HomeMy WebLinkAbout430 CALIFORNIA AVENUE (4)MONITORING SYSTEM CERTIFICATION
For Use By All Jurisdictions Within the Slate ofCalifornia
Authority Cited: Chapter 6 7, Health and Safety Code; Chapter 16, Division 3, Title 23, California Code ofRegulations
This form must be used to document testing and servicing of monitoring equipment. A separate certification or report must be
prepared for each monitoring system control panel by the technician who performs the work. A copy of this form must be provided
to the tank system owner /operator. The owner /operator must submit a copy of this form to the local agency regulating UST systems
within 30 days of this date.
A. General Information
Facility Name: HP Go Go
Site Address: 430 East California Avenue
Facility Contact Person: Alondra Hernandez
Make /Model of Monitoring System: Veeder -Root TLS -350
B. Inventory of Equipment Tested /Certified
Check the appropriate boxes to indicate specific equipment Inspected /serviced:
City: Bakersfield
Bldg. No.:
Zip: 93306
Contact Phone No.: 835 -8044 (0279)
Date of Testing/Servicing: 4/7/2011
Tank ID: 10000 gal. Regular Tank ID: 10000 gal. Super
U In -Tank Gauging Probe. Model: 847390 -107 x] In -Tank Gauging Probe. Model: 847390 -107
x] Annular Space or Vault Probe. Model: 794390-409 X] Annular Space or Vault Sensor. Model: 794390 -409
rx] Piping Sump / Trench Sensor(s). Model: 794380 -208 Piping Sump / Trench Sensor(s). Model: 794380 -208
U Fill Sump Sensor(s) Model: 794380 -208 X] Fill Sump Sensor(s). Model: 78380 -208
Lx I Mechanical Line Leak Detector. Model: STP -MAD X] Mechanical Line Leak Detector. Model: FX1y
Electronic Line Leak Detector. Model: Electronic Line Leak Detector. Model:
Cx1 Tank Overfill / High Level Sensor. Model: 794390 -107 U Tank Overfill / High Leval Sensor. Model: 794390 -107
Other (specify equip. type and model in Sec. E on Pg. 2) Other (specify equip. type and model in Sec. E on Pg. 2)
Tank ID: Tank 1D:
In -Tank Gauging Probe. Model: In -Tank Gauging Probe. Model:
Annular Space or Vault Sensor. Model: Annular Space or Vault Sensor. Model:
Piping Sump / Trench Sensor(s). Model: Piping Sump / Trench Sensor(s). Model:
Fill Sump Sensors(s). Model: Fill Sump Sensor(s). Model:
D Mechanical Line Leak Decector. Model: Mechanical Line Leak Detector. Model:
Electronic Line Leak Detector. Model: Electronic Line Leak Detector. Model:
Tank Overfill / High Level Sensor. Model: Tank Overfill / High Level Sensor. Model:
Other (specify equip. type and model in Sec. E on Pg. 2) Other (specify equip. typs and model in Sec. E on Pg. 2)
Dispenser ID: 1 & 2 Dispenser ID: 3&4
x-1 Dispenser Containment Sensor(s). Model: 794380 -208 x] Dispenser Containment Sensor(s). Model: 794380 -208
X] Shear Valve(s). LX] Shear Valve(s).
Dispenser Containment Float(s) and Chain(s). Dispenser Containment Float(s) and Chain(s)
Dispenser ID: 5 & 6 Dispenser ID:
Lx] Dispenser Containment Sensor(s). Model: 794380 -208 Dispenser Containment Sensor(s). Model:
Lx] Shear Valve(s). Shear Valve(s).
Dispenser Containment Float(s) and Chains(s). Dispenser Containment Float(s) and Chain(s).
Dispenser ID: Dispenser ID:
Dispenser Containment Sensor(s). Model: Dispenser Containment Sensor(s). Model:
Shear Valve(s). Shear Valve(s).
Dispenser Containment Float(s) and Chain(s) Dispenser Containment Float(s) and Chain(s).
If the facility contains more tanks or dispensers, copy this.form. Include information for every tank and dispenser at the facility.
C. Certification - I certify that the equipment identified in this document was inspected /services in accordance with the
manufacturers' guidlines. Attached to this Certification is information (e.g. manufacturers' checklist) necessary to varify that
this information is correct and a plot plan showing the layout of monitoring equipment. For equipment capable of generating
such reports, I have attached a copy of the report; (check all that apply) Q Systee Set -up Alarm history report
Technician Name (print): Edward Mitchell Signature: ZM41 (
Certification No: B34472 License No: 804904
Testing Company Name: Confidence UST Services, Inc.
