Loading...
HomeMy WebLinkAbout CUPA 6-12-19BAKERSFIELD FIRE DEPARTMENT Prevention Services Division Underground Storage Tank Program 2101 H Street DW Inspection Report Bakersfield, CA 93301 Permission to Inspect: Cil' kw r Phone: 661-326-3979 Fax: 661-852-2171 Business Name: Valley Plaza Arco 15-021-105646 Date:6-12-2019 CAL000330203 [Address Name: 3220 Ming Ave Bakersfiels Ca, 93304 Inspector Name: Peter Armagost #8856813 Inspection Type: Routine Report: Final NVO = No Violation Observed OUT = Out of Compliance NA = Not Applicable UD = Undetermined COS = Corrected On Site RPT = Repeat Violation Program Requirement ° .o SOC Comments Violation No 0 �' o •° z o z` = o> File Review Facility Tank Information 2030021 Facility has a valid Permit Tank 1 -20000 -REG -DW to Operate from the Tank 2 -10000 -REG -DW CUPA - 23 CCR 16 2712(i); ® ❑ ❑ ❑ ❑ ❑ None Tank 3 -12000 -PRM -DW HSC 6.7 25284 UST Operating Permit CERS submittals not accepted 2010010 Application for Facility information and Tank ❑ ® E] ❑ F] E]None information submitted/maintained - 23 CCR 16 2711; HSC 6.7 25286(a Invalid BOE number 2010001 Current BOE number submitted to the CUPA ❑ ® ❑ ❑ ❑ ❑ None and/or CERS - HSC 6.7 25286(c) 2030011 UST compliance statement and/or Designated Operator ® ❑ ❑ ❑ [� None current certification submitted - 23 CCR 16 2715(a), 2715(b 2030046 A complete and accurate response plan has been submitted, approved and ® ❑ ❑ ❑ ❑ ❑ None maintained - 23 CCR 16 2632, 2634(e), 2641(h), 2712(i-) 2030041 A complete and accurate plot plan has been submitted, approved and ® El ❑ ❑ ❑ ❑ Minor maintained - 23 CCR 16 2632 d 1 C, 2711 a( 2010006 Owner/Operator has not made false statements or ® ❑ ❑ ❑ ❑ ❑ None representation on any required document - HSC 6.7 25299 2010003 Owner/Operator has a DO and/or informed the CUPA of any change (s) ® ❑ El ❑ F ] None within 30 days - 23 CCR 16 2715(a) Violation Program Requirement w.. o SOC Comments No o _ Q, o o a 0.o z o z v �' o> Testing 2030002 Owner/Operator has tested and certified leak ® ❑ ❑ ❑ ❑ ❑ None detection equipment annual) - 23 CCR 16 2638 2030048 Secondary containment testing conducted every 36 months in accordance ® ❑ ❑ ❑ ❑ ❑ None with requirements - 23 CCR 16 2637 2030055 Spill buckets have been tested annually as ® ❑ ❑ ❑ ❑ ❑ None req wired - HSC 6.7 25284.2 2010009 Secondary containment test results submitted to the CUPA within 30 days ® ❑ ❑ ❑ ❑ ❑ None after the test - 23 CCR 16 2637(e) 2030064 CUPA was poperly notified within the prescribed number of ® ❑ ❑ ❑ ❑ ❑ None hours prior to testing - 23 CCR 16 26370, 2638(e), 2643(g), 2644.1(a)(4) Install/Repair 2060009 Permits obtained to install, replace, repair, or ® ❑ ❑ E] F-1 E] None modify part of the UST system - 23 CCR 16 2712 UST System Observation General Monitoring 2030003 Leak detection system maintains continuous RD monitoring that activates® ❑ ❑ ❑ 7 E] None ❑ an audible and visual Yes alarm - 23 CCR 16 2632, 2634, 2636, 2666 2030016 The annular space of the tank, piping and sumps RD are continuously monitored and activates ® ❑ ❑ ❑ ❑ ❑ None ❑ the alarm - 23 CCR 16 Yes 2631(g), 2632(c)(2)(A)&(8), 2633(c), 2636 2030017 