAN 1, 1996
START TIME : DISABLED
TEST RATE :0.20 GAL!HR
DURATION . 2 HOURS
LEAK TEST REPORT FORMAT
NORMAL
LIQUID SENSOR SETUP
IN-TANK SETUP - - - - - - - - - - - -
L 1:1 -2 DISP
TRI -STATE (SINGLE FLOAT)
T I:PREM CATEGORY : DISPENSER PAN
PRODUCT CODE 1
THERMAL COEFF :.000700
TANK DIAMETER 95.75
TANI' PROFILE 1 PT L 2:3-4 'DISP
FULL VOL 10152 TRI -STATE (SINGLE FLOAT)
CATEGORY : DISPENSER PAN
FLOAT SIZE: 4.0 I IV 8496
L 8:87 STP
WATER WARNING 2.0 L 3:5 -6 DISP
HIGH WATER. LIt "IIT: 3.0 TRI -STATE (SINGLE FLOAT)
OVERFILL LIMIT
CATEGORY :
CATEGORY : DISPENSER PAN
MAX. OR LABEL VOL: 10152
OVERFILL LIMIT 90%
913E
TANK DIAMETER
HIGH PRODUCT 95% L 4:91 FILL
TANK PROFILE
9644 TRI- STATE (SINGLE FLOAT)
DELIVERY LIMIT 10 %. CATEGORY : OTHER SENSORS
CATEGORY :
1015
R 1:POSITIVE SHUT
LOW PRODUCT 500
TYPE:
LEAK ALARM LIMIT: 99 L 5:87 FILL
SUDDEN LOSS LIMIT: 50 TRI -STATE (SINGLE FLOAT)
TANK TILT 0.00 CATEGORY : OTHER SENSORS
MANIFOLDED TANKS
T #: NONE
LIQUID SENSOR ALMS
DELIVERY DELAY : 15 1.11N
L 6:91 STP
DELIVERY DELAY : 15 I'll N TRI -STATE (SINGLE FLOAT)
CATEGORY : STP SUI "IP
L 7:91 ANN
TRI -STATE (SINGLE FLOAT)
CATEGORY : ANNULAR SPACE
FLOAT SIZE: 4.0 IN. 8496
WATER WARNING 2.0
L 8:87 STP
HIGH WATER LIh9IT: 3.0
TRI -STATE SINGLE FLOAT)
T 2:UNLEADED
OVERFILL LIMIT
CATEGORY : STP SUMP
PRODUCT CODE
18134
HIGH PRODUCT
THERMAL COEFF :.000700
19141
TANK DIAMETER 113.75 L 9:87 ANN
TANK PROFILE 1 PT TRI -STATE SINGLE FLOAT)
FULL VOL 20149 CATEGORY : ANNULAR SPACE
FLOAT SIZE: 4.0 IN. 8496
WATER WARNING 2.0
HIGH WATER LIh9IT: 3.0
MAX OR LABEL VOL: 20149
OVERFILL LIMIT 90%
18134
HIGH PRODUCT 95%
19141
DELIVERY LIMIT 101/0
2014 OUTPUT RELAY SETUP
LOW PRODUCT 500
LEAK ALARM LIMIT: 99 R 1:POSITIVE SHUT
SUDDEN LOSS LIMIT: 99 TYPE:
TANK, TILT 0.00 STANDARD
NORMALLY CLOSED
MANIFOLDED TANKS
T #: NONE
LIQUID SENSOR ALMS
DELIVERY DELAY : 15 1.11N ALL:FUEL ALARM
ALL:SENSOR OUT ALARM
ALARM HISTORY REPORT
SYSTEM ALARM
PAPER OUT
FEB 11, 2011 9:02 All
PRINTER ERROR
FEB 1 1 , 2011 9:02 AP9
BATTERY IS OFF
JAN 1, 1996 8:00 All.
ALARM HISTORY REPORT
I N- TAr0JK ALARM -
T 1:PREM
SETUP DATA WARNING
ALARM
JAN 1. 1996 8:58 Arl
OVERFILL ALARRll
2005
FEB 24, 2011 9:42 All
LOW PRODU, T LHRr °I
FEB 24,
FEB 7. 0 1 1 r: i' :; F P9
JAN 201 1 1 '_ : ii Fr1
DEC ilir=
PM
1'P'i
HIGH PRODUCT
12:15
ALARM
FEB 10,
FEB 24, 2011 9:42 AM
INVALID FUEL LEVEL
FEB 24.