Site Address: 430 East California Avenue, Bakersfield, Ca 93306
Phone No: 800- 339 -9930
Date of Testing/Servicing: 41712011
D. Results of Testing/Servicing
Software Version Installed:
Complete the following checklist:
x] Yes No* Is the audible alarm operational?
x Yes No* s e Visual alarm operational?
x Yes No* Were all sensors visually inspected, functionally tested, and confirmed operational?
x Yes No* Were all sensors installed at the lowest point of secondary containment and positioned so that other
equipment will not interfere with their proper operation?
Yes No* If alarms are relayed to a remote monitoring station, is all communications equipment (e.g. modem) Hx N/A operational?
x Yes No* For pressurized piping systems, does the turbine automatically shut down ifthe piping secondary
N/A containment monitoring system detects a leak, fails to operate, or is electrically disconnected? If yes:
which sensors initate positive shut -down? U Sump/Trench Sensors [x:] Dispenser Containment Sensors
Did you confirm positive shut -down due to leaks and sensor failure /disconnected? [x] Yes; No;
U Yes No* For tank systems that utilize the monitoring system as the primary tank overfill warning device (i.e. no
r] N/A mechanical overfill prevention valve is installed), is the overfill warning alarm visual and audible at
the tank fill point(s) and operating properly? If so, at what percent of tank capasity does the alarm
trigger? 90 I %
E Yes* No Was any monitoring equipment replaced? IfYes, identify specific sensors, probes, or other equipment
replaced and list the manufacturer name and model for all replacement parts in Section E, below.
Yes* U No Was liquid found inside any secondary containment systems designed as dry systems?
Product; Water. If yes, describe causes in Section E, below.
Tx N * Was monitoring system set -up reviewed to ensure proper settings? Attach set -up reports, if applicable.
x yes No* I Is all monitoring equipment operational per manufacturer's specifications?
In Section E below, discribe how and when these deficiencies were or will be corrected.
E. Comments: Premium Fill Spill Bucket failed.
Replaced the Spill Bucket on Regular and the Fill Adapter on Regular Fill.
F. In -Tank Guaging / SiR Equipment: [x] Check this box iftank guaging is used only for inventory control.
Check this box if tank guaging or SIR equipment is installed.
This section must be completed if in -tank guaging equipment is used to perform leak detection monitoring.
Complete the following checklist:
U Yes No* Has all input wiring been inspected for proper enter and termination,including testing for ground faults?
x Yes No* Were all tank guaging probes visually inspected for damage and residue buildup?
Ix Yes No* Was accuracy of system product level readings tested?
Fxj Yes No* Was accuracy of system water level readings tested?
x Yes No* Were all probes reinstalled properly?
E Yes No* I Were all items on the equipment manufacturer's maintenance checklist completed?
In the Section H, below, describe how and when these deficiencies were or will be corrected.
G. Line Leak Detectors (LLD): Check this box if LLD's are not installed.
Complete the following checklist:
Cx] Yes No* For equip. start-up or annual equipment certification, was a leak simulated to varify LLD performance?
Check all that apply) Simulated leak rate: 3 g.p.h.: 0.1 g.p.h.; 0.2 g.p.h.;
x Yes No* Were all LLD's confirmed operational and accurate within regulatory requirments?
x Yes No Was the testing apparatus properly calibrated?
Yes No For mac anica LLD's, does the LLD restrict product flow if it detects a leak?
N/A
Yes No* For electronic LLD's, does the turbine automatically shut off ifthe LLD detects a leak?
x] N/A
Yes 7 No* For electronic LLD's, does the turbine automatically shut off if any portion of the monitoring system is
x] N/A disabled or disconnected?
Yes No* For electronic LLD's, does the turbine automatically shut off if any portion of the monitoring system
Lx] N/A malfunction or fails a test?
Yes No* For electronic LLD's, have all accessible wiring connections been visually inspected?
U N/A
x Yes I ONo I Were all items on the equipment manufacturer's maintenance checklist completed?
In the section H, below, describe how and when these deficiencies were or will be corrected.