Product piping outside the UDC is fail-safe and shuts down the pump or ® ❑ ❑ E:] F-10 None restricts flow - 23 CCR 16 2636(0 (5) 2030018 Turbine sump monitor RD activates an audible and visual alarm or stops the ® ❑ ❑ ❑ ❑ ❑ None E:] flow of at the dispenser - Yes 23 CCR 16 2636 (1 Underground Storage Tank Program - DW Inspection Report v 2.0 Violation Program Requirement a o SOC Comments No O (1)E— ' o o> z o z o ° 2030019 Monitoring system in the U DCs activates an audible and visual alarm ® ❑ ❑ ❑ ❑ ❑ None or stops the flow at the UDC -23 CCR 16 2636(f)(1) 2030043 Leak detection equipment RD properly programmed or ® ❑ ❑ ❑ ❑ ❑ None ❑ properly operated - 23 CCR 16 2632, 2634, 2636, Yes 2666 2060005 System constructed with a monitoring system capable of detecting entry ® ❑ ❑ ❑ ❑ ❑ None into secondary containment - HSC 6.7 25291 b 2060014 Correct leak detection equipment installed for RD the type of system ® ❑ ❑ ❑ ❑ ❑ None ❑ present - 23 CCR 16 2638; Yes HSC 6.7 25290.1, 25290.2, 25291 RD 2060015 Sensor located in the proper position/location - ® 0 ❑ ❑ ❑ ❑ None ❑ 23 CCR 16 2630(d), 2641(a) Yes 2030062 Facility is in compliance RD L- 13 sensor was programmed to show closed. with not tampering with or disabling leak detection ❑ ® ❑ ❑ ❑ ❑ None ❑ Replace and retest the sensor devices or alarms - HSC Yes 6.7 25299 a 9) 2060022 System constructed with a monitoring system capable of detecting entry ® ❑ ❑ ❑ None into secondary containment - HSC 6.7 25290.2(d) 2030034 Tag/sticker on affixed monitoring equipment being certified, repaired, ® ❑ ❑ ❑ ❑ ❑ None or replaced - 23 CCR 16 2638 VPH Monitoring VPH 2030065 Interstitial monitoring of RD Vent Box was leaking brine fluid. Repair vent box and retest using a the annular spaces of the ❑ ® ❑ ❑ ❑ ❑ None ❑ third party contractor. UST is properly maintained - HSC 6.7 Yes 25290.1 e 2060023 System constructed with a monitoring system capable of detecting entry into secondary El❑ ® ❑ ❑ ❑ None containment - HSC 6.7 25290.1(d) Underground Storage Tank Program - DW Inspection Report v 2.0 Violation Program Requirement 0.2 SOC Comments No o _ Q o o a CDCO L— z_ o Z o> Line Leak Detector 2060012 Line leak detector installed on pressurized RD piping system - HSC 6.7 ❑ ❑ ® ❑ ❑ ❑ None ❑ 25290.1(h), 25290.2(8), Yes 25291(1), 25292(e), 2636(0(2)... 2030026 Line leak detectors detect a 3 gph leak and/or RD audible and visual alarm ❑ ® ❑ ❑ ❑ None ❑ function properly - 23 Yes CCR 16 2636(0(6), 2666(c) Turbine shuts down when RD 2030027 a leak is detected or when line leak detector is ❑ ❑ ® ❑ ❑ ❑ None ❑ disconnected - 23 CCR 16 Yes 2666(c) 2030025 Pressurized piping able to detect a 3.0 gph leak RD within an hour, and ❑ ❑ ® ❑ ❑ ❑ None ❑ restricts the flow or Yes alarms - 23 CCR 16 2636(0 (2) Secondary Containment 2060010 UST storing a hazardous RD substance has secondary ®❑ ❑ ❑ ❑ ❑ None [:1containment - HSC 6.7 Yes 25292 Underground Storage Tank Program - DW Inspection Report v 2.0 Violation Program Requirement 0 o �, ._ SOC Comments No 0 _ Q o o F- z> 0 z L)W D-- 2030008 UDC, sumps, and/or other secondary containment in good ® ❑ El ❑ ❑ ❑ None condition and/or are free of