FEB '24. 2011 9:41 All
FEB 7. 2011 6:09 PM
JAN 29, 2011 5:56 PNl
PROBE OUT
FEB 24, 2011 9:40 AN
JAN 1, 1996 8:59 All
JAN 1, 1996 8:32 All
DELIVERY NEEDED
FEB 24, 2011 9:40 All
FEB 17, 2011 3:22 PM
FEB 8. 2011 11:18 All
MAX PRODUCT ALARM
FEB 24. 2011 9:42 All
ALARM HISTORY REPORT
IN-TAN}; ALARM -
T :UNLEADED
OVERFILL ALARM
FEB 24, 2011 9:44 All
NOV 17, 2005 4:44 PM
HIGH PRODUCT
OCT 17, 2008
ALARM FUEL ALARM
FEB 24, 2011 9:44 All
INVALID FUEL LEVEL
FEB 17, 2011 3:05 PM
FEB 14, 2011 12:15 PM
FEB 10, 2011 1:53 P11
PROBE OUT
FEB 24. 2011 9:39 All
DELIVERY NEEDED
FEB 22, 2011 8:01 P11
FEB 16, 2011 4:32 PM
FEB 13, 2011 10:43 All
MAX PRODUCT ALARM
FEB 24, 2011 9:44 All
ALARM HISTORY REPORT
SENSOR ALARM:---- -
L 1:1 -2 DISP
DISPENSER PAN
FUEL ALARM
OCT 13, 2009 9:17 All
FUEL ALARM
OCT 13, 2009 9:09 All
SENSOR OUT ALARM
OCT 17, 2006 10:39 All
ALARM HISTORY REPORT
SENSOR ALARM _ - - --
L 2:3 -4 DISP
DISPENSER PAN
FUEL ALARM
OCT 13, 2009 9:18 All
SENSOR OUT ALARM
OCT 17, 2008 10:39 AM
FUEL ALARM
OCT 17, 2008 10:38 All
ALARM HISTORY REPORT
SENSOR ALARM - - - --
L 3:5 -6 DISP
DISPENSER PAN
FUEL ALARM
OCT 13, 2009 9:19 All
SENSOR OUT ALARM
OCT 17, 2008 10:39 AM
FUEL ALARM
OCT 17, 2008 10:38 All
ALARM HISTORY REPORT
SENSOR ALARM - - - --
L 4:91 FILL
OTHER SENSORS
FUEL ALARM
FEB 24, 2011 9:59 All
FUEL ALARM
OCT 13, 2009 9:20 AM
FUEL ALARM
OCT 17, 2008 10:46 All
ALARM HISTORY REPORT
SENSOR ALARM - - - --
L 5:87 FILL
OTHER SENSORS
FUEL ALARM
FEB 24, 2011 9:52 AM
SETUP DATA WARNING
DEC. 18, 2010 5:38 PM
FUEL ALARM
DEC 18, 2010 4:17 PM
ALARM HISTORY REPORT
SENSOR ALARM - - - --
L 6:91 STP
STP SUMP
FUEL ALARM
FEB '24, 2011 9:56 All
FUEL ALARM
OCT 13, 2009 9:22 All
SENSOR OUT ALARM
OCT 17, 2008 10:39 AM
ALARI"1 HISTORY REPORT
SENSOR ALARM - - - --
L 7:91 ANN
ANNULAR SPACE
FUEL ALARM
FEB 24, 2011 10:28 All
FUEL ALARM
OCT 13, 2009 924 All
SENSOR OUT ALARM
OCT 17, 2008 10 :39 AM
ALARM HISTORY REPORT
SENSOR ALARM - - - --
L 8:87 STP
STP SUMP
FUEL ALARM
FEB 24, 2011 9:54 APM
FUEL' ALARM
OCT 13, 2009 9 :23 AM
SENSOR OUT ALARH
OCT 17, 2008 10 :39 Al
ALARM HISTORY REPORT
SENSOR ALARM - - - --
L 9:87 ANN
ANNULAR SPACE
SENSOR OUT ALARM
FEB 24, 2011 10:38 AM
SENSOR OUT ALARM
FEB 24, 2011 10:33 All
FUEL ALARM
FEB 24, 2011 10:30 All
ALARM HISTORY REPORT
SENSOR ALARM - - - --
L10:
OTHER SENSORS