H. Comments:
HP 925 GO GO MARKET
430 E.CALIFORNIA AVE
BAKERSFIELD CA 93304
661 -861 -8505
APR 7. 2011 1:12 PM
SYSTEM STATUS REPORT
T 1:DELIVERY NEEDED
T 2:DELIVERY NEEDED
HP 925 GO GO MARKET
430 E.CALIFORNIA AVE
BAKERSFIELD CA 93304
661 -861 -8505
APR 7. 2011 1:13 PM
SYSTEM STATUS REPORT
T 1:DELIVERY NEEDED
T 2 :1)EL I VERY NEEDED,
INVENTORY REPORT
T I.:PREM
VOLUME - '739 GALS
ULLAGE - 9413 GALS
90% ULLAGE- 8397 GALS
TC VOLUME - 728 GALS
HEIGHT - 12.04 INCHES
WATER VOL - 0 GALS
WATER - 0.00 INCHES
TEMP - 80.5 DEG F
T 2:UNLEADED
VOLUME - 1743 GALS
ULLAGE - 18406 GALS
903. ULLAGE- 16391 GALS
TO VOLUME - 1727 GALS
HEIGHT - 16.10 INCHES
WATER VOL - 0 GALS
WATER. - 0.00 INCHES
TEMP - 72,8 DEG F
0 x w w W END x x x x x
ALARM HISTORY REPORT
SENSOR ALARM - - - --
L 1:1 -2 DISP
DISPENSER PAN
FUEL ALARM
OCT 13. 2009 9:17 AM
FUEL ALARM
OCT 13. 2009 9:09 AM
SENSOR OUT ALARM
OCT 17. 2008 10:39 AM
ALARM HISTORY REPORT
SENSOR ALARM - - - --
L 2:3 -4 DISP
DISPENSER PAN
FUEL ALARM
OCT 13. 2009 9 :18 AM
SENSOR OUT ALARM.
OCT 17. 2008 10:39 AM
FUEL ALARM
OCT 17. 2008 10:36 AM
ALARM HISTORY REPORT
SENSOR ALARM - - - --
L 3:5 -6 DISP
DISPENSER PAN
FUEL ALARM
OCT 13, 2009 9:19 AM
SENSOR OUT ALARM
OCT 17,2008 10:39 AM
FUEL ALARM
OCT 17. 2008 10:38 AM
ALARM HISTORY.REPORT
SENSOR ALARM - - - --
L 4:91 FILL
OTHER SENSORS
FUEL ALARM
FES 24. 2011 9:59 AM
FUEL ALARM
OCT 13, 2009 9:20 AM
FUEL ALARM
OCT 17. 2008 10:46 AM
ALARM HISTORY REPORT
SENSOR ALARM
L 5:87 FILL
OTHER SENSORS
FUEL ALARM
APR 3. 2011 9 :37 PM
SETUP DATA WARNING
MAR 22, 2011 6:46 AM
FUEL ALARM
MAR 20, 2011 6 :42 PM
ALARM HISTORY REPORT
SENSOR ALARM - - - --
L 6:91 STP
STP SUMP
FUEL ALARM
FEB.24. 2011 9:56 AM
FUEL ALARM
OCT 13. 2009 9:22 AM
SENSOR OUT ALARM
OCT 17. 2008 10:39 AM
ALARM HISTORY REPORT
SENSOR ALARM
L 7:91 ANN
ANNULAR SPACE
FUEL ALARM
FEB 24. 2011 10:28 AM
FUEL ALARM
OCT 13 2009 9:24 AM
SENSOR OUT ALARM
OCT 17, 2008 10 :39 AM
ALARM HISTORY REPORT
SENSOR ALARM - - - --
L 8:87 STP
STP SUMP
FUEL ALARM
FEB 24. 2011 9:54 AM
FUEL ALARM
OCT 13. 2009 9:23 AM
SENSOR OUT ALARM
OCT 17. 2008 10:39 AM
ALARM HISTORY REPORT
SENSOR ALARM - - - --
L 9:87 ANN
ANNULAR SPACE
SENSOR OUT ALARM
F£S 24. 2011 10:38 AM
SENSOR OUT ALARM
FES.24. 2011 10:33 AM
FUEL. ALARM
FEB 24. 2011 10:30 AM
ALARM HISTORY REPORT
SENSOR ALARM - - - --
L10:
OTHER SENSORS
ALARM HISTORY REPORT
SENSOR ALARM -
L11:
OTHER SENSORS
ALARM HISTORY REPORT
SENSOR ALARM - - - --
L12
OTHER SENSORS
ALARM HISTORY REPORT
E[ENSOR ALARM - - - --
L13:
OTHER SENSORS
ALARM HISTORY REPORT
SENSOR ALARM --- --
LI4:
OTHER SENSORS
ALARM HISTORY REPORT
SENSOR ALARM - - - --
L15:
OTHER SENSORS
ALARM HISTORY REPORT
SENSOR ALARM - - - --
L16:
OTHER SENSORS
SYSTEM SETUP
APR 7. 2011 113 PM
SYSTEM UNITS
U.S.