debris/liquid - HSC 6.7 25290.1, 25290.2, 25291 2030040 Secondarily contained RD piping maintained to allow ® ❑ ❑ ❑ ❑ ❑ None ❑ liquid to drain into sump - Yes 23 CCR 16 2630(d), 2641(a 2060006 Secondary containment piping slopes back to the ® ❑ ❑ ❑ ❑ ❑ None collection sump - 23 CCR 16 263(c) 2030047 Secondary containment maintained tight and has been confirmed by testing ® ❑ ❑ ❑ ❑ ❑ None - 23 CCR 16 2662; HSC 6.7 25290.1(c)(2), 25290.2(c)(2), 25291(a), 25292(e) 2030060 Entry fittings in secondary containment for UST rD system maintained ® ❑ ❑ ❑ ❑ None tight/sealed - 23 CCR 16 2630, 2635(d), 2636(c), 2666 2060020 Spill bucket is installed RP and has a functional drain ® ❑ ❑ ❑ ❑ ❑ None ❑ valve or other means to remove liquid - 23 CCR 16 Yes 2030054 2635 )),2665 Spill bucket maintained in RP Spill bucket was broken because the riser was set to high which good condition and free of E]® ❑ ❑ ❑ ❑ None ❑ pushed the bucket down when the debris and/or liquid - 23 Yes lid was in place causing it to leak CCR 16 2635(b), 2715(c) (2) 87 spill bucket leaked water into 2060019 Spill bucket to has a sump when filled with water for minimum capacity of five ❑ ® ❑ ❑ ❑ ❑ None testing gallons - 23 CCR 16 2635(b), 2665 Overfill 2030 035 UST system is operated RP Audible / Visual Alarm did not activate during overfill test as well to prevent unauthorized ❑ ® ❑ ❑ ❑ ❑ None ❑ as on manual test of the device release, including spills Yes seprate from the overfill and overfills - HSC 6.7 25292.1 a 2030036 Overfill prevention system RP has not been overridden and meets overfill ® ❑ ❑ ❑ ❑ ❑ None ❑ requirements - 23 CCR 16 Yes 2635 b 2 , 2665 Underground Storage Tank Program - DW Inspection Report v 2.0 Violation Program Requirement a°, ,o SOC Comments No o _ a o o a a� L— z o z o> On Site Records Certifications 2030023 Required designated operators or contractors maintain a proper and ® ❑ ❑ E]❑ E] None current ICC certification - 23 CCR 16 2715 2030024 Service technician, installer, and/ or employee maintain a ® E] E]❑ ❑ F-1 None proper license - 23 CCR 162715 2030031 Employee or contractor obtained and maintained proper manufacturer ® ❑ ❑ El ❑ ❑ None certification - 23 CCR 16 2715 2010007 Submit/maintain current Certificate of Financial Responsibility/mechanism of financial assurance - ® ❑ ❑ ❑ ❑ ❑ None 23 CCR 16 2711; 23 CCR 18 2808.1, 2809-2809.2; HSC 6.7 25292.2; HSC 6.75 25299.30-25299.34 Designated Operator 2010004 Copies of DO inspections for last 12 months and list of trained employees ® ❑ ❑ El ❑ None maintained - 23 CCR 16 2715 2030013 Designated operator properly conducted the monthly inspection and ® ❑ ❑ ❑ ❑ ❑ None the reports are complete - 23 CCR 16 2715 2030010 DO notified operator of any condition observed during the monthly ® ❑ ❑ ❑ ❑ ❑ None inspection that may require action - 23 CCR 16 2715(d) 2030012 DO employee training performed, current for at ® EJ El❑ ❑ F-] None least one employee on site, and a log kept - 23 CCR 16 2715(c)(6), 2715(1) Underground Storage Tank Program - DW Inspection Report v 2.0 Violation Program Requirement w 0 ;o SOC Comments No O E- Cn � o z O z D Logs 2030001 Leak detection alarm