SYSTEM LANGUAGE
ENGLISH
SYSTEM DATE /TIME FORMAT
MON DD YYYY HH:MM:SS xM
HP 925 GO GO MARKET
430 E.CALIFORNIA AVE
BAKERSFIELD CA 93304
661- 861 -8505
SHIFT TIME I : DISABLED
SHIFT TIME 2 : DISABLED
SHIFT TIME 3 : DISABLED
SHIFT TIME 4 : DISABLED
PERIODIC TEST WARNINGS
DISABLED
ANNUAL TEST WARNINGS
DISABLED
PRINT TC VOLUMES
ENABLED
TEMP COMPENSATION
VALUE (DEG F f: 60.0
SYSTEM SECURITY
CODE : 000000
COMMUNICATIONS SETUP
PORT SETTINGS:
NONE FOUND
RS -232 SECURITY
CODE : 000000
RS -232 END OF MESSAGE
DISABLED
1N -TANK SETUP
T I:PREM
PRODUCT CODE. 1
THERMAL COEFF :.000700
DIAMETER 95•PTTANK
TANK PROFILE
FULL VOL 10152
FLOAT SIZE: 4.0 IN. 8496
i MATER WARNING 2.0
HIGH WATER LIMIT: 3.0
MAX OR LABEL VOL: 10152
OVERFILL LIMIT :
g90y:
HIGH PRODUCT 95U
9644
DELIVERY LIMIT
1105
LOW PRODUCT 500
99LEAKALARMLIMIT:
SUDDEN LOSS LIMIT: 50
TANK TILT 0.00
p1ANIFOLDED TANKS
Td: NONE
DELIVERY DELAY 15 MIN
T!2 :UNLEADED
PRODUCT CODE. 2
THERMAL COEFF :.000700
TANK DIAMETER 113.75
TANK PROFILE 1 PT
f FULL VOL 20149f
SIZE: FLOAT 4.0 IN. 8496
WATER WARNING 2.0
HIGH WATER LIMIT: 3.0
MAX OR LABEL VOL: 20149
OVERFILL LIMIT 90%
1813
HIGH PRODUCT
19141
DELIVERY LIMIT 1031
2014
LOW PRODUCT 500
LEAK ALARM LIMIT: 99
SUDDEN LOSS LIMIT: 99
TANK TILT 0.00
MANIFOLDED TANKS
TO: NONE
DELIVERY DELAY : 15 MIN
1
LEAK TEST METHOD
TEST ON DATE : ALL TANKfJAN1. 1996
START TIME : DISABLED
TEST RATE :0.20 GAL /HR'
DURATION : 2 HOURS
LEAK TEST REPORT FORMAT
NORMAL
LIQUID SENSOR SETUP
L 1:1 -2 DISP
TRI -STATE (SINGLE FLOAT)
CATEGORY : DISPENSER PAN
L 2:3 -4 DISP -
TRI -STATE (SINGLE FLOAT)
CATEGORY : DISPENSER PAN
L 3:5 -6 DISP
TRI -STATE (SINGLE FLOAT)
CATEGORY : DISPENSER PAN
L 4:91 FILL
TRI -STATE (SINGLE FLOAT)
CATEGORY : OTHER SENSORS
L 5 :.87 FILL
TRI -STATE (SINGLE FLOAT)
CATEGORY : OTHER SENSORS
L 6:91 STP
TRI -STATE (SINGLE FLOAT)
CATEGORY : STP SUMP
L 7:91 ANN
TRI -STATE (SINGLE FLOAT)
CATEGORY : ANNULAR SPACE
L 8:87 STP
TRI -STATE (SINGLE FLOAT)
CATEGORY : STP SLOP
L 9:87 ANN
TRI -STATE (SINGLE FLOAT)
CATEGORY : ANNULAR SPACE
OUTPUT RELAY SETUP
R 1:POSITIVE SHUT
TYPE:
STANDARD
NORMALLY CLOSED
LIQUID SENSOR ALMS
ALL:FUEL ALARM
ALL:SENSOR OUT ALARM
4
SENSOR ALARM - - - --
L 8:87 STP
STP SUMP
FUEL ALARM
APR 7. 2011 1:14 PM
SENSOR ALARM - - - --
L 8:87 STP
STP SUMP
FUEL ALARM
APR 7, 2011 1:21 PM
SENSOR ALARM - - - --
L 6:91 STP
STP SUMP
FUEL ALARM
APR 7. 2011 1:22 PM
SENSOR ALARM - - - --
L 7:91 ANN
ANNULAR SPACE
FUEL ALARM
APR 7. 2011 1:23 PM
SENSOR ALARM - - - --
L 7:91 ANN
ANNULAR SPACE
FUEL ALARM
APR 7. 2011 1:24 PI-1
SENSOR ALARM -- - --
L 9:87 AN14
ANNULAR SPACE
FUEL ALARM
APR T. 2011 1:24 PM
i -- - -- SYSTEM ALARM - - - --
PRINTER ERROR
APR 7. 2011 1:31 P11
HP 925 GO GO MARKET
430 E.CALIFORNIA AVE
BAKERSFIELD CA 93304
661 -861 -8505
APR 7, 2011 1:35 PM
SYSTEM STATUS REPORT
T 1:DELIV£RY NEEDED
T 2:DELIVERY NEEDED
HP 925 G0, GO MARKET
430 E XALIFORNIA AVE
BAKERSFIELD CA 93304
661-861-8505
APR 7. 2011 1:35 PM
SYSTEM STATUS REPORT
T (:DELIVERY NEEDED
T 2:DELIVERY NEEDED
ALARM HISTORY REPORT
SENSOR ALARM - - - --
L 1:1 -2 DISP
DISPENSER PAN
SENSOR OUT ALARM
APR 7, 2011 1:30 PM
FUEL ALARM
APR 7 2011 1:25 PM
FUEL ALARM
OCT 13, 2009 9:17 AM
ALARM HISTORY REPORT
SENSOR ALARM - - - --
L 2:3 -4 DISP
DISPENSER PAN
SENSOR OUT ALARM
APR '7. 201'1 1 :30 PM
FUEL ALARM
APR 7. 2911 1:27 PM
FUEL ALARM
OCT 13. 2009 9:10 NM
u
ALARM HISTORY REPORT
SENSOR ALARM - - - --
L 3:5 -6 DISP
DISPENSER PAN
SENSOR OUT ALARM
APR 7, 2011 1:30 PM
FUEL ALARM
APR 7. 2011 1:28 PM
FUEL ALARM
OCT 13, 2009 9:19 All
ALARM HISTORY REPORT
SENSOR ALARM - - - --
L 4:91 FILL
OTHER SENSORS
SENSOR OUT ALARM
APR 7, 2011 1:30 PM
FUEL ALARM
APR 7. 2011 1:28 PM
FUEL ALARM
FEB 24. 2011 9:59 AM
ALARM HISTORY REPORT
SENSOR ALARM
L 5:87 FILL
OTHER SENSORS
SENSOR OUT ALARM
APR 7. 2011 1:30 PM
FUEL ALARM
APR 7, 2011 1:29 PM
FUEL ALARM
APR 3. 2011 9:37 PM
ALARM HISTORY REPORT ALARM HISTORY REPORT
SENSOR ALARM - ---- SENSOR ALARM - - ---
L 6:91 STP L10:
STP SUMP OTHER SENSORS ALARM HISTORY REPORT
SENSOR OUT ALARM
APR 7. 2011 1:30 PM SENSOR ALARM - - - --
L15:
FUEL ALARM OTHER SENSORS
APR 7. 2011 1 :22 PM
FUEL ALARM
FEB 24, 2011 9:56 All
ALARM HISTORY REPORT
7-,SENSOR ALARM - - - --
L11
OTHER SENSORS ALARM HISTORY REPORT
SENSOR ALARM - - - --
L16:
OTHER SENSORS
ALARM HISTORY REPORT
SENSOR ALARM - -- --
L 7 :91 ANN
ANNULAR SPACE
SENSOR OUT ALARM ALARM HISTORY REPORT
APR 7. 2011 1 :30 PM
SENSOR ALARM - - - --
FUEL ALARM L12:
APR 7. 2011 1:24 PM OTHER SENSORS ALARM HISTORY REPORT
FUEL ALARM SENSOR ALARM - - - --
APR 7. 2011 1:23 PM L 1:1-2 DISP
DISPENSER PAN
SENSOR OUT ALARM
APR 7. 2011 1:30 PM
FUEL ALARM
APR 7, 2011 1:25 PM
ALARM HISTORY REPORT
FUEL ALARM
SENSOR ALARM - - - -- OCT 13. 2009 9:17 AM
L13:
ALARM HISTORY REPORT OTHER SENSORS
SENSOR ALARM - - - --
L 8:87 STP
STP SUMP
SENSOR OUT ALARM
APR 7. 2011 1 :30 PM
FUEL ALARM
APR 7. 2011 1:21 PM
ALARM HISTORY REPORT
FUEL ALARM
APR 7, 2011 1:14 PM SENSOR ALARM - ----
L14:
OTHER SENSORS
ALARM HISTORY REPORT
SENSOR ALARM - - - --
L 9:87 ANN
ANNULAR SPACE
FUEL ALARM
APR, 7. 2011 1 :24 PM
SENSOR OUT ALARM
FEB 24.. 2011 10:38 F1M
SENSOR OUT ALARM