logs, maintenance and RD records of appropriate ® ❑ ❑ ❑ ❑ ❑ None ❑ follow-up actions Yes maintained - 23 CCR 16 2632, 2634, 2712(b) Maintenance/Tests 2010008 Monitoring, maintenance, repairs, linings, and RD upgrade records ® ❑ ❑ ❑ ❑ ❑ None ❑ maintained for the proper Yes time period - 23 CCR 16 2712(b) Documentation 2030033 Failure to maintain on site an approved monitoring ® ❑ ❑ ❑ ❑ ❑ None plan - 23 CCR 16 2632, 2634, 2711, 2712(1) 2030037 Written agreement between the tank owner and tank operator to monitor the tank system ❑ ❑ ❑ ❑ ❑ None is maintained - 23 CCR 16 2620(b); HSC 6.7 25284 a (3) 2030061 Suspected or actual RD unauthorized release reported in appropriate El El El ElNone ❑ time frame - HSC 6.7 Yes 29294, 29295 General Operating Requirements Permit Condition/Approval 2030039 Compliance with all operating permit ® ❑ ❑ ❑ ❑ ❑ None conditions - 23 CCR 16 2712; HSC 6.7 25299 2030059 UST system maintained in accordance with exclusion/exemption ® ❑ ❑ ❑ ❑ ❑ None status - HSC 6.7 25281.6, 25283.5 2030014 Owner/Operator received approval and has implemented a training ❑ ❑ ® ❑ ❑ ❑ None program at an unstaffed facility - 23 CCR 16 2715 (0(2) 2030015 Facility exhibited that the method used to monitor the tank meets the monitoring methods in ® ❑ ❑ ❑ ❑ ❑ None 2643(f) - 23 CCR 16 2643 Underground Storage Tank Program - DW Inspection Report Violation Program Requirement ° o SOC Comments No OO _ Q o n~. CD 'o z o z D 0 o> Red Tag 2030045 Red Tag information is legible and has not been ❑ ❑ ® ❑ ❑ ❑ None tampered with - 23 CCR 162717.1( 2030044 Facility did not allow for deposit of petroleum into a UST that has a red tag ❑ ❑ ® ❑ ❑ ❑ None affixed to the fill - 23 CCR 16 2717.1 Install/Repair 2060024 UST system is made of or lined with materials that are compatible with the ® ❑ ❑ ❑ ❑ ❑ None substance stored - 23 CCR 16 2631.1 2060021 Striker plate installed and positioned correctly - 23 ❑ ❑ ❑ ❑ ❑ None CCR 16 2631(c), 2662(d ❑ There were no violations noted for this inspection. ®This report shall serve as a "NOTICE TO COMPLY" for Minor Violations, and a "NOTICE OF VIOLATION" for Major violations. You are, hereby, ordered to correct the above noted violations within 30 days, or according to correction summaries provided. Formal enforcement and/or penalty assessment may be initiated for any violations noted, and for those not corrected in a timely manner. (NOTE: If this is a preliminary report, a final report will follow.) Inspectors Signature: Date: Inspector: Enter # of Violations: RD: RP: Check one box for facility Significant Operational Status (SOC) to be reported to SWRCB and US EPA: ❑ SOC with both Release Detection and Release Detection (Facility has no Release Prevention and no Release Prevention Violations) ❑ Not in SOC (Facility has both Release Prevention and Release Detection Violations) ❑SOC with Release Detection only (Facility has no Release Detection violations but one or more Release Prevention violations) ❑ SOC with Release Prevention only (Facility has no Release Prevention violations but one or more Release Detection violations) Underground Storage Tank Program - DW Inspection Report v 2.0