FEB 24. 2011 10:33 AM
SWRCB, January 2006
Spill Bucket Testing Report Form
Thisform is intendedfor use by contractors performing annual testing of UST spill containment structures. The completedform and
printoutsfrom tests (ifapplicable), should be provided to thefacility owner /operatorfor submittal to the local regulatory agency.
1. FACILITY INFORMATION
Facility HP Go Go Date of Testing: 4/7/2011
Facility Address: 430 East California Avenue, Bakersfield, Ca 93306
Facility Contact: Alondra Hernandez Phone: 835- 8044 /fax: (0279)
Date Local Agency Was Notified of Testing:
Name of Local Agency Inspector (ifpresent during testing): Ernie Medina
2. TESTING CONTRACTOR INFORMATION
Company Name: Confidence ust service,inc.
Technician Conducting Test: Edward Mitchell
Credentials: El CSLB Contractor x ICC Service Tech. SWRCB Tank Tester Other (Spec)
License Number(s): CSLB: 804904 ICC: 5474332702
3. SPILL BUCKET TESTING INFORMATION
Test Method Used: x Hydrostatic Vacuum Other
Test Equipment Used: Lake Test Equipment Resolution: 0.0625"
Identify Spill Bucket (By Tank
Number, Stored Product, etc.)
1 Regular 2 Premium 3 4
Bucket Installation Type: Direct Bury
Contained in Sump
Direct Bury
Contained in Sump
Direct Bury
Contained in Sump
Direct Bury
Contained in Sum
Bucket Diameter: 10.50" 10.50"
Bucket Depth: 10.00" 10.00"
Wait time between applying
vacuum /water and start of test: 5 min 5 min
Test Start Time (Tj): 1:30 pm 1:30pm
Initial Reading (Rj): 9.00" 9.00"
Test End Time (TF): 2:30pm 2:30pm
Final Reading (RF): 9.00" 7.00"
Test Duration (TF — Ti): 1 Hour 1 Hour
Change in Reading (RF - Ri): 0.00" 2.00"
Pass/Fail Threshold or
Criteria: 0.0625" 0.0625"
Test Result: Pass Fail Pass OO Fail Pass Fail Pass Fail
Comments — (include information on repairs made prior to testing, and recommendedfollow -upforfailed tests)
CERTIFICATION OF TECHNICIAN RESPONSIBLE FOR CONDUCTING THIS TESTING
I hereby certify that all the information contained in this report is true, accurate, and in full compliance with legal requirements
Technician's Signature- _ Q Date: 4/7/2011
State laws and regulations do no t currently require testing to be performed by a qualified contractor. However, local requirements
may be more stringent.
4O ,
OfID4
U fV
CM 11 nMUKr Invoice No.: 26334
HP Go Go
430 East California Avenue
Bakersfield, CA 93306
Repairs completed:
Replaced Regular Fill Spill Bucket and Regular Fill Adapter
Required Repairs, Still Pending:
Premium Fill Spill Bucket needed to be replaced.
Technician Name: Edward Mitchell
Signature: -
Date: 417/2011